ANovel Approachto Detect Faults Occurring During Power Swingsby Abrupt Changeof Impedance Trajectory
ANovel Approachto Detect Faults Occurring During Power Swingsby Abrupt Changeof Impedance Trajectory
Jalal Khodaparast, Mojtaba Khederzadeh, Filipe Faria da Silva & Claus Leth
Bak
To cite this article: Jalal Khodaparast, Mojtaba Khederzadeh, Filipe Faria da Silva & Claus
Leth Bak (2017): A Novel Approach to Detect Faults Occurring During Power Swings by
Abrupt Change of Impedance Trajectory, Electric Power Components and Systems, DOI:
10.1080/15325008.2017.1378774
Article views: 17
Download by: [Universitetbiblioteket I Trondheim NTNU] Date: 13 January 2018, At: 00:56
Electric Power Components and Systems, 0(0):1–15, 2017
Copyright C Taylor & Francis Group, LLC
ISSN: 1532-5008 print / 1532-5016 online
DOI: 10.1080/15325008.2017.1378774
CONTENTS
Abstract—The main purpose of power swing blocking is to distin-
1. Introduction guish faults from power swings. However, faults occurred during a
2. Limitation of Concentric Power Swing Blocker (CPSB) power swing should still be detected and cleared promptly. This paper
proposes an index based on detecting abrupt jump of impedance
3. Performance of Commercial Distance Relay in Detecting
trajectory by utilization of the predicting capability of the Kalman
Fault During Power Swing Filter. The proposed index is calculated by assessing the difference
4. Kalman Filter between predicted and actual samples of impedance. The predicted
5. Dynamic Phasor impedance samples are obtained using the Kalman filter and Taylor
expansion, which are used in this paper to track the phasor precisely.
6. Proposed Method for Detecting Fault During Power Swing Second order of Taylor expansion is used to decrease the corrugation
7. Simulation Results effect of impedance estimation and increase the reliability of the pro-
8. Conclusion posed method. Furthermore, in order to increase the selectivity of the
proposed method, the proposed index is armed with phase compari-
References son logic to detect internal faults. The instantaneous estimation and
prediction capability of the Kalman filter are two reasons for propos-
ing the use of Kalman filter. Intensive studies have been performed
and the merit of the method is demonstrated by test simulations.
1. INTRODUCTION
Distance relay mal-operation has raised concerns about black-
outs in power systems. Distance relays make decisions based
on the entering of impedance trajectory in protected zones.
When a fault occurs in a protected line, the impedance trajec-
tory enters in the distance relay zones and the relay operates.
However, this event (distance relay’s zones penetration) may
occur during power swing condition. During a power swing,
the voltage and current fluctuate simultaneously, causing fluc-
tuation in the measured apparent impedance at the distance
relay, which, hence, may enter the relay tripping zones. This
Keywords: Kalman filter, power swing, dynamic phasor, symmetrical fault, condition causes relay mal-operation and may lead to consec-
impedance trajectory, fault during power swing
Received 14 July 2016; accepted 2 September 2017 utive events (cascading outages) and even a major blackout
Address correspondence to Mojtaba Khederzadeh, Faculty of Electrical eventually [1]–[3].
Engineering, Shahid Beheshti University, A.C., Tehran 1658953571, Iran. To avoid this malfunction, power swing blocker (PSB) has
E-mail: [email protected]
Color versions of one or more of the figures in the article can be found online
become as a vital part of modern distance relay [4]. The major
at www.tandfonline.com/uemp. duty of PSB is discriminating power swing from fault and
1
2 Electric Power Components and Systems, Vol. 0 (2017), No. 0
based on negative sequence component of current and cumu- 2. LIMITATION OF CONCENTRIC POWER SWING
lative sum (CUSUM) for detecting three-phase fault during BLOCKER (CPSB)
power swing in series compensated line. A new method based
In order to show the capability and incapability of CPSB in
on extracted transient monitor (TM) index of current signal by
discriminating between fault and power swing under different
least square dynamic phasor is proposed in [22]. Phase space
conditions, three different cases are analyzed in this section. It
algorithm is presented in [23] to discriminate three-phase
is worthy to note that Mho characteristic is considered in this
fault during power swing based on shape information. Phase
section but the limitation is raiseable of all kinds of concentric
space representation of signal can be obtained based on main
characteristics such as Blinder and Lens.
signal and lagged main signal. The proposed index uses the
Case1: First test is programmed to examine capability of
distance between mapped point and the origin of x–y plane.
CPSB in detecting power swing. Consider that the power
Dimension of phase space and lagging sample number are
system shown in Figure 1 is under power swing condition.
two important quantities, which should be selected carefully.
Downloaded by [Universitetbiblioteket I Trondheim NTNU] at 00:56 13 January 2018
SWING xk−1 are states of the system at time steps k and k − 1, respec-
Although commercial distance relay used negative sequence tively, Ak−1 and Hk are transition and measurement matrices of
for detecting unsymmetrical fault during power swing, they the system, respectively, qk−1 and rk are process and measure-
use different solutions for detecting symmetrical fault during ments noise, respectively, and finally yk is the measurement at
power swing. According to manuals of some of the commer- step k. The Kalman filter algorithm involves two stages: the
cial relays, these solutions are given in the following. prediction step, where the next state of the system is predicted
given the previous measurements, and the update step, where
the current state of the system is estimated given the mea-
3.1. Detection Based on Communication Facilities
surement at that time step [31]. The standard Kalman filter
Some commercial distance relays are equipped with power equations for the prediction stage are given in Eq. (2):
swing logic (PSL), whose main purpose is to secure selec- −
tive and reliable operation of distance protection for fault dur- mk = Ak−1 mk−1
(2)
ing power swing [27]. PSL detects all kinds of faults during Pk− = Ak−1 Pk−1 ATk−1 + Qk−1
power swing by communication facilities and extra distance
where m− −
k and Pk are the predicted mean and covariance of
zones at both ends of the protected line, and it is activated
state at the time step k before seeing the measurement. The
after power swing detection. The main issue of this method is
predicted mean is updated by measurement in updating step:
the delay problem, which is common in communication-based ⎧
methods. ⎪
⎪ v = yk − Hk m−
⎪ k
⎪
k
⎪ = − T
⎪
⎨ S k Hk Pk Hk + Rk
− T
3.2. Detection Based on Additional Set of Inner Blinders Kk = Pk Hk /Sk (3)
⎪
⎪
⎪ mk = m− + Kk v k
⎪
These relays include an additional set of inner blinders to pro- ⎪
⎪ k
⎩
vide proper detection of the internal symmetrical fault [28]. If Pk = Pk− − Kk Sk KkT
the positive sequence impedance resides between these blin-
where
ders for a specific duration, PSB unblocks. The challenge
faced by this method is its performance in high-resistance
mk and Pk estimated mean and covariance of the state at the
fault, which may cause locating impedance outer of inner
time step k after seeing the measurement, respectively;
blinders.
v k measurement residual;
Sk posterior measurement covariance; and
3.3. Detection Based on Magnitude of Current Kk Kalman filter gain, which indicates how much modification
In order to protect the network against a fault that may occur is needed for the state variables based on measurement.
during power swing, blocking signals can be stopped when
current thresholds are exceeded [29]. Fault is detected when These formulations can help estimating the impedance at
the absolute value of differential current becomes greater than the first step (necessary in distance relay) and can also help
10% of the nominal current for three cycles. The main issue of to predict next sample of impedance in fault detection during
this method is the low level of current in high-resistance fault power swing. Since voltage and current signals are modulated
or fault in heavily loaded line. during power swing, the ordinary Kalman filter for impedance
Khodaparast et al.: A Novel Approach to Detect Faults Occurring during Power Swings by Abrupt Change of Impedance Trajectory 5
calculation leads to insufficient accuracy in phasor estimation. 6. PROPOSED METHOD FOR DETECTING FAULT
Therefore, combination of Kalman filter and second order of DURING POWER SWING
Taylor expansion is used in this paper to increase accuracy
In this section, a new method is proposed to solve the limi-
of phasor estimation during power swing. This aim can be
tation of CPSB for detecting fault during power swing. This
achieved by dynamic phasor concept described in the next
method is based on abrupt change of impedance trajectory,
section.
whose index can be extracted via phasor estimation process.
Based on the proposed method, utilization of the Kalman filter
5. DYNAMIC PHASOR for phasor estimation in distance relay provides foundation for
solving the problem faced by CPSB when attempting to detect
Dynamic phasor is a recent concept in phasor estimation area, fault during power swing. Suppose a power swing occurs,
which considers phasor as a time varying complex parameter by considering (|V1 |/|V2 |)= constant, where |V1 | and |V2 | are
(both amplitude and phase are time varying parameters). This
Downloaded by [Universitetbiblioteket I Trondheim NTNU] at 00:56 13 January 2018
FIGURE 4. Flowchart of the proposed complete CPSB (CPSB and proposed method).
7. SIMULATION RESULTS
Three simulation cases are provided next. The first case is
the assessment of the augmented Kalman filter performance
for phasor estimation during power swing to ensure the accu-
racy of dynamic phasor estimation process that is used in this
paper. The second case is a simulation of single machine to
infinite bus (SMIB) and the third case consists of the simu-
lation of a large power system (IEEE 39 Bus) to ensure the
appropriate performance of the proposed method in a large
power system. FIGURE 6. Outputs of zero-order Taylor and Kalman filter.
8 Electric Power Components and Systems, Vol. 0 (2017), No. 0
FIGURE 7. Outputs of second-order Taylor and Kalman filter. swing (t = 1.9 sec at 25% of the line) and the impedance tra-
jectory of this condition is shown in Figure 9. According to
of phasor, which is shown in Figure 6, is a result of unsuit- the figure, the power swing makes impedance trajectory to
able definition of the phasor during power swing. However, move toward protected zone 3, which could lead to malfunc-
this corrugation effect is eliminated by dynamic phasor con- tion of the distance relay. In order to prevent such malfunction,
cept (i.e., use of a higher order Taylor expansion) as shown in CPSB (with two blinder characteristics) is designed for a dis-
Figure 7, which helps reducing the error of phasor estimation tance relay. The recorded time by CPSB is about 0.036 sec and
during power swing and results in a more reliable detection since this value is lower than the threshold (h1 = 0.005 sec),
process. CPSB operates accurately and detects it as a power swing, so it
blocks distance relay. Moreover, CPSB triggers the proposed
7.2. Simulation Results of Proposed Method in SMIB method to be ready for detecting fault during power swing.
In order to validate the proposed method for detecting fault Another three-phase fault (F2) occurs during power swing,
during power swing, the power system shown in Figure 8 is which should be detected by the proposed index. Under this
considered and simulated in PSCAD (power system’s data are condition, the proposed index (Index) and PC are calculated
presented in [8]). In order to accurate modeling of the power at every sample, which are shown in Figure 10. The figure
system in PSCAD, digital waveforms are created by using a shows that there is a peak value (190 ) corresponding to a
sampling rate of 10 kHz, and then downsampled to 20 sam- fault during power swing at t = 1.9 sec. Since the index value
ple/cycle and finally processed by MATLAB. A distance relay is higher than the threshold (h2 =15 ) and PC is higher than
is at bus 1 in the upper line (Line-1 = 280 km, Z1 = 0.12 h3 = 5º, internal fault is detected by the proposed method.
+ j0.88 /km). A three-phase fault (F1) is simulated at the Output of the proposed method (trip command) under this
middle of the lower line, which occurs at t = 1 sec, and it is
cleared after 0.03 sec by opening the breakers at both ends
(CB1, CB2). This occurrence causes a power swing on the
line between buses 1 and 2, which is observed by the distance
relay R. Another three-phase fault (F2) occurs during power
FIGURE 8. SMIB power system with two parallel transmis- FIGURE 10. Output of the proposed method in SMIB for
sion lines. fault during power swing.
Khodaparast et al.: A Novel Approach to Detect Faults Occurring during Power Swings by Abrupt Change of Impedance Trajectory 9
Case Swing Frequency (Hz) Fault Initiation (sec) Power Angle (º) Fault Location (%) Index Value (Swing) () Index Value (Fault) ()
condition is also shown in Figure 10. According to the fig- two-phase fault (Phase-B and Phase-C to ground). According
ure, the proposed method detects internal fault during power to the left column, the proposed method can detect Phase-A
Downloaded by [Universitetbiblioteket I Trondheim NTNU] at 00:56 13 January 2018
swing and issues trip command to distance relay accurately. It as internal faulted phase and the trip command is sent just for
is worth mentioning that the time requirement for the Kalman Phase-A. However, in the right column, the proposed method
filter performance in every sample is about 50 μsec using a detects that Phase-B and Phase-C are two internal faulted
processor (Intel (R) Core(TM) 2 Duo, CUP 2.66 GHz, RAM phases and issues trip command for both of these phases.
4GB, Dell Vostro, Texas, USA) and about 30 µsec using a pro- According to these results, we can conclude that the proposed
cessor (Intel (R) Core(TM) i7-4600U, CUP 2.7 GHz, RAM method is applicable for both symmetrical and unsymmetrical
8GB, Dell Latitude, Texas, USA). faults during power swing.
7.3. Simulation Results for IEEE 39 Bus (New England) at t = 2.2 sec, during power swing. Based on the proposed
Figure 13 shows the location of the distance relay and of hypo- method, future sample of impedance trajectory is predicted
thetical three-phase faults in the IEEE 39 Bus system (data of by the Kalman filter and it is compared with the measured
this power system is presented in [34]). This power system impedance one sample later.
is simulated in PSCAD and in order to accurate modeling of Figure 14 shows the output of the proposed method for
the power system in PSCAD, digital waveforms are created internal fault during power swing. According to this figure,
by using sampling rate of 10 kHz, and then downsampled to there is an increase in index value at the fault during power
20 sample/cycle and finally processed by MATLAB. A three- swing at t = 2.2 sec. When a fault happens during power
phase fault (F1) occurs at t = 1sec in the line between Bus swing, the proposed method compares the index value (Index)
10 and Bus 13 and it is cleared after 0.25 sec. Consequently, with the threshold (h2 = 15 ) and predicts fault occur-
a power swing is created, which is detected by CPSB (Mho rence during power swing. In the next step, PC is compared
characteristic) first and then trigger command is sent to the with its threshold value (h3 = 5º) and detects an internal
proposed method to be ready for detecting fault during power fault because PC is higher than the threshold. Finally, the trip
swing. Suddenly, another three-phase fault (F2) occurs at 50% command is sent to distance relay, which is also shown in
of the line between Bus 16 and Bus 19 (line under analysis) Figure 14.
Khodaparast et al.: A Novel Approach to Detect Faults Occurring during Power Swings by Abrupt Change of Impedance Trajectory 11
Downloaded by [Universitetbiblioteket I Trondheim NTNU] at 00:56 13 January 2018
1 Load switching 16 3
2 Load switching 15 1.25
3 Load switching 24 1.75
4 Capacitor switching 16 4.7
5 Capacitor switching 24 3.5
6 Capacitor switching 17 2.1
pare the proposed method (PM) with other methods, five dif-
ferent methods are programmed (none of these five methods FIGURE 16. Performance of the proposed method and five
have the limitation presented in Section 2). These five meth- other methods in IEEE 39 Bus.
ods are as follows:
(M1) The method based on frequency component of three-
phase active power [20]: This method is based on the index values are normalized (divided by the maximum value)
detection of frequency components of an instantaneous three- so the maximum values (1 p.u.) in all methods are related
phase active power. It is demonstrated that during a power to fault initiation. So, by analyzing the index value during
swing, the instantaneous three-phase active power has a fre- power swing, the reliability of methods is compared. The cor-
quency component of slip frequency whereas after the fault responding indices of all six methods (shown in Figure 16)
inception time, a damping power-frequency component will during power swing and fault are tabulated in Table 2. Since
be created on its profile. the index values become normalized, the index value of all
(M2) T he method based on superimposed current [35]: methods are equal to one during fault, and so it is possible
This method is based on extracting superimposed component, to compare different methods with their index values dur-
created in fault time. When a fault occurs in power system, ing power swing so that the lowest value during power swing
it transits from normal to fault condition. The change cre- demonstrates the largest possible region for threshold selec-
ated as a consequence of this transition is considered as an tion and so the most reliable method.
index named superimposed component. This component is Therefore, by comparing the normalized index values dur-
calculated based on the expected no-fault current sample and ing power swing (according to the second column of Table 2),
subtracting it from the latest measured sample. the lowest value is related to the proposed method, so this
(M3) T he method based on transient monitor[22]: This method provides the largest region for threshold selection.
method is based on the extracted TM index of current signal In order to make clear the performance of different methods
by least square dynamic phasor, which is low during power (Methods 1—5) and the superiority of the proposed method,
swing and high at fault initiation. comparative results are shown in Figure 17. This chart shows
(M4) T he method based on a sample estimation and error the region of the maximum (third column of Table 2) and
calculation[25]: This method is based on estimating a future the minimum index (second column of Table 2) and so the
sample current and error calculation and then index value allowable region for selecting the threshold. According to this
(DI) based on sum of the entire squares of errors in the data chart, the proposed method has the largest allowable region
window. for selecting the threshold, which shows the highest reliability
(M5) T he method based on negative component [21]: Due compared to other methods.
to transients in current signals in the initial period, a negative Computational burden is another criteria, which is exam-
sequence component is noticeable even for three-phase faults. ined in this section for comparison between different meth-
Therefore, this component is extracted for current signal for ods. All six methods are compared based on float point oper-
detecting fault during power swing. ations (FLOPs) and the their results are tabulated in Table 3
All of these methods are simulated under the presented (last column). FLOP is a count of operations carried out by a
condition (fault occurs at t = 2.2 sec during power swing) in given algorithm or computer program. It is of interest to com-
IEEE 39 Bus power system and their performances are shown pare the computational complexity of two algorithms. Instead
in Figure 16. In order to provide comparison foundation, the of runtime counting, it is decided to count the FLOPs by
Khodaparast et al.: A Novel Approach to Detect Faults Occurring during Power Swings by Abrupt Change of Impedance Trajectory 13
Method Power Swing Fault FLOPs of the augmented Kalman filter performance for phasor esti-
mation during power swing. The second case is a simula-
Proposed method 2×10−4 1 268,596
Method 1 1.25×10−3 1 87,532
tion of SMIB and the third case consists of the simulation
Method 2 0.040 1 47,766 of a large power system (IEEE 39 Bus). Moreover, the pro-
Method 3 5×10−4 1 241,596 posed method is compared with some other methods and the
Method 4 0.007 1 67,532 simulation results show that it has the highest level of reli-
Method 5 4×10−4 1 14,922 ability and the highest CPU computation time compared to
other methods. To sum up, according to the simulation results,
TABLE 3. Normalized index values and computational burden for
all six methods. the proposed method demonstrates its capability to properly
unblock a distance relay under fault condition during power
swing.
Downloaded by [Universitetbiblioteket I Trondheim NTNU] at 00:56 13 January 2018
REFERENCES
[1] N. Moaddabi and G. B. Gharehpetian, “Wide-area method for
self-healing of smart grids in unstable oscillations,” Electr.
Power Compon. Syst., vol. 41, no. 4, pp. 365–382, Jan. 2013.
[2] M. Moazzami, R. A. Hooshmand, and A. Khodabakhshian,
“Blackout prevention in power system using flexible AC trans-
mission system devices and combined corrective actions,”
Electr. Power Compon. Syst., vol. 41, no. 15, pp. 1433–1455,
Oct. 2013.
[3] S. R. Samantaraya, R. K. Dubeyb, and B. Chitti Babub, “A
novel time frequency transform based spectral energy function
for fault detection during power swing,” Electr. Power Compon.
FIGURE 17. Comparison between methods according to Syst., vol. 40, no. 8, pp. 881–897, Apr. 2012.
allowable region for threshold. [4] IEEE PSRC WG D6, “Power swing and out of step con-
siderations on transmission lines,” A report to power system
relaying committee of the IEEE Power Engineering Society,
scanning and parsing each line of the MATLAB codes and 2005.
infer the floating point operations. The required mathemati- [5] A. Mechraoui and D. W. P. Thomas, “A new blocking principle
cal operations of any program can be analyzed by matrix sizes with phase and earth fault detection during fast power swings
[36]. for distance protection,” IEEE Trans. Power Del., vol. 10, no.
According to Table 3, the highest computational burden is 3, pp. 1242–1248, Jul. 1995.
[6] A. Mechraoui and D. W. P. Thomas, “A new principle for high
related to the proposed method that shows the difficulty of
resistance earth fault detection during fast power swings for
this method. It is obvious that this high computational burden distance protection,” IEEE Trans. Power Del., vol. 12, no. 4,
is related to dynamic phasor estimation and phasor calculation pp. 1452–1457, Oct. 1997.
of both voltage and current in the proposed method. [7] J. Ganeswara and A. Pradhan, “Differential power based sym-
metrical fault detection during power swing,” IEEE Trans.
Power Del., vol. 27, no. 3, pp. 1557–1564, Jul. 2012.
[8] S. Brahma, “Distance relay with out of step blocking function
8. CONCLUSION
using wavelet transform,” IEEE Trans. Power Del., vol. 22, no.
This paper presents a new method for detecting a fault dur- 3, pp. 1360–1366, Jul. 2007.
ing power swing using abrupt change of impedance trajec- [9] R. Dubey and S. R. Samantaray, “Wavelet singular entropy-
based symmetrical fault-detection and Out-of-Step protection
tory at the fault initiation. This abrupt change is detected by
during power swing,” IET Generat., Trans. Distribut., vol. 7,
the deviation between measured impedance and an impedance no. 10, pp. 1123–1134, Oct. 2013.
predicted using the Kalman filter. In addition, dynamic pha- [10] N. Mohamad, A. Abidin, and I. Musirin, “Intelligent power
sor concept is employed to reduce the phasor estimation error swing detection scheme to prevent false relay tripping using
during power swing and so increase the reliability of the pro- S-transform,” Int. J. Emerg. Electric. Power Syst., vol. 15, no.
3, pp. 195–311, Jun. 2014.
posed method. Finally, phase comparison logic is used in the
[11] Z. Moravej, J. D. Ashkezari, and M. Pazoki, “An effective
proposed method to increase its selectivity for discrimina- combined method for symmetrical faults identification during
tion of internal from external faults. Three simulation cases power swing,” Electric Power System. Res., vol. 64, no. 1, pp.
are provided in this paper. The first case is the assessment 24–34, Jan. 2015.
14 Electric Power Components and Systems, Vol. 0 (2017), No. 0
[12] H. Zade and Z. Li, “A novel power swing blocking scheme [29] MiCOM P441/P442/P444 – Technical Manual of Numerical
using adaptive neuro-fuzzy inference system,” Electric Power Distance Protection. ALSTOM, 2011.
Syst. Res., vol. 78, no. 7, pp. 1138–1146, 2008. [30] R. Faragher, “Understanding the basis of the Kalman filter via
[13] M. J. Reddy and D. K. Monhanta, “Adaptive-neuro-fuzzy infer- a simple and intuitive derivation,” IEEE Signal Process. Mag.,
ence system approach for transmission line fault classifica- vol. 29, no. 5, pp. 128–132, Sep. 2012.
tion and location incorporating effects of power swings,” IET [31] Jouni Hartikainen, Arno Solin, and Simo Sarkka, Optimal Fil-
Generat., Trans. Distribut., vol. 2, no. 2, pp. 235–244, Mar. tering with Kalman Filters and Smoothers. Espoo, Finland:
2008. Aalto Univ. School of Science, 2011.
[14] N. G. Chothani, B. R. Bhalja, and U. B. Parikh, “New support [32] Jose Antonio de la o serna, “Dynamic phasor estimates for
vector machine-based digital relaying scheme for discrimina- power system oscillations,” IEEE Trans. Instrument. Measur.,
tion between power swing and fault,” IET Generat., Trans. Dis- vol. 56, no. 5, pp. 1648–1657, Oct. 2007.
tribut., vol. 1, no. 1, pp. 17–25, Jan. 2014. [33] J. Serna and J. Rodriguez-Maldonado, “Instantaneous oscillat-
[15] S. Gautam and S. Brahma, “Out-of-step blocking function in ing phasor estimates with Taylor–Kalman filters,” IEEE Trans.
distance relay using mathematical morphology,” IET Generat., Power Sys., vol. 26, no. 4, pp. 2336–2344, Nov. 2011.
Downloaded by [Universitetbiblioteket I Trondheim NTNU] at 00:56 13 January 2018
Trans. Distribut., vol. 6, no. 4, pp. 313–319, Apr. 2012. [34] A. Pai, Energy Function Analysis for Power System Stability.
[16] A. P. Morais, G. C. Junior, L. Mariotto, and G. Marchesan, “A Berlin, Germany: Springer, 1989.
Morphological filtering algorithm for fault detection in trans- [35] A. Apostolov, D. Tholomier, and S. Richard, “Superim-
mission lines during power swings,” Electric Power Syst. Res., posed components based sub-cycle protection of transmission
vol. 122, no. 1, pp. 10–18, May2015. lines,” in Proc. Power Sys. Conf. Exposit., pp. 592–597, Oct.
[17] J. Rao and K. Pradhan, “Power swing detection using moving 2004.
averaging of current signals,” IEEE Trans. Power Del., vol. 30, [36] H. Qian, “Counting the Floating Point Operations (FLOPS),”
no. 1, pp. 368–376, Feb. 2015. MATLAB Central File Exchange, No. 50608, Ver. 1.0, June
[18] X. Lin, Y., Gao, and P. Liu, “A novel scheme to identify sym- 30, 2015.
metrical fault occurring during power swings,” IEEE Trans.
Power Del., vol. 21, no. 1, pp. 73–78, Jan. 2008.
[19] K. Andanapalli and P. LiB. Varmau, “Parks transformation
based symmetrical fault detection during power swing,” in
Proc. 18th Natl. Power Syst. Conf., Dec. 2014, pp. 1–5. BIOGRAPHIES
[20] B. Mahamedi and J. Zhu, “A novel approach to detect symmet-
Jalal Khodaparast was born in Iran in 1987. He received
rical faults occurring during power swings by using frequency
components of instantaneous three phase active power,” IEEE the B.Sc. and M.Sc. degrees in electrical engineering from
Trans. Power Del., vol. 27, no. 3, pp. 1368–1376, Jul. 2012. Shahrood University of Technology, Shahrood, Iran, in 2008
[21] P. Nayak and P. Bajpai, “A fault detection technique for the and 2010, respectively, and is currently working toward
series-compensated line during power swing,” IEEE Trans. the Ph.D. degree in the Electrical Engineering Department,
Power Del., vol. 28, no. 2, pp. 714–722, Apr. 2013. Shahid Beheshti University, Tehran, Iran. He was a Guest
[22] J. Khodapaast and M. Khederzadeh, “Three-phase fault detec-
tion during power swing by transient monitor,” IEEE Trans.
Ph.D. Student (visiting period) in the Aalborg University,
Power Syst., vol. 30, no. 5, pp. 2558–2565, Sep. 2015. Denmark, 2015–2016. His research interests include wide
[23] R. Dubey, S. R. Samantaray, B. K. Panigrahi, and V. G. area protection, flexible AC transmission systems (FACTS),
Venkoparao, “Phase-space-based symmetrical fault detection power system dynamics, digital signal processing, and phasor
during power swing,” IET Generat., Transmiss. Distrib., estimation.
vol. 10, no. 8, pp. 1947–1956, Feb. 2016.
[24] R. Jafari, N. Moaddabi, M. Eskandari-Nasab, and G. B.
Gharehpetian, “A novel power swing detection scheme inde- Mojtaba Khederzadeh (SM’06) received the B.Sc. degree
pendent of the rate of change of power system parameters,” in electrical engineering from Sharif University of Technol-
IEEE Trans. Power Del., vol. 29, no. 3, pp. 1192–1202, Feb. ogy, Tehran, Iran, in 1980, the M.Sc. degree in electrical engi-
2014. neering from Tehran University, Tehran, Iran, in 1990, and the
[25] I. G. Tekdemir and B. Alboyaci, “A novel approach for Ph.D. degree in electrical engineering from Sharif University
improvement of power swing blocking and deblocking func-
tions in distance relays,” IEEE Trans. Power Del., vol. 32,
of Technology in 1996. He was a Postdoctoral Fellow in the
no. 4, pp. 1986–1994, Aug. 2017. University of Western Ontario, London, ON, Canada, from
[26] P. Kundu and K. Pradhan, “Wide area measurement based pro- 2004 to 2005. He is currently an Associate Professor and the
tection support during power swing,” Electric Power Sys. Res., Director of the Power System Protection and Control Research
vol. 63, no. 1, pp. 546–554, Dec. 2014. Center, Electrical Engineering Department, Shahid Beheshti
[27] REL670 IEC – Manual of Line Distance Protection. ABB
University, Tehran, Iran. His research interests include power
Group, 2016.
[28] SEL-421 Relay – Instruction Manual of Protection and system protection, control and monitoring, and power system
Automation System. SEL, 2011. dynamics.
Khodaparast et al.: A Novel Approach to Detect Faults Occurring during Power Swings by Abrupt Change of Impedance Trajectory 15
Filipe Faria da Silva was born in Portugal in 1985. He Claus Leth Bak was born in Denmark, in 1965. He received
received the M.Sc. degree in electrical and computers engi- the B.Sc. degree in electrical power engineering in 1992, the
neering from Instituto Superior Técnico, Portugal in 2008 and M.Sc. degree in electrical power engineering, Aalborg Uni-
the Ph.D. degree in electric power systems from Aalborg Uni- versity (AAU), in 1994, and the Ph.D. degree in 2015. He
versity, Denmark, in 2011. He was with EDP-Labelec in 2008 was a Professional Engineer with Electric Power Transmis-
and with Energinet.dk from 2008 to 2011. He is currently an sion and Substations, NV Net Transmission Company, with
Associate Professor in the Department of Energy Technology, specializations within the area of power system protection. In
Aalborg University, where he is also the Semester Coordina- 1999, he was an Assistant Professor with ET-AAU. He cur-
tor of the Electrical Power System and High Voltage Engi- rently holds a Full Professor position with ET-AAU. He serves
neering’ master program and the Vice Leader of the Mod- as the Head of the Energy Technology Ph.D. Program and
ern Power Transmission Systems’ research program. He is an the Head of the Section of Electric Power Systems and High
Active Member of CIGRE and IEEE, being currently the Head Voltage with AAU and is a Member of the Ph.D. Board in
Downloaded by [Universitetbiblioteket I Trondheim NTNU] at 00:56 13 January 2018
of Denmark’s IEEE-PES and a regular Member of the Cigré the Faculty of Engineering and Science. His research interests
SC C4. He has authored more than 70 articles and a book. include corona phenomena on overhead lines, power system
His research interests include power cables, electromagnetic modeling and transient simulations, underground cable trans-
transients, system modeling, network stability, HVDC trans- mission, power system harmonics, power system protection,
mission, and HV phenomena. and HVDC-VSC offshore transmission networks.