Electrical Technical Specifications _School, Gym and Kindergarten Electrical Technical Specifications _School, Gym and Kindergarten

“Ramazan Karaj”, Nikel “Ramazan Karaj”, Nikel

exclude manually from the UPS device network connection. Battery specifications
Charging power Programmable from 1% TO 20% of UPS
The UPS shall be a single-UPS unit, operating in double-conversion mode, it shall be a type of Capacity, Default IS 10%
UPS (as per standard IEC 62040-2), made up of the following components, described in detail in Maximum charging power (W) 6000
this specification: Nominal battery voltage (VDC) +/- 240
• rectifier; Nominal float voltage (VDC) +/-270
• battery charger; End of discharge voltage (Full load) (VDC) +/-198
• inverter; Battery current at full load and nominal battery 66
• battery; voltage (A)
• static bypass (via a static switch); Battery current at full load and minimum battery 81
• manual maintenance bypass; voltage (A)
Ripple current <5% C10
• user and communications interface;
Maximum short circiut withstand Icc=10 kA
• battery management system;
Recommended cable sizes
Input cable size (mm2) 16
The UPS shall ensure continuity of electric power to the load within the specified tolerances, Bypass cable size (mm2) 16
without interruption upon failure or deterioration of the normal AC source (utility power) for a
Output cable size (mm2) 16
maximum protection time determined by the capacity of the backup batteries installed. Battery input cable size (mm2) 25
PE cable size (mm2) 16
For the uninterrupted power supply for the office building project 4 ups have been chosen for each
floor, so that the floors are independent of each other, thereby increasing the security of
• Specification for the Main Low Voltage Electrical Panel
uninterrupted power supply.
Requirements of construction of the system of installation
Below are the technical specifications for each of 30kVA UPS:

• General information
b) Technical features of UPS 30 kVA, On-Line
The main L.V low voltage switchboard will be manufactured in conformance to standard IEC 61439-
UPS equipment is completed with batteries and must fulfil the following features: 2 and will be tested according to the 15 tests defined by this international standard of LV electrical
switchgear assemblies.
Electrical Data Sheet
UPS Rating 30 kVA − 12 Type tests carried out by the manufacturer:
Input Specifications 1. Strength of material and parts
Input voltage 380V/400V/415V 2. Degree of protection of enclosures
Nominal input current (A) 48/46/44 3. Clearance and creepage creep age distances
Maximum input current (A) 58/55/53 4. Protection against electric shocks and integrity of protective circuits
Input current limitation (A) 65/63/60 5. Incorporation of switching devices and components
Input frequency 45-65 Hz 6. Internal electrical circuits and connections
Input wiring 3P+N+PE 7. Terminals for external conductors
Input thdi <3%@ 10Kva, <4%@ 15-40 kVa 8. Dielectric properties
Bypass Specifications 9. Temperature rise limits
Bypass voltage 380V/400V/415V 10. Short circuit withstand strength
Minimum bypass voltage 304/320/332 11. Electromagnetic compatibility
Maximum bypass voltage 437/460/477 12. Mechanical operation
Nominal bypass current (A) 46/43/42
Bypass frequency 50/60Hz
Bypass wiring 3P+N+PE − 3 routine tests carried out by the panel builder:
Output Specifications 1. Wiring, functional operation
Output voltage 380V/400V/415V 2. Insulation
Nominal output current (A) 46/43/42 3. Protection measures
Output frequency 50/60Hz
Output wiring 3P+N+PE In order to guarantee the quality of the delivered assembly, the contractor of this batch will
Output THDU <3%@ 100% LINEAR LOAD, <5.5%@ 100% obligatorily provide the certificates or compliance certificates of the 12 Type tests of the manufacturer
NON-LINEAR LOAD as well as a copy of the routine test certificates.

5 6
Electrical Technical Specifications _School, Gym and Kindergarten Electrical Technical Specifications _School, Gym and Kindergarten
“Ramazan Karaj”, Nikel “Ramazan Karaj”, Nikel

In the same way, a declaration of conformance signed by the attesting panel builder panel builder of ✓ Power frequency: 50Hz;
the 3 routine tests will accompany the switchboard. Other tests could be performed in accordance with ✓ Main circuit breaker: MCB type, In=32A, Icc=15kA, 3~ 400V/ 50Hz;
the combined documents ✓ Breaking Capacity Icc: 15kA;
✓ With overvoltage discharge SPD, 3~ 400V / 50Hz;
To fulfil the requirements as regards EMC behaviour, the equipment will be designed for application ✓ Degrees of protection: Metallic type, IK08, IP40;
in an environment of the type has in accordance with standard IEC 61439-2. The panel builder must ✓ Connections: Inlet and outlet connection cable should be below;
be able to present the manufacturers guaranteeing EMC performances of the equipment and confirm ✓ Connection clamps for connection of all inlet and outlet cables
✓ (According to the scheme of single line diagram given the project).
that this assembly conforms to manufacturer instructions.
To guarantee the electric performances of the equipment installed and their longevity, the system of • Electrical Distribution Board 1 Ground Floor – School (E.D.B1.G.F-S)
switchboard and apparatus will come from a single manufacturer. ✓ Type: tested;
✓ Installation: flush mounted
In this building, the electrical distribution board will be divided related on the building functionality ✓ Rated Voltage: 1kV (AC);
and zones, as shown in the electrical design. Electrical Distribution Board and panels will be installed ✓ Operating Voltage: 0.4kV (AC);
as follow: ✓ Power frequency: 50Hz;
1. Main Electrical Panel Ground Floor – School (M.E.P.G.F-S); ✓ Main circuit breaker: MCB type, In=32A, Icc=10kA, 3~ 400V/ 50Hz
2. Technical Room Electrical Panel – School (T.R.E.P-S); ✓ Breaking Capacity Icc: 10kA;
3. Electrical Distribution Board 1 Ground Floor – School (E.D.B1.G.F-S); ✓ With overvoltage discharge SPD, 3~ 400V/ 50Hz;
4. Electrical Distribution Board 2 Ground Floor – School (E.D.B2.G.F-S); ✓ Degrees of protection: plastic type, IK08, IP40;
5. Electrical Distribution Board 1 First Floor – School (E.D.B1.F.F-S); ✓ Connections: Inlet and outlet connection cable should be below;
6. Electrical Distribution Board 2 First Floor – School (E.D.B2.F.F-S); ✓ Connection clamps for connection of all inlet and outlet cables
7. Electrical Distribution Board First Floor – UPS (E.D.B.F.F-UPS); ✓ (According to the scheme of single line diagram given the project).
8. Electrical Distribution Board 1 Second Floor – School (E.D.B1.S.F-S);
9. Electrical Distribution Board 2 Second Floor – School (E.D.B2.F.F-S); • Electrical Distribution Board 2 Ground Floor – School (E.D.B2.G.F-S)
10. Electrical Distribution Board First Floor – Info. Cabinet (E.D.B.F.F-I.C); ✓ Type: tested;

11. Electrical Distribution Board Second Floor – Info. Cabinet (E.D.B.S.F-I.C); ✓ Installation: flush mounted

12. Main Electrical Panel Ground Floor - Gym School (M.E.P.G.F-G); ✓ Rated Voltage: 1kV (AC);

13. Main Electrical Panel Ground Floor - Kindergarten (M.E.P.G.F-G.S). ✓ Operating Voltage: 0.4kV (AC);
✓ Power frequency: 50Hz;
✓ Main circuit breaker: MCB type, In=32A, Icc=10kA, 3~ 400V/ 50Hz
According to the project Main Electrical Panel have the following technical features:
✓ Breaking Capacity Icc: 10kA;

• Main Electrical Panel Ground Floor – School (M.E.P.G.F-S) ✓ With overvoltage discharge SPD, 3~ 400V/ 50Hz;

✓ Type: tested; ✓ Degrees of protection: plastic type, IK08, IP40;

✓ Installation: surface mounted ✓ Connections: Inlet and outlet connection cable should be below;

✓ Rated Voltage: 1kV (AC); ✓ Connection clamps for connection of all inlet and outlet cables

✓ Operating Voltage: 0.4kV (AC); ✓ (According to the scheme of single line diagram given the project).

✓ Power frequency: 50Hz;


✓ External auxiliary voltage: 400/230V AC;
• Electrical Distribution Board 1 First Floor – School (E.D.B1.F.F-S)
✓ Main circuit breaker: MCCB type, In=250A, Icc=25kA, 3~ 400V/ 50Hz; ✓ Type: tested;

✓ Breaking Capacity Icc: 25kA; ✓ Installation: flush mounted

✓ With Digital Analyzer of Electrical Parameters; ✓ Rated Voltage: 1kV (AC);

✓ With overvoltage discharge SPD, 3~ 400V/ 50Hz; ✓ Operating Voltage: 0.4kV (AC);

✓ Degrees of protection: Metallic type, IK08, IP40; ✓ Power frequency: 50Hz;

✓ Connections: Inlet and outlet connection cable should be below; ✓ Main circuit breaker: MCB type, In=32A, Icc=10kA, 3~ 400V/ 50Hz

✓ Connection clamps for connection of all inlet and outlet cables ✓ Breaking Capacity Icc: 10kA;
✓ With overvoltage discharge SPD, 3~ 400V/ 50Hz;
✓ (According to the scheme of single line diagram given the project).
✓ Degrees of protection: plastic type, IK08, IP40;

• Technical Room Electrical Panel – School (T.R.E.P-S) ✓ Connections: Inlet and outlet connection cable should be below;

✓ Type: tested; ✓ Connection clamps for connection of all inlet and outlet cables

✓ Rated Voltage: 1kV (AC); ✓ (According to the scheme of single line diagram given the project).

✓ Operating Voltage: 0.4kV (AC);