Motorized Volume Control Damper - Mar Rev.01
Motorized Volume Control Damper - Mar Rev.01
Design & Construction of New Light Industrial Unit-City Neon at Ras Bu Fontas Free Zone
CLIENT
M/s. Qatar Free Zone Authority
CONSULTANT
M/s. Al Khaleej & Industrial Consultancy (KEIC)
MAIN CONTRACTOR
M/s. Amana Contracting
MEP CONTRACTOR
M/s. Q-Tec Engineering W.L.L.
BRAND
SAFID
SUPPLIER
GULF FACILITIES TRADING & CONTRACTING CO.
Tel: +974 4501152/68, Fax: +974 4607714
PO Box. 24212, Doha, Qatar
QATAR 2022
**************************
The Free Zones Authority of
the State of Qatar
Reviewed Document / Drawing No.: R49-AMA-MAR-AC-0101 Submittal No. : R49-AMA-MAR-AC-0101 Issued Date : 03 Jan 2023.
Comply.
2 KEIC-KA Specification R49-AMA-MAR-AC-0101 C OPEN
Please find enclosed Compliance Statement.
Provide reference drawings for the project with highlight on the areas Comply.
3 KEIC-KA Area of application R49-AMA-MAR-AC-0101 B Open
where the material shall be used. Please find enclosed highlighted drawings.
4 KEIC-KA Size Size of the damper is subject to the approved drawings R49-AMA-MAR-AC-0101 Will be comply. B OPEN
Reviewed Document / Drawing No.: R49-AMA-MAR-AC-0101 Submittal No. : R49-AMA-MAR-AC-0101 Issued Date : 03 Jan 2023.
9 KEIC-KA GSAS Provide compliance with GSAS where applicable R49-AMA-MAR-AC-0101 Not Applicable. B OPEN
Prepared &
Kamal Azayem Sr. Mechanical Engineer
Reviewed by :
Checked by: Anees Gafoor Construction Manager
01 02 03 04 05 06 TRUE °
66
EAD 700x500 NORTH
T/A
EAD 800x500
T/A
CSU-GF-11 EAD 700x400
107
2-SCD 600x600 T/A
°
EG 500x150
350x350 N.S
L FAD 300x150
150
186 L/s EACH
FAD 900x500
FROM FAHU-GF-01
L
RG 1050x300 FAD 500x500 QUIBLA
FAD 300x150 136 L/S NORMAL MODE FROM TFA-RF-02 CITYNEON-
93 L/S NORMAL MODE EAD 900x500 ANGLE
TO FAHU-GF-01 OFFICE,SHOW
ROOM
500x400 &WORKSHOP
300x150
CSU-GF-07
900x500
900x500
4-SCD 600x600 500x350 300x150 LEGEND:
300x300
EG N.S
450x150 900x300
160 L/s EACH
35 L/s
RG 900x300
VD VD FAD 300x250
229 L/S NORMAL MODE 900x300
K 500x400
SOFT CAST URETHANE PAINT ROOM K
VD
300x250 005 003
400x150 400x150 400x150 MOLD 400x150 900x300
FRP / COMPOSITES SPRAY
500x350 FAD 1400x1000
007 500x250
008 500x200 FROM FAHU-GF-03&03A
550x300
004 2. D&B CONTRACTOR SHALL CO-ORDINATE WITH END USER
FOR THE EXACT LOCATION OF EACH EQUIPMENT AND ITS
400x150
250x250
EXHAUST/VENT CONNECTION.
400x150
PAINT PREP.
C
H VD 028 H
LINE TYPE DIFFERENTIATION
300x300 550x300
D (CONTINUOUS) QFZ
400x150
VD
CSU-GF-08
400x150
4-SCD 600x600
300x300 N.S (HIDDEN) CITYNEON
FRP / COMPOSITES HAND
150 L/s EACH LAYUP
RG 850x300 REFERENCE MODEL:
EG 350x150
009 3229-ECG-MB-ZZ-3DM-A-AA-00001 00
102 L/s
EAD 800x500 OTHER REFERENCES:
750x450 TIE IN
G 250x150 E G
6-SCD 600x600
650x350
400x400 N.S
282 L/s EACH SCULPTING / SCENIC SHOP
2- RG 1250x300
EG 350x150 VD VD
026 SPACE FOR EQUIPMENTS
102 L/s CSU-GF-09
SG 2600x300 500x350 650x350
1916 L/s 027
VD FAD 250x100
450x250 46 L/S NORMAL MODE
F F
450x250 FAD 250x100 STAFF TOILET 01 EAD 300x250 0 5 [m]
1 2 3 4
VD UP TO EF-RF-03
025 200x100 Scale: 1:100
450x250 650x350 CSU-GF-10
FRP / COMPOSITES
PROCESSING 450x250 VD
450x250 300x250
010 VD VD 200x100
200x100
250x200 250x200
VD VD VD 6-EG 150x150
650x350 200x100
250x150 250x150 35 L/s EACH F
VD VD 00 DEC-2022 DESIGN DEVELOPMENT Y.TAHA M.ASAB M.DARM A.MAMR
200x150 200x150
E ODU-GF-01
IDU-GF-03A 200x100 200x100 REV DATE ISSUED FOR DRW CHK TL PM E
MALE VISTITOR'S TOILET
4-EG 150x150
CLIENT:
IDU-GF-03 IDU-GF-03B 35 L/s EACH 4-EG 150x150 019
IDU-GF-01
200x100 35 L/s EACH QATAR FREE ZONES
ODU-GF-03
G AUTHORITY
STAFF TOILET 02 200x100 200x150 200x200 250x200
PROJECT MANAGEMENT:
REF TO 1 / 3229-ECG-MB-GR-DWG-M-HV-01102
ODU-GF-03A IDF ROOM
ELECT. ROOM 026
012
011
ODU-GF-03B LEAD CONSULTANT:
D D
AUTOMATED DOOR
LEAD CONSULTANT:
FD
H ECG
ENGINEERING CONSULTANTS GROUP S.A.
FOR CONTINUATION
C www.ecgsa.com C
FCU-GF-04 FCU-GF-05 FCU-GF-06 FCU-GF-07 PROJECT TITLE:
SCD 600x600 SCD 600x600 SCD 600x600 SCD 600x600
350x350 N.S
207 L/s
350x350 N.S
207 L/s
250x250 N.S
67 L/s
250x250 N.S
67 L/s DESIGN & BUILD OF THE NEW LIGHT
450x200 2-EG 450x150 RG 600x150 RG 600x150 RG 250x150 RG 250x150
INDUSTRIAL UNITS
MATCH LINE
118 L/s EACH
EG 450x250 AT LOW LEVEL
236 L/s
EF-GF-02
300 mm FROM at Ras Bufontas Free Zone PA-WH-08-01
FFL
450x200 AUTOMATED DOOR CITYNEON-OFFICE, SHOWROOM & WORKSHOP
400x150 400x150 300x100 RECIEVING AND DISCIPLINE
VD VD WAREHOUSING
SHEET SIZE - ISO A1 (841* 594 MM)
B 600x100 600x100
018
Mechanical HVAC B
400x150 400x150 300x100 300x100 SHEET TYPE
1.3_MECHANICAL_HVAC WORKS PLANS
I SHEET TITLE
FLAMABLE LIQUID STORAGE MEETING ROOM
(PROTECTED WITH FOAM
MEETING ROOM SCULPT / MOLD SHOP SCENIC SHOP MANAGER GROUND FLOOR PLAN
SYSTEM) 014
015 016 017 SHEET 01 OF 03
013
GROUND FLOOR - DUCT - PART 01 OF 03 SCALE: 1 : 100 SHEET SIZE: A1 SUITABILITY: S4
1 SCALE 1 : 100
Drawing No: Rev:
A 3229-ECG-MB-GR-DWG-M-HV-01101 00 A
1 2 3 4 5 6 7 8 9 10 11 12 13 ECG Copyright - Produced Using BIM Technology
1 2 3 4 5 6 7 8 9 10 11 12 13
PROJECT KEY PLAN:
NORTH
01 02 03 04 05 06 TRUE 66
°
NORTH
107
EAD 700x500 TO PACU-RF-05
FAD 500x500
°
L L
MD FAL 1500x1200 QUIBLA CITYNEON-
FAL 1200x1200
1916 L/s PACU-RF-02 ANGLE
1274 L/s BDD OFFICE,SHOW
FAHU-GF-01 FD FD FD FD
MD ROOM
900x550
700x500
MD TFA-RF-02 EF-RF-04 &WORKSHOP
900x500 SAT VD
SAT 450x150
300x250 LEGEND:
TFA-RF-01 900x500 500x500
450x250
900x400
600x350 600x550 450x250
FAD 700x500 VD VD VD VD VD VD
750x600 VD 450x150
VD
EAD 700x400
EAD 250x500 600x350 600x350 600x350 600x350 600x350
600x350 RAD 950x600 600x350
FD 600x350 600x350 600x350 SAD 850x550 600x350 600x350
B
J J
700x400
NOTES:
550x400
LINE TYPE DIFFERENTIATION
(CONTINUOUS) QFZ
450x300
G G
F F
0 1 2 3 4 5 [m]
Scale: 1:100
F
300x150
REF TO 1 / 3229-ECG-MB-02-DWG-M-HV-01102
QATAR FREE ZONES
AUTHORITY
PROJECT MANAGEMENT:
LEAD CONSULTANT:
D D
FOR CONTINUATION
Tel:+974 44016222, Fax:+97444121543
11-Dec-22 3:12:56 PM
LEAD CONSULTANT:
ECG
ENGINEERING CONSULTANTS GROUP
MATCH LINE
S.A.
C www.ecgsa.com C
PROJECT TITLE:
B Mechanical HVAC B
SHEET TYPE
1.3_MECHANICAL_HVAC WORKS PLANS
SHEET TITLE
SECOND FLOOR PLAN
SECOND FLOOR - DUCT - PART 01 OF 03 SHEET 01 OF 03
1 SCALE 1 : 100 SCALE: 1 : 100 SHEET SIZE: A1 SUITABILITY: S4
Drawing No: Rev:
A 3229-ECG-MB-02-DWG-M-HV-01101 00 A
1 2 3 4 5 6 7 8 9 10 11 12 13 ECG Copyright - Produced Using BIM Technology
1 2 3 4 5 6 7 8 9 10 11 12 13
PROJECT KEY PLAN:
NORTH
TRUE °
66
NORTH
01 02 03 04 05 06
107
°
L L
QUIBLA CITYNEON-
SAD 900x550 ANGLE OFFICE,SHOW
RAD 900x550 ROOM
&WORKSHOP
LEGEND:
FD FD
900x550
900x550 500x200
SAT SAT
K K
FD
FAD 1400x1000
EAD 1400x1000
FD
J J
NOTES:
(CONTINUOUS) QFZ
D
(HIDDEN) CITYNEON
PACU-RF-04
F F
0 1 2 3 4 5 [m]
Scale: 1:100
FAL 400x400
536 L/s
SAT
300x200
MD
750x650
F 00 DEC-2022 DESIGN DEVELOPMENT Y.TAHA M.ASAB M.DARM A.MAMR
E 800x500 REV DATE ISSUED FOR DRW CHK TL PM E
CLIENT:
VD
REF TO 1 / 3229-ECG-MB-RF-DWG-M-HV-01102
LEAD CONSULTANT:
D D
LEAD CONSULTANT:
SEF-RF-01
H ECG
ENGINEERING CONSULTANTS GROUP S.A.
C C
FOR CONTINUATION
www.ecgsa.com
PROJECT TITLE:
MATCH LINE
at Ras Bufontas Free Zone PA-WH-08-01
CITYNEON-OFFICE, SHOWROOM & WORKSHOP
DISCIPLINE
SHEET SIZE - ISO A1 (841* 594 MM)
B Mechanical HVAC B
SHEET TYPE
1.3_MECHANICAL_HVAC WORKS PLANS
SHEET TITLE
I
ROOF FLOOR PLAN
SHEET 01 OF 03
ROOF FLOOR - DUCT - PART 01 OF 03 SCALE: 1 : 100 SHEET SIZE: A1 SUITABILITY: S4
1 SCALE 1 : 100 Drawing No: Rev:
A 3229-ECG-MB-RF-DWG-M-HV-01101 00 A
1 2 3 4 5 6 7 8 9 10 11 12 13 ECG Copyright - Produced Using BIM Technology
1 2 3 4 5 6 7 8 9 10 11 12 13
PROJECT KEY PLAN:
NORTH
07 08 09 10 11 12 13 14 14'
TRUE °
66
NORTH
SAD 900x550
RAD 900x550
107
RAD 900x550
°
L L
QUIBLA CITYNEON-
FAL 800x450 FAL 800x450 ANGLE OFFICE,SHOW
322 L/s 322 L/s VRF-GF-01 VRF-FF-01 VRF-SF-01 CU-GF-04
ROOM
FD FD FD &WORKSHOP
PACU-RF-05 PACU-RF-06
500x200 MD 500x200
SAT SAT MD
LEGEND:
SAT SAT
K K
TOP
FD MD
FAD 1400x1000 EAD 450x300 450x300
FAD 650x400
650x400
FAL 900x500
FD 417 L/s FAHU-GF-02
EAD 1400x1000
SAT B
J SAT
SAT
J
CU-RF-02
NOTES:
M4
M4
CONSIDERED AS PER REVISED LIST OF EQUIPMENT SHARED,
PACU-RF-03 ACCORDINGLY THE TIE IN/STUB OUT CONNECTIONS ARE
SHOWN IN THE DRAWINGS.
M3
M3
ODU-SF-01A ODU-SF-01B ODU-SF-02A ODU-FF-01 ODU-SF-04
C
1300x750
M2
M2
SAT 2. D&B CONTRACTOR SHALL CO-ORDINATE WITH END USER
FAHU-GF-03 FAHU-GF-03A
FOR THE EXACT LOCATION OF EACH EQUIPMENT AND ITS
600x550 900x650 900x650 EXHAUST/VENT CONNECTION.
D
H H
1250x700
M1
VD
M1
VD
LINE TYPE DIFFERENTIATION
600x350 600x600 850x600 850x600 600x600
M6
M6
CU-RF-01 CU-RF-05 VD
(CONTINUOUS) QFZ
VD VD
EAL 1500x1800 600x550
5286 L/s 600x350 600x550 600x350 600x350 (HIDDEN) CITYNEON
VRF-GF-02 600x350 600x550
E REFERENCE MODEL:
1400x1000 3229-ECG-MB-ZZ-3DM-A-AA-00001 00
MD
BDD 950x800 OTHER REFERENCES:
FAL 2500x2000
G 5286 L/s 1400x1000 G
PACU-RF-04
950x800
950x800 CU-GF-03 CU-GF-03A
EAL 1500x1800
5286 L/s
FAL 400x400
F 536 L/s F
0 1 2 3 4 5 [m]
SEF-RF-04
300x200
MD Scale: 1:100
600x300 700x400 600x300 700x400 FD 00 DEC-2022 DESIGN DEVELOPMENT Y.TAHA M.ASAB M.DARM A.MAMR
E EAD 500x250 REV DATE ISSUED FOR DRW CHK TL PM E
CLIENT:
G
QATAR FREE ZONES
REF TO 1 / 3229-ECG-MB-RF-DWG-M-HV-01103
AUTHORITY
REF TO 1 / 3229-ECG-MB-RF-DWG-M-HV-01101
PROJECT MANAGEMENT:
LEAD CONSULTANT:
D D
MSFD MSFD MSFD MSFD
SEF-RF-03
AMANA QATAR CONTRACTING CO. W.L.L
SEF-RF-01 SEF-RF-02 SEF-RF-05
H P.O.Box:23377, Doha-Qatar
Tel:+974 44016222, Fax:+97444121543
11-Dec-22 3:15:24 PM
LEAD CONSULTANT:
FOR CONTINUATION
ECG
FOR CONTINUATION
MATCH LINE
MATCH LINE
B I Mechanical HVAC B
SHEET TYPE
1.3_MECHANICAL_HVAC WORKS PLANS
SHEET TITLE
ROOF FLOOR PLAN
ROOF FLOOR - DUCT - PART 02 OF 03 SHEET 02 OF 03
1 SCALE 1 : 100 SCALE: 1 : 100 SHEET SIZE: A1 SUITABILITY: S4
Drawing No: Rev:
A 3229-ECG-MB-RF-DWG-M-HV-01102 00 A
1 2 3 4 5 6 7 8 9 10 11 12 13 ECG Copyright - Produced Using BIM Technology
1 2 3 4 5 6 7 8 9 10 11 12 13
PROJECT KEY PLAN:
NORTH
14' 15 16 17 18 19 20 TRUE
NORTH
66
°
107
RAD 1500x700 SAD 1500x700
EAD 250x250
°
RAD 1500x700
L L
QUIBLA CITYNEON-
ANGLE OFFICE,SHOW
ROOM
EAD 450x300 &WORKSHOP
CU-GF-04 FD FD EAD 450x300
EF-RF-07
FD FD FD FD FD LEGEND:
BDD SAT SAT SAT 450x300
K K
EAD 400x400 SAT
1500x700
EAD 150x150 ODU-GF-06 1500x700 1500x700 1500x700
FAHU-GF-02 BDD
EAL 1200x550
J 1259 L/s J
B NOTES:
FAL 1800x800
1361 L/s 1. SPECIAL VENTILATION EQUIPMENT LOCATIONS ARE
FAL 1200x550
CONSIDERED AS PER REVISED LIST OF EQUIPMENT SHARED,
MD FAL 1000x550
361 L/s PACU-RF-08 PACU-RF-09 ACCORDINGLY THE TIE IN/STUB OUT CONNECTIONS ARE
MD 493 L/s
SHOWN IN THE DRAWINGS.
PACU-RF-03 500x250
2. D&B CONTRACTOR SHALL CO-ORDINATE WITH END USER
350x350
SAT
SAT
C FOR THE EXACT LOCATION OF EACH EQUIPMENT AND ITS
EXHAUST/VENT CONNECTION.
VD
H 600x550
VD SAT H
LINE TYPE DIFFERENTIATION
1050x600 850x600 650x600 650x350
RAD 900x500 D
VD SAD 900x500
VD (CONTINUOUS) QFZ
FD
600x600 600x350 VD VD
G G
F F
0 1 2 3 4 5 [m]
Scale: 1:100
SEF-RF-06 SEF-RF-08 SEF-RF-10
AUTHORITY
PROJECT MANAGEMENT:
LEAD CONSULTANT:
D D
SEF-RF-09
SEF-RF-07
H LEAD CONSULTANT:
ECG
FOR CONTINUATION
B Mechanical HVAC B
SHEET TYPE
I 1.3_MECHANICAL_HVAC WORKS PLANS
SHEET TITLE
ROOF FLOOR PLAN
SHEET 03 OF 03
ROOF FLOOR - DUCT - PART 03 OF 03 SCALE: 1 : 100 SHEET SIZE: A1 SUITABILITY: S4
1 SCALE 1 : 100 Drawing No: Rev:
A 3229-ECG-MB-RF-DWG-M-HV-01103 00 A
1 2 3 4 5 6 7 8 9 10 11 12 13 ECG Copyright - Produced Using BIM Technology
1 2 3 4 5 6 7 8 9 10 11 12 13
KEY PLAN:
1 2 3 4 PROJECT
NORTH
TRUE
SAD 500x250 SAD 500x250 24° NORTH
450 L/s 450 L/s
L SAD 500x250 SAD 500x250 10
7 ° SUBSTATION L
407 L/s 450 L/s
SAD 400x250 QUIBLA
299 L/s ANGLE
A A
LEGEND:
K K
SG 700x250 3- SG 700x250 SG 450x250
407 L/s 450 L/s EACH 299 L/s
RG 700x250 3-RG 700x250 RG 450x250
J J
B B NOTES:
H H
1 2 3 4
REFERENCE MODEL:
Ground Floor Level 3229-ECG-SB-ZZ-3DM-A-AA-00001
OTHER REFERENCES:
00
1 1 : 100
G G
1 2 3 4
F F
0 1 2 3 4 5 [m]
A VD VD VD
VD 400x250 A 00 DEC-2022 DESIGN DEVELOPMENT Y.TAHA M.ASAB M.DARM A.MAMR
E 500x250 750x450
REV DATE ISSUED FOR DRW CHK TL PM E
CLIENT:
PACU-RF-01A
LEAD CONSULTANT:
D MD
FAL 500x300 D
SAD 900x400
RAD 900x400 VD 137 L/s
VD
500x250 850x450
LEAD CONSULTANT:
RAD 500x250
373 L/s
RAD 500x250
RAD 500x250
438 L/s
RAD 500x250
RAD 400x250
232 L/s ECG
ENGINEERING CONSULTANTS GROUP S.A.
C 438 L/s 438 L/s
www.ecgsa.com C
PROJECT TITLE:
B Mechanical HVAC B
SHEET TYPE
1.3_MECHANICAL_HVAC WORKS PLANS
SHEET TITLE
FLOOR PLANS (GROUND FLOOR PLAN, ROOF PLAN)
OVERALL
SCALE: 1 : 100 SHEET SIZE: A1 SUITABILITY: S4
Drawing No: Rev:
A 3229-ECG-SB-ZZ-DWG-M-HV-01001 00 A
1 2 3 4 5 6 7 8 9 10 11 12 13 ECG Copyright - Produced Using BIM Technology
SafidDampers
Class 1A & Class 1
Low Leakage Volume Control Damper SPK 30 Series
( Flange Type )
BLADES:
100mm, 125mm and 150mm wide airfoil shaped blades
FINISH:
Frame of mill galvanized.
Blades of mill galvanized.
EXTERNAL LINKAGE:
Galvanized steel side linkage concealed in frame for opposed
blade operation.
CASE BEARING:
Brass bearing as standard.
Sintered bronze oilite (optional).
CONTROL SHAFT:
Description 12mm diameter zinc plated mild steel.
SPK 30-400 Class 1A & Class 1 Low Leakage Volume Control
Dampers are recommended for use in multiple Air Conditioning Units TIP SEAL
with one common air duct system on which one or two A/C Units Bubble type seal.
needs to be isolated during standby mode while the other A/C Unit is For Alr Leakage "Class 1A" and "Class 1".
on operational mode.
SIDE SEAL (Jamb Seal):
In building pressurization it can be used as an isolation damper to
maintain the required pressure in the space. Compression type stainless steel grade 304 to close
gap between frame and blades.
In office buildings where some occupants are outside most of the
time, this type of damper is recommended to shutdown the flow of air
MINIMUM & MAXIMUM SINGLE SECTION SIZE:
when the space is unoccupied on which can save energy
consumption.
100 x 100mm minimum and 900 x 900mm maximum.
It is also being used as a fresh air intake damper for Air Conditioning
Units where it needs a fresh air damper to be closed upon detection
of heavy dust on the fresh air side.
SPK 30 - 410
The blades with airfoil construction provides a low pressure drop in
the open position for smooth airflow and reduced air turbulence.
General construction as type SPK 30-400 damper but with
frame, linkage, case bearing, axles and control shaft are from
stainless steel (Grade 304).
SAFID certifies that the Class 1A & Class 1 Low Leakage Volume Control Damper
shown herein is licensed to bear the AMCA Seal for Model SPK 30-400. The ratings
shown are based on tests and procedures performed in accordance with AMCA
Publication 511 and comply with the requirements of the AMCA Certified Ratings
Program.
The AMCA Certified Ratings Seal applies to Air Leakage and Air Performance Ratings.
Test Information
Tested for air leakage in accordance with ANSI / AMCA Standard 500-D-07,
Figure 5.4. Air leakage is based on operation between 32 ºF and 120 ºF.
Tested for air performance in accordance with ANSI / AMCA Standard 500-D-07
(Pressure Drop), Figure 5.3.
Catalog ID: SPK 30-400 January 23, 2014
Only 150mm blade width is AMCA certified.
1
SafidDampers
Class 1A & Class 1
Low Leakage Volume Control Damper SPK 30 Series
Data are based on a torque of 24.6 in.-lb/ft2 applied to close and seat the damper during the test.
SAFID certifies that the Class 1A & Class 1 Low Leakage Volume Control Damper shown
herein is licensed to bear the AMCA Seal for Model SPK 30-400. The ratings shown are
based on tests and procedures performed in accordance with AMCA Publication 511 and
comply with the requirements of the AMCA Certified Ratings Program.
The AMCA Certified Ratings Seal applies to Air Leakage and Air Performance Ratings.
Test Information
Tested for air leakage in accordance with ANSI / AMCA Standard 500-D-07,
Figure 5.4. Air leakage is based on operation between 32 ºF and 120 ºF.
Tested for air performance in accordance with ANSI / AMCA Standard 500-D-07
(Pressure Drop), Figure 5.3.
Only 150mm blade width is AMCA certified.
Catalog ID: SPK 30-400 January 23, 2014
2
SafidDampers
Class 1A & Class 1
Low Leakage Volume Control Damper SPK 30 Series
Air Performance
Pressure Drop
SAFID certifies that the Class 1A & Class 1 Low Leakage Volume Control Damper shown
herein is licensed to bear the AMCA Seal for Model SPK 30-400. The ratings shown are
based on tests and procedures performed in accordance with AMCA Publication 511 and
comply with the requirements of the AMCA Certified Ratings Program.
The AMCA Certified Ratings Seal applies to Air Leakage and Air Performance Ratings.
Test Information
Tested for air leakage in accordance with ANSI / AMCA Standard 500-D-07,
Figure 5.4. Air leakage is based on operation between 32 ºF and 120 ºF.
Tested for air performance in accordance with ANSI / AMCA Standard 500-D-07
(Pressure Drop), Figure 5.3.
Only 150mm blade width is AMCA certified.
Catalog ID: SPK 30-400 January 23, 2014
3
SafidDampers
Class 1A & Class 1
Low Leakage Volume Control Damper SPK 30 Series
Air Performance
Pressure Drop
SAFID certifies that the Class 1A & Class 1 Low Leakage Volume Control Damper shown
herein is licensed to bear the AMCA Seal for Model SPK 30-400. The ratings shown are
based on tests and procedures performed in accordance with AMCA Publication 511 and
comply with the requirements of the AMCA Certified Ratings Program.
The AMCA Certified Ratings Seal applies to Air Leakage and Air Performance Ratings.
Test Information
Tested for air leakage in accordance with ANSI / AMCA Standard 500-D-07,
Figure 5.4. Air leakage is based on operation between 32 ºF and 120 ºF.
Tested for air performance in accordance with ANSI / AMCA Standard 500-D-07
(Pressure Drop), Figure 5.3.
Only 150mm blade width is AMCA certified.
Catalog ID: SPK 30-400 January 23, 2014
4
SafidDampers
Class 1A & Class 1
Low Leakage Volume Control Damper SPK 30 Series
Air Performance
Pressure Drop
SAFID certifies that the Class 1A & Class 1 Low Leakage Volume Control Damper shown
herein is licensed to bear the AMCA Seal for Model SPK 30-400. The ratings shown are
based on tests and procedures performed in accordance with AMCA Publication 511 and
comply with the requirements of the AMCA Certified Ratings Program.
The AMCA Certified Ratings Seal applies to Air Leakage and Air Performance Ratings.
Test Information
Tested for air leakage in accordance with ANSI / AMCA Standard 500-D-07,
Figure 5.4. Air leakage is based on operation between 32 ºF and 120 ºF.
Tested for air performance in accordance with ANSI / AMCA Standard 500-D-07
(Pressure Drop), Figure 5.3.
Only 150mm blade width is AMCA certified.
Catalog ID: SPK 30-400 January 23, 2014
5
SafidDampers
Class 1A & Class 1
Low Leakage Volume Control Damper SPK 30 Series
Dimensions
1 - Casing 3 - Side Linkage 5 - Tip Seal 7 - Bearing
2 - Actuator 4 - Blade 6 - Side Seal (Jamb Seal) 8 - Landing Angles
6
SafidDampers
Class 1A & Class 1
Low Leakage Volume Control Damper SPK 30 Series
Materials - Construction
Axle and Drive Shaft fixing details Mounting Bracket for Actuator
7
SafidDampers
Class 1A & Class 1
Low Leakage Volume Control Damper SPK 30 Series
Installation Details
Damper to Slide on Flange connection Damper to Angle Flange connection
8
SafidDampers
Class 1A & Class 1
Low Leakage Volume Control Damper SPK 30 Series
Order Details
Order Code
Blade Operation
OB = Opposed Blades operation
External Controls
* R = Right hand (Standard Supply)
Variants - Bearings L = Left Hand
*B = Brass case bearing (Standard Supply)
B1 = Sintered bronze (oilite) case bearing
ORDER EXAMPLE
STANDARD
Make: SAFID
1. Type : SPK 30 - 400 - OB - B - R - 900 x 900 - A
2. Type : SPK 30 - 400 - OB - B1 - R - 900 x 900 - A
9
OpenAir™
2 Nm nominal torque
Operating voltage AC 24 V ~ / DC 24…48 V or AC 100…240 V ~
Prewired with 0.9 m connecting cable
Gear train disengagement button for manual adjustment
Position indication
Auxiliary switches for auxiliary functions
30
A6V10636055_en--_e Siemens
2019-03-21 Building Technologies
Features
The rotary actuator drives the damper to the desired operating position after connecting the
operating voltage.
Brushless, robust DC motors ensure reliable operation regardless of load.
The rotary actuators do not require an end position switch, are overload proof, and remain
in place upon reaching the end stop.
The gears are maintenance free and low noise.
Simple and reliable shaft integration.
Mounting bracket included.
Use
Non-spring return rotary actuators. Application in ventilation and air conditioning plants to
operate air dampers and air throttles.
For damper areas up to 0.3 m 2, friction dependent.
Suitable for use with modulating controllers (DC 0/2...10 V), open-close or three-position
controllers.
For directly driven zone dampers to control air flow in air ducts.
We recommend a minimum pulse length of 500 ms on rotary actuators operated with
3-point control to ensure continuous and accurate operation.
Functions
AC 24 V ~ / GSD14..1A GSD16..1A
Type DC 24…48 V
AC 100…240 V ~ GSD34..1A GSD361.1A
2 / 10
Siemens A6V10636055_en--_e
Building Technologies 2019-03-21
Technical design/mechanical design
Housing
The housing consists essentially of flame retardant, non brominated, non chlorinated glass
fibre reinforced plastic.
Type summary
Type Stock number Control Operating Positioning Position Aux. Rotary Aux.
voltage signal Y indicator U = switches direction power supply
DC 0/2...10 V switch
GSD141.1A S55499-D281 AC 24 V ~ /
Open- DC 24…48 V
GSD146.1A S55499-D227 close 2
or three- yes
GSD341.1A S55499-D282
position AC 100…240 V ~
GSD346.1A S55499-D230 2
GSD161.1A S55499-D228 AC 24 V ~ / yes
GSD166.1A S55499-D229 Modulating DC 24…48 V DC 0/2...10 V yes 2 yes
GSD361.1A S55499-D231 AC 100…240 V ~ yes yes
Product documentation
Notes
Safety
Caution
Engineering
Auxiliary switches
Auxiliary switches cannot be added in the field.
3 / 10
A6V10636055_en--_e Siemens
2019-03-21 Building Technologies
Technical data
Functional data
Nominal torque 2 Nm
Maximum torque 5 Nm
Nominal rotational angle 90°
Maximum rotational angle (mechanically limited) 95° ± 2°
Runtime at nominal rotational angle 90° 30 s
Duty cycle 100 %
Direction of rotation Clockwise / counterclockwise
Mechanical life 100 000 cycles
Actuator sound power level 35 dB(A)
Inputs
Positioning signal for GSD14..1A
Operating voltage (wires 1-6/G-Y1) clockwise
AC 24 V ~ / DC 24…48 V (wires 1-7/G-Y2) counterclockwise
Positioning signal for GSD34..1A
Operating voltage (wires 4-6/N-Y1) clockwise
AC 100…240 V ~ (wires 4-7/N-Y2) counterclockwise
Positioning signal for GSD16..1.A
Input voltage (wires 8-2/Y-G0) DC 0/2…10 V
Current consumption 0.1 mA
Input resistance >100 k
Outputs
Position indicator
Output signal (GSD16..1.A) (wires 9-2/U-G0)
Output signal (GSD361.1.A) (wires 9-2/U-G-)
Output voltage U DC 0...10 V
Max. output current DC ±1 mA
Protected against faulty wiring max. AC 24 V ~ / DC 24…48 V
Aux. power supply (GSD361.1A) (wires 1-2/G+-G-) DC 24 V ±20 %, max. 10 mA
Auxiliary switches
Switching voltage AC 24…250 V ~ / DC 12…30 V
Contact rating 6 A resistive, 2 A inductive, min. 10 mA @ AC
4 A resistive, 2 A inductive, min. 10 mA @ DC 30 V
0.8 A res., 0.5 A inductive, min. 10 mA @ DC 60 V
Electric strength auxiliary switches against housing AC 4 kV
Factory switches setting: Switch A / Switch B 5° / 85° (fixed position)
5 / 10
A6V10636055_en--_e Siemens
2019-03-21 Building Technologies
Connection cables
Cable length 0.9 m
2
Cross-section 0.75 mm
Degree of protection
Insulation protective class As per EN 60730
AC 24 V ~ / DC 24…48 V III
AC 100…240 V ~ II
Housing protection IP54 as per EN 60529
Environmental conditions
Operation IEC 60721-3-3
Climatic conditions Class 3K5
Mounting location Interior, weather-protected
Temperature (extended) -32...+55 °C
Humidity, non-condensing <95 % r.F.
Transportation IEC 60721-3-2
Climatic conditions Class 2K3
Temperature (extended) -32...+70 °C
Humidity, non-condensing <95 % r.F.
Storage IEC 60721-3-1
Climatic conditions Class 1K3
Temperature (extended) -32...+50 °C
Humidity, non-condensing <95 % r.F.
Mechanical conditions Class 2M2
Environmental compatibility
2)
The product environmental declaration A5W00030346-A contains data on environmentally compatible product
design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal).
Dimensions
Actuator W x H x D See "Dimensions” p. 9
Damper shaft
round 8…15 mm
Square 6…11 mm
Min. shaft length 20 mm
Shaft hardness <300 HV
Weight
Excl. packaging Max. 0.55 kg, without switches
Max. 0.7 kg, with switches
1)
Permitted only to DC 30 V
2)
The documents can be downloaded from http://siemens.com/bt/download.
6 / 10
Siemens A6V10636055_en--_e
Building Technologies 2019-03-21
Diagrams
Internal Diagrams
AC 24 V ~ / DC 24…48 V AC 100…240 V ~
III
AC 24 V ~ AC 24...250 V ~ / 6 (2) A AC 24...250 V ~ / 6 (2) A
DC 24...48 V DC 12...30 V / 2 A AC 100...240 V ~ DC 12...30 V / 2 A
1 S1 S4 6 7 S1 S4
M 1) 1)
M
6 7 S2 S3 S5 S6 4 S2 S3 S5 S6
N
AC 24 V ~ / DC 24…48 V AC 100…240 V ~
100%
1) 100%
M M
0% 0%
G0 U N G-
2 9 4 2 9
N
DC 0/2...10 V DC 0/2...10 V
1)
Actuator Switch A Switch B
Position Common S1 Common S4
connected to connected to
0°…5° S3 S6
5°…85° S2 S6
85°…90° S2 S5
7 / 10
A6V10636055_en--_e Siemens
2019-03-21 Building Technologies
Connection diagrams
Open-close, single wire control Open-close, two wire control Three-position control Modulating control
Single Pole Single Throw (SPST) Single Pole Double Throw (SPDT)
AC 24 V ~ AC 24 V ~ AC 24 V ~ AC 24 V ~
DC 24...48 V DC 24...48 V DC 24...48 V DC 24...48 V
G G G
Y1 Y2 Y1 Y2 Y1 Y2 G Y U
G0
AC 24 V ~ AC 24 V ~ AC 24 V ~
DC 24...48 V DC 24...48 V DC 24...48 V
Y1 Y2 Y1 Y2 Y1 Y2
G G G
Open-close, single wire control Open-close, two wire control Three-position control Modulating control
Single Pole Single Throw (SPST) Single Pole Double Throw (SPDT)
Y1 Y2 Y1 Y2 Y1 Y2 L G+ Y U
N N N N G-
N N N N
Cable labeling
8 / 10
Siemens A6V10636055_en--_e
Building Technologies 2019-03-21
Dimensions
Dimensions in mm
9 / 10
A6V10636055_en--_e Siemens
2019-03-21 Building Technologies
Air damper actuators
GEB..1E
Electronic rotary
y actuators for 2-position, 3-position, and modulating control
Nominal torque 20 Nm
Mechanica
Pre-wired with standard 0.9 m connection cables
Type-specific
Type specific variations with adjustable offset and span for
the positioning signal
Position indication: Mechanical and electrical
Feedback potentiometer
Self-adaption
adap of the rotation angle range and adjustable auxiliary switches
for supplemental functions
Functions
0 0... 0 0...
The actuator remains in the respective
position with no power applied.
The actuator remains in the deployed
position:
Self-adaptation
adaptation of the The actuator automatically determines the
rotation angle range mechanical end positions of the rotation
angle range.
The characteristic function (Uo, U) is
-
mapped to the calculated rotation angle
range.
Power must be connected to DIL switch 2
(self-adaptation) for the function to operate.
Manual adjustment The actuator can be manually adjusted by pressing the gear train disengagement
button.
Rotation angle limitation
2
Siemens A6V11449860_en--a
Smart Infrastructure 2019-09-10
Technical design
Housing
Robust and light cast aluminum housing. The housing guarantees long life, even under
harsh ambient conditions.
Actuator / gears
Brushless, robust DC motors ensure reliable operation regardless of load. The damper
actuators do not require an end position switch, are overload proof, and remain in place
upon reaching the end stop.
The gears are maintenance free and low noise.
Type summary
Type Stock number Open-loop Operating Positioning Position Feedback Self-adapting Auxili- Rotation
control voltage signal input Y indicator potentio- rotation angle ary direction
U = DC meter ranges switch switch
5k
GEB141.1E S55499-D329 -
AC 24 V ~ / -
GEB142.1E S55499-D330 Yes
2- or 3-
GEB146.1E S55499-D331 - - - 2 Yes
position
GEB341.1E S55499-D336 - -
GEB346.1E S55499-D337 2
GEB161.1E S55499-D332 DC 0/
-
GEB163.1E S55499-D333 AC 24 V ~ /
GEB164.1E S55499-D334 Modulating Yes - Yes Yes
2
GEB166.1E S55499-D335
GEB361.1E S55499-D338 -
Accessories/spare parts
See data sheet N4697
Product documentation
Data sheet Accessory and spare parts for air damper actuators N4697
3
Siemens A6V11449860_en--a
Smart Infrastructure 2019-09-10
Notes
Safety
CAUTION
Engineering
Mounting
Shaft connection
When mounting, comply with the notes on shaft diameters and damper surface areas in
Technical data (page 8) and use only quality materials typical to the sector for the damper
shaft.
Installation
WARNING
Maintenance
The GEB..1E actuators are maintenance-free.
4
Siemens A6V11449860_en--a
Smart Infrastructure 2019-09-10
Disposal
5
Siemens A6V11449860_en--a
Smart Infrastructure 2019-09-10
Technical data
Function data
Nominal torque 20 Nm
Maximum torque (when blocked) 35 Nm 2)
Minimum holding torque 20 Nm
Nominal rotation angle (with position indication)
Maximum rotation angle (mechanically limited)
Runt 150 s
Actuator sound power level (at a positioning time of 150 s) <35 dB(A)
Inputs
Positioning signal for GEB14..1E
Operating voltage (wires 1-6/G-Y1) Clockwise
(wires 1-7/G-Y2) Counterclockwise
Positioning signal for GEB34..1E
Operating voltage (wires 1-6/G-Y1) Clockwise
(wires 1-7/G-Y2) Counterclockwise
Positioning signal for GEB16..1E
Input voltage (wires 8-2/Y-G0) DC 0/
Power consumption 0.1 mA
Input resistance >100 k
Max. permissible input voltage DC 35 V limited internally to DC 10 V
Protected against faulty wiring
Hysteresis for non-adjustable characteristic function 60 mV
for adjustable characteristic function 0.6
Adjustable characteristic (GEB163.1E, GEB164.1E)
Adjustable with 2 potentiometers: Offset Uo
6
Siemens A6V11449860_en--a
Smart Infrastructure 2019-09-10
Outputs
Position indicator
Output signal (GEB16..1E) (wires 9-2/U-G0)
Output signal (GEB36..1E) (wires 9-2/U-G-)
Output voltage U
Max. output current
Protected against faulty wiring
Aux. power supply (G-/G+)
GEB36.. DC 24 V
Feedback potentiometer (for GEB142.1E)
Change in resistance (wires P1-P2)
Load <0.25 W
Max. contact current <0.1 mA
Permissible voltage at potentiometer (SELV/PELV)
Insulation resistance between potentiometer and AC 500 V ~
housing
Connection cables
Cable length 0.9 m
Cross-section 0.75 mm2
Permissible length for signal wires 300 m
Degree of protection of housing IP54 as per EN 60529 (see "Mounting", page 4, and
Mounting instructions A6V11476940)
Environmental conditions
Operation IEC 60721-3-3
Climatic conditions Class 3K5
Mounting location interior, weather-protected
Temperature -
Humidity, non-condensing <95 % r.h.
Transportation IEC 60721-3-2
Climatic conditions Class 2K3
Temperature -
Humidity, non-condensing <95 % r.h.
Storage IEC 60721-3-1
Climatic conditions Class 1K3
Temperature -
Humidity, non-condensing <95 % r.h.
Mechanical conditions Class 2M2
7
Siemens A6V11449860_en--a
Smart Infrastructure 2019-09-10
Standards, directives and approvals
Product standards EN60730
Part 2-14: Particular requirements for electric
actuators
Electromagnetic compatibility (field of use) For residential, commercial, and industrial
environments
EU conformity (CE) A5W00051707 3)
RCM conformity A5W00051708 3)
EAC compliance Eurasian conformity
UL UL as per 60730 http://ul.com/databse
Federal Communications Commission cUL as per CSA-C22.2 No. 24-93
Environmental compatibility
The product environmental declaration A5W00055607 3) contains data on environmentally compatible product
design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal).
Dimensions
Actuator (W x H x D) See "Dimensions" (page 11)
Damper shaft
Round
Square (diagonal) .5 mm
Min. length 20 mm
Max. shaft hardness <300 HV
Weight
Excl. packaging Max. 1.1 kg, without auxiliary switches
Max. 1.3 kg, with auxiliary switches
8
Siemens A6V11449860_en--a
Smart Infrastructure 2019-09-10
Connection diagrams
Internal Diagrams
GEB14..1E GEB34..1E
(open-close, 3-position control) (open-close, 3-position control)
1 6 7 S1 S4
100%
M 5° 85°
M 5° 85°
0%
6 7 4 S2 S3 S5 S6
N
SELV/PELV
III AC 24 V ~ AC 24...250 V ~ / 6 (2) A III AC 24 V ~ AC 24...250 V ~ / 6 (2) A DC 24 V DC 0/2...10 V
DC 24...48 V DC 0/2...10 V DC 12...30 V / 2 A DC 24...48 V DC 0...35 V DC 12...30 V / 2 A AC 100...240 V ~
3 1 8
1 8 1 8
100%
100% 100%
M
M M
0%
0% 0%
N G-
G0 U G0 U
4 2 9
2 9 2 9 N
DC 0/2...10 V
DC 0/2...10 V DC 0/2...10 V
Connection diagrams
)
Open-close, single wire control Open-close, double wire control 3-position control Modulating control
Single pole single throw (SPST) Single pole double throw (SPDT)
AC 24 V ~ AC 24 V ~ AC 24 V ~ AC 24 V ~
DC 24...48 V DC 24...48 V DC 24...48 V DC 24...48 V
G G G
Y1 Y2 Y1 Y2 Y1 Y2 G Y U
G0
AC 24 V ~ AC 24 V ~ AC 24 V ~
DC 24...48 V DC 24...48 V DC 24...48 V
Y1 Y2 Y1 Y2 Y1 Y2
G G G
9
Siemens A6V11449860_en--a
Smart Infrastructure 2019-09-10
Open-close, single wire control Open-close, double wire control 3-position control Modulating control
Single pole single throw (SPST) Single pole double throw (SPDT)
AC 100...240 V ~ AC 100...240 V ~ AC 100...240 V ~
AC 100...240 V ~
Y1 Y2 Y1 Y2 Y1 Y2 L G+ Y U
N N N N G-
N N N N
Cable designations
10
Siemens A6V11449860_en--a
Smart Infrastructure 2019-09-10
Dimensions
min. 60
min. 100
Dimensions in mm
11
Siemens A6V11449860_en--a
Smart Infrastructure 2019-09-10
Appendix to the License Agreement To Use
The AMCA Certified Ratings Program Seal
Appendix No: 8
In accordance with the License Agreement issued on November 21, 2012 by Air Movement and Control
Association International, Inc., SAFID, is hereby authorized to use the AMCA Certified Ratings Seal on the specific
air movement and control devices listed below. Such use shall in all respects be governed by and subject to the
provisions of said License Agreement.
Dampers
Product Line Catalog ID
SPK30-400 Class 1A & Class 1 Low Leakage SPK30-400 January, 2014
Volume Control Damper
*License to Bear the AMCA Seal for Air Leakage, Air Performance
Please verify current certification status in the AMCA International Directory of Licensed Products located at
www.amca.org.
Granted This 18th day of March, 2014.
Lisa R. Ullrich
Certified Ratings Program Manager
AIR MOVEMENT AND CONTROL ASSOCIATION
INTERNATIONAL, INC.
Page 1 of 1
The Free Zones Authority of
the State of Qatar
Reviewed Document / Drawing No.: R49-AMA-MAR-AC-0101 Submittal No. : R49-AMA-MAR-AC-0101 Issued Date : 03 Jan 2023.
2 KEIC-KA Specification R49-AMA-MAR-AC-0101 fully compatible with future BMS interface and connection. C OPEN
Provide reference drawings for the project with highlight on the areas
3 KEIC-KA Area of application R49-AMA-MAR-AC-0101 B Open
where the material shall be used.
4 KEIC-KA Size Size of the damper is subject to the approved drawings R49-AMA-MAR-AC-0101 B OPEN
9 KEIC-KA GSAS Provide compliance with GSAS where applicable R49-AMA-MAR-AC-0101 B OPEN
Reviewed Document / Drawing No.: R49-AMA-MAR-AC-0101 Submittal No. : R49-AMA-MAR-AC-0101 Issued Date : 03 Jan 2023.
Prepared &
Kamal Azayem Sr. Mechanical Engineer
Reviewed by :
Checked by: Anees Gafoor Construction Manager
We SAFID LTD, Doha, QATAR, herewith certify and confirm that M/s. Gulf Facilities Trading & Contracting
W.L.L. located in Qatar is our local dealer and trader of SAFID LTD CO. MAKE PRODUCTS in State of Qatar.
Dampers
Silencers
Acoustic Enclosures
Plenum Boxes
Louvers
Kitchen Hoods
Access Doors
Supports & Bands
Flexible Connectors
Flanges & Accessories
Tapes & Sealants
Develop & manufacture certified products
SAFID Mission
Our mission is to offer our customers and end users a completely
bespoke product line that is reliable in performance and delivery and
is of the highest standard.
SAFID Strategy
Our strategy is to offer the most innovative and complete indoor air
solutions in order to maintain our position as the region’s leading
HVAC manufacturer.
SAFID Positioning
SAFID is well positioned to add real value to projects of all sizes by
offering a reliable custom-made product that meets international
standards of safety and design as well as engineering guidance on
product development.
11
Our Team
Safid currently employs in the GCC area a total work force of over 900
highly qualified staff distributed on the departments as follows:
13
Products & Services
Air Distribution Systems Catalogue
• Spiral Ductwork & Accessories
• Double Wall Ductwork & Accessories
• Oval Ductwork & Accessories
• Oval Double Wall Ductwork & Accessories
• Rectangular Ductwork & Accessories
• Flexible Ductwork & Accessories
• LINDAB Safe Spiral Ductwork & Accessories
• LINDAB Tranfer
• LINDAB Comfort
15
Standards & Certifications
21
2. Industrial/Trade License
><Bar Code
2022/12/04 ﺗﺎﺭﻳﺦ ﺍﻟﻄﺒﺎﻋﺔ:
No 1 of 1 ﺻﻔﺤﺔ ﺭﻗﻢ:
ﺭﺧﺼﺔ ﺗﺠﺎﺭﻳﺔ
**42969
2014/12/09 ﺗﺎﺭﻳﺦ ﺍﺻﺪﺍﺭ ﺍﻟﺮﺧﺼﺔ: 42969 ﺭﻗﻢ ﺍﻟﺮﺧﺼﺔ:
2023/12/09 ﺗﺎﺭﻳﺦ ﺍﻧﺘﻬﺎﺀ ﺍﻟﺮﺧﺼﺔ: ﺷﺮﻛﺔ ﺍﻟﺘﺴﻬﻴﻼﺕ ﺍﻟﺨﻠﻴﺠﻴﺔ ﻟﻠﺘﺠﺎﺭﺓ ﺍﻷﺳﻢ ﺍﻟﺘﺠﺎﺭﻯ:
ﻭﺍﻟﻤﻘﺎﻭﻻﺕ
25454 ﺭﻗﻢ ﺍﻟﺴﺠﻞ ﺍﻟﺘﺠﺎﺭﻯ: ﺷﺮﻛﺔ ﻧﻮﻉ ﺍﻟﻤﻨﺸﺄﺓ ﺍﻟﺘﺠﺎﺭﻳﺔ:
ﺍﻟﺴﻤﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ:
1 These dampers shall be installed in ductwork to maintain a constant air flow regardless of
changes of pressure conditions. The damper shall be suitable for duct velocities ranging
between 2 m/s to 8 m/s and shall operate from a minimum pressure of 20 Pa up to a
maximum of 200 Pa. These dampers shall be installed in branch ducts fitted with high
efficiency particle (HEPA) filters.
1 The Contractor shall furnish and install, control dampers as required for the proper
functioning of the system.
3 Dampers frames shall be formed channels of not less than 1.8 mm galvanized steel with
mounting holes for enclosed duct mounting.
4 Damper blades shall be of not less than 1.5 mm form galvanized steel. Blades on multi-
blade dampers shall not exceed 200 mm in width and 1200 mm in length. Blade shaft
bearings shall be provided at the ends of each blade. Blade side edges shall seal off against
spring stainless steel seals.
6 Dampers shall be suitable for operation within the temperature limit of – 40 C to 93 C.
Horizontal dampers shall have a rated face velocity of 2 m/s at 1500 Pa static pressure
differential.
7 Dampers used for shut off function shall be of the low leakage type.
8 Damper blades shall have neoprene or PVC edging on all outside air dampers.
1 Backdraft dampers shall be low leakage with parallel blades and neoprene edge seals.
2 Damper frames shall be constructed from galvanized sheet steel with aluminium blades.
Bearing shafts shall be stainless steel, in brass bearings.
3 All blades shall be coupled at the blade centres and shall be in width of not more than 1000
mm, with maximum blade size of 200 mm.
3 2
4 Leakage shall not exceed 10 m /h per m at 1000 Pa pressure differential.
5 Pressure relief dampers shall be multi-parallel blade with weighted arm closing assist. The
frame shall be anodised aluminium channel sections with formed aluminium blades.
Maximum blade length shall be 100 mm, and polyester foam seating strips shall be
incorporated on blade edges. Bearing shall be in PVC with non-corrodible shafts.
LIST OF PROPOSED MATERIAL
1/1
SafidDampers
Class 1A & Class 1
Low Leakage Volume Control Damper SPK 30 Series
( Flange Type )
BLADES:
100mm, 125mm and 150mm wide airfoil shaped blades
FINISH:
Frame of mill galvanized.
Blades of mill galvanized.
EXTERNAL LINKAGE:
Galvanized steel side linkage concealed in frame for opposed
blade operation.
CASE BEARING:
Brass bearing as standard.
Sintered bronze oilite (optional).
CONTROL SHAFT:
Description 12mm diameter zinc plated mild steel.
SPK 30-400 Class 1A & Class 1 Low Leakage Volume Control
Dampers are recommended for use in multiple Air Conditioning Units TIP SEAL
with one common air duct system on which one or two A/C Units Bubble type seal.
needs to be isolated during standby mode while the other A/C Unit is For Alr Leakage "Class 1A" and "Class 1".
on operational mode.
SIDE SEAL (Jamb Seal):
In building pressurization it can be used as an isolation damper to
maintain the required pressure in the space. Compression type stainless steel grade 304 to close
gap between frame and blades.
In office buildings where some occupants are outside most of the
time, this type of damper is recommended to shutdown the flow of air
MINIMUM & MAXIMUM SINGLE SECTION SIZE:
when the space is unoccupied on which can save energy
consumption.
100 x 100mm minimum and 900 x 900mm maximum.
It is also being used as a fresh air intake damper for Air Conditioning
Units where it needs a fresh air damper to be closed upon detection
of heavy dust on the fresh air side.
SPK 30 - 410
The blades with airfoil construction provides a low pressure drop in
the open position for smooth airflow and reduced air turbulence.
General construction as type SPK 30-400 damper but with
frame, linkage, case bearing, axles and control shaft are from
stainless steel (Grade 304).
SAFID certifies that the Class 1A & Class 1 Low Leakage Volume Control Damper
shown herein is licensed to bear the AMCA Seal for Model SPK 30-400. The ratings
shown are based on tests and procedures performed in accordance with AMCA
Publication 511 and comply with the requirements of the AMCA Certified Ratings
Program.
The AMCA Certified Ratings Seal applies to Air Leakage and Air Performance Ratings.
Test Information
Tested for air leakage in accordance with ANSI / AMCA Standard 500-D-07,
Figure 5.4. Air leakage is based on operation between 32 ºF and 120 ºF.
Tested for air performance in accordance with ANSI / AMCA Standard 500-D-07
(Pressure Drop), Figure 5.3.
Catalog ID: SPK 30-400 January 23, 2014
Only 150mm blade width is AMCA certified.
1
SafidDampers
Class 1A & Class 1
Low Leakage Volume Control Damper SPK 30 Series
Data are based on a torque of 24.6 in.-lb/ft2 applied to close and seat the damper during the test.
SAFID certifies that the Class 1A & Class 1 Low Leakage Volume Control Damper shown
herein is licensed to bear the AMCA Seal for Model SPK 30-400. The ratings shown are
based on tests and procedures performed in accordance with AMCA Publication 511 and
comply with the requirements of the AMCA Certified Ratings Program.
The AMCA Certified Ratings Seal applies to Air Leakage and Air Performance Ratings.
Test Information
Tested for air leakage in accordance with ANSI / AMCA Standard 500-D-07,
Figure 5.4. Air leakage is based on operation between 32 ºF and 120 ºF.
Tested for air performance in accordance with ANSI / AMCA Standard 500-D-07
(Pressure Drop), Figure 5.3.
Only 150mm blade width is AMCA certified.
Catalog ID: SPK 30-400 January 23, 2014
2
SafidDampers
Class 1A & Class 1
Low Leakage Volume Control Damper SPK 30 Series
Air Performance
Pressure Drop
SAFID certifies that the Class 1A & Class 1 Low Leakage Volume Control Damper shown
herein is licensed to bear the AMCA Seal for Model SPK 30-400. The ratings shown are
based on tests and procedures performed in accordance with AMCA Publication 511 and
comply with the requirements of the AMCA Certified Ratings Program.
The AMCA Certified Ratings Seal applies to Air Leakage and Air Performance Ratings.
Test Information
Tested for air leakage in accordance with ANSI / AMCA Standard 500-D-07,
Figure 5.4. Air leakage is based on operation between 32 ºF and 120 ºF.
Tested for air performance in accordance with ANSI / AMCA Standard 500-D-07
(Pressure Drop), Figure 5.3.
Only 150mm blade width is AMCA certified.
Catalog ID: SPK 30-400 January 23, 2014
3
SafidDampers
Class 1A & Class 1
Low Leakage Volume Control Damper SPK 30 Series
Air Performance
Pressure Drop
SAFID certifies that the Class 1A & Class 1 Low Leakage Volume Control Damper shown
herein is licensed to bear the AMCA Seal for Model SPK 30-400. The ratings shown are
based on tests and procedures performed in accordance with AMCA Publication 511 and
comply with the requirements of the AMCA Certified Ratings Program.
The AMCA Certified Ratings Seal applies to Air Leakage and Air Performance Ratings.
Test Information
Tested for air leakage in accordance with ANSI / AMCA Standard 500-D-07,
Figure 5.4. Air leakage is based on operation between 32 ºF and 120 ºF.
Tested for air performance in accordance with ANSI / AMCA Standard 500-D-07
(Pressure Drop), Figure 5.3.
Only 150mm blade width is AMCA certified.
Catalog ID: SPK 30-400 January 23, 2014
4
SafidDampers
Class 1A & Class 1
Low Leakage Volume Control Damper SPK 30 Series
Air Performance
Pressure Drop
SAFID certifies that the Class 1A & Class 1 Low Leakage Volume Control Damper shown
herein is licensed to bear the AMCA Seal for Model SPK 30-400. The ratings shown are
based on tests and procedures performed in accordance with AMCA Publication 511 and
comply with the requirements of the AMCA Certified Ratings Program.
The AMCA Certified Ratings Seal applies to Air Leakage and Air Performance Ratings.
Test Information
Tested for air leakage in accordance with ANSI / AMCA Standard 500-D-07,
Figure 5.4. Air leakage is based on operation between 32 ºF and 120 ºF.
Tested for air performance in accordance with ANSI / AMCA Standard 500-D-07
(Pressure Drop), Figure 5.3.
Only 150mm blade width is AMCA certified.
Catalog ID: SPK 30-400 January 23, 2014
5
SafidDampers
Class 1A & Class 1
Low Leakage Volume Control Damper SPK 30 Series
Dimensions
1 - Casing 3 - Side Linkage 5 - Tip Seal 7 - Bearing
2 - Actuator 4 - Blade 6 - Side Seal (Jamb Seal) 8 - Landing Angles
6
SafidDampers
Class 1A & Class 1
Low Leakage Volume Control Damper SPK 30 Series
Materials - Construction
Axle and Drive Shaft fixing details Mounting Bracket for Actuator
7
SafidDampers
Class 1A & Class 1
Low Leakage Volume Control Damper SPK 30 Series
Installation Details
Damper to Slide on Flange connection Damper to Angle Flange connection
8
SafidDampers
Class 1A & Class 1
Low Leakage Volume Control Damper SPK 30 Series
Order Details
Order Code
Blade Operation
OB = Opposed Blades operation
External Controls
* R = Right hand (Standard Supply)
Variants - Bearings L = Left Hand
*B = Brass case bearing (Standard Supply)
B1 = Sintered bronze (oilite) case bearing
ORDER EXAMPLE
STANDARD
Make: SAFID
1. Type : SPK 30 - 400 - OB - B - R - 900 x 900 - A
2. Type : SPK 30 - 400 - OB - B1 - R - 900 x 900 - A
9
OpenAir™
2 Nm nominal torque
Operating voltage AC 24 V ~ / DC 24…48 V or AC 100…240 V ~
Prewired with 0.9 m connecting cable
Gear train disengagement button for manual adjustment
Position indication
Auxiliary switches for auxiliary functions
30
A6V10636055_en--_e Siemens
2019-03-21 Building Technologies
Features
The rotary actuator drives the damper to the desired operating position after connecting the
operating voltage.
Brushless, robust DC motors ensure reliable operation regardless of load.
The rotary actuators do not require an end position switch, are overload proof, and remain
in place upon reaching the end stop.
The gears are maintenance free and low noise.
Simple and reliable shaft integration.
Mounting bracket included.
Use
Non-spring return rotary actuators. Application in ventilation and air conditioning plants to
operate air dampers and air throttles.
For damper areas up to 0.3 m 2, friction dependent.
Suitable for use with modulating controllers (DC 0/2...10 V), open-close or three-position
controllers.
For directly driven zone dampers to control air flow in air ducts.
We recommend a minimum pulse length of 500 ms on rotary actuators operated with
3-point control to ensure continuous and accurate operation.
Functions
AC 24 V ~ / GSD14..1A GSD16..1A
Type DC 24…48 V
AC 100…240 V ~ GSD34..1A GSD361.1A
2 / 10
Siemens A6V10636055_en--_e
Building Technologies 2019-03-21
Technical design/mechanical design
Housing
The housing consists essentially of flame retardant, non brominated, non chlorinated glass
fibre reinforced plastic.
Type summary
Type Stock number Control Operating Positioning Position Aux. Rotary Aux.
voltage signal Y indicator U = switches direction power supply
DC 0/2...10 V switch
GSD141.1A S55499-D281 AC 24 V ~ /
Open- DC 24…48 V
GSD146.1A S55499-D227 close 2
or three- yes
GSD341.1A S55499-D282
position AC 100…240 V ~
GSD346.1A S55499-D230 2
GSD161.1A S55499-D228 AC 24 V ~ / yes
GSD166.1A S55499-D229 Modulating DC 24…48 V DC 0/2...10 V yes 2 yes
GSD361.1A S55499-D231 AC 100…240 V ~ yes yes
Product documentation
Notes
Safety
Caution
Engineering
Auxiliary switches
Auxiliary switches cannot be added in the field.
3 / 10
A6V10636055_en--_e Siemens
2019-03-21 Building Technologies
Technical data
Functional data
Nominal torque 2 Nm
Maximum torque 5 Nm
Nominal rotational angle 90°
Maximum rotational angle (mechanically limited) 95° ± 2°
Runtime at nominal rotational angle 90° 30 s
Duty cycle 100 %
Direction of rotation Clockwise / counterclockwise
Mechanical life 100 000 cycles
Actuator sound power level 35 dB(A)
Inputs
Positioning signal for GSD14..1A
Operating voltage (wires 1-6/G-Y1) clockwise
AC 24 V ~ / DC 24…48 V (wires 1-7/G-Y2) counterclockwise
Positioning signal for GSD34..1A
Operating voltage (wires 4-6/N-Y1) clockwise
AC 100…240 V ~ (wires 4-7/N-Y2) counterclockwise
Positioning signal for GSD16..1.A
Input voltage (wires 8-2/Y-G0) DC 0/2…10 V
Current consumption 0.1 mA
Input resistance >100 k
Outputs
Position indicator
Output signal (GSD16..1.A) (wires 9-2/U-G0)
Output signal (GSD361.1.A) (wires 9-2/U-G-)
Output voltage U DC 0...10 V
Max. output current DC ±1 mA
Protected against faulty wiring max. AC 24 V ~ / DC 24…48 V
Aux. power supply (GSD361.1A) (wires 1-2/G+-G-) DC 24 V ±20 %, max. 10 mA
Auxiliary switches
Switching voltage AC 24…250 V ~ / DC 12…30 V
Contact rating 6 A resistive, 2 A inductive, min. 10 mA @ AC
4 A resistive, 2 A inductive, min. 10 mA @ DC 30 V
0.8 A res., 0.5 A inductive, min. 10 mA @ DC 60 V
Electric strength auxiliary switches against housing AC 4 kV
Factory switches setting: Switch A / Switch B 5° / 85° (fixed position)
5 / 10
A6V10636055_en--_e Siemens
2019-03-21 Building Technologies
Connection cables
Cable length 0.9 m
2
Cross-section 0.75 mm
Degree of protection
Insulation protective class As per EN 60730
AC 24 V ~ / DC 24…48 V III
AC 100…240 V ~ II
Housing protection IP54 as per EN 60529
Environmental conditions
Operation IEC 60721-3-3
Climatic conditions Class 3K5
Mounting location Interior, weather-protected
Temperature (extended) -32...+55 °C
Humidity, non-condensing <95 % r.F.
Transportation IEC 60721-3-2
Climatic conditions Class 2K3
Temperature (extended) -32...+70 °C
Humidity, non-condensing <95 % r.F.
Storage IEC 60721-3-1
Climatic conditions Class 1K3
Temperature (extended) -32...+50 °C
Humidity, non-condensing <95 % r.F.
Mechanical conditions Class 2M2
Environmental compatibility
2)
The product environmental declaration A5W00030346-A contains data on environmentally compatible product
design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal).
Dimensions
Actuator W x H x D See "Dimensions” p. 9
Damper shaft
round 8…15 mm
Square 6…11 mm
Min. shaft length 20 mm
Shaft hardness <300 HV
Weight
Excl. packaging Max. 0.55 kg, without switches
Max. 0.7 kg, with switches
1)
Permitted only to DC 30 V
2)
The documents can be downloaded from http://siemens.com/bt/download.
6 / 10
Siemens A6V10636055_en--_e
Building Technologies 2019-03-21
Diagrams
Internal Diagrams
AC 24 V ~ / DC 24…48 V AC 100…240 V ~
III
AC 24 V ~ AC 24...250 V ~ / 6 (2) A AC 24...250 V ~ / 6 (2) A
DC 24...48 V DC 12...30 V / 2 A AC 100...240 V ~ DC 12...30 V / 2 A
1 S1 S4 6 7 S1 S4
M 1) 1)
M
6 7 S2 S3 S5 S6 4 S2 S3 S5 S6
N
AC 24 V ~ / DC 24…48 V AC 100…240 V ~
100%
1) 100%
M M
0% 0%
G0 U N G-
2 9 4 2 9
N
DC 0/2...10 V DC 0/2...10 V
1)
Actuator Switch A Switch B
Position Common S1 Common S4
connected to connected to
0°…5° S3 S6
5°…85° S2 S6
85°…90° S2 S5
7 / 10
A6V10636055_en--_e Siemens
2019-03-21 Building Technologies
Connection diagrams
Open-close, single wire control Open-close, two wire control Three-position control Modulating control
Single Pole Single Throw (SPST) Single Pole Double Throw (SPDT)
AC 24 V ~ AC 24 V ~ AC 24 V ~ AC 24 V ~
DC 24...48 V DC 24...48 V DC 24...48 V DC 24...48 V
G G G
Y1 Y2 Y1 Y2 Y1 Y2 G Y U
G0
AC 24 V ~ AC 24 V ~ AC 24 V ~
DC 24...48 V DC 24...48 V DC 24...48 V
Y1 Y2 Y1 Y2 Y1 Y2
G G G
Open-close, single wire control Open-close, two wire control Three-position control Modulating control
Single Pole Single Throw (SPST) Single Pole Double Throw (SPDT)
Y1 Y2 Y1 Y2 Y1 Y2 L G+ Y U
N N N N G-
N N N N
Cable labeling
8 / 10
Siemens A6V10636055_en--_e
Building Technologies 2019-03-21
Dimensions
Dimensions in mm
9 / 10
A6V10636055_en--_e Siemens
2019-03-21 Building Technologies
s
OpenAir™
● Nominal torque 5 Nm
● Operating voltage AC 24 V ~ / DC 24…48 V ⎓ or AC 100…240 V ~
● Mechanically adjustable span between 0...90°
● Pre-wired with 0.9 m long connection cables
● Type-specific variations with adjustable offset and span for
the positioning signal
● Position indication: mechanical and electrical
● Feedback potentiometer
● Self-adaption of rotational angle range and adjustable auxiliary switches for
supplementary functions
30
A6V10636149_en--_b Siemens
2016-12-14 Building Technologies
Use
The rotary actuators are used in ventilation and air conditioning plants to regulate and shut
off air dampers:
● For damper areas up to 0.8 m2 (guideline, always observe damper manufacturer’s data).
● Suitable for use with modulating controllers (DC 0/2...10 V), open-close or three-position
controllers for air dampers or air throttles.
● We recommend a minimum pulse length of 500 ms on rotary actuators operated with 3-
point control to ensure continuous and accurate operation.
Functions
GD..1ERW_Z08
GD..1E_Z06
0... 0 0... 0
Technical design
Housing
The housing consists essentially of flame retardant, non brominated, non chlorinated glass
fibre reinforced plastic.
2 / 10
Siemens A6V10636149_en--_b
Building Technologies 2016-12-14
Actuator motor / Gears
● Brushless, robust DC motors ensure reliable operation regardless of load. The damper
actuators do not require an end position switch, are overload proof, and remain in place
upon reaching the end stop.
● The gears are maintenance free and low noise.
Type summary
Type Stock no. Control Operating Positioning Position Feedback Self-adaption Aux. Rotary
voltage signal Y indicator U = potentio- of rotational switches direction
DC 0…10 V ⎓ meter 5 kΩ angle range switch
GDB141.1E S55499-D184 ‒
Open- AC 24 V ~ / ‒
GDB142.1E S55499-D185 yes
close DC 24…48 V ⎓
GDB146.1E S55499-D186 or ‒ ‒ ‒ 2 yes
three-
GDB341.1E S55499-D187 ‒ ‒
position AC 100…240 V ~
GDB346.1E S55499-D188 2
Accessories
See data sheet N4698
Product documentation
Notes
Safety
Caution
3 / 10
A6V10636149_en--_b Siemens
2016-12-14 Building Technologies
Engineering
Potentiometer and auxiliary switches
Potentiometer and auxiliary switches cannot be added in the field
Installation
WARNING
Maintenance
Disposal
Technical data
Function data
Nominal torque 5 Nm
Maximum torque (blocked) 10 Nm
Minimum holding torque 5 Nm
Nominal rotary angle (with position indication) 90°
Maximum rotary angle (mechanic limitation) 95° ± 2°
Runtime for 90° rotary angle 150 s
Actuator sound power level 28 dB(A)
1)
C-UL: Permitted only to DC 30 V ⎓
4 / 10
Siemens A6V10636149_en--_b
Building Technologies 2016-12-14
Inputs
Positioning signal for GDB14..1E
Operating voltage (wires 1-6/G-Y1) clockwise
AC 24 V ~ / DC 24…48 V ⎓ (wires 1-7/G-Y2) counterclockwise
Positioning signal for GDB34..1E
Operating voltage (wires 4-6/N-Y1) clockwise
AC 100…240 V ~ (wires 4-7/N-Y2) counterclockwise
Positioning signal for GDB16..1.E
Input voltage (wires 8-2/Y-G0) DC 0/2…10 V ⎓
Current consumption 0.1 mA
Input resistance >100 kW
Max. permissible input voltage DC 35 V ⎓ limited to DC 10 V ⎓
Protected against faulty wiring max. AC 24 V ~ / DC 24…48 V ⎓
Hysteresis for non-adjustable characteristic function 60 mV
for adjustable characteristic function 0.6 % of ∆U
Adjustable characteristic function (GDB163.1E, GDB164.1E)
Adjustable with 2 potentiometers: Offset Uo DC 0…5 V ⎓
Span ∆U DC 2…30 V ⎓
Max. input voltage DC 35 V ⎓
Protected against faulty wiring max. AC 24 V ~ / DC 24…48 V ⎓
Outputs
Position indicator
Output signal (GDB16..1E) (wires 9-2/U-G0)
Output signal (GDB36..1E) (wires 9-2/U-G-)
Output voltage U DC 0...10 V ⎓
Max. output current DC ±1 mA
Protected against faulty wiring max. AC 24 V ~ / DC 24…48 V ⎓
Aux. power supply (G- / G+)
GDB36.. DC 24 V ⎓ ±20 %, max. 10 mA
Feedback potentiometer (for GDB142.1E)
Change of resistance (wires P1-P2) 0…5000 W
Load <0.25 W
Max. sliding contact current <10 mA
Permissible voltage at potentiometer (SELV/PELV) AC 24 V ~ / DC 24…48 V ⎓
Insulation resistance between potentiometer and
housing AC 500 V ~
Connection cables
Cable length 0.9 m
2
Cross section of prewired connection cables 0.75 mm
Permissible length for signal lines 300 m
Degree of protection
Insulation class As per EN 60730
AC 24 V ~ / DC 24…48 V ⎓, feedback potentiometer III
AC 100…240 V ~, auxiliary switches II
Housing protection IP 54 as per EN 60529
5 / 10
A6V10636149_en--_b Siemens
2016-12-14 Building Technologies
Environmental conditions
Operation IEC 60721-3-3
Climatic conditions Class 3K5
Mounting location interior, weather-protected
Temperature extended -32…+55 °C
Humidity (non-condensing) <95 % r.F.
Transport IEC 60721-3-2
Climatic conditions Class 2K3
Temperature extended -32…+70 °C
Humidity (non-condensing) <95 % r.F.
Storage IEC 60721-3-1
Climatic conditions Class 1K3
Temperature extended -32…+50 °C
Humidity (non-condensing) <95 % r.F.
Mechanical conditions Class 2M2
Environmental compatibility
2)
The product environmental declaration A5W00026066 contains data on environmentally compatible product
design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal).
Dimensions
Actuator W x H x D see „Dimensions“, p. 9
Damper shaft
round 8…16 mm
round 8…10 mm (with centering element)
Square 6…12.8 mm
Min. shaft length 20 mm
Shaft hardness <300 HV
Weight
Without packaging Max. 0.49 kg, without switches
Max. 0.63 kg, with switches
2)
The documents can be downloaded from http://siemens.com/bt/download.
6 / 10
Siemens A6V10636149_en--_b
Building Technologies 2016-12-14
Diagrams
Internal Diagrams
GDB14..1E (open-close, three-p.) GDB34..1E (open-close, three-p.)
AC 24 V ~ / DC 24…48 V ⎓ AC 100…240 V ~
Connection diagrams
GDB1..1E (AC 24 V ~ / DC 24…48 V ⎓)
Open-close, single wire control Open-close, two wire control Three-position control Modulating control
Single Pole Single Throw (SPST) Single Pole Double Throw (SPDT)
7 / 10
A6V10636149_en--_b Siemens
2016-12-14 Building Technologies
GDB3.. 1E (AC 100…240 V ~)
Open-close, single wire control Open-close, two wire control Three-position control Modulating control
Single Pole Single Throw (SPST) Single Pole Double Throw (SPDT)
Cable labeling
8 / 10
Siemens A6V10636149_en--_b
Building Technologies 2016-12-14
Dimensions
2.7
x
4.5
max 95°
68
50
min. 6
4634M01
min. 60
min.
Dimensions in mm
Revision numbers
Type Valid from rev. no. Type Valid from rev. no.
GDB141.1E ..B GDB164.1E ..B
GDB142.1E ..B GDB166.1E ..B
GDB146.1E ..B GDB361.1E ..B
GDB161.1E ..B GDB341.1E ..B
GDB163.1E ..B GDB346.1E ..B
9 / 10
A6V10636149_en--_b Siemens
2016-12-14 Building Technologies
s
OpenAir™
● Nominal torque 10 Nm
● Operating voltage AC 24 V ~ / DC 24…48 V ⎓ or AC 100…240 V ~
● Mechanically adjustable span between 0...90°
● Pre-wired with 0.9 m long connection cables
● Type-specific variations with adjustable offset and span for
the positioning signal
● Position indication: mechanical and electrical
● Feedback potentiometer
● Self-adaption of rotational angle range and adjustable auxiliary switches for
supplementary functions
30
A6V10636202_en--_b Siemens
2016-12-14 Building Technologies
Use
The rotary actuators are used in ventilation and air conditioning plants to regulate and shut
off air dampers:
● For damper areas up to 1.6 m2 (guideline, always observe damper manufacturer’s data).
● Suitable for use with modulating controllers (DC 0/2...10 V), open-close or three-position
controllers for air dampers or air throttles.
● We recommend a minimum pulse length of 500 ms on rotary actuators operated with 3-
point control to ensure continuous and accurate operation.
Functions
AC 24 V ~ /
141.1E / 142.1E / 146.1E 161.1E / 163.1E / 164.1E / 166.1E
GLB.. DC 24…48 V ⎓
AC 100…240 V ~ 341.1E / 346.1E 361.1E
Control type Open-close / three-position Modulating control (0/2…10 V)
Rotary direction Clockwise or counter-clockwise direction depends …
… on the type of control … on the setting of the rotary direction DIL
… on the setting of the rotary direction switch
switch. cw ccw
cw ccw 2... 2...
GD..1ERW_Z08
GD..1E_Z06
0... 0 0... 0
Technical design
Components
The housing consists essentially of flame retardant, non brominated, non chlorinated glass
fibre reinforced plastic.
2 / 10
Siemens A6V10636202_en--_b
Building Technologies 2016-12-14
Actuator motor / Gears
● Brushless, robust DC motors ensure reliable operation regardless of load. The damper
actuators do not require an end position switch, are overload proof, and remain in place
upon reaching the end stop.
● The gears are maintenance free and low noise.
Type summary
Type Stock no. Control Operating Positioning Position Feedback Self-adaption Aux. Rotary
voltage signal Y indicator U = potentio- of rotational switches direction
DC 0…10 V ⎓ meter 5 kΩ angle range switch
GLB141.1E S55499-D192 ‒
Open- AC 24 V ~ / ‒
GLB142.1E S55499-D193 yes
close DC 24…48 V ⎓
GLB146.1E S55499-D194 or ‒ ‒ ‒ 2 yes
three-
GLB341.1E S55499-D195 ‒ ‒
position AC 100…240 V ~
GLB346.1E S55499-D196 2
Accessories
See data sheet N4698
Product documentation
Notes
Safety
Caution
3 / 10
A6V10636202_en--_b Siemens
2016-12-14 Building Technologies
Engineering
Potentiometer and auxiliary switches
Potentiometer and auxiliary switches cannot be added in the field.
Installation
WARNING
Maintenance
Disposal
Technical data
Function data
Nominal torque 10 Nm
Maximum torque (blocked) 16 Nm
Minimum holding torque 10 Nm
Nominal rotary angle (with position indication) 90°
Maximum rotary angle (mechanic limitation) 95° ± 2°
Runtime for 90° rotary angle 150 s
Actuator sound power level 28 dB(A)
1)
C-UL: Permitted only to DC 30 V ⎓
4 / 10
Siemens A6V10636202_en--_b
Building Technologies 2016-12-14
Inputs
Positioning signal for GLB14..1E
Operating voltage AC/DC 24 V (wires 1-6/G-Y1) clockwise
AC 24 V ~ / DC 24…48 V ⎓ (wires 1-7/G-Y2) counterclockwise
Positioning signal for GLB34..1E
Operating voltage (wires 4-6/N-Y1) clockwise
AC 100…240 V ~ (wires 4-7/N-Y2) counterclockwise
Positioning signal for GLB16..1.E
Input voltage (wires 8-2/Y-G0) DC 0/2…10 V ⎓
Current consumption 0.1 mA
Input resistance >100 kW
Max. permissible input voltage DC 35 V ⎓ limited to DC 10 V ⎓
Protected against faulty wiring max. AC 24 V ~ / DC 24…48 V ⎓
Hysteresis for non-adjustable characteristic function 60 mV
for adjustable characteristic function 0.6 % of ∆U
Adjustable characteristic function (GLB163.1E, GLB164.1E)
Adjustable with 2 potentiometers: Offset Uo DC 0…5 V ⎓
Span ∆U DC 2…30 V ⎓
Max. input voltage DC 35 V ⎓
Protected against faulty wiring max. AC 24 V ~ / DC 24…48 V ⎓
Outputs
Position indicator
Output signal (GLB16..1E) (wires 9-2/U-G0)
Output signal (GLB36..1E) (wires 9-2/U-G-)
Output voltage U DC 0...10 V ⎓
Max. output current DC ±1 mA
Protected against faulty wiring max. AC 24 V ~ / DC 24…48 V ⎓
Aux. power supply (G- / G+)
GLB36.. DC 24 V ⎓ ±20 %, max. 10 mA
Feedback potentiometer (for GLB142.1E)
Change of resistance (wires P1-P2) 0…5000 W
Load <0.25 W
Max. sliding contact current <10 mA
Permissible voltage at potentiometer (SELV/PELV) AC 24 V ~ / DC 24…48 V ⎓
Insulation resistance between potentiometer and
housing AC 500 V ~
Connection cables
Cable length 0.9 m
2
Cross section of prewired connection cables 0.75 mm
Permissible length for signal lines 300 m
Degree of protection
Insulation class As per EN 60730
AC 24 V ~ / DC 24…48 V ⎓, feedback potentiometer III
AC 100…240 V ~, auxiliary switches II
Housing protection IP 54 as per EN 60529
5 / 10
A6V10636202_en--_b Siemens
2016-12-14 Building Technologies
Environmental conditions
Operation IEC 60721-3-3
Climatic conditions Class 3K5
Mounting location interior, weather-protected
Temperature extended -32…+55 °C
Humidity (non-condensing) <95 % r.F.
Transport IEC 60721-3-2
Climatic conditions Class 2K3
Temperature extended -32…+70 °C
Humidity (non-condensing) <95 % r.F.
Storage IEC 60721-3-1
Climatic conditions Class 1K3
Temperature extended -32…+50 °C
Humidity (non-condensing) <95 % r.F.
Mechanical conditions Class 2M2
Environmental compatibility
2)
The product environmental declaration A5W00026066 contains data on environmentally compatible product
design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal).
Dimensions
Actuator W x H x D see „Dimensions“, p. 9
Damper shaft
round 8…16 mm
round 8…10 mm (with centering element)
Square 6…12.8 mm
Min. shaft length 20 mm
Shaft hardness <300 HV
Weight
Without packaging Max. 0.49 kg, without switches
Max. 0.63 kg, with switches
2)
The documents can be downloaded from http://siemens.com/bt/download.
6 / 10
Siemens A6V10636202_en--_b
Building Technologies 2016-12-14
Diagrams
Internal Diagrams
GLB14..1E (open-close, three-p.) GLB34..1E (open-close, three-p.)
AC 24 V ~ / DC 24…48 V ⎓ AC 100…240 V ~
Connection diagrams
GLB1.. 1E (AC 24 V ~ / DC 24…48 V ⎓)
Open-close, single wire control Open-close, two wire control Three-position control Modulating control
Single Pole Single Throw (SPST) Single Pole Double Throw (SPDT)
7 / 10
A6V10636202_en--_b Siemens
2016-12-14 Building Technologies
GLB3.. 1E (AC 100…240 V ~)
Open-close, single wire control Open-close, two wire control Three-position control Modulating control
Single Pole Single Throw (SPST) Single Pole Double Throw (SPDT)
Cable labeling
8 / 10
Siemens A6V10636202_en--_b
Building Technologies 2016-12-14
Dimensions
2.7
x
4.5
max 95°
68
50
min. 6
4634M01
min. 60
Dimensions in mm min.
Revision numbers
Type Valid from rev. no. Type Valid from rev. no.
GLB141.1E ..B GLB164.1E ..B
GLB142.1E ..B GLB166.1E ..B
GLB146.1E ..B GLB361.1E ..B
GLB161.1E ..B GLB341.1E ..B
GLB163.1E ..B GLB346.1E ..B
9 / 10
A6V10636202_en--_b Siemens
2016-12-14 Building Technologies
OpenAir™
● Nominal torque 20 Nm
● Operating voltage AC 24 V ~ / DC 24…48 V ⎓ or AC 100…240 V ~
● Mechanically adjustable span between 0…90°
● Pre-wired with standard 0.9 m connection cables
● Type-specific variations with adjustable offset and span for
the positioning signal
● Position indication: Mechanical and electrical
● Feedback potentiometer
● Self-adaption of the rotation angle range and adjustable auxiliary switches
for supplemental functions
Functions
0 0... 0 0...
The actuator remains in the respective … on the positioning signal.
position with no power applied.
The actuator remains in the deployed
position:
…if the positioning signal is maintained at a
cw = Clockwise constant value
ccw = Counterclockwise …in the event of power loss
Position indication
Rotation angle position indication using a position indicator.
Mechanical
Position indication By connecting the feedback potentio- Position indicator: Output voltage
Electric meter to external voltage, output voltage U = DC 0/2…10 V is generated proportional
is generated proportional to rotation to rotation angle.
angle. The direction of rotation (inverted or non-
inverted) for output voltage U is based on
the DIL switch position.
Auxiliary switch The switching points for auxiliary switches A and B can be set independently in
increments of 5° from 0 to 90°.
Self-adaptation of the The actuator automatically determines the
rotation angle range mechanical end positions of the rotation
angle range.
The characteristic function (Uo, ΔU) is
-
mapped to the calculated rotation angle
range.
Power must be connected to DIL switch 2
(self-adaptation) for the function to operate.
Manual adjustment The actuator can be manually adjusted by pressing the gear train disengagement
button.
Rotation angle limitation A set screw can limit the rotation angle to between 0° and 90°.
2
Siemens A6V11449860_en--a
Smart Infrastructure 2019-09-10
Technical design
Housing
● Robust and light cast aluminum housing. The housing guarantees long life, even under
harsh ambient conditions.
Actuator / gears
● Brushless, robust DC motors ensure reliable operation regardless of load. The damper
actuators do not require an end position switch, are overload proof, and remain in place
upon reaching the end stop.
● The gears are maintenance free and low noise.
Type summary
Type Stock number Open-loop Operating Positioning Position Feedback Self-adapting Auxili- Rotation
control voltage signal input Y indicator potentio- rotation angle ary direction
U = DC meter ranges switch switch
0…10 V ⎓ 5 kΩ
GEB141.1E S55499-D329 -
AC 24 V ~ / -
GEB142.1E S55499-D330 Yes
DC 24…48 V ⎓
2- or 3-
GEB146.1E S55499-D331 - - - 2 Yes
position
GEB341.1E S55499-D336 - -
AC 100…240 V ~
GEB346.1E S55499-D337 2
Accessories/spare parts
See data sheet N4697
Product documentation
Data sheet Accessory and spare parts for air damper actuators N4697
3
Siemens A6V11449860_en--a
Smart Infrastructure 2019-09-10
Notes
Safety
CAUTION
Engineering
Mounting
Shaft connection
When mounting, comply with the notes on shaft diameters and damper surface areas in
Technical data (page 8) and use only quality materials typical to the sector for the damper
shaft.
Installation
WARNING
Maintenance
The GEB..1E actuators are maintenance-free.
4
Siemens A6V11449860_en--a
Smart Infrastructure 2019-09-10
Disposal
5
Siemens A6V11449860_en--a
Smart Infrastructure 2019-09-10
Technical data
Function data
Nominal torque 20 Nm
Maximum torque (when blocked) 35 Nm 2)
Minimum holding torque 20 Nm
Nominal rotation angle (with position indication) 90°
Maximum rotation angle (mechanically limited) 95° ± 2°
Runtime at nominal rotation angle 90° 150 s
Actuator sound power level (at a positioning time of 150 s) <35 dB(A)
Inputs
Positioning signal for GEB14..1E
Operating voltage (wires 1-6/G-Y1) Clockwise
AC 24 V ~ / DC 24…48 V ⎓ (wires 1-7/G-Y2) Counterclockwise
Positioning signal for GEB34..1E
Operating voltage (wires 1-6/G-Y1) Clockwise
AC 100…240 V ~ (wires 1-7/G-Y2) Counterclockwise
Positioning signal for GEB16..1E
Input voltage (wires 8-2/Y-G0) DC 0/2…10 V ⎓
Power consumption 0.1 mA
Input resistance >100 kΩ
Max. permissible input voltage DC 35 V ⎓ limited internally to DC 10 V ⎓
Protected against faulty wiring Max. AC 24 V ~/ DC 24…48 V ⎓
Hysteresis for non-adjustable characteristic function 60 mV
for adjustable characteristic function 0.6 % of ΔU
Adjustable characteristic (GEB163.1E, GEB164.1E)
Adjustable with 2 potentiometers: Offset Uo DC 0…5 V ⎓
Span ΔU DC 2…30 V ⎓
Max. input voltage DC 35 V ⎓
Protected against faulty wiring Max. AC 24 V ~ / DC 24…48 V ⎓
6
Siemens A6V11449860_en--a
Smart Infrastructure 2019-09-10
Outputs
Position indicator
Output signal (GEB16..1E) (wires 9-2/U-G0)
Output signal (GEB36..1E) (wires 9-2/U-G-)
Output voltage U DC 0…10 V ⎓
Max. output current DC ± 1 mA
Protected against faulty wiring Max. AC 24 V ~/ DC 24…48 V ⎓
Aux. power supply (G-/G+)
GEB36.. DC 24 V ⎓ ± 20 %, max. 10 mA
Feedback potentiometer (for GEB142.1E)
Change in resistance (wires P1-P2) 0…5000 Ω
Load <0.25 W
Max. contact current <0.1 mA
Permissible voltage at potentiometer (SELV/PELV) AC 24 V ~ / DC 24…48 V ⎓
Insulation resistance between potentiometer and AC 500 V ~
housing
Connection cables
Cable length 0.9 m
Cross-section 0.75 mm2
Permissible length for signal wires 300 m
Environmental conditions
Operation IEC 60721-3-3
Climatic conditions Class 3K5
Mounting location interior, weather-protected
Temperature -32…55 °C
Humidity, non-condensing <95 % r.h.
Transportation IEC 60721-3-2
Climatic conditions Class 2K3
Temperature -32…70 °C
Humidity, non-condensing <95 % r.h.
Storage IEC 60721-3-1
Climatic conditions Class 1K3
Temperature -32…50 °C
Humidity, non-condensing <95 % r.h.
Mechanical conditions Class 2M2
7
Siemens A6V11449860_en--a
Smart Infrastructure 2019-09-10
Standards, directives and approvals
Product standards EN60730
Part 2-14: Particular requirements for electric
actuators
Electromagnetic compatibility (field of use) For residential, commercial, and industrial
environments
EU conformity (CE) A5W00051707 3)
RCM conformity A5W00051708 3)
EAC compliance Eurasian conformity
UL UL as per 60730 http://ul.com/databse
Federal Communications Commission cUL as per CSA-C22.2 No. 24-93
Environmental compatibility
The product environmental declaration A5W00055607 3) contains data on environmentally compatible product
design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal).
Dimensions
Actuator (W x H x D) See "Dimensions" (page 11)
Damper shaft
Round 8…20.5 mm
Square (diagonal) 8…14.5 mm
Min. length 20 mm
Max. shaft hardness <300 HV
Weight
Excl. packaging Max. 1.1 kg, without auxiliary switches
Max. 1.3 kg, with auxiliary switches
NOTICE
8
Siemens A6V11449860_en--a
Smart Infrastructure 2019-09-10
Connection diagrams
Internal Diagrams
GEB14..1E GEB34..1E
(open-close, 3-position control) (open-close, 3-position control)
AC 24 V ~ / DC 24…48 V ⎓ AC 100…240 V ~
1 6 7 S1 S4
(Q21)
(a)
(b)
(c)
(Q21)
(Q11)
(Q11)
100%
M 5° 85°
M 5° 85°
0%
(Q12)
(Q14)
(Q22)
(Q24)
(Q12)
(Q14)
(Q22)
(Q24)
6 7 4 S2 S3 S5 S6
N
SELV/PELV
III AC 24 V ~ AC 24...250 V ~ / 6 (2) A III AC 24 V ~ AC 24...250 V ~ / 6 (2) A DC 24 V DC 0/2...10 V
DC 24...48 V DC 0/2...10 V DC 12...30 V / 2 A DC 24...48 V DC 0...35 V DC 12...30 V / 2 A AC 100...240 V ~
3 1 8
1 8 1 8
(Q21)
(Q21)
(Q11)
(Q11)
100%
100% 100%
M
M M
0%
0% 0%
(Q12)
(Q14)
(Q22)
(Q24)
(Q12)
(Q14)
(Q22)
(Q24)
N G-
G0 U G0 U
4 2 9
2 9 2 9 N
DC 0/2...10 V
DC 0/2...10 V DC 0/2...10 V
Connection diagrams
Control on GEB1..1E (AC 24 V ~ / DC 24…48 V ⎓)
Open-close, single wire control Open-close, double wire control 3-position control Modulating control
Single pole single throw (SPST) Single pole double throw (SPDT)
AC 24 V ~ AC 24 V ~ AC 24 V ~ AC 24 V ~
DC 24...48 V DC 24...48 V DC 24...48 V DC 24...48 V
G G G
Y1 Y2 Y1 Y2 Y1 Y2 G Y U
G0
AC 24 V ~ AC 24 V ~ AC 24 V ~
DC 24...48 V DC 24...48 V DC 24...48 V
Y1 Y2 Y1 Y2 Y1 Y2
G G G
9
Siemens A6V11449860_en--a
Smart Infrastructure 2019-09-10
Control on GEB3..1E (AC 100…240 V ~)
Open-close, single wire control Open-close, double wire control 3-position control Modulating control
Single pole single throw (SPST) Single pole double throw (SPDT)
AC 100...240 V ~ AC 100...240 V ~ AC 100...240 V ~
AC 100...240 V ~
Y1 Y2 Y1 Y2 Y1 Y2 L G+ Y U
N N N N G-
N N N N
Cable designations
10
Siemens A6V11449860_en--a
Smart Infrastructure 2019-09-10
Dimensions
min. 100
10.5
min. 100
min. 7
min. 60
min. 150
min. 100
Dimensions in mm
11
Siemens A6V11449860_en--a
Smart Infrastructure 2019-09-10
7. Test Reports
Appendix to the License Agreement To Use
The AMCA Certified Ratings Program Seal
Appendix No: 8
In accordance with the License Agreement issued on November 21, 2012 by Air Movement and Control
Association International, Inc., SAFID, is hereby authorized to use the AMCA Certified Ratings Seal on the specific
air movement and control devices listed below. Such use shall in all respects be governed by and subject to the
provisions of said License Agreement.
Dampers
Product Line Catalog ID
SPK30-400 Class 1A & Class 1 Low Leakage SPK30-400 January, 2014
Volume Control Damper
*License to Bear the AMCA Seal for Air Leakage, Air Performance
Please verify current certification status in the AMCA International Directory of Licensed Products located at
www.amca.org.
Granted This 18th day of March, 2014.
Lisa R. Ullrich
Certified Ratings Program Manager
AIR MOVEMENT AND CONTROL ASSOCIATION
INTERNATIONAL, INC.
Page 1 of 1
8. Material Safety Data Sheets
SafidDampers
Class 1A & Class 1
Low Leakage Volume Control Damper SPK 30 Series
Installation Details
Damper to Slide on Flange connection Damper to Angle Flange connection
8
MATERIAL SAFETY DATA SHEET
9. Previous Approvals
External Transmittal
INFRASTRUCTURE & CIVIL PROJECTS-DUKHAN
Project No : 3932C Transmittal No :
Contract No : GC19104100 PID/GC19104100/EXT/TN/0762
Contract Title : CONSTRUCTION OF OIL AND GAS DATA CENTRE BUILDING IN QPSFA DUKHAN
Item
No. QP Document No. Rev. Your ref. Description Code Due date
1 3932-9-MS-0093 1 GC19104100/PID/TN/ MATERIAL SUBMITTAL FOR MOTORIZED 10
0829 VOLUME CONTROL DAMPER
Remarks:
Condition:
Document Controller Nominated Deputy QP Representative Date
Tel: 40136625 Tel: 40135735
Suresh Wadye, PSD17 Kamal Moghaddam, PID11 Khalid Mohd Kaldari, PID 27-08-2020
If applicable, please resubmit documents before due date
This is QP system generated transmittal and therefore requires No Signature
Page 1 of 1 27-08-2020
10. List of Previous Projects
MEP CONTRACTOR PROJECT NAME
AL MALKI TRADING AND CONTRACTING WESTERN MID FUEL FARM - HIA
We certify that the country of origin of SAFID MAKE DAMPERS is STATE OF QATAR.
The fabrication/Assembly of the same for the above- m e n t i o n e d project is done by SAFID
LIMITED (QATAR FACTORY).
PROJECT : Design & Construction of New Light Industrial Unit-City Neon at Ras Bu
Fontas Free Zone
Our Company warrants SAFID QATAR MAKE DAMPERS or parts thereof to be free from
workmanship and material within 24 months from the date of delivery or 12 months from the date
commissioning, by the use as a result normal use and service.
Our company will replace the part or parts so determined by it to be defective with new parts, at
Company's cost and expense. This warranty is exclusive, and there are no other warranties or
representations, expressed or implied.
For the period of 12 months from the date of commissioning, our company warrants to the original
purchaser, that a new Unit is free from defect in material and workmanship and agrees to repair or
replace any defective parts. However, parts that don’t have a predictable life are not covered in
this warranty.
This warranty does not apply to units which, after our inspection, are determined to have been
damaged due to neglect, abuse, overloading, accident or improper usage. All shipping and handling
charges will be paid by the customer. Under no circumstances shall consequential damages be
recoverable
DATED: DD/MMM/YYYY
13. Material/Product Sample Photo