PSTX37-690-70 1/6

PRODUCT-DETAILS

PSTX37-690-70
PSTX37-690-70 Softstarter - 37 A - 208 ... 690
V AC

General Information

© 2024 ABB. All rights reserved. 2024/06/24 Subject to change without notice
PSTX37-690-70 2/6

Global Commercial Alias PSTX37-690-70


Extended Product Type PSTX37-690-70
Product ID 1SFA898204R7000
ABB Type Designation PSTX37-690-70
EAN 7320500501429
Catalog Description PSTX37-690-70 Softstarter - 37 A - 208 ... 690 V AC
The softstarter PSTX37-690-70 has a rated maximum operational current of 37 A with
an operating voltage span from 208...690 V AC. The rated control voltage is between
100...250 V AC at 50/60 Hz. PSTX features a three-phase control soft start and stop
through a voltage or a torque ramp. It has built-in bypass for easy installation and
energy saving. A RUN, TOR and Event signal is available from relay outputs in NO
(normally open state). The PSTX has functions such as current limit, kickstart, analog
output, EOL, motor heating and pump cleaning. PSTX also features features jog,
braking, stand-still brake, diagnostics, sequence start and emergency/fire pump
mode as standard.To interact with PSTX, it has a detachable full graphic display with
Long Description IP66 and 4x outdoor rating. There are four ways to communicate with PSTX. It can be
done by hardwire inputs Start/Stop/Reset of fault, and by three programmable digital
inputs. Another popular option is the built-in Fieldbus communication Modbus RTU
and incl optional ANYBUS modules with every major protocol such as for example
Profinet, Profibus, Modbus TCP, Ethernet IP and others. Another way to communicate
with PSTX is to use an external adaptor and a Fieldbus plug. PSTX is the complete
alternative for any motor starting application. It’s suitable for medium to large-sized
three-phase motors with nominal currents from 30...1250 A inline connection or
52...2160 A inside delta connection. Typical applications are, for example, pumps, fans,
compressors, and conveyors.

Ordering
Minimum Order Quantity 1 piece
Customs Tariff Number 85371091

Popular Downloads
Data Sheet, Technical 1SFC132012C0201
Information
Instructions and 1SFC132081M0201
Manuals
CAD Dimensional 2CDC001079B0201
Drawing
Wiring Diagram N/A

Dimensions
Product Net Width 150 mm
Product Net Height 314 mm
Product Net Depth / 198 mm
Length
Product Net Weight 4.6 kg

Technical
Rated Operational 208 ... 690 V AC
Voltage
Rated Control Supply 100 ... 250 V AC
Voltage (U s )
Rated Control Circuit 24 V DC
Voltage (U c )
Rated Frequency (f) 50/60 Hz

© 2024 ABB. All rights reserved. 2024/06/24 Subject to change without notice
PSTX37-690-70 3/6

Main Circuit 50 / 60 Hz
Rated Operational Power (230 V) 9 kW
- In-Line Connection (Pe) (400 V) 18.5 kW
(500 V) 22 kW
(690 V) 30 kW
Rated Operational 37 A
Current - In-Line
Connection (Ie)
Rated Operational Power at 230 V 15 kW
- Inside Delta at 400 V 30 kW
Connection at 500 V 37 kW
at 690 V 55 kW
Rated Operational 64 A
Current - Inside Delta
Connection
Service Factor 100 %
Percentage
Overload Protection Built-in electronic overload protection
Integrated Electronic Yes
Overload
Adjustable Rated Motor 30 ... 100 %
Current Ie
Starting Capacity at 4xIe for 10s
Maximum Rated Current
Ie
Ramp Time 1 ... 120 second [unit of time]
Initial Voltage During 10 ... 99 %
Start
Step Down Voltage 100 ... 10 %
Special Ramp
Current Limit Function 1.5 ... 7.5 xle
Switch for Inside Delta Yes
Connection
Run Signal Relay Yes
By-pass Signal Relay Yes
Fault Signal Relay Yes
Overload Signal Relay Yes
Analog Outputs 0…10 V, 0…20 mA, 4…20 mA
Signal Indication Ready Green
to Start/Standby ON
(LED)
Signal Indication Green
Running R (LED)
Signal Indication Yellow
Protection (LED)
Signal Indication Fault Red
(LED)
Communication Modbus-RTU; Modbus-TCP; Ethernet-IP; EtherCAT; DeviceNet; CANopen;
Profibus; Profinet; BACnet-IP; BACnet-MSTP
Degree of Protection IP00
Terminal Type Cable Clamp
Connecting Capacity Hole Diameter 8.5 mm
Main Circuit
Connecting Capacity Rigid 1 x 2.5 mm²
Control Circuit
Connecting Capacity Rigid 1 x 2.5 mm²
Supply Circuit
Tightening Torque Main Circuit 8 N·m
Product Main Type PSTX37
Function Auto phase sequence detection
Automatic restart

© 2024 ABB. All rights reserved. 2024/06/24 Subject to change without notice
PSTX37-690-70 4/6

Current limit
Current limit ramp
Dual current limit
Dynamic brake
Electricity metering
Electronic overload Time-to-cool
Emergency mode
Event log
Full voltage start
Jog with slow speed, forward and reverse
Keypad password
Kick start
Limp mode with two-phase motor control if one set of thyristors is
shorted
Motor heating
Pre-start function
Pump cleaning
Real time clock
Sequence start
Soft start with torque control
Soft start with voltage ramp
Soft stop with torque control
Soft stop with voltage ramp
Stand still brake
Start reverse (external contactors)
Thyristor runtime measurement
Torque limit
Voltage sags detection
Protection Function Bypass open protection; Current imbalance protection; Current underload
protection; Dual overload (separate overload for start and run); Earth fault
protection / ground fault protection; Electronic overload protection, EOL;
Extension IO failure protection; Fieldbus failure protection; HMI failure
protection; Locked rotor protection; Max number of starts/hour; Over
voltage protection; Phase reversal protection; Power factor underload
protection; PT-100 connection; PTC connection; Too long current limit
protection; Too long start time protection; Under voltage protection; User
defined protection; Voltage imbalance protection
Warning Details Current imbalance warning; Current underload warning; Electronic
overload Time-to-trip; EOL warning; Faulty fan warning; Locked rotor
warning; Motor runtime limit warning; Over voltage warning; Phase loss
warning (for standby); Power factor underload warning; Short circuit
warning (for Limp mode); THD(U) - Total Harmonic Distortion warning;
Thyristor overload warning (SCR); Under voltage warning; Voltage
imbalance warning

Technical UL/CSA
Maximum Operating Main Circuit 690 V
Voltage UL/CSA
Tightening Torque Main Circuit 70.8
UL/CSA

Environmental
Ambient Air Operation -25 ... +60 °C
Temperature Storage -40 ... +70 °C
Degree of Protection IP00

Material Compliance
Conflict Minerals 9AKK108467A5658
Reporting Template
(CMRT)
REACH Declaration 2CMT2022-006481

© 2024 ABB. All rights reserved. 2024/06/24 Subject to change without notice
PSTX37-690-70 5/6

RoHS Information 2CMT2022-006500


RoHS Status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances 2CMT2023-006524
Control Act - TSCA
WEEE B2C / B2B Business To Business
WEEE Category 5. Small Equipment (No External Dimension More Than 50 cm)

Certificates and Declarations


CQC Certificate CN: CQC2014010304744405 / SE: CQC2014010304724380
Declaration of CN: 2020980304001091 / SE: 2020980304001489
Conformity - CCC
Declaration of 2CMT005209
Conformity - CE

Container Information
Package Level 1 Width 200 mm
Package Level 1 Depth / 282 mm
Length
Package Level 1 Height 388 mm
Package Level 1 Gross 5.6 kg
Weight
Package Level 1 EAN 7320500501429
Package Level 1 Units box 1 piece

Classifications
Object Classification Q
Code
ETIM 7 EC000640 - Soft starter
ETIM 8 EC000640 - Soft starter
ETIM 9 EC000640 - Soft starter
eClass V11.0 : 27370907
UNSPSC 39121521
IDEA Granular Category 4740 >> Soft starter
Code (IGCC)

Categories

Drives → Softstarters → Softstarters → PSTX Softstarters → PSTX37


Low Voltage Products and Systems → Control Products → Softstarters → Softstarters → PSTX Softstarters → PSTX37

© 2024 ABB. All rights reserved. 2024/06/24 Subject to change without notice
PSTX37-690-70 6/6

© 2024 ABB. All rights reserved. 2024/06/24 Subject to change without notice

You might also like