SCL Configurator Software
User Guide
NR Electric Co., Ltd.
SCL Configurator Software User Guide
CONTENTS
1. Introduction .....................................................................................................................................1
2. Run IEDconfigurator .......................................................................................................................1
3. Configuration procedure for a new project ...................................................................................2
3.1. Create a new project ............................................................................................................2
3.2. Add IEDs ...............................................................................................................................5
3.3. GOOSE transmitting signal configuration........................................................................12
3.4. GOOSE input signal configuration ...................................................................................15
3.5. Communication configuration...........................................................................................20
3.6. Configuration of the communication port for GOOSE ....................................................21
3.7. Export the cid file and goose.txt file .................................................................................26
V 1.01 NR ELECTRIC CO., LTD.
SCL Configurator Software User Guide
1. Introduction
SCL Configurator is used to configure the GOOSE and SMV between IEDs.
In this document all the operation is based on the SCL configrator R3.1.2.
2. Run IEDconfigurator
Run SCL Configurator by clicking the shortcut “SCL Configurator”
Figure 2-1 Run SCL Configurator
The main interface of SCL Configurator show as below
1
V 1.00 NR ELECTRIC CO., LTD.
SCL Configurator Software User Guide
Figure 2-2 Interface of SCL Configurator
3. Configuration procedure for a new project
3.1. Create a new project
Click the “File” on the menu bar and select “new” in the list menu to create a new project.
2
NR ELECTRIC CO., LTD. V 1.00
SCL Configurator Software User Guide
Figure 3.1-1 Create a new project
Fill in the project name for the new project in the pop-up window, click “Save” button to save the new
project.
3
V 1.00 NR ELECTRIC CO., LTD.
SCL Configurator Software User Guide
Figure 3.1-2 Fill in the project name
The SCD file of the new project includes five configuration parts: History, Substation, Communication,
IED and DateTypeTemplates.
History
Record the modification to the SCD file. If someone creates the new project or makes any change in the
SCD file, a new record shall be manually added to the history.
This function helps engineer to review the modification to the SCD file caused by other engineer.
Select history, in the right side window click “New” to add a new record.
Figure 3.1-3 Add new record
4
NR ELECTRIC CO., LTD. V 1.00
SCL Configurator Software User Guide
Substation:
Set the name for the substation.
Select substation, then in the right side window click “New” to add a new substation and set its name.
Figure 3.1-4 Set the name for substation
Communication
Set the communication parameters.
IED
Add IEDs and configure the IEDs.
DataTypeTemplates
Display the DataType which is used in this SCD file.
3.2. Add IEDs
Select IED and click “New” in the right side window
5
V 1.00 NR ELECTRIC CO., LTD.
SCL Configurator Software User Guide
Figure 3.2-1 Add a new IED
In the pop-up window “import IED wizard” click “Next”
6
NR ELECTRIC CO., LTD. V 1.00
SCL Configurator Software User Guide
Figure 3.2-2 import IED wizard
In the IED information window, fill in the IED name.
IED name is the instance name of one IED, the IED name of each IED should be unique in system.
Normally the IED name can start with a letter and plus the IED address. For example we can use “P100”
as the IED name for the IED. P means protection, 100 is the address of the IED. In this case the IED
name will not conflict with each other due to the address of IED in system is unique.
In import options, user can choose import from ICD or from IED.
From ICD: If it is the first time that add the IED or without the existing IED adopting the same ICD file in
the project, choose import from ICD file.
From IED: If the ICD file of the new IED is same as one existing IED in the project, in this case no need
to import ICD file again. User can choose import from IED to create a copy of existing IED.
7
V 1.00 NR ELECTRIC CO., LTD.
SCL Configurator Software User Guide
Figure 3.2-3 import from ICD
8
NR ELECTRIC CO., LTD. V 1.00
SCL Configurator Software User Guide
Figure 3.2-4 import from IED
Click “Next” to next step “Schema Validation Result”
9
V 1.00 NR ELECTRIC CO., LTD.
SCL Configurator Software User Guide
Figure 3.2-5 Schema Validation Result
In “Update communication” window, enable “not import communication configuration”. Because we will
configure the communication parameters of the IED later, so here we no need to import communication
configuration.
10
NR ELECTRIC CO., LTD. V 1.00
SCL Configurator Software User Guide
Figure 3.2-6 Update Communication
Click “Next” button the conclusion window will pop up and the brief information of the imported IED will
be listed.
11
V 1.00 NR ELECTRIC CO., LTD.
SCL Configurator Software User Guide
Figure 3.2-7 Conclusion
Figure 3.2-8 Added new IED
3.3. GOOSE transmitting signal configuration
GOOSE control block control the sending of GOOSE signal. Which signal will be transmitted depends on
the corresponding dataset controlled by goose control block.
Check the member list of Data Set
Select one IED and choose the Data set and logical device, we can check the members of one dataset
of one IED in SCL Configurator. Figure 3.3-1 and Figure 3.3-2
12
NR ELECTRIC CO., LTD. V 1.00
SCL Configurator Software User Guide
Figure 3.3-1 Select Data Set type
Figure 3.3-2 Select logical device
Select the dataset, the members of the dataset will be listed in the below window.
13
V 1.00 NR ELECTRIC CO., LTD.
SCL Configurator Software User Guide
Figure 3.3-3 Data Set members
GOOSE control block configuration
The signal will be transmitted or not depends on the GOOSE control block. The GOOSE control block
normally is not configured in an ICD file. If the signal of one IED needs to be transmitted via GOOSE on
network, we should configure the GOOSE control block for this IED according to engineering application.
The next example illustrates how to configure the GOOSE control block for an IED.
Step 1
Select the IED choose the GSE Control (GOOSE control block) and Logical device. The configured
GOOSE control block will be listed. If there is no any required GOOSE control block available. We shall
add the new GOOSE control block for this IED.
14
NR ELECTRIC CO., LTD. V 1.00
SCL Configurator Software User Guide
Figure 3.3-4 GSE Control Block
Step 2
Click “new” button to add a new GOOSE control block.
Name: GOOSE control block name
Data Set: choose the Data Set which will be controlled by this GOOSE control block. The data in the
chosen Data Set can be transmitted via GOOSE on network.
Config Revision: configuration revision. Use default value
Type: type of GSE control block. Use default value
APP ID: application identification. Use default value
Description: the description of the GOOSE control block
Figure 3.3-5 Configure GOOSE control block
3.4. GOOSE input signal configuration
If the IED needs to receive the signal from other IEDs via GOOSE on network, GOOSE input signal shall
be configured. The signal from other IED is external signal. The internal signal is a kind of signal which
value is determined by an external signal. For example, the circuit breaker position signal of a relay, it is
an internal signal of the relay and its value is determined by circuit breaker position signal from IBC
(intelligent breaker controller).
The purpose of GOOSE input signal configuration is to create the mapping relationship between the
internal signal and external signal. If one IED needs to receive the signal from another IED, we need to
15
V 1.00 NR ELECTRIC CO., LTD.
SCL Configurator Software User Guide
configure the GOOSE input signal for this IED. If one IED doesn’t receive the signal from other IEDs, we
don’t need to configure the GOOSE input signal for this IED.
In the next example illustrates the procedure of GOOSE input signal configuration. There are two IEDs in
this example, one is PCS-902 distance relay and the other is PCS-222 IBC. The distance relay transmits
the tripping and reclosing signal to IBC and the IBC transmits the circuit breaker position to the distance
relay.
Configure the GOOSE input signal for PCS-902
Step 1: configure the “Inputs”
Select the IED then choose the Inputs and logical device. Configure the GOOSE input signal, first we
shall select the “External signal” attribute page then select the external IED. See Figure 3.4-1 GOOSE
input signal configuration_1
Figure 3.4-1 GOOSE input signal configuration_1
Step 2: Configure external signal
Select the external IED and double click it.
Select the G1 access point under the external IED and extract it by double clicking it. Click the G1, there
are three Datasets dsGOOSE0, dsGOOSE1 and dsGOOSE2 under the G1 access point. Click one
16
NR ELECTRIC CO., LTD. V 1.00
SCL Configurator Software User Guide
dataset the DA (data attribute) of each member will be listed under the dataset.
Select the signal which will be transmitted to the internal IED from the right side window. Right click it and
add it to the left side window. All the selected external signals will be listed in the left side window. See
Figure 3.4-2 GOOSE input signal configuration_2.
Figure 3.4-2 GOOSE input signal configuration_2
The meaning of the DA of each member in dataset
Example: RPIT/Q0XCBR1$ST$Pos$stVal:CB_pos
RPIT: logical device name
Q0XCBR1: instance name of logical node
ST: functional constraint
Pos: Data name
stVal: DA name (data attribute)
CB_pos: description of the data
“/” is used to separate the logical device and logical node
“$” is used to delimit the different level of hierarchy within the MMS named variable
17
V 1.00 NR ELECTRIC CO., LTD.
SCL Configurator Software User Guide
Step 3: Configure the internal signal
Select the internal signal page, the IED will display on the right side window. Select the IED and double
click it to extract it. The access point of the IED will be listed under the IED, click the G1 access point the
internal signal will be listed under the G1 access point. See Figure 3.4-3 GOOSE input signal
configuration_3. If there is no signal or can’t find the expected signal under the list, open the filter and
clear or change the condition, then the signals will be listed under it. See Figure 3.4-4 Open the filter.
Figure 3.4-3 GOOSE input signal configuration_3
18
NR ELECTRIC CO., LTD. V 1.00
SCL Configurator Software User Guide
Figure 3.4-4 Open The Filter
Select the corresponding signal from the internal signal and drag the signal to the left side to match the
external signal. The selected external signal and internal signal shall be at the same level. For example
the external signal is DA level the corresponding internal signal must be DA level. Otherwise, the
selected external signal and internal signal will display in grey color to indicate the configuration is not
correct. See Figure 3.4-5 Selected external signal and internal signal
Figure 3.4-5 Selected External Signal and Internal Signal
In substation, if the IED shall receive the signal from other IED via GOOSE, the received signal shall be
configured in Inputs.
19
V 1.00 NR ELECTRIC CO., LTD.
SCL Configurator Software User Guide
3.5. Communication configuration
When the input signal of each IED is completed, we shall configure the communication parameters for
GOOSE control block. In communication configuration we shall set the multicast address and AppID for
each GOOSE control block that will transmit signal via GOOSE.
Steps for communication configuration
Step 1:
Select the communication and click new button to add a communication network. See figure 3.5-1 Add
communication network.
Set the name for the new communication network
Select the type of communication network. Here 8-MMS is the type of MMS network, IECGOOSE is the
type of the GOOSE network and SMV is the type of the SMV network.
Figure 3.5-1 Add communication network
Step 2
Select the GOOSE network in communication
Select GSE attribute page and drag GOOSE access point from the right side window to the middle
window. See figure 3.5-2 Configure GOOSE network.
20
NR ELECTRIC CO., LTD. V 1.00
SCL Configurator Software User Guide
Figure 3.5-2 Configure GOOSE network
Step 3
We shall set the MAC-Address and APPID for the GOOSE control block. See figure 3.5-3 Set the
parameters for GOOSE control block.
MAC-Address: multicast address of the GOOSE control block. It is comprised of 6 octets. the first 4
octets is fixed, only the last two octets can be configured.
APPID: it is a four-bit hex number. It allows a user to assign a system unique identification for the
application.
Figure 3.5-3 Set the parameters for GOOSE control block
3.6. Configuration of the communication port for GOOSE
The NET-DSP module is used for GOOSE communication. This module consists of high-performance
DSP (digital signal processor), maximum up to 8 100Mbit/s optical-fibre interface (LC type). It supports
GOOSE and SV by IEC 61850-9-2 protocols. It can receive and send GOOSE messages to intelligent
21
V 1.00 NR ELECTRIC CO., LTD.
SCL Configurator Software User Guide
control device, and receive SV from MU (merging unit).
There are two different types of NET-DSP module, one type is NR1136A, it with 8 100Mbit/s optical-fibre
interface (LC type), the other type is NR1136C, it with 6 100Mbit/s optical-fibre interface (LC type) and 1
IRIG-B interface (ST type). See figure 3.6-1 NET-DSP module.
NR 1136A NR 1136C
RX
Figure 3.6-1 NET-DSP Modules
User could configure the port of NET-DSP module to transmit or receive the GOOSE signal of one
GOOSE control block. For example we can set the tripping signal of GOOSE control block “gocb3” of
PCS-902 transmitted from port 1 of NET-DSP module of PCS-902, and the circuit breaker position signal
of GOOSE control block “gocb1” of PCS-222 breaker intelligent controller received from port 2 of
NET-DSP module of PCS-902.
If the board configuration is not enabled, the color of board configuration icon is grey. See Figure 3.6-2
Board Configuration Function is disabled
22
NR ELECTRIC CO., LTD. V 1.00
SCL Configurator Software User Guide
Figure 3.6-2 Board Configuration Function is disabled
Before we start board configuration, we shall enable the board configuration function. Click File in the
menu bar and select Add, in the sub-menu choose board, then board configuration function will be
enabled. Then the color of board configuration icon will change to green.
Figure 3.6-3 Enable Board Configuration Function
Click the board configuration icon, and right click in the board explorer window. Select “New board
config…”. See Figure 3.6-4 New board configuration
23
V 1.00 NR ELECTRIC CO., LTD.
SCL Configurator Software User Guide
Figure 3.6-4 New Board Configuration
Then in the pop-up window select the IED. See Figure 3.6-5 Select IED
Figure 3.6-5 Select IED
Select the IED in board explorer window, the detail information of the board and control block will be
listed at the right side window.
The configurable NET-DSP module will be displayed under the boards.
The transmitted and received control blocks will be listed under the control blocks
24
NR ELECTRIC CO., LTD. V 1.00
SCL Configurator Software User Guide
In GOOSE TX lists all the GOOSE control blocks of the selected IED.
In GOOSE RX lists all the GOOSE control blocks that the selected IED will receive the GOOSE data
transmitted by this GOOSE control block. The GOOSE control block in GOOSE RX does not belong to
the selected IED itself. These GOOSE control blocks belong to the IEDs which will transmitted the data
to selected IED via GOOSE.
Figure 3.6-6 Boards and Control Blocks
Select the NET-DSP module in the fight side window and drag it to the middle window.
Select the GOOSE control block configured in communication under GOOSE TX in the right side window
and drag it to the corresponding GOOSE TX in the middle window. The selected GOOSE control block
will be added to the GOOSE TX in the middle window. See Figure 3.6-7 Select IED
Figure 3.6-7 GOOSE Control Block Configuration
Click the control block in the middle window, in the pop-up window input the optical-fiber port number
which used to transmit or receive the GOOSE data. The number is the optical-fiber port number on
NET-DSP module, the value start from 1. If more than 1 port will be used, use the “,” to separate the
different number. If no number is configured, it means the data will transmit or receive from all the ports.
25
V 1.00 NR ELECTRIC CO., LTD.
SCL Configurator Software User Guide
See figure 3.6-8 port configuration.
Figure 3.6-8 Port Configuration
The GOOSE control block which the port is configured, the port number will displayed behind the
GOOSE control block. See figure 3.6-9 Configured port information.
Figure 3.6-9 Configured port information
3.7. Export the cid file and goose.txt file
If all the configurations are completed, click SCL validate icon to validate to SCD file. If there is no any
error, we can save the SCD file and export the cid file and goose.txt file for each IED. See figure 3.7-1
and Figure 3.7-2.
26
NR ELECTRIC CO., LTD. V 1.00
SCL Configurator Software User Guide
Figure 3.7-1 SCL Validation
Figure 3.7-2 Result of Validation
Click the SCL export icon, and select “batch export CID and Uapc-Goose file”. See Figure 3.7-3 SCL
export
27
V 1.00 NR ELECTRIC CO., LTD.
SCL Configurator Software User Guide
Figure 3.7-3 SCL Export
In the pop-up window select the directory to save the exported file and select the IED, then click export
button to export the cid file and goose.txt file. See Figure 3.7-4.
28
NR ELECTRIC CO., LTD. V 1.00
SCL Configurator Software User Guide
Figure 3.7-4 Export CID file and goose.txt file
In the directory we just selected, there are two new folders. The folder name is the IED name. Open the
folder P100, there are two files, one is the cid file of the IED, the other is the goose.txt file.
The cid file name is device.cid. For all PCS series IED the cid file name is fixed as device.cid.
The goose.txt name is B07_NR1136_goose.txt. B07 is the slot number of NET-DSP module, NR1136 is
module type.
Figure 3.7-5 Two new folders
29
V 1.00 NR ELECTRIC CO., LTD.
SCL Configurator Software User Guide
Figure 3.7-6 CID file and goose.txt file
Download the goose.txt file to the NET-DSP module with PCS-EXPLORER.
If the IED will communicate with other IED via MMS, download CID file to the CPU module with
PCS-EXPLORER.
Note:
The cid file should not be downloaded to the NET-DSP module.
30
NR ELECTRIC CO., LTD. V 1.00
SCL Configurator Software User Guide
Version
Date Version Description Author
12th Feb, 2014 <1.00> Create the document Marc Miao
31
V 1.00 NR ELECTRIC CO., LTD.