380V TVR Pro Service Manual
380V TVR Pro Service Manual
Service Manual
TVR Pro CO Series
4TVY0077HE000AA 4TVY0192HE000AA
4TVY0096HE000AA 4TVY0210HE000AA
4TVY0115HE000AA 4TVY0229HE000AA
4TVY0140HE000AA 4TVY0249HE000AA
4TVY0155HE000AA 4TVY0268HE000AA
4TVY0170HE000AA 4TVY0290HE000AA
CONTENTS
1
2
Part 1
General Information
1 Indoor and Outdoor Unit Capacities ...................................................... 4
2 External Appearance.............................................................................. 6
4 Nomenclature...................................................................................... 10
3
1 Indoor and Outdoor Unit Capacities
1.1 Indoor Units
1.1.1 Standard indoor units
Table 1-1.1: Standard indoor unit abbreviation codes
Abbreviation Abbreviation
Type Type
code code
Q1 One-way Cassette T1 High Static Pressure Duct
Q2 Two-way Cassette G Wall-mounted
Q4C Compact Four-way Cassette DL Ceiling & Floor
Q4 Four-way Cassette F Floor Standing
T2 Medium Static Pressure Duct
4
1.3 Outdoor Units
Table 1-1.5: Outdoor unit capacity range
Capacity Model Name Combination Type
8HP 4TVY0077HE000AA /
10HP 4TVY0096HE000AA /
12HP 4TVY0115HE000AA /
14HP 4TVY0140HE000AA /
16HP 4TVY0155HE000AA /
18HP 4TVY0170HE000AA /
20HP 4TVY0192HE000AA /
22HP 4TVY0210HE000AA /
24HP 4TVY0229HE000AA /
26HP 4TVY0249HE000AA /
28HP 4TVY0268HE000AA /
30HP 4TVY0290HE000AA /
32HP 4TVY0310HE000AA 16HP+16HP
34HP 4TVY0325HE000AA 22HP+12HP
36HP 4TVY0347HE000AA 20HP+16HP
38HP 4TVY0365HE000AA 22HP+16HP
40HP 4TVY0384HE000AA 24HP+16HP
42HP 4TVY0404HE000AA 26HP+16HP
44HP 4TVY0423HE000AA 28HP+16HP
46HP 4TVY0445HE000AA 30HP+16HP
48HP 4TVY0459HE000AA 26HP+22HP
50HP 4TVY0478HE000AA 28HP+22HP
52HP 4TVY0500HE000AA 30HP+22HP
54HP 4TVY0517HE000AA 28HP+26HP
56HP 4TVY0536HE000AA 28HP+28HP
58HP 4TVY0558HE000AA 30HP+28HP
60HP 4TVY0580HE000AA 30HP+30HP
62HP 4TVY0600HE000AA 30HP+16HP+16HP
64HP 4TVY0614HE000AA 26HP+22HP+16HP
66HP 4TVY0633HE000AA 28HP+22HP+16HP
68HP 4TVY0655HE000AA 30HP+22HP+16HP
70HP 4TVY0672HE000AA 28HP+26HP+16HP
72HP 4TVY0691HE000AA 28HP+28HP+16HP
74HP 4TVY0713HE000AA 30HP+28HP+16HP
76HP 4TVY0735HE000AA 30HP+30HP+16HP
78HP 4TVY0746HE000AA 28HP+28HP+22HP
80HP 4TVY0768HE000AA 30HP+28HP+22HP
82HP 4TVY0790HE000AA 30HP+30HP+22HP
84HP 4TVY0804HE000AA 28HP+28HP+28HP
86HP 4TVY0826HE000AA 30HP+28HP+28HP
88HP 4TVY0848HE000AA 30HP+30HP+28HP
90HP 4TVY0870HE000AA 30HP+30HP+30HP
Notes:
1. The combinations of units shown in the table are factory-recommended. Other combinations of units are also possible.
5
2 External Appearance
2.1 Indoor Units
2.1.1 Standard indoor unit
Table 1-2.1: Standard indoor unit appearance
Q1 Q2
Q4C Q4
T2 T1
G DL
Floor Standing
6
2.3 Outdoor Units
2.3.1 Single units
Table 1-2.4: Single outdoor unit appearance
8/10/12/14/16HP 18/20/22HP 24/26/28/30
(with single fan) (with dual fans) (with dual fans)
40/42/44/46HP 48/50/52HP
54/56/58/60HP 62HP
64/66/68HP 70/72/74/76HP
7
Table continued on next page…
Table 1-2.5: Combination outdoor unit appearance
78/80/82HP 84/86/88/90HP
8
Table continued on next page…
Table 1-3.1: Outdoor unit combinations
Number Outdoor branch
System capacity Modules1
of units joint kit2
242.0 86 3 ●● ●
248.5 88 3 ● ●● TODK03UTHP
255.0 90 3 ●●●
Notes:
1. The combinations of units shown in the table are factory-recommended. Other combinations of units are also possible.
2. For systems with two or more outdoor units, outdoor branch joints (sold separately) are required.
9
4 Nomenclature
4.1 Indoor Units
4.1.1 Standard indoor units
4 T V E 0 0 0 7 E F 0 0 0 A A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Legend
No. Code Remarks
1 4 R-410A
2 T Trane
3 V TVR
Indoor Unit Type
E: One - Way Cassette
G: Two - Way Cassette
B: Compact Four - Way Cassette
C: Four - Way Cassette
4 D: Medium Static Pressure Duct
A: High Static Pressure Duct
W: Wall - Mounted
C: Ceiling & Floor
S, N, U: Floor Standing
F: Fresh air processing unit
5 0 Currently not used
6 0
7 0 Btu/h x 1000
8 7
9 E TVR Ultra
10 F 380V50-60Hz/1P
11 0 Currently not used
12 0 Currently not used
13 0 Currently not used
14 A First design sequence
15 A First service sequence
10
4.2 Heat recovery ventilator
AC Series
T E R V 0 1 2 0 A B 0 A A
1 2 3 4 5 6 7 8 9 10 11 12 13
Legend
No. Code Remarks
1 T
2 E Energy recovery Fan
3 R Trane TVR
4 V
5 0
6 1
CFM
7 2
8 0
9 A TVR
1: 380V/60Hz/1Ph
10 B
B: 380/50Hz/1Ph
11 0 Currently not used
12 A First design sequence
13 A First service sequence
11
Part 2
Component Layout and
Refrigerant Circuits
1 Layout of Functional Components ....................................................... 13
12
1 Layout of Functional Components
8-16HP
Figure 2-1.1: 8-16HP layout of functional components
4 11
Legend
No. Parts name
1 Compressor
2 Discharge temperature sensor
3 High pressure sensor
13 4 Oil separator
13
5 Heat exchanger
5
6 6 Electronic expansion valve (EXV)
2
7 Fan motor
8 Fan
9 Stop valve (liquid side)
10 Stop valve (gas side)
11 Accumulator
12 Low pressure switch
8
13 Solenoid valve
7
13
12
3
9 10
13
18-22HP
Figure 2-1.2: 18-22HP layout of functional components
4 11
Legend
No. Parts name
1 Compressor
2 Discharge temperature sensor
3 High pressure sensor
13 4 Oil separator
5 Heat exchanger
13
5 6 Electronic expansion valve (EXV)
6
7 Fan motor
8 Fan
9 Stop valve (liquid side)
10 Stop valve (gas side)
2 2 11 Accumulator
12 Low pressure switch
13 Solenoid valve
8 8
7
7
13
12
3
1
1
9 10
14
24-30HP
Figure 2-1.3: 24-30HP layout of functional components
4 11 11
Legend
No. Parts name
1 Compressor
Discharge temperature
2
3 sensor
6 5 Heat exchanger
5
Electronic expansion
6
valve (EXV)
7 Fan motor
8 Fan
2 2
9 Stop valve (liquid side)
10 Stop valve (gas side)
8 8 11 Accumulator
13
12
9 10
15
2 Piping Diagrams
8-16HP
Figure 2-2.1: 8-16HP piping diagram
8
7 EXVA 9
5 XX°C 6
T3
XX°C
T4 10
4
3 SV2
13
2
SV7
1 12 11
SV4
13
13
Legend
No. Parts name No. Parts name
1 Compressor 10 Stop valve (gas side)
2 Discharge temperature sensor 11 Accumulator
3 High pressure sensor 12 Low pressure switch
4 Oil separator 13 Solenoid valve
5 Heat exchanger T3 Heat exchanger temperature sensor
6 Electronic expansion valve (EXV) T4 Outdoor ambient temperature sensor
7 Fan motor SV2 Liquid injection valve
8 Fan SV4 Oil return valve
9 Stop valve (liquid side) SV7 Pressure valve
16
18-22HP
Figure 2-2.2: 18-22HP piping diagram
8 8
7 7 EXVA 9
5 XX°C 6
T3
XX°C
T4
10
3 4
SV7
13
2 2
1 1 12 11
13 SV4
16
SV2
13
Legend
No. Parts name No. Parts name
1 Compressor 10 Stop valve (gas side)
2 Discharge temperature sensor 11 Accumulator
3 High pressure sensor 12 Low pressure switch
4 Oil separator 13 Solenoid valve
5 Heat exchanger T3 Heat exchanger temperature sensor
6 Electronic expansion valve (EXV) T4 Outdoor ambient temperature sensor
7 Fan motor SV2 Liquid injection valve
8 Fan SV4 Oil return valve
9 Stop valve (liquid side) SV7 Pressure valve
17
24-30HP
Figure 2-2.3: 24-30HP piping diagram
8 8
7 7 EXVA 9
5 XX°C 6
T3
XX°C
T4
10
3 4
SV2
13
SV7
13
2 2
1 1 12 11 11
SV4
13
Legend
No. Parts name No. Parts name
1 Compressor 10 Stop valve (gas side)
2 Discharge temperature sensor 11 Accumulator
3 High pressure sensor 12 Low pressure switch
4 Oil separator 13 Solenoid valve
5 Heat exchanger T3 Heat exchanger temperature sensor
6 Electronic expansion valve (EXV) T4 Outdoor ambient temperature sensor
7 Fan motor SV2 Liquid injection valve
8 Fan SV4 Oil return valve
9 Stop valve (liquid side) SV7 Pressure valve
18
Key components:
1. Oil separator:
Separates oil from gas refrigerant pumped out of the compressor and quickly returns it to the compressor. Separation
efficiency is up to 99%.
2. Accumulator:
Stores liquid refrigerant and oil to protect compressor from liquid hammering.
3. Electronic expansion valve (EXV):
Controls refrigerant flow and reduces refrigerant pressure.
4. Solenoid valve SV2:
Protects the compressor. If compressor discharge temperature rises above 100oC, SV2 opens and sprays a small
amount of liquid refrigerant to cool the compressor. SV2 closes again once the discharge temperature has fallen
below 90oC.
5. Solenoid valve SV4:
Returns oil to the compressor. Opens once the compressor has run for 200 seconds and closes 600 seconds later and
then opens for 3 minutes every 20 minutes.
6. Solenoid valve SV7:
Allows refrigerant to return directly to the compressor. Opens when indoor air temperature is close to the set
temperature to avoid frequent compressor on/off. Opens when superheat degree is insufficient to avoid liquid
hammer to compressor.
7. Low pressure switches:
Regulate system pressure. When system pressure falls below the lower limit, the low pressure switches turn off,
stopping the compressor. After 10 minutes, the compressor restarts.
19
3 Refrigerant Flow Diagrams
8-16HP
Cooling operation
Figure 2-3.1: 8-16HP refrigerant flow during cooling operation
Unit on
High temperature, high pressure gas Fan Thermostat on
on
High temperature, high pressure liquid Filter Filter
Low temperature, low pressure
Normal control
8
7 EXVA 9
4
3 SV2
13
Fan Unit off
off
Filter Filter
Closed
2
SV7
1 12 11
SV4
13
13 Unit on
Fan Thermostat off
on
Filter Filter
Closed
20
18-22HP
Cooling operation
Figure 2-3.3: 18-22HP refrigerant flow during cooling operation
Unit on
High temperature, high pressure gas Fan Thermostat on
on
High temperature, high pressure liquid
Filter Filter
Low temperature, low pressure
Normal control
8 8
7 7 EXVA 9
3 4
off
13 Filter Filter
Closed
2 2
1 1 12 11
Unit on
SV4
21
24-30HP
Cooling operation
Figure 2-3.5: 24-30HP refrigerant flow during cooling operation
Unit on
High temperature, high pressure gas Fan Thermostat on
on
High temperature, high pressure liquid
Filter Filter
Low temperature, low pressure
Normal control
8 8
7 7 EXVA 9
3 4
SV2
13 Unit off
SV7
Fan
off
13
Filter Filter
Closed
2 2
1 1 12 11 11
SV4
Unit on
13 Fan Thermostat off
on
Filter Filter
Closed
22
23
Part 3
Control
1 General Control Scheme Flowchart .......................................................... 25
24
1 General Control Scheme Flowchart
Sections 3-2 to 3-6 on the following pages detail when each of the controls in the flowchart below is activated.
2
Stop operation
Abnormal shutdown
System stops 6
Special control
A unit stops when the load demanded decreases
Thermo on
3
Startup control
Thermo on
Compressor startup delay control Outdoor unit duty cycling
Startup control for cooling operation
4
Normal operation control
Component control during normal operation
Conditions met
Compressor output control
for oil return
Compressor step control Oil return operation
Operation priority and rotation of compressors
Electronic expansion valve control
Outdoor fan control
5
Protection control
High pressure protection control
Low pressure protection control Legend
Discharge temperature protection control Numbers in the top right-hand
corners of boxes indicate the
Compressor and inverter module protection relevant section of text on the
following pages.
control
25
2 Stop Operation
The stop operation occurs for one of the three following reasons:
1. Abnormal shutdown: in order to protect the compressors, if an abnormal state occurs the system makes a 'stop with
thermo off' operation and an error code is displayed on the outdoor unit digital displays.
2. The system stops when the set temperature has been reached.
3. A unit stops when the load demanded by the indoor units decreases and can be handled by fewer outdoor units.
3 Startup Control
3.1 Compressor Startup Delay Control
In initial startup control, compressor startup is delayed for 12 minutes in order to let the master unit search for the indoor
units’ addresses. In restart control (except in oil return operation), compressor startup is delayed such that a minimum of 7
minutes has elapsed since the compressor stopped, in order to prevent frequent compressor on/off and to equalize the
pressure within the refrigerant system.
26
4 Normal Operation Control
4.1 Component Control during Normal Operation
Table 3-4.1: Component control during normal cooling operation
Wiring diagram
Component 8-12HP 14-16HP 18-22HP 24-30HP Control functions and states
label
Inverter compressor A BP1 ● ● ● ●
Controlled according to load requirement
Inverter compressor B BP2 ● ●
During operation the compressors are controlled according to the nominal capacity of indoor units currently running and
the indoor unit heat exchanger temperatures. If the actual load requirement can be provided by one unit alone, then only
one unit starts up. If the actual load requirement requires all outdoor unit modules to operate, the weighted average
actual load requirement is sent to each module and each module operates according to this distributed load
requirement.
27
Figure 3-4.1: Compressor priority and rotation – one outdoor unit
BP BP1 BP2
BP BP BP BP1 BP2 BP BP
① No. 1 No. 2 No. 3 No. 4 No. 5 ① No. 1 No. 2 No. 3 No. 4 No. 5 No. 6
② No. 4 No. 5 No. 1 No. 2 No. 3 ② No. 5 No. 6 No. 1 No. 2 No. 3 No. 4
③ No. 2 No. 3 No. 4 No. 5 No. 1 ③ No. 3 No. 4 No. 5 No. 6 No. 1 No. 2
BP1 BP2 BP1 BP2 BP BP1 BP2 BP1 BP2 BP1 BP2
In cooling mode:
When all outdoor units are in standby:
All EXVAs are at position 352×6(steps).
When some outdoor units are running and some outdoor units are in standby:
EXVAs on running outdoor units are controlled according to discharge temperature. EXVAs of units in standby are
28
fully closed.
When all outdoor units are running:
All EXVAs are controlled according to discharge temperature.
29
5 Protection Control
5.1 High Pressure Protection Control
This control protects the system from abnormally high pressure and protects the compressors from transient spikes in
pressure.
Figure 3-5.1: High pressure protection control
Normal operation
Notes:
1. Pc: Discharge pressure
Normal operation
Discharge temperature
Compressor off
120oC
100oC
90oC 90oC
When the discharge temperature rises above 120°C the system displays P4 protection and all units stop running. When P4
protection occurs 3 times in 100 minutes, the H6 error is displayed. When an H6 error occurs, a manual system restart is
required before the system can resume operation.
Normal operation
Normal operation
31
6 Special Control
6.1 Outdoor Unit Duty Cycling
In systems with multiple outdoor units, outdoor unit duty cycling is used to prevent compressor burn out due to
unbalanced oil levels between outdoor units.
Figure 3-6.1 shows an example of duty cycling in a system with 3 outdoor units.
Figure 3-6.1: Duty cycling in a system with 3 outdoor units1
Outdoor unit Priority Priority Priority Outdoor unit Priority Priority Priority
duty cycling 1 2 3 duty cycling 3 1 2
Notes:
1. The address settings on the outdoor unit main PCBs for “master unit”, “slave unit 1”, and “slave unit 2” do not change.
32
6.2 Oil Return Operation
In order to prevent compressors from running out of oil, the oil return operation is conducted to recover oil that has
flowed out of the compressor(s) and into the piping system. This operation is performed for all units including units that
are in standby. When the outdoor unit is running in oil return, the digital display on outdoor main PCB will display “d0”.
Timing of oil return operation:
When the initial cumulative operating time reaches 140 minutes and then every 8 hours.
Tables 3-6.1 and 3-6.2 show component control during oil return operation in cooling mode.
Table 3-6.1: Outdoor unit component control during oil return operation in cooling mode
Component Wiring diagram label 8-12HP 14-16HP 18-22HP 24-30HP Control functions and states
Inverter compressor A BP1 ● ● ● ●
Fixed frequency
Inverter compressor B BP2 ● ●
Table 3-6.2: Indoor unit component control during oil return operation in cooling mode
Component Unit state Control functions and states
Thermo on Remote controller setting
Fan Standby Off
Thermo off Off
Thermo on Normal control
Electronic expansion valve Standby 300 (steps)
Thermo off 300 (steps)
33
Part 4
Field Settings
1 Outdoor Unit Field Settings ................................................................. 35
34
1 Outdoor Unit Field Settings
1.1 PCB Switches and Switch Settings
Figure 4-1.1: Outdoor unit main PCB switches
Reserved Reserved
S6-1
No action (default)
Clear indoor
S6-2 unit addresses
Clear indoor unit addresses
Reserved Reserved
S8-1
Start-up time is 12 minutes (default)
Start-up time
S8-2
Start-up time is 7 minutes
Reserved Reserved
S8-3
S7 Reserved
36
1.2 Modes Set on Main PCB
1.2.1 Silent time setting
1.2.1.1 Night silent time setting
Night silent mode is activated X hours after the peak daytime temperature, and is deactivated after Y hours, where X and Y
are as specified in Table 4-1.2.
Table 4-1.2: Night silent time setting
Switch Switch positions Description X Y
0 Night silent time is 6h/10h (default) 6 10
ENC5
1 Night silent time is 6h/12h 6 12
2 Night silent time is 8h/10h 8 10
3 Night silent time is 8h/12h 8 12
Maximum
output
Load
6 10
Operation
sound dB Max. 15dB
reduction
8:00 14:00 20:00 6:00
Night silent Night silent mode
mode activated deactivated
37
1.2.1.2 Silent mode setting
In silent mode 1 / 2 / 3 and night silent mode, the outdoor fan speed decreases gradually. In super silent mode 1 / 2 / 3 / 4,
not only the fan speed decreases gradually, but also the compressor frequency decreases gradually.
Table 4-1.3: Silent mode setting
Switch Switch positions Description
5 Silent mode 1 (only limit max. fan speed)
6 Silent mode 2 (only limit max. fan speed)
7 Silent mode 3 (only limit max. fan speed)
8 Super silent mode 1 (limit max. fan speed and compressor frequency)
ENC5
9 Super silent mode 2 (limit max. fan speed and compressor frequency)
A Super silent mode 3 (limit max. fan speed and compressor frequency)
B Super silent mode 4 (limit max. fan speed and compressor frequency)
1.2.1.3 Maximum fan speed and capacity output control in different silent mode
Table 4-1.4: Maximum fan speed and capacity output control in different silent mode
Max.
ENC5 Max. fan speed index1 capacity
Switch Description output
positions
8-10HP 12HP 14-16HP 18HP 20-22HP 24-26HP 28-30HP 8-30HP
0 Night silent time is 6h/10h (default)
1 Night silent time is 6h/12h
28 28 30 29 29 31 31
2 Night silent time is 8h/10h
3 Night silent time is 8h/12h
100%
4 No silent mode 29 30 33 33 35 33 35
5 Silent mode 1 28 28 30 31 31 31 31
6 Silent mode 2 26 26 28 29 29 29 29
7 Silent mode 3 24 24 27 27 27 27 27
8 Super silent mode 1 28 28 29 23 23 28 28 80%
9 Super silent mode 2 27 27 28 22 22 27 27 70%
A Super silent mode 3 26 26 27 21 21 26 26 60%
B Super silent mode 4 25 25 26 20 20 25 25 50%
Notes:
1. Fan speed (rpm) for different fan speed index refers to Table 3-4.2 in Part 3, 4.6 “Outdoor Fan Control”.
2. If the system pressure is over 3.5MPa, the system exits silent mode automatically.
38
Part 5
Electrical Components and
Wiring Diagrams
1 Outdoor Unit Electric Control Box Layout .............................................. 40
39
1 Outdoor Unit Electric Control Box Layout
8-16HP
Figure 5-1.1: 8-16HP top layer of electric control box
40
18-30HP
Figure 5-1.3: 18-30HP top layer of electric control box
41
2 Outdoor Unit Main PCB
2.1 Ports
Figure 5-2.1: Outdoor unit main PCB ports1
Notes:
1. Label descriptions are given in Table 5-2.1.
42
Table 5-2.1: Main PCB ports
Label Port code Content Port voltage
1 CN18 Reserved /
2 CN19 Low pressure switch connection 0V or 5V DC
Compressor top temperature sensor (single compressor
3 CN4 units) or compressor A compressor top temperature sensor 0-5V DC (varying)
(dual compressor units) connection
Discharge pipe temperature sensor (single compressor units)
4 CN5 or compressor B compressor top temperature sensor (dual 0-5V DC (varying)
compressor units) connection
5 CN3 Inverter module temperature sensor A connection 0-5V DC (varying)
6 CN13 Inverter module temperature sensor B connection 0-5V DC (varying)
7 CN17 High pressure sensor connection 0-5V DC (varying)
8 CN15 Reserved /
9 CN16 Reserved /
10 CN8 Reserved /
Outdoor ambient temperature sensor and outdoor heat
11 CN1 0-5V DC (varying)
exchanger temperature sensor connections
12 CN6 Reserved /
13 CN22-CN23 Communication port to outdoor units 2.5-2.7V DC
14 CN26 Communication port to compressor drive board 2.5-2.7V DC
15 CN27 Communication port to fan drive board 2.5-2.7V DC
16 CN9 Communication USB port 2.5-2.7V DC
17 CN28 Reserved /
18 CN71 Reserved /
19 CN70 EXVA drive port 0V or 12V DC
20 CN72 Reserved /
21 CN82 Control port of relay for AC filter board 0V or 12V DC
CN41, CN43,
22 Solenoid valve drive ports 0V or 220V AC
CN46
220V AC between A/B/C and N;
23 CN30 Power input of main board
380V AC between A,B and C
24 CN66-CN67 Power supply to compressor crankcase heater 220V AC
43
2.2 Components
Layout
Figure 5-2.2: Outdoor unit main PCB components
Button Function
SW3 (UP) In menu mode: previous and next buttons for menu
modes.
SW4 (DOWN) Not in menu mode: previous and next buttons for
system check information.
44
Menu mode
Only master unit has the full menu functions, slaves units only have error codes check and cleaning functions.
1. Long press SW5 “MENU” button for 5 seconds to enter menu mode, and the digital display displays “n1”;
2. Press SW3 / SW4 “UP / DOWN” button to select the first level menu “n1”, “n2”, “n3”, “n4”or “nb”;
3. Press SW6 “OK” button to enter specified first level menu, for example, enter “n4” mode;
4. Press SW3 / SW4 “UP / DOWN” button to select the second level menu from “n41” to “n47”;
5. Press SW6 “OK” button to enter specified second level menu, for example, enter “n43” mode;
Start
Short press SW5
“MENU” button
Confirm “-nXY”
45
Menu mode function:
Table 5-2.3: Menu mode function
Digital display
Menu mode Remarks
content
n14 Debug mode Only available for the master unit (all indoor units running in cooling mode)
n16 Maintenance mode Only available for the master unit, the system does not check the indoor units’ number.
n24 Reserved
n25 Reserved
Only available for outdoor unit with two compressors. If one of the two compressors is
n26 Backup run
fail, the other compressor will keep running for up to 4 days and then stop automatically.
It is only used in maintenance process. The digital display displays “R006”, all solenoid
n27 Vacuum mode
valves are open and EXVs are open to the maximum steps.
n31 History error codes Display recent ten history error codes
n33 Reserved
n42 Power limitation mode 2 Only available for the master unit, 90% capacity output
n43 Power limitation mode 3 Only available for the master unit, 80% capacity output
n44 Power limitation mode 4 Only available for the master unit, 70% capacity output
n45 Power limitation mode 5 Only available for the master unit, 60% capacity output
n46 Power limitation mode 6 Only available for the master unit, 50% capacity output
n47 Power limitation mode 7 Only available for the master unit, 40% capacity output
nb1 Fahrenheit degree setting (oF) Only available for the master unit
According to outdoor ambient temperature (T4), the outdoor fan(s) periodically stop for
nb5 Auto snow-blowing mode 1 (customized)
15 minutes and run for 2 minute
According to outdoor ambient temperature (T4), the outdoor fan(s) periodically stop for
nb6 Auto snow-blowing mode 2 (customized)
30 minutes and run for 2 minute
The digital display will display “IdXX”, “XX” stands for VIP address, use UP / DOWN button
nb8 VIP address setting
to change the VIP address and press OK button to confirm the specified VIP address.
nF1 Reserved
nF2 Reserved
Notes:
1. Auto power save mode means EMS mode, the evaporating temperature (in cooling) and condensing temperature (in heating) are automatically adjusted
according to both indoor and outdoor temperature to maximize the comfort and energy efficiency. Exit auto power save mode, the evaporating temperature
(in cooling) and condensing temperature (in heating) are fixed.
46
How to exit specified menu mode:
Table 5-2.4: Exit specified menu mode method:
Menu mode Manual exit method Automatic exit method System restart
Long press SW6 “OK” button when the digital
Debug mode After running 120 minutes Invalid
display is not in menu selection state
DSP1
Parameters displayed on DSP2 Remarks
content
0.-- Unit address Master unit: 0; slave units: 1, 2
1.-- Unit capacity Refer to Note 1
2.-- Number of outdoor units Displayed on master unit PCB only
3.-- Number of indoor units as set on PCB Displayed on master unit PCB only
Only available for master unit, displayed on slave
4.-- Total capacity of outdoor unit
units has no sense
5.-- Total capacity requirement of indoor units Displayed on master unit PCB only
6.-- Total corrected capacity requirement of master units Displayed on master unit PCB only
7.-- Operating mode Refer to Note 2
8.-- Outdoor unit actual operating capacity
9.-- Fan A speed index Refer to Note 3
10.-- Fan B speed index Refer to Note 3
11.-- Indoor heat exchanger pipe (T2/T2B) temperature (°C) Actual value = value displayed
12.-- Main heat exchanger pipe (T3) temperature (°C) Actual value = value displayed
13.-- Outdoor ambient (T4) temperature (°C) Actual value = value displayed
14.-- Inverter compressor A discharge temperature (°C) Actual value = value displayed
15.-- Inverter compressor B discharge temperature (°C) Actual value = value displayed
16.-- Inverter module A heatsink temperature (°C) Actual value = value displayed
17.-- Inverter module B heatsink temperature (°C) Actual value = value displayed
18.-- Discharge superheat degree (°C) Actual value = value displayed
19.-- Reserved
20.-- Reserved
21.-- EXVA position Refer to Note 4
22.-- Compressor discharge pressure (MPa) Actual value = value displayed × 0.1
23.-- Reserved
24.-- Number of indoor units currently in communication with master unit Actual value = value displayed
25.-- Number of indoor units currently operating Displayed on master unit PCB only
26.-- Reserved
27.-- Silent mode Refer to Note 5
28.-- Static pressure mode Refer to Note 6
29.-- Reserved
30.-- Reserved
31.-- DC voltage A Actual value = value displayed × 10
32.-- DC voltage B Actual value = value displayed × 10
33.-- Reserved
Table continued on next page …
47
Table 5-2.5: System check (continued)
DSP1
Parameters displayed on DSP2 Remarks
content
34.-- Address of VIP indoor unit
35.-- Reserved
36.-- Reserved
37.-- Refrigerant quantity Refer to Note 7
38.-- Reserved
39.-- Power mode Refer to Note 8
“--“ is displayed if no error or protection events
40.-- Most recent error or protection code
have occurred since start-up
-- -- End
Notes:
1. Outdoor unit capacity setting:
0: 8HP; 1: 10HP; 2: 12HP; 3: 14HP; 4: 16HP; 5: 18HP; 6: 20HP; 7: 22HP; 8: 24HP; 9: 26HP; A: 28HP; B: 30HP; C: 30HP.
2. Operating mode:
0: off; 2: cooling; 3: null; 4: forced cooling.
3. The fan speed index is related to the fan speed in rpm and can take any integer value in the range 1 (slowest) to 37 (fastest).
4. 480P: steps = value displayed × 4; 3000P: steps = value displayed × 24.
5. Silent mode:
0: night silent time 6h/10h; 1: night silent time 6h/12h; 2: night silent time 8h/10h; 3: night silent time 8h/12h; 4: no silent mode; 5: silent mode 1; 6:
silent mode 2; 7: silent mode 3; 8: super silent mode 1; 9: super silent mode 2; 10: super silent mode 3; 11: super silent mode 4.
6. Static pressure mode:
0: standard static pressure; 1: low static pressure; 2: medium static pressure; 3: high static pressure; 4: super high static pressure.
7. Refrigerant quantity:
0: normal; 1: slightly excessive; 2: significantly excessive; 3: slightly insufficient; 4: significantly insufficient; 5: critically insufficient.
8. Power mode:
0: 100% capacity output; 1: 90% capacity output; 2: 80% capacity output; 3: 70% capacity output; 4: 60% capacity output; 5: 50% capacity output; 6:
40% capacity output; 10: auto power save mode, 100% capacity output; 11: auto power save mode, 90% capacity output; 12: auto power save
mode, 80% capacity output; 13: auto power save mode, 70% capacity output; 14: auto power save mode, 60% capacity output; 15: auto power save
mode, 50% capacity output; 16: auto power save mode, 40% capacity output;
48
3 Compressor Inverter Module
3.1 Ports
Figure 5-3.1: Compressor inverter module ports
49
3.2 Layout
Figure 5-3.2: Compressor inverter module components
Inverter module operating indicator. Continuously on if the compressor is running normally and
LED 1
flashing if an inverter module error has occurred1.
LED 2 Inverter module error indicator. Continuously on if an inverter module error has occurred1.
Note:
1. If an inverter module error occurs, refer to Part 6, “Xh4 Troubleshooting”. The error code is displayed on the digital display.
50
4 Fan Module
4.1 Ports
Figure 5-4.1: Fan module ports
51
8-16HP
RA_A
CN6
CN1
5 Wiring Diagrams
RA_A
Figure 5-5.1: 8-16HP wiring diagram
CN11
CN2(CN3)
CN12 CN13 CN14
EEVA
CN70
EEVA
L1’ L2’ L3’ RA_A
ENC1 ENC2
52
CN82
N-ON
NUM_S POWER CN30
DSP1 DSP2
CN18
S12 ENC3
H-PRO
ON
CN19
123 Alarm
L-PRO
IN_NUM
HEATB
CN3
TF1
TF1
CN67 HEATB
HEATB
CN4
T7C1 CN67_1
Main board HEATB
T7C1
HEATA HEATA/HEATB Crankcase heater
CN66 HEATA Alarm Alarm output
H-YL1
CN17
HEATA
H-YL1
CN66_1 HEATA
T4
CN1
SV7 CN46 SV7
T4 T3
T3
X Y E P Q E O A E H1 H2 E CN91
ON/OFF SWITCH
XT1 (for priority mode )
L1 L2 L3 N
To To To
To indoor outdoor
centrali- kilowatt-
units hour units com-
zed communi- munication
controller cation meter bus
bus
Power in
18-30HP
RA_A RA_B
CN6 CN6
RA_A RA_B
CN11 CN11
Figure 5-5.2: 18-30HP wiring diagram
CN2(CN3)
CN2(CN3)
Note
CN12 CN13 CN14 CN12 CN13 CN14
EEVA
CN70
EEVA
RA_A/RA_B
ENC1 ENC2
53
CN82
N-ON
NUM_S POWER
DSP1 DSP2 CN30
S12 ENC3
CN18
H-PRO
ON
MENU DOWN UP OK
CN19
L-PRO 123 Alarm
L-PRO
CN80 Alarm
IN_NUM
CN3
TF1
TF1
HEATB
CN67 HEATB
TF2
TF2
CN13
HEATB
CN4
T7C1 CN67_1
Main board HEATB
HEATA/HEATB Crankcase heater
HEATA
CN5
T7C2 CN66 HEATA Alarm Alarm output
T7C1 T7C2
HEATA
CN17
H-YL1 CN66_1 HEATA
T4
CN1
SV7 CN46 SV7
T3 H-YL1 T4 T3
CN9
O-C O-FAN
X Y E P Q E O A E H1 H2 E CN91
ON/OFF SWITCH
XT1 (for priority mode )
L1 L2 L3 N
To To To
To indoor outdoor
centrali- kilowatt-
units hour units com-
zed communi- munication
controller cation meter bus
bus
Power in
Part 6
Diagnosis and
Troubleshooting
1 Error Code Table .................................................................................... 55
2 Troubleshooting .................................................................................... 56
54
1 Error Code Table
Table 6-1.1: Error code table
55
Table 6-1.1: Error code table (continued)
2 Troubleshooting
2.1 Warning
Warning
All electrical work must be carried out by competent and suitably qualified, certified and
accredited professionals and in accordance with all applicable legislation (all national, local and other laws,
standards, codes, rules, regulations and other legislation that apply in a given situation).
Power-off the outdoor units before connecting or disconnecting any connections or wiring, otherwise electric
shock (which can cause physical injury or death) may occur or damage to components may occur.
56
2.2 E0: Communication error between outdoor units
Digital display output
Description
Communication error between outdoor units.
All units stop running.
Error code is only displayed on the slave unit with the error.
Possible causes
Incorrect outdoor unit address setting.
Communication wires between outdoor units not connected properly.
Loosened wiring within electric control box.
Damaged main PCB or electric control box communication terminals block.
57
Procedure
E0
ODU addresses on switch ENC1 are set Yes Set the ODU addresses correctly
incorrectly1
No
Notes:
1. The master unit address should be set as 0, slave units addresses should be set from 1 to 2, and the addresses should not be repeated within one system.
2. All the wires for H1, H2, E connections should be three-core shielded cable, the wiring should be connected according to polarity (H1 to H1, etc), the wiring
should not be open or short circuited.
58
2.3 E2: Communication error between indoor and master unit
Digital display output
Description
Communication error between indoor and master unit.
All units stop running.
Error code is only displayed on the master unit.
Possible causes
Communication wires between indoor and outdoor units not connected properly.
Indoor unit power supply abnormal.
Loosened wiring within electric control box.
Interference from high voltage wires or other sources of electromagnetic radiation.
Communication wire too long.
Damaged main PCB or electric control box communication terminals block.
59
Procedure
E2
No
Interference from high voltage (220V or Yes Ensure the communication wires and
higher) wires high voltage wires are separated
No
The length of communication wire is over Yes Reduce the wire length to less than
1200m 1200m or strengthen the signal
No
Notes:
1. Measure the resistance among P, Q and E. The normal resistance between P and Q is 120Ω, between P and E is infinite, between Q and E is infinite.
60
2.4 E4: Temperature sensor (T3/T4) error
Digital display output
Description
Outdoor heat exchanger temperature sensor (T3) error or outdoor ambient temperature sensor (T4) error.
All units stop running.
Error code is only displayed on the unit with the error.
Possible causes
Temperature sensor not connected properly or has malfunctioned.
Damaged main PCB.
61
Procedure
E4
Temperature sensor connection on main Yes Ensure the sensor is connected properly
PCB is loose1
No
Notes:
1. Outdoor ambient temperature sensor (T4) and heat exchanger temperature sensor (T3) connection is port CN1 on the main PCB (labeled 11 in Figure 5-2.1
in Part 5, 2.1 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Table 6-3.1 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”.
62
2.5 E5: Abnormal power supply voltage
Digital display output
Description
Abnormal power supply voltage.
All units stop running.
Error code is only displayed on the unit with the error.
Possible causes
Outdoor unit power supply voltage is abnormal or a phase is missing.
Loosened wiring within electric control box.
High voltage circuit error.
Main PCB damaged.
63
Procedure
E5
Notes:
1. The normal voltage between A and N, B and N, and C and N is 198-242V.
2. The normal resistances of the inverter compressor are 0.7-1.5Ω among U V W and infinite between each of U V W and ground. If any of the resistances
differ from these specifications, the compressor has malfunctioned.
3. The normal resistances of the fan motor coil among U V W are less than 10Ω. If a measured resistance is 0Ω, the fan motor has short-circuited.
4. Set a multi-meter to buzzer mode and test any two terminals of P N U V W of the inverter module. If the buzzer sounds, the inverter module has
short-circuited.
64
2.6 E7: Temperature sensor (T7C1/2) error
Digital display output
Description
A compressor top temperature sensor or discharge pipe temperature sensor (T7C1/2) error.
All units stop running.
Error code is only displayed on the unit with the error.
Possible causes
Temperature sensor not connected properly or has malfunctioned.
Damaged main PCB.
65
Procedure
E7
Temperature sensor connection on main Yes Ensure the sensor is connected properly
PCB is loose1
No
Notes:
1. Compressor top temperature sensor and discharge pipe temperature sensor connections are ports CN4 and CN5 on the main PCB (labeled 3 and 4,
respectively, in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Table 6-3.2 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”.
66
2.7 E8: Outdoor unit address error
Digital display output
Description
Outdoor unit address error.
All units stop running.
Error code is only displayed on the unit with the error.
Possible causes
Invalid outdoor unit address.
Main PCB damaged.
67
Procedure
E8
The ODU's address is not in the valid Yes Slave units addresses should be set from
range1 1 to 2
No
Notes:
1. The master unit address should be set as 0, slave units addresses should be set from 1 to 2, and the addresses should not be repeated within one system.
68
2.8 xE9: EEPROM mismatch
Digital display output
In the error code, 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1
representing compressor system A and 2 representing compressor system B.
Description
1E9 indicates a compressor A EEPROM mismatch.
2E9 indicates a compressor B EEPROM mismatch.
All units stop running.
Error code is only displayed on the unit with the error.
Possible causes
Outdoor unit was powered on immediately after being powered off.
Main PCB damaged.
69
Procedure
xE9
Notes:
1. When performing a manual restart of an outdoor unit, once the unit has been powered off it should not be powered on again until the digital display has
turned off.
70
2.9 xF1: DC bus voltage error
Digital display output
'x' is a placeholder for the compressor system (compressor and related electrical components), with 1 representing
compressor system A and 2 representing compressor system B.
Description
1F1 indicates compressor A DC bus voltage error; 2F1 indicates compressor B DC bus voltage error.
All units stop running.
Error code is only displayed on the unit with the error.
Possible causes
Loosened wiring of the compressor inverter module.
Incorrect wiring of the reactor and DC bus wire.
Abnormal power supply.
Inverter module damaged.
Procedure
F1 error
No
No
71
2.10 F6: Electronic expansion valve connection error
Digital display output
Description
Electronic expansion valve connection error.
All units stop running.
Error code is only displayed on the unit with the error.
Possible causes
Electronic expansion valve coil not connected properly or has malfunctioned.
Damaged main PCB.
72
Procedure
F6
Electronic expansion valve coil Yes Ensure the sensor is connected properly
connection on main PCB is loose1
No
Notes:
1. Electronic expansion valve coil connections is port CN70 on the main PCB (labeled 19 in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. The normal resistances between EXV coil wiring terminals RED and white / yellow / orange / blue are 40-50Ω. If any of the resistances differ from the value,
the EXV coil has malfunctioned.
Figure: EXV coil wiring terminals
73
2.11 xH0: Communication error
Digital display output
In the error code, 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1
representing compressor system A and 2 representing compressor system B.
Description
1H0 indicates a communication error between the main control chip and the compressor A inverter driver chip.
2H0 indicates a communication error between the main control chip and the compressor B inverter driver chip.
All units stop running.
Error code is only displayed on the unit with the error.
Possible causes
Incorrect compressor inverter module address setting. Bridge rectifier damaged.
Loosened communication wiring from the main PCB to Main PCB damaged.
the inverter module. Compressor inverter module damaged.
Procedure
H0 error
Both LED1 and LED2 on inverter module Yes Check the power supply
are off when power on 3 circuit
No
No
74
Notes:
1. Compressor inverter module address is set through dial switch S7 on the inverter module. The compressor inverter module A/B location refers to the
wiring diagram.
2. Communication wire from outdoor main PCB CN26 to inverter module CN8/CN9.
3. LED1/2 on inverter module
75
2.12 H2, H3: Slave units decreased/increased
Digital display output
Description
H2 indicates that the number of slave units detected by master unit has decreased.
H3 indicates that the number of slave units detected by master unit has increased.
All units stop running.
Error code is only displayed on the master unit.
Possible causes
Some outdoor units are powered off.
Power supply abnormal.
Incorrect outdoor unit address setting.
Communication wires between outdoor units not connected properly.
Loosened wiring within electric control box.
Damaged main PCB or electric control box communication terminals block.
76
Procedure
H2 / H3
Some outdoor units in the system are Yes Power on all the outdoor units
powered off
No
The power supply is abnormal Yes Check the power supply equipment
No
Notes:
1. See “E0 Troubleshooting”.
77
2.13 xH4: Inverter module protection
Digital display output
In the error code, 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1
representing compressor system A and 2 representing compressor system B.
Description
1H4 indicates compressor A inverter module protection.
2H4 indicates compressor B inverter module protection.
All units stop running.
Error code is only displayed on the unit with the error.
Possible causes
Inverter module protection.
DC bus low or high voltage protection.
MCE error.
Zero speed protection.
Phase sequence error.
Excessive compressor frequency variation.
Actual compressor frequency differs from target frequency.
78
The specific error codes xL0, xL1, xL2 and xL4 can also be obtained from the inverter module LED indicators. If an inverter
module error has occurred, LED2 is continuously on and LED1 flashes.
79
L0: Inverter module protection
L0 protection
No
No
The inverter module is not well heat Yes Yes Fasten IPM
The IPM screws is loosen
dissipation screws again
No No
Ensure enough Yes The compressor has less than 12 hours The silica gel is coated not Yes Coat with silica
preheating time preheating before initial operating well for heat radiation gel
No No
Yes
80
L1: DC bus low voltage protection
L1 protection
No
Yes
No output from bridge rectifier
No
No
Yes
Replace the inverter module
Note:
1. The normal DC voltage between terminals P and N on inverter module should be 450-650V. When the voltage is lower than 350V, L1
protection will be appeared.
Figure: Inverter module terminals
81
L2: DC bus high voltage protection
L2 protection
No
No
Note:
1. The normal DC voltage between terminals P and N on inverter module should be 450-650V. When the voltage is higher than 700V, L2
protection will be appeared.
Figure: Inverter module terminals
82
L4: MCE error
Notes:
1. Compressor inverter module address is set through dial switch S7 on the inverter module. The compressor inverter module A/B location refers to the
wiring diagram.
83
L7: Phase sequence error
84
L8: Compressor frequency variation greater than 15Hz within one second protection
L9: Actual compressor frequency differs from target frequency by more than 15Hz protection
85
Compressor replacement procedure
Step 1: Remove faulty compressor and remove oil
Remove the faulty compressor from the outdoor unit.
Before removing the oil, shake the compressor so as to not allow impurities to remain settled at the bottom.
Drain the oil out of the compressor and retain it for inspection. Normally the oil can be drained out from the
compressor discharge pipe.
Step 6: Replace the faulty compressor and re-fit the other compressors
Replace the faulty compressor.
If the oil had been spoiled and was drained from the non-faulty compressors in Step 3, use clean oil to clean them
before re-fitting them into the units. To clean, add oil into the compressor through the discharge pipe using a funnel,
shake the compressor, and then drain the oil. Repeat several times and then re-fit the compressors into the units.
(The discharge pipe is connected to the oil pool of the compressor by the inner oil balance pipe.)
86
2.14 H7: Unmatched total number of indoor units
Digital display output
Description
Number of indoor units detected by master unit not same as number set on main PCB.
All units stop running.
Error code is only displayed on the master unit.
Possible causes
Number of indoor units set on main PCB not same as actual number of indoor units.
Some indoor units are powered off.
Communication wires between indoor and outdoor units not connected properly.
Indoor unit PCB damaged.
Indoor unit without address or indoor unit address duplicated.
Main PCB damaged.
87
Procedure
H7
Number of indoor units set on main PCB Change the setting on the PCB to be the
not same as actual number of indoor Yes same as the actual number of indoor
units1 units
No
Some indoor units are powered off Yes Power on all indoor units
No
After re-starting the ODUs and IDUs and Refer to indoor unit troubleshooting
then waiting 2 minutes, an IDU displays Yes guide. Resolving the indoor unit error
an E1 or FE error2 resolves the outdoor unit error
No
Notes:
1. The number of indoor units can be set on switches EN3 and S12 on the main PCB.
2. Indoor unit error code E1 indicates a communication error between indoor and master unit. Indoor unit error code FE indicates that an indoor unit has not
been assigned an address.
3. Indoor unit addresses can be checked and manually assigned using indoor unit remote/wired controllers. Alternatively, indoor unit addresses can be
automatically assigned by the master outdoor unit.
88
2.15 H8: High pressure sensor error
Digital display output
Description
High pressure sensor error.
All units stop running.
Error code is only displayed on the unit with the error.
Possible causes
Pressure sensor not connected properly or has malfunctioned.
Insufficient refrigerant.
Low pressure side blockage.
Poor evaporator heat exchange.
Main PCB damaged.
89
Procedure
H8
High pressure sensor connection on main Yes Ensure the sensor is connected properly
PCB is loose1
No
Insufficient refrigerant caused by Yes Add refrigerant and inspect system for
refrigerant leakage3 leaks
No
The low pressure side is blocked, caused Inspect the system and fix the error. If the
by crushed or bent pipe, closed EXV or Yes filter is blocked by ice, the piping should
dirty filter4 be cleaned
No
The evaporator heat exchange is poor5 Yes Inspect the system and fix the error
No
Notes:
1. High pressure sensor connection is port CN17 on the main PCB (labeled 7 in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure the resistance among the three terminals of the pressure sensor. If the resistance is of the order of mega Ohms or infinite, the pressure sensor
has failed.
3. An insufficiency of refrigerant causes compressor discharge temperature to be higher than normal, discharge and suction pressures to be lower than
normal and compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. These issues disappear once sufficient
refrigerant has been charged into the system. For normal system parameters refer to Table 6-3.4 in Part 6, 3.2 “Normal Operating Parameters of
Refrigerant System”.
4. A low pressure side blockage causes compressor discharge temperature to be higher than normal, suction pressure to be lower than normal and
compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. For normal system parameters refer to Table 6-3.4 in
Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
5. In cooling mode check indoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check outdoor heat exchangers, fans and air outlets
for dirt/blockages.
90
2.16 yHd: Slave unit malfunction
Digital display output
In the error code, 'y' is a placeholder for the address (1 or 2) of the slave unit with the error.
Description
1Hd indicates an error on the slave unit with address 1.
2Hd indicates an error on the slave unit with address 2.
All units stop running.
Error code is only displayed on the master unit.
Possible causes
Slave unit malfunction.
91
Procedure
yHd
92
2.17 P1: Discharge pipe high pressure protection
Digital display output
Description
All units stop running.
Error code is only displayed on the unit with the error.
Possible causes
Outdoor unit stop valves are closed.
High pressure sensor not connected properly or has malfunctioned.
Excess refrigerant.
System contains air or nitrogen.
High pressure side blockage.
Poor condenser heat exchange.
Main PCB damaged.
Procedure
P1
ODU stop valves are closed Yes Open the stop valves
No
High pressure sensor connection on main Yes Ensure the sensor is connected properly
PCB is loose1
No
No
93
… flowchart continued from previous page
The high pressure side is blocked, caused Yes Inspect the system and fix the error
by crushed or bent pipe or blocked EXV5
No
The condenser heat exchange is poor6 Yes Inspect the system and fix the error
No
Notes:
1. The high pressure sensor connection is port CN17 on the main PCB (labeled 7 in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure the resistance among the three terminals of the high pressure sensor. If the resistance is of the order of mega Ohms or infinite, the high pressure
sensor has failed.
3. Excess refrigerant causes discharge temperature to be lower than normal, discharge pressure to be higher than normal and suction pressure to be higher
than normal. For normal system parameters refer to Table 6-3.4 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
4. Air or nitrogen in the system causes discharge temperature to be higher than normal, discharge pressure to be higher than normal, compressor current to
be higher than normal, abnormal compressor noise and an unsteady pressure meter reading. For normal system parameters refer to Table 6-3.4 in Part 6,
3.2 “Normal Operating Parameters of Refrigerant System”.
5. High pressure side blockage causes discharge temperature to be higher than normal, discharge pressure to be higher than normal and suction pressure to
be lower than normal. For normal system parameters refer to Table 6-3.4 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
6. In cooling mode check outdoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check indoor heat exchangers, fans and air outlets
for dirt/blockages.
94
2.18 P2, H5: Suction pipe low pressure protection
Digital display output
Description
All units stop running.
Error code is only displayed on the unit with the error.
Possible causes
Outdoor unit stop valves are closed.
Insufficient refrigerant.
Low pressure side blockage.
Poor evaporator heat exchange.
Main PCB damaged.
95
Procedure
P2 / H5
ODU stop valves are closed Yes Open the stop valves
No
Insufficient refrigerant caused by Yes Add refrigerant or inspect the system for
refrigerant leakage1 leaks
No
The low pressure side is blocked, caused Inspect the system and fix the error. If the
by crushed or bent pipe, blocked EXV, or Yes filter is blocked by ice, the piping should
dirty filter2 be cleaned
No
The evaporator heat exchange is poor5 Yes Inspect the system and fix the error
No
Notes:
1. An insufficiency of refrigerant causes compressor discharge temperature to be higher than normal, discharge and suction pressures to be lower than
normal and compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. These issues disappear once sufficient
refrigerant has been charged into the system. For normal system parameters refer to Table 6-3.4 in Part 6, 3.2 “Normal Operating Parameters of
Refrigerant System”.
2. A low pressure side blockage causes compressor discharge temperature to be higher than normal, suction pressure to be lower than normal and
compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. For normal system parameters refer to Table 6-3.4 in
Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
3. In cooling mode check indoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check outdoor heat exchangers, fans and air outlets
for dirt/blockages.
96
2.19 P4, H6: Discharge temperature protection
Digital display output
Description
Discharge temperature protection.
All units stop running.
Error code is only displayed on the unit with the error.
Possible causes
Outdoor unit stop valves are closed. Insufficient refrigerant. System contains air or nitrogen.
Temperature sensor/switch not connected System blockage. Poor condenser heat exchange.
properly or has malfunctioned. Indoor load too large. Main PCB damaged.
Procedure
P4 / H6
ODU stop valves are closed Yes Open the stop valves
No
97
Insufficient refrigerant caused by Yes Add refrigerant and inspect the system
refrigerant leakage3 for leaks
No
The condenser heat exchange is poor7 Yes Inspect the system and fix the error
No
Notes:
1. Compressor top temperature sensor and discharge pipe temperature sensor connections are ports CN4 and CN5 on the main PCB (labeled 3 and 4,
respectively, in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Table 6-3.2 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”.
3. An insufficiency of refrigerant causes compressor discharge temperature to be higher than normal, discharge and suction pressures to be lower than
normal and compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. These issues disappear once sufficient
refrigerant has been charged into the system. For normal system parameters refer to Table 6-3.4 in Part 6, 3.2 “Normal Operating Parameters of
Refrigerant System”.
4. A low pressure side blockage causes compressor discharge temperature to be higher than normal, suction pressure to be lower than normal and
compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. For normal system parameters refer to Table 6-3.4 in
Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
5. An indoor load that is too large causes suction and discharge temperatures to be higher than normal. For normal system parameters refer to Table 6-3.4 in
Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
6. Air or nitrogen in the system causes discharge temperature to be higher than normal, discharge pressure to be higher than normal, compressor current to
be higher than normal, abnormal compressor noise and an unsteady pressure meter reading. For normal system parameters refer to Table 6-3.4 in Part 6,
3.2 “Normal Operating Parameters of Refrigerant System”.
7. In cooling mode check outdoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check indoor heat exchangers, fans and air outlets
for dirt/blockages.
98
2.20 P5: Outdoor heat exchanger temperature protection
Digital display output
Description
Outdoor heat exchanger temperature protection.
All units stop running.
Error code is only displayed on the unit with the error.
Possible causes
Outdoor unit stop valves are closed.
Temperature sensor not connected properly or has malfunctioned.
Indoor load too large.
System contains air or nitrogen.
Poor condenser heat exchange.
High pressure side blockage.
Main PCB damaged.
99
Procedure
P5
ODU stop valves are closed Yes Open the stop valves
No
Outdoor heat exchanger temperature Yes Ensure the sensor is connected properly
sensor connection on main PCB is loose1
No
The condenser heat exchange is poor5 Yes Inspect the system and fix the error
No
The high pressure side is blocked, caused Yes Inspect the system and fix the error
by crushed or bent pipe or blocked EXV6
No
Notes:
1. Outdoor heat exchanger temperature sensor connection is port CN1 on the main PCB (labeled 11 in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Table 6-3.1 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”
3. An indoor load that is too large causes suction and discharge temperatures to be higher than normal. For normal system parameters refer to Table 6-3.4 in
Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
4. Air or nitrogen in the system causes discharge temperature to be higher than normal, discharge pressure to be higher than normal, compressor current to
be higher than normal, abnormal compressor noise and an unsteady pressure meter reading. For normal system parameters refer to Table 6-3.4 in Part 6,
3.2 “Normal Operating Parameters of Refrigerant System”.
5. In cooling mode check outdoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check indoor heat exchangers, fans and air outlets
for dirt/blockages.
6. High pressure side blockage causes discharge temperature to be higher than normal, discharge pressure to be higher than normal and suction pressure to
be lower than normal. For normal system parameters refer to Table 6-3.4 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
100
2.21 xP9, xH9: Fan module protection
Digital display output
;
'x' is a placeholder for the fan motor system (fan motor and related electrical components), with 1 representing fan motor
system A and 2 representing fan motor system B.
Description
Fan module protection.
All units stop running.
Error code is only displayed on the unit with the error.
Possible causes
Switch ENC2 incorrectly set.
Power or communication wires not connected properly.
Fan motor blocked or has failed.
Power supply abnormal.
AC filter board damaged.
Fan module damaged.
Main PCB damaged.
Procedure
xP9 / xH9
The capacity set on switch ENC2 on the Ensure the setting on switch ENC2
main PCB and the capacity given on the matches the unit capacity given on the
unit’s nameplate do not match unit’s nameplate
No
101
… flowchart continued from previous page
The power supply is abnormal Yes Check the power supply equipment
No
Notes:
1. The normal voltage between P and N on the fan module is 540V DC.
102
2.22 PL, C7: Inverter module temperature protection
Digital display output
'x' is a placeholder for the compressor system (compressor and related electrical components), with 1 representing
compressor system A and 2 representing compressor system B.
Description
1PL indicates inverter module A temperature protection.
2PL indicates inverter module B temperature protection.
All units stop running.
Error code is only displayed on the unit with the error.
Possible causes
Blocked, dirty or loose heat sink.
Temperature sensor not connected properly or has malfunctioned.
Main PCB damaged.
103
Procedure
PL / C7
The inverter module heat sink is blocked Yes Clean or replace the heat sink
or dirty
No
The screws connecting the heat sink to Yes Tighten the screws and make sure the
the inverter module are loose heat sink is well-connected
No
Inverter module temperature sensor Yes Ensure the sensor is connected properly
connection on main PCB is loose1
No
Notes:
1. Inverter module temperature sensor connection is port CN3 and CN3_1 on the main PCB (labeled 5 and 6, respectively, in Figure 5-2.1 in Part 5, 2.1
“Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Table 6-3.3 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”.
104
2.23 PP: Compressor discharge insufficient superheat protection
Digital display output
Description
Compressor discharge insufficient superheat protection.
All units stop running.
Error code is only displayed on the unit with the error.
Possible causes
Temperature sensor not connected properly or has malfunctioned.
Poor temperature sensor heat insulation.
Excess refrigerant.
Discharge pressure too high.
Main PCB damaged.
105
Procedure
PP
No
Notes:
1. Compressor top temperature sensor and discharge pipe temperature sensor connections are ports CN4 and CN5 on the main PCB (labeled 3 and 4,
respectively, in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Table 6-3.2 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”.
3. Excess refrigerant causes discharge temperature to be lower than normal, discharge pressure to be higher than normal and suction pressure to be higher
than normal. For normal system parameters refer to Table 6-3.4 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
4. See “P1 Troubleshooting”.
106
3 Appendix to Part 6
3.1 Temperature Sensor Resistance Characteristics
Table 6-3.1: Outdoor ambient temperature sensor and outdoor heat exchanger temperature sensor resistance characteristics
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance
(°C) (kΩ) (°C) (kΩ) (°C) (kΩ) (°C) (kΩ)
-20 115.3 20 12.64 60 2.358 100 0.6297
-19 108.1 21 12.06 61 2.272 101 0.6115
-18 101.5 22 11.50 62 2.191 102 0.5939
-17 96.34 23 10.97 63 2.112 103 0.5768
-16 89.59 24 10.47 64 2.037 104 0.5604
-15 84.22 25 10.00 65 1.965 105 0.5445
-14 79.31 26 9.551 66 1.896 106 0.5291
-13 74.54 27 9.124 67 1.830 107 0.5143
-12 70.17 28 8.720 68 1.766 108 0.4999
-11 66.09 29 8.336 69 1.705 109 0.4860
-10 62.28 30 7.971 70 1.647 110 0.4726
-9 58.71 31 7.624 71 1.591 111 0.4596
-8 56.37 32 7.295 72 1.537 112 0.4470
-7 52.24 33 6.981 73 1.485 113 0.4348
-6 49.32 34 6.684 74 1.435 114 0.4230
-5 46.57 35 6.400 75 1.387 115 0.4116
-4 44.00 36 6.131 76 1.341 116 0.4006
-3 41.59 37 5.874 77 1.291 117 0.3899
-2 39.82 38 5.630 78 1.254 118 0.3796
-1 37.20 39 5.397 79 1.2133 119 0.3695
0 35.20 40 5.175 80 1.174 120 0.3598
1 33.33 41 4.964 81 1.136 121 0.3504
2 31.56 42 4.763 82 1.100 122 0.3413
3 29.91 43 4.571 83 1.064 123 0.3325
4 28.35 44 4.387 84 1.031 124 0.3239
5 26.88 45 4.213 85 0.9982 125 0.3156
6 25.50 46 4.046 86 0.9668 126 0.3075
7 24.19 47 3.887 87 0.9366 127 0.2997
8 22.57 48 3.735 88 0.9075 128 0.2922
9 21.81 49 3.590 89 0.8795 129 0.2848
10 20.72 50 3.451 90 0.8525 130 0.2777
11 19.69 51 3.318 91 0.8264 131 0.2708
12 18.72 52 3.192 92 0.8013 132 0.2641
13 17.80 53 3.071 93 0.7771 133 0.2576
14 16.93 54 2.959 94 0.7537 134 0.2513
15 16.12 55 2.844 95 0.7312 135 0.2451
16 15.34 56 2.738 96 0.7094 136 0.2392
17 14.62 57 2.637 97 0.6884 137 0.2334
18 13.92 58 2.540 98 0.6682 138 0.2278
19 13.26 59 2.447 99 0.6486 139 0.2223
107
Table 6-3.2: Compressor top temperature sensor and discharge pipe temperature sensor resistance characteristics
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance
(°C) (kΩ) (°C) (kΩ) (°C) (kΩ) (°C) (kΩ)
108
Table 6-3.3: Inverter module temperature sensor resistance characteristics
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance
(°C) (kΩ) (°C) (kΩ) (°C) (kΩ) (°C) (kΩ)
109
3.2 Normal Operating Parameters of Refrigerant System
Under the following conditions, the operating parameters given in Tables 6-3.4 should be observed:
The master outdoor unit can detect all the indoor units.
The number of indoor units displayed on DSP2 is steady and is equal to the actual number of indoor units installed.
All stop valves are open and all indoor unit EXVs are connected to their unit’s PCB.
If the combination ratio is 100% or less, all the indoor units are currently running and if the combination ratio is more
than 100%, indoor units with total capacity equal to the total capacity of the outdoor units are currently running.
The system is being run in cooling mode with the following settings: temperature 17°C; fan speed high.
The system has been running normally for more than 30 minutes.
110