CVDFD
CVDFD
Rate Amount
S.NO. DESCRIPTION Unit Qty.
(Rs.) (Rs.)
Plumbing Plant Room - Railway Station (Assumed for filling up two trains of 24
coach simultaneously)
No. of Working minutes - 5 Min.
1.3 Coach Filling pump ( 1 Set = 3 working + 1 standby)
Location - Plumbing Plant Room
Capacity 3460 LPM (Each Pump)
Head 60 m
HP/kW Load 77.0 HP / 57.45 kW (Each Pump) Set 1
Page 1
Rate Amount
S.NO. DESCRIPTION Unit Qty.
(Rs.) (Rs.)
2 Variable Frequency Drive System:
Vertical centrifugal (direct coupled) pumps cast-iron Casing material, Impellers shall
be one-piece, zinc free bronze and dynamically balanced Shaft for pumps with
suffing boxes shall be of stainless steel with IE3 motor mounted on a common M.S.
structural frame work, including common suction header with flange for inlet
connection, common outlet, header with flange for outlet connections and
interconnecting piping with isolating valves, non-return valves, pressure gauges with
isolation cock etc.
Precharged diaphragm pressure vessel FRP of suitable size (minimum 400 Ltrs
capacity (approx.) or as per manufacturer calculation / recommendation) for the
system mentioned below with charging connection, connected to outlet header with
necessary flanges, gaskets, isolating, valves, nuts/bolts etc. complete.
Fully automatic control panel including starters, instruments, incoming isolator, level
control for low water gaurd for pumps, microprocess based PLC, variable frequency
drive (VFD) and all controls, pressure transmitter, low and high system pressure
switch with alarm auto/manual selector switches, interconnecting power /control
cabling etc. all accessories which are required to complete the system for working
conditions as per specifications.
Hydropneumatic system as described above and as under given capacities:
For Sump Pump (1 Working + 1 Standby) For Drainage (Plant Room) (North Side
3.1
Building)
Discharge 380 lpm
Head 15 m
HP/kw Load 2.2 hp (approx.) Set 1
For Sump Pump (1 Working + 1 Standby) For Drainage (Plant Room) (South Side
3.2
Building)
Discharge 250 lpm
Head 15 m
Page 2
Rate Amount
S.NO. DESCRIPTION Unit Qty.
(Rs.) (Rs.)
HP/kw Load 1.4 hp (approx.) Set 1
For Sump Pump (1 Working + 1 Standby) For Drainage (Station Building Supply at
4.1
PRS)
(Pumps to be suitable to handle solids upto 10-15 mm size)
Discharge 420 lpm
Head 75 m
HP/kw Load 11.6 hp (approx.) Set 1
Electric Panel For Basement Drainage Sump Pump (Station Building Supply at
a
PRS)
All internal wiring colour coded from incoming mains to various switchgear, starters,
meters, indicating lamps and bus bar with a changeover facility to run each pump
alternatively with an alarm bell in case of both pump’s running at one time.
Switchegear offered must be compatible with the HP of the motors offered.
Motor control centre as described above Set 1
4.2 For Sump Pump (1 Working + 1 Standby) For Drainage (South Side Basement)
(Pumps to be suitable to handle solids upto 10-15 mm size)
Discharge 500 lpm
Head 30 m
HP/kw Load 5.6 hp (approx.) Set 3
a Electric Panel For Basement Drainage Sump Pump (South Side Basement)
All internal wiring colour coded from incoming mains to various switchgear, starters,
meters, indicating lamps and bus bar with a changeover facility to run each pump
alternatively with an alarm bell in case of both pump’s running at one time.
Switchegear offered must be compatible with the HP of the motors offered.
Motor control centre as described above Set 3
4.3 For Sump Pump (1 Working + 1 Standby) For Drainage (North Side Basement)
Page 3
Rate Amount
S.NO. DESCRIPTION Unit Qty.
(Rs.) (Rs.)
(Pumps to be suitable to handle solids upto 10-15 mm size)
Discharge 300 lpm
Head 30 m
HP/kw Load 3.4 hp (approx.) Set 4
Electric Panel For Basement Drainage Sump Pump (North Side Basement)
a
All internal wiring colour coded from incoming mains to various switchgear, starters,
meters, indicating lamps and bus bar with a changeover facility to run each pump
alternatively with an alarm bell in case of both pump’s running at one time.
Switchegear offered must be compatible with the HP of the motors offered.
Motor control centre as described above Set 4
4.4 For Sump Pump (1 Working + 1 Standby) For Drainage (MLCP Basement)
(Pumps to be suitable to handle solids upto 10-15 mm size)
Discharge 1150 lpm
Head 80 m
HP/kw Load 10.6 hp (approx.) Set 1
All internal wiring colour coded from incoming mains to various switchgear, starters,
meters, indicating lamps and bus bar with a changeover facility to run each pump
alternatively with an alarm bell in case of both pump’s running at one time.
Switchegear offered must be compatible with the HP of the motors offered.
Motor control centre as described above Set 1
For Sump Pump (1 Working + 1 Standby) For Sewerage (South Side Basement) For
4.5
Solid handling capacity upto 40mm
Discharge 220 lpm
Head 25 m
HP/kw Load 2.1 hp (approx.) Set 1
Electric Panel For Basement Sewerage Sump Pump (North Side Basement)
a
Page 4
Rate Amount
S.NO. DESCRIPTION Unit Qty.
(Rs.) (Rs.)
One rotary duty selector switch
Two manual/auto/off switches.
Two single phasing presenters.
One panel type voltmeter with rotary selector switch for reading voltage between
phases.
Two ampere meters one for each motor.
Three neon phase indicating lights on the incoming mains.
Space for one liquid level controllers.
All internal wiring colour coded from incoming mains to various switchgear, starters,
meters, indicating lamps and bus bar with a changeover facility to run each pump
alternatively with an alarm bell in case of both pump’s running at one time.
Switchegear offered must be compatible with the HP of the motors offered.
Motor control centre as described above Set 1
For Sump Pump (1 Working + 1 Standby) For Sewerage (North Side Basement
4.6
Right Side) For Solid handling capacity upto 40mm
Discharge 190 lpm
Head 20 m
HP/kw Load 2.1 hp (approx.) Set 1
Electric Panel For Basement Sewerage Sump Pump (North Side Basement
a
Right Side)
All internal wiring colour coded from incoming mains to various switchgear, starters,
meters, indicating lamps and bus bar with a changeover facility to run each pump
alternatively with an alarm bell in case of both pump’s running at one time.
Switchegear offered must be compatible with the HP of the motors offered.
Motor control centre as described above Set 1
For Sump Pump (1 Working + 1 Standby) For Sewerage (North Side Basement
4.7
South Side) For Solid handling capacity upto 40mm
Discharge 230 lpm
Head 20 m
HP/kw Load 1.8 hp (approx.) Set 1
Electric Panel For Basement Sewerage Sump Pump (North Side Basement
a
South Side)
All internal wiring colour coded from incoming mains to various switchgear, starters,
meters, indicating lamps and bus bar with a changeover facility to run each pump
alternatively with an alarm bell in case of both pump’s running at one time.
Switchegear offered must be compatible with the HP of the motors offered.
Page 5
Rate Amount
S.NO. DESCRIPTION Unit Qty.
(Rs.) (Rs.)
Motor control centre as described above Set 1
Page 6
Rate Amount
S.NO. DESCRIPTION Unit Qty.
(Rs.) (Rs.)
Supplying, installing, testing & commissioning of ultravoilet dis-infection unit. The unit
shall have over 99.9 % bacterial reduction from inlet to outlet. The dis-infection
chamber shall be constructed of SS 316L on all welted parts. The UV lamp shall be
8 of low pressure mercury vapour type with hard glass enclosure, the sockets shall be
water tight & vibration resistant. The lamp life shall be rated for 6000 hours. The unit
shall be complete with temperature safety control and lamp out alert circuit.
The UV unit shall have with reactor, cabinet housing, cabinet cooling, treatment
chamber, electrical panel, temperature safety control, lampout alert. The UV Dosage
should be > 30,000 uW – Sec / sq.cm. The lamps should be selected based upon
the flow requirement of respective unit.
8.1 Flow rate - 45.6 m3/hr (For North Side Building) No 1
8.2 Flow rate - 30 m3/hr (For South Side Building) No 1
Supply, installation, testing and commissioning of Digital Turbine Type flow meter
9
with online sensor and cable at WTP outlet for flow monitoring.
9.1 Flow rate - 45.6 m3/hr (For North Side Building) No 1
9.2 Flow rate - 30 m3/hr (For South Side Building) No 1
Providing and fixing mild steel (MS) puddle flanges of required size with 5mm thick
12 mild steel (MS) plate including necessary welding as per details shown on drawings
and directions of Engineer-in-charge for water tanks.
12.1 25mm dia (4mm wall thickness) Each 16
12.2 50mm dia (4mm wall thickness) Each 4
12.3 80mm dia (4mm wall thickness) Each 8
12.4 100mm dia (4mm wall thickness) Each 20
12.5 150mm dia (4mm wall thickness) Each 18
Supply, installation, testing & commissioning of Hot dipped galvanised 'Y' Strainer of
13
following sizes as per specification:
13.1 100 mm dia Each 4
13.2 150mm dia Each 2
To switch on the pumps when the level of water in the supply water tank is low and to
cut off the pump when the level in the recieving water tank is high and switch off the
pumps when the level of water in the supply water tank is low .
To indicate 5 levels of water in all tanks through a control panle with LEDs
To start the pumps in a cyclic order.
The system shall be complete to ensure automatic quotation of pump in accordance
to water level in respective tanks.
Supply, fixing, testing and commissioning of Site Tube (of 3.0 - 5 M) with isolation
15 valve at top and bottom demarcation on tube for making the installation of level Each 14
indication on the RCC water tank complete.
Providing, fixing, testing & commissioning of 100 mm dia Burden type, Stainless
16 Steel dial type pressure gauge including brass isolation valve and pipe having Each 14
caliberation of 0-16 Kg/cm2.
Page 7
Rate Amount
S.NO. DESCRIPTION Unit Qty.
(Rs.) (Rs.)
Providing, laying, testing & commissioning of 'C' class Heavy duty G.I. pipe
conforming to IS 1239 including welding, fittings like elbows, tees, flanges, tapers,
17 nuts, bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable
clamp/support frame and painting with two or more coats of synthetic enamel paint of
required shade complete as required :
17.1 65mm dia Meter 80
17.2 80mm dia Meter 60
17.3 100 mm dia Meter 65
17.4 150 mm dia Meter 50
Providing and fixing gun metal gate valve with C.I. wheel of approved quality
18 Each
(screwed end) :
a 40 mm nominal bore Each 4
b 50 mm nominal bore Each 15
c 65 mm nominal bore Each 16
d 80 mm nominal bore Each 10
e 100 mm nominal bore Each 10
Supplying, Installation, testing & commissioning complete testing kit with all
19 chemicals complete suitable for conducting test on water quantity. The test kit shall L.S 2
be suitable for measuring, TDS, PH, hardness, iron content etc.
Providing and fixing Butterfly valve Rated for PN16 pressure rating including rubber
20
gasket, flanges, nuts, bolts, washers & painting complete as required.
20.1 50 mm dia Nos. 10
20.2 65 mm dia Nos. 20
20.3 80 mm dia Nos. 8
20.4 100 mm dia Nos. 4
20.5 150 mm dia Nos. 4
Providing & fixing C.I. dual plate type check valve tested to a pressure of 15Kg/sqcm.
21 Including rubber gasket, flanges, union, nuts, bolts, washers & painting complete as
required.
21.1 50 mm dia Nos. 6
21.2 65 mm dia Nos. 8
21.3 80 mm dia Nos. 6
21.4 100 mm dia Nos. 6
21.5 150 mm dia Nos. 6
22 VIBRATION ELIMINATORS :
Providing, fixing, testing & commissioning of rubber neoprene lined style arch
vibration eliminators suitable pressure.
22.1 Pressure Rating PN 16 :
22.2 40 mm dia Each R.O.
22.3 50 mm dia Each 4
22.4 65 mm dia Each 6
22.5 80 mm dia Each 6
22.6 100 mm dia Each 4
22.7 150 mm dia Each 4
Page 8
Rate Amount
S.NO. DESCRIPTION Unit Qty.
(Rs.) (Rs.)
Incoming
1 No. - 630A 4P ATS
1 No. - 630A 4P MCCB of fault breaking capacity 25 kA (Ics = Icu upto 415V), fitted
with interlocked door, automatic safety shutters, mechanical ON/OFF and
service/test/isolated position indicators and frame earthing contact, conforming to IS-
13947-2 1993 as amended up-to-date complete with following accessories for each
MCCB.
Dual core calibrated digital Multifunctional meter of class 1.0 to record demand
(KVA), energy (KWH & KVAH), power factor, current (in each phase and the neutral),
voltage (between phases and between each phase and neutral) and 3 Nos. dual core
CT of A Class 1.0 accuracy and 15 VA burden.
Following indicating lamps and push buttons for each MCCB with back up 2A SP
MCB .
3 No. Phase indicating Lamps .
Indicating Lamps for the following;
Bus Bar
630 Amp. 25 kA, TPN Copper Bus Bar
One No. 630 amps 4P incoming MCCB complete with the following:
1 No. 0-500 volts 96x96 sq. mm ammeter with selector switch and fuses. (1 set).
1 No. 0-630 amps 96x96sq.mm ammeter with 630/5 amps ratio CT's and selector
switch.
Over voltage and under voltage tripping machanism for persistent voltage fluctations
of more than ±10% of the rated voltage for more than 5 minutes. (1set)
4 No Fully Star Delta starters suitable for 77 H.P. Pump Motor with over load
relay,contractors, time, push buttons, Auto/Manual selector switch and phase
indication light with MCB Ammeter (0- 160 Amp) with selector switch an CT’s of ratio
160/5A, 5VA class 1.0 and including 160A MCCB complete; as required .(for coach
filling transfer pumps )
25 amps TP MCCB with Dol starter each suitable 8.5 HP hydropneumatic pumps (3
Nos) (Only connection to inbuilt panel of Domestic water hydropneumatic system)
16 amps TP MCCB With Dol starter each suitable for 2.0 HP sump pumps in Plant
Room (2 Nos)
32 amps TP MCCB With Dol starter each suitable for 16.5 HP sump pumps Coach
Watering (2 Nos)
6A DP MCB with ON/OFF selector switch for Dosing Pumps - 1 No.
16A DP MCB with ON/OFF Selector switch for UV - 1 No.
MCB for PH Controller, Flow Meter
Spares
160 amps TPN MCCB - 2 Nos.
25 amps TPN MCCB - 1 Nos.
32 amps TPN MCCB - 1 Nos.
16 amps TPN MCCB - 2 Nos.
Note :
All switch gear/panels shall be suitable for 25 KA rating.
All outgoing will have 96 sq. mm size ammeter and CT.
All starter will have spare 25/16/32/160 amps 230 V coil auxiliary contractor for
building Automation system.
All starter units for pumps to be provided with 3 level liquid level contractor.
Lamps.
All pumps to be provided with duty selector switch.
All pumps to be provided with sequence timer 220/440 V AC/DC and alternate
working of pumps between 6 to 8 hours or alternate use of pumps after one service
in sequence.
All pumps to be provided with over load relay.
All starter to be provided with single phase preventor.
Necessary cable alleys for space switches, level controller internal wiring and copper
earthing of all equipment shall also be included. All switch gears/control gears shall
be motor duty rating.
Provisions of BMS system for pumps to be included in electrical control panel. The
panel manufacuturer shall include the following:
PF contact at Pumps Starter panels for Pumps Start/Stop Command for all pumps
indicated above.
Page 9
Rate Amount
S.NO. DESCRIPTION Unit Qty.
(Rs.) (Rs.)
PF contact at Pumps Starter panels for Pumps Run Status for all pumps indicated
above.
PF contact at Pumps Starter panels for AUTO/MANUAL switches for all pumps
indicated above.
PF contact at Pumps Starter panels for over load relay trip signals for all pumps
indicated above.
24.1 Cabling from BMS system to this panels will be done by BMS contractor. Set 1
Providing and fixing Electrical Cabling for all equipment feed supplies & Copper
25 Lot 1
flexible for control cabling including GI wires & strips for earthing .
Providing and fixing GI Cable Trays and supports of suitable sizes for all equipment
26 Lot 1
feed supplies.
Incoming
1 No. - 100A 4P ATS
1 No. - 100A 4P MCCB of fault breaking capacity 25 kA (Ics = Icu upto 415V), fitted
with interlocked door, automatic safety shutters, mechanical ON/OFF and
service/test/isolated position indicators and frame earthing contact, conforming to IS-
13947-2 1993 as amended up-to-date complete with following accessories for each
MCCB.
Dual core calibrated digital Multifunctional meter of class 1.0 to record demand
(KVA), energy (KWH & KVAH), power factor, current (in each phase and the neutral),
voltage (between phases and between each phase and neutral) and 3 Nos. dual core
CT of A Class 1.0 accuracy and 15 VA burden.
Following indicating lamps and push buttons for each MCCB with back up 2A SP
MCB .
3 No. Phase indicating Lamps .
Indicating Lamps for the following;
Bus Bar
100 Amp. 25 kA, TPN Copper Bus Bar
One No. 100 amps 4P incoming MCCB complete with the following:
1 No. 0-500 volts 96x96 sq. mm ammeter with selector switch and fuses. (1 set).
1 No. 0-100 amps 96x96sq.mm ammeter with 100/5 amps ratio CT's and selector
switch.
Over voltage and under voltage tripping machanism for persistent voltage fluctations
of more than ±10% of the rated voltage for more than 5 minutes. (1set)
25 amps TP MCCB with Dol starter each suitable 6.1 HP hydropneumatic pumps (3
Nos) (Only connection to inbuilt panel of Domestic water hydropneumatic system)
16 amps TP MCCB With Dol starter each suitable for 2.0 HP sump pumps (2 Nos)
Page 10
Rate Amount
S.NO. DESCRIPTION Unit Qty.
(Rs.) (Rs.)
16 amps TPN MCCB - 2 Nos.
Note :
All switch gear/panels shall be suitable for 25KA rating.
All outgoing will have 96 sq. mm size ammeter and CT.
All starter will have spare 25/16 amps 230 V coil auxiliary contractor for building
Automation system.
Page 11
Rate Amount
S.NO. DESCRIPTION Unit Qty.
(Rs.) (Rs.)
All starter units for pumps to be provided with 3 level liquid level contractor.
Lamps.
All pumps to be provided with duty selector switch.
All pumps to be provided with sequence timer 220/440 V AC/DC and alternate
working of pumps between 6 to 8 hours or alternate use of pumps after one service
in sequence.
All pumps to be provided with over load relay.
All starter to be provided with single phase preventor.
Necessary cable alleys for space switches, level controller internal wiring and copper
earthing of all equipment shall also be included. All switch gears/control gears shall
be motor duty rating.
Provisions of BMS system for pumps to be included in electrical control panel. The
panel manufacuturer shall include the following:
PF contact at Pumps Starter panels for Pumps Start/Stop Command for all pumps
indicated above.
PF contact at Pumps Starter panels for Pumps Run Status for all pumps indicated
above.
PF contact at Pumps Starter panels for AUTO/MANUAL switches for all pumps
indicated above.
PF contact at Pumps Starter panels for over load relay trip signals for all pumps
indicated above.
27.1 Cabling from BMS system to this panels will be done by BMS contractor. Set 1
Providing and fixing Electrical Cabling for all equipment feed supplies & Copper
28 Lot 1
flexible for control cabling including GI wires & strips for earthing .
Providing and fixing GI Cable Trays and supports of suitable sizes for all equipment
29 Lot 1
feed supplies.
Note: Actual requiment of MGF and ACF shall be design only after the water quality
report.
Page 12