Circuit-breaker,�4�p,�320A

Part�no. LZMC3-4-A320-I
Article�no. 116439

Similar to illustration

Delivery�programme
Product range Circuit-breaker

Protective function System and cable protection

Standard/Approval IEC

Installation type Fixed

Release system Thermomagnetic release

Construction size LZM3

Description Set value in neutral conductor is synchronous with set value Ir of main pole.

Number of poles 4 pole

Standard equipment Screw connection

Switching�capacity
400/415 V 50/60 Hz Icu kA 36

Rated�current�=�rated�uninterrupted�current
Rated current = rated uninterrupted current In = Iu A 320

Neutral conductor % of phase CSA 100


conductor

Setting�range
Overload trip

Ir A 250 - 320

Main pole Ir A 250 - 320

Short-circuit releases

Non-delayed Ii = In x … 6 - 10

Technical�data
General
Standards IEC/EN 60947, VDE 0660

Protection against direct contact Finger and back-of-hand proof to VDE 0106 part 100

Climatic proofing Damp heat, constant, to IEC 60068-2-78


Damp heat, cyclic, to IEC 60068-2-30

Mechanical shock resistance (10 ms half-sinusoidal shock) according to IEC g 20 (half-sinusoidal shock 20 ms)
60068-2-27

Safe isolation to EN 61140

Between auxiliary contacts and main contacts V AC 500

between the auxiliary contacts V AC 300

Mounting position Vertical and 90° in all directions


With XFI earth-fault release:
- NZM1, N1, NZM2, N2: vertical and
90° in all directions
with plug-in unit
- NZM1, N1, NZM2, N2: vertical, 90°
right/left
with withdrawable unit:

12/11/2015 116439 - HPL-ED2015 V18.0 EN 1/9


- NZM3, N3: vertical, 90° left
- NZM4, N4: vertical
with remote operator:
- NZM2, N(S)2, NZM3, N(S)3,
NZM4, N(S)4: vertical and 90° in all
directions

Direction of incoming supply as required

Degree of protection

Device In the area of the HMI devices: IP20 (basic protection type)

Enclosures with insulating surround: IP40with door coupling rotary handle: IP66

Terminations Tunnel terminal: IP10


Phase isolator and band terminal: IP00
Circuit-breakers
Rated current = rated uninterrupted current In = Iu A 320

Rated surge voltage invariability Uimp

Main contacts V 8000

Auxiliary contacts V 6000

Rated operational voltage Ue V AC 690

Rated operational voltage Ue V DC 750

The specifications apply to three-pole system-protective circuit breakers with an


NZMN(H)1(2)(3)-A… thermomagnetic release rated for currents of up to 500 A.

The following applies when using the rated operating voltage for switching on 3
contacts:

DC correction factor for instantaneous release response value: NZM1: 1.25, NZM2:
1.35, NZM3: 1.45

Set current for Ii for DC = Set current Ii for AC / DC correction factor

Switching�of�one�pole Switching�of�one
via�two�series�contacts pole�via�three�series
contacts

Overvoltage category/pollution degree III/3

Rated insulation voltage Ui V 1000

Use in unearthed supply systems V


690
Switching�capacity
Rated short-circuit making capacity Icm

240 V 50/60 Hz Icm kA 121

400/415 V 50/60 Hz Icm kA 76

440 V 50/60 Hz Icm kA 63

525 V 50/60 Hz Icm kA 24

690 V 50/60 H Ic kA 14

Rated short-circuit breaking capacity Icn Icn

Icu to IEC/EN 60947 test cycle O-t-CO Icu kA

240 V 50/60 Hz Icu kA 55

400/415 V 50/60 Hz Icu kA 36

440 V 50/60 Hz Icu kA 30

525 V 50/60 Hz Icu kA 12

690 V 50/60 Hz Icu kA 8

Ics to IEC/EN 60947 test cycle O-t-CO-t-CO Ics kA

230 V 50/60 Hz Ics kA 55

400/415 V 50/60 Hz Ics kA 36

12/11/2015 116439 - HPL-ED2015 V18.0 EN 2/9


440 V 50/60 Hz Ics kA 22.5

525 V 50/60 Hz Ics kA 9

690 V 50/60 Hz Ics kA 4

Maximum back-up fuse, if the expected short-circuit currents at the installation


location exceed the switching capacity of the circuit-breaker.

Rated short-time withstand current

t = 0.3 s Icw kA 3.3

t=1s Icw kA 3.3

Utilization category to IEC/EN 60947-2 A

Rated making and breaking capacity

Rated operational current Ie A

AC-1

380 V 400 V Ie A 500

415 V Ie A 500

690 V Ie A 500

AC--3

380 V 400 V Ie A 320

415 V Ie A 320

660 V 690 V Ie A 320

Lifespan, mechanical Operations 15000

Lifespan, electrical

AC-1

400 V 50/60 Hz Operations 5000

690 V 50/60 Hz Operations 3000

AC-2, AC-3

400 V 50/60 Hz Operations 2000

690 V 50/60 Hz Operations 2000

Max. operating frequency Ops/h 60

Current heat losses per pole at Iu are based on the maximum rated operational W 40
current of the frame size.

For current heat loss per pole the specification refers to the maximum rated
operational current of the frame size.

Total downtime in a short-circuit ms < 10


Terminal�capacity
Standard equipment Screw connection

Round copper conductor

Tunnel terminal

Solid mm
2 1 x (16 - 185)

Copper busbar (width x thickness) mm

Bolt terminal and rear-side connection

Screw connection M10

Design�verification�as�per�IEC/EN�61439
Technical data for design verification

Rated operational current for specified heat dissipation In A 320

Equipment heat dissipation, current-dependent Pvid W 94.0032

IEC/EN 61439 design verification

10.2 Strength of materials and parts

10.2.2 Corrosion resistance Meets the product standard's requirements.

10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.

10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.

10.2.3.3 Verification of resistance of insulating materials to abnormal heat Meets the product standard's requirements.
and fire due to internal electric effects

10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.

10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.

10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.

12/11/2015 116439 - HPL-ED2015 V18.0 EN 3/9


10.2.7 Inscriptions Meets the product standard's requirements.

10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.

10.4 Clearances and creepage distances Meets the product standard's requirements.

10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.

10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.

10.7 Internal electrical circuits and connections Is the panel builder's responsibility.

10.8 Connections for external conductors Is the panel builder's responsibility.

10.9 Insulation properties

10.9.2 Power-frequency electric strength Is the panel builder's responsibility.

10.9.3 Impulse withstand voltage Is the panel builder's responsibility.

10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.

10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.

10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.

10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.

10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.

Technical�data�ETIM�6.0
Low-voltage industrial components (EG000017) / Power circuit-breaker for trafo/generator/installation prot. (EC000228)

Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Circuit breaker for power transformer, generator and system
protection ([email protected] [AJZ716010])

Rated permanent current Iu A 320

Rated voltage V 690 - 690

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz kA 36

Overload release current setting A 250 - 320

Adjustment range short-term delayed short-circuit release A 0-0

Adjustment range undelayed short-circuit release A 1920 - 3200

Integrated earth fault protection No

Type of electrical connection of main circuit Screw connection

Device construction Built-in device fixed built-in technique

Suitable for DIN rail (top hat rail) mounting No

DIN rail (top hat rail) mounting optional No

Number of auxiliary contacts as normally closed contact 0

Number of auxiliary contacts as normally open contact 0

Number of auxiliary contacts as change-over contact 0

Switched-off indicator available No

With under voltage release No

Number of poles 4

Position of connection for main current circuit Front side

Type of control element Rocker lever

Complete device with protection unit Yes

Motor drive integrated No

Motor drive optional Yes

Degree of protection (IP) IP20

12/11/2015 116439 - HPL-ED2015 V18.0 EN 4/9


Characteristics

12/11/2015 116439 - HPL-ED2015 V18.0 EN 5/9


12/11/2015 116439 - HPL-ED2015 V18.0 EN 6/9
12/11/2015 116439 - HPL-ED2015 V18.0 EN 7/9
Dimensions

Blow out area, minimum clearance to other parts

Minimum clearance to adjacent parts

12/11/2015 116439 - HPL-ED2015 V18.0 EN 8/9


Additional�product�information�(links)
IL01208013Z�LZMC3�circuit-breaker,�LN3�switch-disconnector

IL01208013Z LZMC3 circuit-breaker, LN3 ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL01208013Z2012_02.pdf


switch-disconnector

12/11/2015 Eaton Industries GmbH 9/9


http://www.eaton.eu
© 12/2015 by Eaton Industries GmbH
116439 - HPL-ED2015 V18.0 EN