100% found this document useful (1 vote)
499 views111 pages

380V TVR Pro Service Manual

Uploaded by

felipe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
499 views111 pages

380V TVR Pro Service Manual

Uploaded by

felipe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 111

R410A

Commercial Air Conditioners

Service Manual
TVR Pro CO Series

4TVY0077HE000AA 4TVY0192HE000AA

4TVY0096HE000AA 4TVY0210HE000AA

4TVY0115HE000AA 4TVY0229HE000AA

4TVY0140HE000AA 4TVY0249HE000AA

4TVY0155HE000AA 4TVY0268HE000AA

4TVY0170HE000AA 4TVY0290HE000AA
CONTENTS

Part 1 General Information ............................................................................ 3

Part 2 Component Layout and Refrigerant Circuits ................................... 12

Part 3 Control ............................................................................................... 24

Part 4 Field Settings ..................................................................................... 35

Part 5 Electrical Components and Wiring Diagrams .................................. 39

Part 6 Diagnosis and Troubleshooting......................................................... 54

1
2
Part 1
General Information
1 Indoor and Outdoor Unit Capacities ...................................................... 4

2 External Appearance.............................................................................. 6

3 Outdoor Unit Combinations................................................................... 8

4 Nomenclature...................................................................................... 10

3
1 Indoor and Outdoor Unit Capacities
1.1 Indoor Units
1.1.1 Standard indoor units
Table 1-1.1: Standard indoor unit abbreviation codes
Abbreviation Abbreviation
Type Type
code code
Q1 One-way Cassette T1 High Static Pressure Duct
Q2 Two-way Cassette G Wall-mounted
Q4C Compact Four-way Cassette DL Ceiling & Floor
Q4 Four-way Cassette F Floor Standing
T2 Medium Static Pressure Duct

Table 1-1.2: Standard indoor unit capacity range


Capacity Capacity
Q1 Q2 Q4C Q4 T2 T1 G DL F
kW HP index
1.8 0.6 18 18 — — — — — — — —
2.2 0.8 22 22 22 22 — 22 — 22 — 22
2.8 1 28 28 28 28 28 28 — 28 — 28
3.6 1.25 36 36 36 36 36 36 — 36 36 36
4.5 1.6 45 45 45 45 45 45 — 45 45 45
5.6 2 56 56 56 — 56 56 — 56 56 56
7.1 2.5 71 71 71 — 71 71 71 71 71 71
8.0 3 80 — — — 80 80 80 80 80 80
9.0 3.2 90 — — — 90 90 90 90 90 —
10.0 3.6 100 — — — 100 — — — — —
11.2 4 112 — — — 112 112 112 — 112 —
14.0 5 140 — — — 140 140 140 — 140 —
16.0 6 160 — — — — — 160 — 160 —
20.0 7 200 — — — — — 200 — — —
25.0 9 250 — — — — — 250 — — —
28.0 10 280 — — — — — 280 — — —
40.0 14 400 — — — — — 400 — — —
45.0 16 450 — — — — — 450 — — —
56.0 20 560 — — — — — 560 — — —

1.1.2 Fresh air processing unit


Table 1-1.3: Fresh air processing unit capacity range
Capacity 12.5kW 14kW 20kW 25kW 28kW 45kw 56kw
Capacity index 125 140 200 250 280 450 560

1.2 Heat recovery ventilator


Table 1-1.4: Heat recovery ventilator capacity range
Capacity 200m3/h 300m3/h 400m3/h 500m3/h 800m3/h 1000m3/h 1500m3/h 2000m3/h

4
1.3 Outdoor Units
Table 1-1.5: Outdoor unit capacity range
Capacity Model Name Combination Type
8HP 4TVY0077HE000AA /
10HP 4TVY0096HE000AA /
12HP 4TVY0115HE000AA /
14HP 4TVY0140HE000AA /
16HP 4TVY0155HE000AA /
18HP 4TVY0170HE000AA /
20HP 4TVY0192HE000AA /
22HP 4TVY0210HE000AA /
24HP 4TVY0229HE000AA /
26HP 4TVY0249HE000AA /
28HP 4TVY0268HE000AA /
30HP 4TVY0290HE000AA /
32HP 4TVY0310HE000AA 16HP+16HP
34HP 4TVY0325HE000AA 22HP+12HP
36HP 4TVY0347HE000AA 20HP+16HP
38HP 4TVY0365HE000AA 22HP+16HP
40HP 4TVY0384HE000AA 24HP+16HP
42HP 4TVY0404HE000AA 26HP+16HP
44HP 4TVY0423HE000AA 28HP+16HP
46HP 4TVY0445HE000AA 30HP+16HP
48HP 4TVY0459HE000AA 26HP+22HP
50HP 4TVY0478HE000AA 28HP+22HP
52HP 4TVY0500HE000AA 30HP+22HP
54HP 4TVY0517HE000AA 28HP+26HP
56HP 4TVY0536HE000AA 28HP+28HP
58HP 4TVY0558HE000AA 30HP+28HP
60HP 4TVY0580HE000AA 30HP+30HP
62HP 4TVY0600HE000AA 30HP+16HP+16HP
64HP 4TVY0614HE000AA 26HP+22HP+16HP
66HP 4TVY0633HE000AA 28HP+22HP+16HP
68HP 4TVY0655HE000AA 30HP+22HP+16HP
70HP 4TVY0672HE000AA 28HP+26HP+16HP
72HP 4TVY0691HE000AA 28HP+28HP+16HP
74HP 4TVY0713HE000AA 30HP+28HP+16HP
76HP 4TVY0735HE000AA 30HP+30HP+16HP
78HP 4TVY0746HE000AA 28HP+28HP+22HP
80HP 4TVY0768HE000AA 30HP+28HP+22HP
82HP 4TVY0790HE000AA 30HP+30HP+22HP
84HP 4TVY0804HE000AA 28HP+28HP+28HP
86HP 4TVY0826HE000AA 30HP+28HP+28HP
88HP 4TVY0848HE000AA 30HP+30HP+28HP
90HP 4TVY0870HE000AA 30HP+30HP+30HP
Notes:
1. The combinations of units shown in the table are factory-recommended. Other combinations of units are also possible.

5
2 External Appearance
2.1 Indoor Units
2.1.1 Standard indoor unit
Table 1-2.1: Standard indoor unit appearance

One-way Cassette Two-way Cassette

Q1 Q2

Compact Four-way Cassette Four-way Cassette

Q4C Q4

Medium Static Pressure Duct High Static Pressure Duct

T2 T1

Wall-mounted Ceiling & Floor

G DL

Floor Standing

2.1.2 Fresh air processing unit


Table 1-2.2: Fresh air processing unit appearance
Fresh Air Processing Unit
FA

2.2 Heat Recovery Ventilator


Table 1-2.3: Heat recovery ventilator appearance
Heat Recovery Ventilator

6
2.3 Outdoor Units
2.3.1 Single units
Table 1-2.4: Single outdoor unit appearance
8/10/12/14/16HP 18/20/22HP 24/26/28/30
(with single fan) (with dual fans) (with dual fans)

2.3.2 Combinations of units


Table 1-2.5: Combination outdoor unit appearance
32HP 34/36/38/HP

40/42/44/46HP 48/50/52HP

54/56/58/60HP 62HP

64/66/68HP 70/72/74/76HP

7
Table continued on next page…
Table 1-2.5: Combination outdoor unit appearance
78/80/82HP 84/86/88/90HP

3 Outdoor Unit Combinations


Table 1-3.1: Outdoor unit combinations
System capacity Number Modules1 Outdoor branch
kW HP of units 8 10 12 14 16 18 20 22 24 26 28 30 joint kit2
22.4 8 1 ●
28.0 10 1 ●
33.5 12 1 ●
40.0 14 1 ●
45.0 16 1 ●
50.0 18 1 ●

56.0 20 1 ●
61.5 22 1 ●
67.0 24 1 ●
73.0 26 1 ●
78.5 28 1 ●
85.0 30 1 ●
90.0 32 2 ●●
95.0 34 2 ● ●
101.0 36 2 ● ●
106.5 38 2 ● ●
112.0 40 2 ● ●
118.0 42 2 ● ●
123.5 44 2 ● ●
130.0 46 2 ● ● TODK02UTHP
134.5 48 2 ● ●
140.0 50 2 ● ●
146.5 52 2 ● ●
151.5 54 2 ● ●
157.0 56 2 ●●
163.5 58 2 ● ●
170.0 60 2 ●●
175.0 62 3 ●● ●
179.5 64 3 ● ● ●
185.0 66 3 ● ● ●
191.5 68 3 ● ● ●
196.5 70 3 ● ● ●
202.0 72 3 ● ●●
208.5 74 3 ● ● ● TODK03UTHP
215.0 76 3 ● ●●
218.5 78 3 ● ●●
225.0 80 3 ● ● ●
231.5 82 3 ● ●●
235.5 84 3 ●●●

8
Table continued on next page…
Table 1-3.1: Outdoor unit combinations
Number Outdoor branch
System capacity Modules1
of units joint kit2
242.0 86 3 ●● ●
248.5 88 3 ● ●● TODK03UTHP
255.0 90 3 ●●●
Notes:
1. The combinations of units shown in the table are factory-recommended. Other combinations of units are also possible.
2. For systems with two or more outdoor units, outdoor branch joints (sold separately) are required.

9
4 Nomenclature
4.1 Indoor Units
4.1.1 Standard indoor units
4 T V E 0 0 0 7 E F 0 0 0 A A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Legend
No. Code Remarks
1 4 R-410A
2 T Trane
3 V TVR
Indoor Unit Type
E: One - Way Cassette
G: Two - Way Cassette
B: Compact Four - Way Cassette
C: Four - Way Cassette
4 D: Medium Static Pressure Duct
A: High Static Pressure Duct
W: Wall - Mounted
C: Ceiling & Floor
S, N, U: Floor Standing
F: Fresh air processing unit
5 0 Currently not used
6 0
7 0 Btu/h x 1000
8 7
9 E TVR Ultra
10 F 380V50-60Hz/1P
11 0 Currently not used
12 0 Currently not used
13 0 Currently not used
14 A First design sequence
15 A First service sequence

10
4.2 Heat recovery ventilator
AC Series
T E R V 0 1 2 0 A B 0 A A
1 2 3 4 5 6 7 8 9 10 11 12 13
Legend
No. Code Remarks
1 T
2 E Energy recovery Fan
3 R Trane TVR
4 V
5 0
6 1
CFM
7 2
8 0
9 A TVR
1: 380V/60Hz/1Ph
10 B
B: 380/50Hz/1Ph
11 0 Currently not used
12 A First design sequence
13 A First service sequence

4.3 Outdoor Units


4 T V Y 0 0 7 7 H E 0 0 0 A A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Legend
No. Code Remarks
1 4 R-410A
2 T Trane
3 V Air Cooled
4 Y Cooling Only
5 0 Currently not used
6 0
7 7 Btu/h x 1000
8 7
9 H TVR Pro CO
10 E 380V50-60Hz/1P
11 0 Currently not used
12 0 Currently not used
0: Standard
13 0
C: Corrosion treatment
14 A First design sequence
15 A First design sequence

11
Part 2
Component Layout and
Refrigerant Circuits
1 Layout of Functional Components ....................................................... 13

2 Piping Diagrams .................................................................................. 16

3 Refrigerant Flow Diagrams .................................................................. 20

12
1 Layout of Functional Components
8-16HP
Figure 2-1.1: 8-16HP layout of functional components
4 11
Legend
No. Parts name
1 Compressor
2 Discharge temperature sensor
3 High pressure sensor
13 4 Oil separator
13
5 Heat exchanger
5
6 6 Electronic expansion valve (EXV)
2
7 Fan motor
8 Fan
9 Stop valve (liquid side)
10 Stop valve (gas side)
11 Accumulator
12 Low pressure switch
8
13 Solenoid valve
7

13

12
3

9 10

13
18-22HP
Figure 2-1.2: 18-22HP layout of functional components

4 11
Legend
No. Parts name
1 Compressor
2 Discharge temperature sensor
3 High pressure sensor

13 4 Oil separator
5 Heat exchanger
13
5 6 Electronic expansion valve (EXV)
6
7 Fan motor
8 Fan
9 Stop valve (liquid side)
10 Stop valve (gas side)
2 2 11 Accumulator
12 Low pressure switch
13 Solenoid valve
8 8
7
7

13

12
3

1
1

9 10

14
24-30HP
Figure 2-1.3: 24-30HP layout of functional components

4 11 11
Legend
No. Parts name
1 Compressor
Discharge temperature
2
3 sensor

13 3 High pressure sensor


13 4 Oil separator

6 5 Heat exchanger
5
Electronic expansion
6
valve (EXV)
7 Fan motor
8 Fan
2 2
9 Stop valve (liquid side)
10 Stop valve (gas side)

8 8 11 Accumulator

7 12 Low pressure switch


7
13 Solenoid valve

13
12

9 10

15
2 Piping Diagrams
8-16HP
Figure 2-2.1: 8-16HP piping diagram

8
7 EXVA 9

5 XX°C 6
T3
XX°C
T4 10

4
3 SV2
13

2
SV7
1 12 11
SV4

13
13

Legend
No. Parts name No. Parts name
1 Compressor 10 Stop valve (gas side)
2 Discharge temperature sensor 11 Accumulator
3 High pressure sensor 12 Low pressure switch
4 Oil separator 13 Solenoid valve
5 Heat exchanger T3 Heat exchanger temperature sensor
6 Electronic expansion valve (EXV) T4 Outdoor ambient temperature sensor
7 Fan motor SV2 Liquid injection valve
8 Fan SV4 Oil return valve
9 Stop valve (liquid side) SV7 Pressure valve

16
18-22HP
Figure 2-2.2: 18-22HP piping diagram

8 8
7 7 EXVA 9
5 XX°C 6
T3
XX°C
T4
10

3 4

SV7
13

2 2
1 1 12 11

13 SV4
16
SV2
13

Legend
No. Parts name No. Parts name
1 Compressor 10 Stop valve (gas side)
2 Discharge temperature sensor 11 Accumulator
3 High pressure sensor 12 Low pressure switch
4 Oil separator 13 Solenoid valve
5 Heat exchanger T3 Heat exchanger temperature sensor
6 Electronic expansion valve (EXV) T4 Outdoor ambient temperature sensor
7 Fan motor SV2 Liquid injection valve
8 Fan SV4 Oil return valve
9 Stop valve (liquid side) SV7 Pressure valve

17
24-30HP
Figure 2-2.3: 24-30HP piping diagram
8 8
7 7 EXVA 9
5 XX°C 6
T3
XX°C
T4
10

3 4

SV2
13

SV7
13

2 2
1 1 12 11 11

SV4
13

Legend
No. Parts name No. Parts name
1 Compressor 10 Stop valve (gas side)
2 Discharge temperature sensor 11 Accumulator
3 High pressure sensor 12 Low pressure switch
4 Oil separator 13 Solenoid valve
5 Heat exchanger T3 Heat exchanger temperature sensor
6 Electronic expansion valve (EXV) T4 Outdoor ambient temperature sensor
7 Fan motor SV2 Liquid injection valve
8 Fan SV4 Oil return valve
9 Stop valve (liquid side) SV7 Pressure valve

18
Key components:
1. Oil separator:
Separates oil from gas refrigerant pumped out of the compressor and quickly returns it to the compressor. Separation
efficiency is up to 99%.
2. Accumulator:
Stores liquid refrigerant and oil to protect compressor from liquid hammering.
3. Electronic expansion valve (EXV):
Controls refrigerant flow and reduces refrigerant pressure.
4. Solenoid valve SV2:
Protects the compressor. If compressor discharge temperature rises above 100oC, SV2 opens and sprays a small
amount of liquid refrigerant to cool the compressor. SV2 closes again once the discharge temperature has fallen
below 90oC.
5. Solenoid valve SV4:
Returns oil to the compressor. Opens once the compressor has run for 200 seconds and closes 600 seconds later and
then opens for 3 minutes every 20 minutes.
6. Solenoid valve SV7:
Allows refrigerant to return directly to the compressor. Opens when indoor air temperature is close to the set
temperature to avoid frequent compressor on/off. Opens when superheat degree is insufficient to avoid liquid
hammer to compressor.
7. Low pressure switches:
Regulate system pressure. When system pressure falls below the lower limit, the low pressure switches turn off,
stopping the compressor. After 10 minutes, the compressor restarts.

19
3 Refrigerant Flow Diagrams
8-16HP
Cooling operation
Figure 2-3.1: 8-16HP refrigerant flow during cooling operation

Unit on
High temperature, high pressure gas Fan Thermostat on
on
High temperature, high pressure liquid Filter Filter
Low temperature, low pressure
Normal control
8
7 EXVA 9

XX°C Fan Unit on


5 6 on
T3 Thermostat on
XX°C Filter Filter
T4

Indoor unit operation


10
Normal control

4
3 SV2
13
Fan Unit off
off
Filter Filter
Closed
2
SV7

1 12 11
SV4

13
13 Unit on
Fan Thermostat off
on
Filter Filter
Closed

Oil return operation in cooling mode


Figure 2-3.2: 8-16HP refrigerant flow during oil return operation in cooling mode

20
18-22HP
Cooling operation
Figure 2-3.3: 18-22HP refrigerant flow during cooling operation

Unit on
High temperature, high pressure gas Fan Thermostat on
on
High temperature, high pressure liquid
Filter Filter
Low temperature, low pressure
Normal control
8 8
7 7 EXVA 9

5 XX°C 6 Fan Unit on


T3 on Thermostat on
XX°C
T4 Filter Filter

Indoor unit operation


10
Normal control

3 4

Fan Unit off


SV7

off
13 Filter Filter
Closed
2 2
1 1 12 11
Unit on
SV4

Fan Thermostat off


13 on
SV2 Filter Filter
13
Closed

Oil return operation in cooling mode


Figure 2-3.4: 18-22HP refrigerant flow during oil return operation in cooling mode

21
24-30HP
Cooling operation
Figure 2-3.5: 24-30HP refrigerant flow during cooling operation

Unit on
High temperature, high pressure gas Fan Thermostat on
on
High temperature, high pressure liquid
Filter Filter
Low temperature, low pressure
Normal control
8 8
7 7 EXVA 9

5 XX°C 6 Fan Unit on


T3 on Thermostat on
XX°C
T4 Filter Filter

Indoor unit operation


10
Normal control

3 4

SV2
13 Unit off
SV7

Fan
off
13
Filter Filter
Closed
2 2
1 1 12 11 11
SV4

Unit on
13 Fan Thermostat off
on
Filter Filter
Closed

Oil return operation in cooling mode


Figure 2-3.6: 24-30HP refrigerant flow during oil return operation in cooling mode

22
23
Part 3
Control
1 General Control Scheme Flowchart .......................................................... 25

2 Stop Operation ......................................................................................... 26

3 Startup Control ........................................................................................ 26

4 Normal Operation Control ........................................................................ 27

5 Protection Control .................................................................................... 30

6 Special Control ......................................................................................... 32

24
1 General Control Scheme Flowchart
Sections 3-2 to 3-6 on the following pages detail when each of the controls in the flowchart below is activated.
2
Stop operation
 Abnormal shutdown
 System stops 6
Special control
 A unit stops when the load demanded decreases

Thermo on

3
Startup control
Thermo on
 Compressor startup delay control  Outdoor unit duty cycling
 Startup control for cooling operation

4
Normal operation control
 Component control during normal operation
Conditions met
 Compressor output control
for oil return
 Compressor step control  Oil return operation
 Operation priority and rotation of compressors
 Electronic expansion valve control
 Outdoor fan control

5
Protection control
 High pressure protection control
 Low pressure protection control Legend
 Discharge temperature protection control Numbers in the top right-hand
corners of boxes indicate the
 Compressor and inverter module protection relevant section of text on the
following pages.
control

25
2 Stop Operation
The stop operation occurs for one of the three following reasons:
1. Abnormal shutdown: in order to protect the compressors, if an abnormal state occurs the system makes a 'stop with
thermo off' operation and an error code is displayed on the outdoor unit digital displays.
2. The system stops when the set temperature has been reached.
3. A unit stops when the load demanded by the indoor units decreases and can be handled by fewer outdoor units.

3 Startup Control
3.1 Compressor Startup Delay Control
In initial startup control, compressor startup is delayed for 12 minutes in order to let the master unit search for the indoor
units’ addresses. In restart control (except in oil return operation), compressor startup is delayed such that a minimum of 7
minutes has elapsed since the compressor stopped, in order to prevent frequent compressor on/off and to equalize the
pressure within the refrigerant system.

3.2 Startup Control for Cooling Operation


Table 3-3.1: Component control during startup in cooling mode
Wiring diagram
Component 8-12HP 14-16HP 18-22HP 24-30HP Control functions and states
label
Inverter compressor A BP1 ● ● ● ● Controlled according to load requirement,
Inverter compressor B BP2 ● ● operating frequency increased by 1 step / sec
DC fan motor A FAN1 ● ● ● ● Fan speed controlled according to discharge
pressure (Pc):
 At initial speed for 90 seconds.
DC fan motor B FAN2 ● ●  Subsequently, Pc checked every 10 seconds:
 Pc ≥ 2.7MPa => 1 step increase.
 Pc ≤ 2.1MPa => 1 step decrease.
Position (steps) from 0 (fully closed) to 3000 (fully
Electronic expansion
EXVA ● ● ● ● open), controlled according to discharge
valve A
temperature
Solenoid valve (Liquid
SV2 ● ● ● ● Controlled according to discharge temperature
injection)
Solenoid valve (oil Closed for 200 secs, open for 600 secs, then
SV4 ● ● ● ●
balance) closed
Solenoid valve Controlled according to load requirement and
SV7 ● ● ● ●
(refrigerant bypass) discharge pressure

26
4 Normal Operation Control
4.1 Component Control during Normal Operation
Table 3-4.1: Component control during normal cooling operation
Wiring diagram
Component 8-12HP 14-16HP 18-22HP 24-30HP Control functions and states
label
Inverter compressor A BP1 ● ● ● ●
Controlled according to load requirement
Inverter compressor B BP2 ● ●

DC fan motor A FAN1 ● ● ● ●


Controlled according to discharge pressure
DC fan motor B FAN2 ● ●

Position (steps) from 0 (fully closed) to 3000 (fully


Electronic expansion
EXVA ● ● ● ● open), controlled according to discharge
valve A
temperature
Solenoid valve (Liquid
SV2 ● ● ● ● Controlled according to discharge temperature
injection)
Solenoid valve (oil
SV4 ● ● ● ● Open regularly
balance)
Controlled according to ambient temperature,
Solenoid valve discharge pressure,compressor running frequency,
SV7 ● ● ● ●
(refrigerant bypass) discharge superheating degree, load requirement,
discharge temperature and discharge pressure.

4.2 Compressor Output Control


The compressor rotation speed is controlled according to the load requirement. Before compressor startup, the outdoor
units first estimate the indoor unit load requirement according to the nominal capacity of indoor units currently running,
and then correct for ambient temperature. The compressors then start up according to the corrected load requirement.

During operation the compressors are controlled according to the nominal capacity of indoor units currently running and
the indoor unit heat exchanger temperatures. If the actual load requirement can be provided by one unit alone, then only
one unit starts up. If the actual load requirement requires all outdoor unit modules to operate, the weighted average
actual load requirement is sent to each module and each module operates according to this distributed load
requirement.

4.3 Compressor Step Control


The compressor speed can be altered in increments of 1 rps (rotations per second) and decrease of 2rps.

4.4 Operating Priority and Rotation of Compressors


Figures 3-4.1 to 3-4.3 show the compressor operating priority and rotation in systems with one, two and three outdoor
units. In units with two compressors, inverter compressor A (BP1) operates in priority to inverter compressor B (BP2). In
multi-unit systems, units operate in rotation. In Figures 3-4.2 and 3-4.3 the master unit and slave units 1 and 2 are shown
from left to right in that order, and the circled numbers (①, ②, ③) indicate the rotation sequence.

27
Figure 3-4.1: Compressor priority and rotation – one outdoor unit

No. 1 No. 1 No. 2

BP BP1 BP2

Figure 3-4.2: Compressor priority and rotation – two outdoor units

① No. 1 No. 2 ① No. 1 No. 2 No. 3 ① No. 1 No. 2 No. 3 No. 4


② ② ②
No. 2 No. 1 No. 2 No. 3 No. 1 No. 3 No. 4 No. 1 No. 2

BP BP BP1 BP2 BP BP1 BP2 BP1 BP2

Figure 3-4.3: Compressor priority and rotation – three outdoor units

① No. 1 No. 2 No. 3 ① No. 1 No. 2 No. 3 No. 4

② No. 3 No. 1 No. 2 ② No. 3 No. 4 No. 1 No. 2

③ No. 2 No. 3 No. 1 ③ No. 2 No. 3 No. 4 No. 1

BP BP BP BP1 BP2 BP BP

① No. 1 No. 2 No. 3 No. 4 No. 5 ① No. 1 No. 2 No. 3 No. 4 No. 5 No. 6

② No. 4 No. 5 No. 1 No. 2 No. 3 ② No. 5 No. 6 No. 1 No. 2 No. 3 No. 4

③ No. 2 No. 3 No. 4 No. 5 No. 1 ③ No. 3 No. 4 No. 5 No. 6 No. 1 No. 2

BP1 BP2 BP1 BP2 BP BP1 BP2 BP1 BP2 BP1 BP2

4.5 Electronic Expansion Valve Control


EXVA control
The position of electronic expansion valve EXVA is controlled in steps from 0 (fully closed) to 3000 (fully open).

In cooling mode:
 When all outdoor units are in standby:
 All EXVAs are at position 352×6(steps).
 When some outdoor units are running and some outdoor units are in standby:
 EXVAs on running outdoor units are controlled according to discharge temperature. EXVAs of units in standby are
28
fully closed.
 When all outdoor units are running:
 All EXVAs are controlled according to discharge temperature.

4.6 Outdoor Fan Control


The speed of the outdoor unit fans is adjusted in steps, as shown in Table 3-4.2.
Table 3-4.2: Outdoor fan speed steps
Fan speed (rpm)
Fan speed index 18-22HP 24-30HP
8-16HP
FANA / FANB FANA / FANB
0 0 0/0 0/0
1 120 150 / 0 120 / 0
2 150 190 / 0 150 / 0
3 170 230 / 0 170 / 0
4 190 270 / 0 190 / 0
5 210 310 / 0 (150 / 150) 210 / 0
6 230 350 / 0 (180 / 180) 230 / 0
7 250 380 / 0 (210 / 210) 250 / 0 (120 / 120)
8 270 410 / 0 (240 / 240) 270 / 0 ( 150 / 150)
9 290 280 / 280 330 / 0 (170 / 170)
10 310 320 / 320 370 / 0 (190 / 190)
11 330 360 / 360 210 / 210
12 350 400 / 400 230 / 230
13 370 440 / 440 250 / 250
14 390 480 / 480 270 / 270
15 410 520 / 520 290 / 290
16 430 560 / 560 310 / 310
17 450 600 / 600 330 / 330
18 470 640 / 640 350 / 350
19 490 680 / 680 370 / 370
20 510 720 / 720 400 / 400
21 530 750 / 750 430 / 430
22 560 780 / 780 470 / 470
23 580 800 / 800 510 / 510
24 600 840 / 840 550 / 550
25 630 880 / 880 600 / 600
26 650 910 / 880 650 / 650
27 700 910 / 910 680 / 680
28 750 940 / 910 700 / 700
29 800 940 / 940 750 / 750
30 850 980 / 940 780 / 780
31 880 980 / 980 800 / 800
32 910 1000 / 980 830 / 830
33 930 1000 / 1000 850 / 850
34 960 1020 / 1000 870 / 870
35 1000 1020 / 1020 890 / 890
36 1050 1050 / 1050 920 / 920
37 1100 1100 / 1100 950 / 950
Note:
1. For 18-22HP unit fan speed 5 to 8 and 24-30HP unit fan speed 7 to 10, when fan speed decreases, the fan speed is shown in the bracket; when fan speed
increases, the fan speed is shown without bracket.

29
5 Protection Control
5.1 High Pressure Protection Control
This control protects the system from abnormally high pressure and protects the compressors from transient spikes in
pressure.
Figure 3-5.1: High pressure protection control

Normal operation

Pc > 4.4MPa Pc < 3.2MPa

High pressure protection, error code P1 is displayed

Notes:
1. Pc: Discharge pressure

5.2 Low Pressure Protection Control


This control protects the system from abnormally low pressure and protects the compressors from transient drops in
pressure.
Figure 3-5.2: Low pressure protection control

Normal operation

Pe < 0.05MPa Pe > 0.15MPa When P2 protection occurs 3 times


in 60 minutes, the H5 error is
displayed. When an H5 error occurs,
Low pressure protection, error code P2 is displayed a manual system restart is required
Notes:
before the system can resume
1. Pe: Suction pressure operation.

5.3 Discharge Temperature Protection Control


This control protects the compressors from abnormally high temperatures and transient spikes in temperature. It is
performed for each compressor.
Figure 3-5.3: Discharge temperature protection control

Discharge temperature
Compressor off
120oC

100oC
90oC 90oC

When the discharge temperature rises above 120°C the system displays P4 protection and all units stop running. When P4
protection occurs 3 times in 100 minutes, the H6 error is displayed. When an H6 error occurs, a manual system restart is
required before the system can resume operation.

5.4 Compressor and Inverter Module Protection Control


This control protects the compressors from abnormally high currents and protects the inverter modules from abnormally
30
high temperatures. It is performed for each compressor and inverter module.
Figure 3-5.4: Compressor current protection control

Normal operation

Current ≥ Currentmax Current < Currentmax

Compressor current protection, error code xH4(xL0) is displayed

Compressor model LNB53 LNB65


Currentmax 48.5 59

Figure 3-5.5: Inverter module temperature protection control

Normal operation

Tf > 74oC Tf < 71oC

Compressor output reduced Tf < 65oC

Tf > 79oC When PL protection occurs 3 times


in 100 minutes, the C7 error is
displayed. When a C7 error occurs, a
Inverter module temperature protection,
manual system restart is required
error code PL is displayed
before the system can resume
Notes: operation.
1. Tf: Heat sink temperature

31
6 Special Control
6.1 Outdoor Unit Duty Cycling
In systems with multiple outdoor units, outdoor unit duty cycling is used to prevent compressor burn out due to
unbalanced oil levels between outdoor units.

Timing of outdoor unit duty cycling:


 After oil return operation.
 On restart following compressor stop after set temperatures achieved.

Figure 3-6.1 shows an example of duty cycling in a system with 3 outdoor units.
Figure 3-6.1: Duty cycling in a system with 3 outdoor units1

After oil return operation or


after defrosting operation or
on restart following compressor
Startup control stop after set temperatures
Normal operation achieved Normal operation

Master Slave 1 Slave 2 Master Slave 1 Slave 2

Outdoor unit Priority Priority Priority Outdoor unit Priority Priority Priority
duty cycling 1 2 3 duty cycling 3 1 2

Notes:
1. The address settings on the outdoor unit main PCBs for “master unit”, “slave unit 1”, and “slave unit 2” do not change.

32
6.2 Oil Return Operation
In order to prevent compressors from running out of oil, the oil return operation is conducted to recover oil that has
flowed out of the compressor(s) and into the piping system. This operation is performed for all units including units that
are in standby. When the outdoor unit is running in oil return, the digital display on outdoor main PCB will display “d0”.
Timing of oil return operation:
 When the initial cumulative operating time reaches 140 minutes and then every 8 hours.
Tables 3-6.1 and 3-6.2 show component control during oil return operation in cooling mode.
Table 3-6.1: Outdoor unit component control during oil return operation in cooling mode
Component Wiring diagram label 8-12HP 14-16HP 18-22HP 24-30HP Control functions and states
Inverter compressor A BP1 ● ● ● ●
Fixed frequency
Inverter compressor B BP2 ● ●

DC fan motor A FAN1 ● ● ● ● Controlled according to


DC fan motor B FAN2 ● ● discharge pressure
Electronic expansion valve A EXVA ● ● ● ● Position 480 (steps)
Solenoid valve (Liquid injection) SV2 ● ● ● ● Normal control
Solenoid valve (oil balance) SV4 ● ● ● ● Normal control
Solenoid valve (refrigerant bypass) SV7 ● ● ● ● Normal control

Table 3-6.2: Indoor unit component control during oil return operation in cooling mode
Component Unit state Control functions and states
Thermo on Remote controller setting
Fan Standby Off
Thermo off Off
Thermo on Normal control
Electronic expansion valve Standby 300 (steps)
Thermo off 300 (steps)

33
Part 4
Field Settings
1 Outdoor Unit Field Settings ................................................................. 35

34
1 Outdoor Unit Field Settings
1.1 PCB Switches and Switch Settings
Figure 4-1.1: Outdoor unit main PCB switches

Table 4-1.1: Outdoor unit main PCB switch settings


Switch Setting Switch positions1 Description
S5 Reserved

Reserved Reserved
S6-1
No action (default)
Clear indoor
S6-2 unit addresses
Clear indoor unit addresses

Addressing Auto addressing (default)

S6-3 mode Manual addressing

Reserved Reserved
S8-1
Start-up time is 12 minutes (default)
Start-up time
S8-2
Start-up time is 7 minutes

Reserved Reserved
S8-3
S7 Reserved

Use the new centralized controller (default)


Controller type
S13
Use the old centralized controller

Outdoor unit Only 0, 1, 2 should be selected (default is 0)


ENC1 address 0 is for master unit; 1 and 2 are for slave units
Only 0, 1, 2, 3, 4, 5, 6, 7, 8, 9, A, B should be selected
Outdoor unit
0: 8HP; 1: 10HP; 2: 12HP; 3: 14HP; 4: 16HP; 5: 18HP; 6: 20HP; 7: 22HP; 8: 24HP;
ENC2 capacity2
9: 26HP; A: 28HP; B:30HP
Network
Only 0, 1, 2, 3, 4, 5, 6, 7 should be selected (default is 0)
ENC4 address
Table continued on next page …
35
Table 4-1.1: Outdoor unit main PCB switch settings (continued)
Switch Setting Switch positions1 Description
The number of indoor units is in the range 0-15
0-9 on ENC3 indicate 0-9 indoor units; A-F on ENC3 indicate 10-15 indoor units
The number of indoor units is in the range 16-31
0-9 on ENC3 indicate 16-25 indoor units; A-F on ENC3 indicate 26-31 indoor units
ENC3 S12
Number of The number of indoor units is in the range 32-47
indoor units 0-9 on ENC3 indicate 32-41 indoor units; A-F on ENC3 indicate 42-47 indoor units
The number of indoor units is in the range 48-63
0-9 on ENC3 indicate 48-57 indoor units; A-F on ENC3 indicate 58-63 indoor units
The number of indoor units is 64
0 on ENC3 indicate 64 indoor units
0 Night silent time is 6h/10h (default)
1 Night silent time is 6h/12h
2 Night silent time is 8h/10h
3 Night silent time is 8h/12h
4 No silent mode
5 Silent mode 1 (only limit max. fan speed)
Silent mode3 6 Silent mode 2 (only limit max. fan speed)
ENC5 7 Silent mode 3 (only limit max. fan speed)
8 Super silent mode 1 (limit max. fan speed and compressor frequency)
9 Super silent mode 2 (limit max. fan speed and compressor frequency)
A Super silent mode 3 (limit max. fan speed and compressor frequency)
B Super silent mode 4 (limit max. fan speed and compressor frequency)
F Set silent mode via centralized controller
Notes:
1. Black denotes the switch position.
2. Switch ENC2 is factory-set and its setting should not be changed.
3. Refer to Part 4, 1.2.1 “Silent mode setting”.

36
1.2 Modes Set on Main PCB
1.2.1 Silent time setting
1.2.1.1 Night silent time setting
Night silent mode is activated X hours after the peak daytime temperature, and is deactivated after Y hours, where X and Y
are as specified in Table 4-1.2.
Table 4-1.2: Night silent time setting
Switch Switch positions Description X Y
0 Night silent time is 6h/10h (default) 6 10
ENC5
1 Night silent time is 6h/12h 6 12
2 Night silent time is 8h/10h 8 10
3 Night silent time is 8h/12h 8 12

Figure 4-1.4: Night silent mode example (default setting, 6h/10h)

The outdoor unit senses the peak daytime


outdoor ambient temperature

Maximum
output

Load
6 10
Operation
sound dB Max. 15dB
reduction
8:00 14:00 20:00 6:00
Night silent Night silent mode
mode activated deactivated

37
1.2.1.2 Silent mode setting
In silent mode 1 / 2 / 3 and night silent mode, the outdoor fan speed decreases gradually. In super silent mode 1 / 2 / 3 / 4,
not only the fan speed decreases gradually, but also the compressor frequency decreases gradually.
Table 4-1.3: Silent mode setting
Switch Switch positions Description
5 Silent mode 1 (only limit max. fan speed)
6 Silent mode 2 (only limit max. fan speed)
7 Silent mode 3 (only limit max. fan speed)
8 Super silent mode 1 (limit max. fan speed and compressor frequency)
ENC5
9 Super silent mode 2 (limit max. fan speed and compressor frequency)
A Super silent mode 3 (limit max. fan speed and compressor frequency)
B Super silent mode 4 (limit max. fan speed and compressor frequency)

1.2.1.3 Maximum fan speed and capacity output control in different silent mode
Table 4-1.4: Maximum fan speed and capacity output control in different silent mode
Max.
ENC5 Max. fan speed index1 capacity
Switch Description output
positions
8-10HP 12HP 14-16HP 18HP 20-22HP 24-26HP 28-30HP 8-30HP
0 Night silent time is 6h/10h (default)
1 Night silent time is 6h/12h
28 28 30 29 29 31 31
2 Night silent time is 8h/10h
3 Night silent time is 8h/12h
100%
4 No silent mode 29 30 33 33 35 33 35
5 Silent mode 1 28 28 30 31 31 31 31
6 Silent mode 2 26 26 28 29 29 29 29
7 Silent mode 3 24 24 27 27 27 27 27
8 Super silent mode 1 28 28 29 23 23 28 28 80%
9 Super silent mode 2 27 27 28 22 22 27 27 70%
A Super silent mode 3 26 26 27 21 21 26 26 60%
B Super silent mode 4 25 25 26 20 20 25 25 50%
Notes:
1. Fan speed (rpm) for different fan speed index refers to Table 3-4.2 in Part 3, 4.6 “Outdoor Fan Control”.
2. If the system pressure is over 3.5MPa, the system exits silent mode automatically.

38
Part 5
Electrical Components and
Wiring Diagrams
1 Outdoor Unit Electric Control Box Layout .............................................. 40

2 Outdoor Unit Main PCB ......................................................................... 42

3 Wiring Diagrams .................................................................................... 51

39
1 Outdoor Unit Electric Control Box Layout
8-16HP
Figure 5-1.1: 8-16HP top layer of electric control box

Figure 5-1.2: 8-16HP bottom layer of electric control box

40
18-30HP
Figure 5-1.3: 18-30HP top layer of electric control box

Figure 5-1.4: 18-30HP bottom layer of electric control box

41
2 Outdoor Unit Main PCB
2.1 Ports
Figure 5-2.1: Outdoor unit main PCB ports1

Notes:
1. Label descriptions are given in Table 5-2.1.

42
Table 5-2.1: Main PCB ports
Label Port code Content Port voltage
1 CN18 Reserved /
2 CN19 Low pressure switch connection 0V or 5V DC
Compressor top temperature sensor (single compressor
3 CN4 units) or compressor A compressor top temperature sensor 0-5V DC (varying)
(dual compressor units) connection
Discharge pipe temperature sensor (single compressor units)
4 CN5 or compressor B compressor top temperature sensor (dual 0-5V DC (varying)
compressor units) connection
5 CN3 Inverter module temperature sensor A connection 0-5V DC (varying)
6 CN13 Inverter module temperature sensor B connection 0-5V DC (varying)
7 CN17 High pressure sensor connection 0-5V DC (varying)
8 CN15 Reserved /
9 CN16 Reserved /
10 CN8 Reserved /
Outdoor ambient temperature sensor and outdoor heat
11 CN1 0-5V DC (varying)
exchanger temperature sensor connections
12 CN6 Reserved /
13 CN22-CN23 Communication port to outdoor units 2.5-2.7V DC
14 CN26 Communication port to compressor drive board 2.5-2.7V DC
15 CN27 Communication port to fan drive board 2.5-2.7V DC
16 CN9 Communication USB port 2.5-2.7V DC
17 CN28 Reserved /
18 CN71 Reserved /
19 CN70 EXVA drive port 0V or 12V DC
20 CN72 Reserved /
21 CN82 Control port of relay for AC filter board 0V or 12V DC
CN41, CN43,
22 Solenoid valve drive ports 0V or 220V AC
CN46
220V AC between A/B/C and N;
23 CN30 Power input of main board
380V AC between A,B and C
24 CN66-CN67 Power supply to compressor crankcase heater 220V AC

43
2.2 Components
Layout
Figure 5-2.2: Outdoor unit main PCB components

Function of buttons SW3 to SW6


Table 5-2.2: Function of buttons SW3 to SW6

Button Function

SW3 (UP) In menu mode: previous and next buttons for menu
modes.

SW4 (DOWN) Not in menu mode: previous and next buttons for
system check information.

SW5 (MENU) Enter / exit menu mode.

SW6 (OK) Confirm to enter specified menu mode.

44
Menu mode
Only master unit has the full menu functions, slaves units only have error codes check and cleaning functions.
1. Long press SW5 “MENU” button for 5 seconds to enter menu mode, and the digital display displays “n1”;
2. Press SW3 / SW4 “UP / DOWN” button to select the first level menu “n1”, “n2”, “n3”, “n4”or “nb”;
3. Press SW6 “OK” button to enter specified first level menu, for example, enter “n4” mode;
4. Press SW3 / SW4 “UP / DOWN” button to select the second level menu from “n41” to “n47”;
5. Press SW6 “OK” button to enter specified second level menu, for example, enter “n43” mode;

Menu mode selection flowchart:

Start
Short press SW5
“MENU” button

Long press SW5 “MENU”


button for 5 seconds

Digital display displays “-n1”


Short press SW5
“MENU” button

Press SW3 / SW4 “UP /


DOWN” button to select
the first level menu “nX”

Digital display displays “-nX”


Short press SW5
“MENU” button

Press SW6 “OK” button


to enter specified first
level menu “-nX”

Digital display displays “-nX1”


Short press SW5
“MENU” button

Press SW3 / SW4 “UP /


DOWN” button to select the
second level menu “nXY”

Digital display displays “-nXY”

Press SW6 “OK” button to


enter specified second level
menu “-nXY”

Confirm “-nXY”

45
Menu mode function:
Table 5-2.3: Menu mode function

Digital display
Menu mode Remarks
content
n14 Debug mode Only available for the master unit (all indoor units running in cooling mode)

n16 Maintenance mode Only available for the master unit, the system does not check the indoor units’ number.

n24 Reserved

n25 Reserved

Only available for outdoor unit with two compressors. If one of the two compressors is
n26 Backup run
fail, the other compressor will keep running for up to 4 days and then stop automatically.

It is only used in maintenance process. The digital display displays “R006”, all solenoid
n27 Vacuum mode
valves are open and EXVs are open to the maximum steps.

n31 History error codes Display recent ten history error codes

n32 Cleaning history error codes

n33 Reserved

n34 Factory reset Only available for the master unit


n41 Power limitation mode 1 Only available for the master unit, 100% capacity output

n42 Power limitation mode 2 Only available for the master unit, 90% capacity output

n43 Power limitation mode 3 Only available for the master unit, 80% capacity output
n44 Power limitation mode 4 Only available for the master unit, 70% capacity output

n45 Power limitation mode 5 Only available for the master unit, 60% capacity output

n46 Power limitation mode 6 Only available for the master unit, 50% capacity output
n47 Power limitation mode 7 Only available for the master unit, 40% capacity output
nb1 Fahrenheit degree setting (oF) Only available for the master unit

nb2 Celsius degree setting ( C)


o
Only available for the master unit
nb3 Exit auto power save mode1 Only available for the master unit
nb4 Enter auto power save mode1 Only available for the master unit

According to outdoor ambient temperature (T4), the outdoor fan(s) periodically stop for
nb5 Auto snow-blowing mode 1 (customized)
15 minutes and run for 2 minute

According to outdoor ambient temperature (T4), the outdoor fan(s) periodically stop for
nb6 Auto snow-blowing mode 2 (customized)
30 minutes and run for 2 minute

nb7 Exit auto snow-blowing mode

The digital display will display “IdXX”, “XX” stands for VIP address, use UP / DOWN button
nb8 VIP address setting
to change the VIP address and press OK button to confirm the specified VIP address.

nF1 Reserved
nF2 Reserved
Notes:
1. Auto power save mode means EMS mode, the evaporating temperature (in cooling) and condensing temperature (in heating) are automatically adjusted
according to both indoor and outdoor temperature to maximize the comfort and energy efficiency. Exit auto power save mode, the evaporating temperature
(in cooling) and condensing temperature (in heating) are fixed.

46
How to exit specified menu mode:
Table 5-2.4: Exit specified menu mode method:

Menu mode Manual exit method Automatic exit method System restart
Long press SW6 “OK” button when the digital
Debug mode After running 120 minutes Invalid
display is not in menu selection state

Maintenance mode / After running 60 minutes Invalid

After running 4 days or both


Backup run / Invalid
two compressors are failed

Long press SW6 “OK” button when the digital


Vacuum mode After running 8 hours Invalid
display is not in menu selection state

Power limitation mode Select power limitation mode 1 “n41” / Valid

Auto power save mode Select “nb3” / Valid


Auto snow-blowing mode 1 (2) Select “nb7” / Valid

VIP address setting / / Valid


o
F / C setting
o
/ / Valid

UP / DOWN system check button


Before pressing UP or DOWN button, allow the system to operate steadily for more than an hour. On pressing UP or DOWN
button, the parameters listed in Table 5-2.5 will be displayed in sequence.
Table 5-2.5: System check

DSP1
Parameters displayed on DSP2 Remarks
content
0.-- Unit address Master unit: 0; slave units: 1, 2
1.-- Unit capacity Refer to Note 1
2.-- Number of outdoor units Displayed on master unit PCB only
3.-- Number of indoor units as set on PCB Displayed on master unit PCB only
Only available for master unit, displayed on slave
4.-- Total capacity of outdoor unit
units has no sense
5.-- Total capacity requirement of indoor units Displayed on master unit PCB only
6.-- Total corrected capacity requirement of master units Displayed on master unit PCB only
7.-- Operating mode Refer to Note 2
8.-- Outdoor unit actual operating capacity
9.-- Fan A speed index Refer to Note 3
10.-- Fan B speed index Refer to Note 3
11.-- Indoor heat exchanger pipe (T2/T2B) temperature (°C) Actual value = value displayed
12.-- Main heat exchanger pipe (T3) temperature (°C) Actual value = value displayed
13.-- Outdoor ambient (T4) temperature (°C) Actual value = value displayed
14.-- Inverter compressor A discharge temperature (°C) Actual value = value displayed
15.-- Inverter compressor B discharge temperature (°C) Actual value = value displayed
16.-- Inverter module A heatsink temperature (°C) Actual value = value displayed
17.-- Inverter module B heatsink temperature (°C) Actual value = value displayed
18.-- Discharge superheat degree (°C) Actual value = value displayed
19.-- Reserved
20.-- Reserved
21.-- EXVA position Refer to Note 4
22.-- Compressor discharge pressure (MPa) Actual value = value displayed × 0.1
23.-- Reserved
24.-- Number of indoor units currently in communication with master unit Actual value = value displayed
25.-- Number of indoor units currently operating Displayed on master unit PCB only
26.-- Reserved
27.-- Silent mode Refer to Note 5
28.-- Static pressure mode Refer to Note 6
29.-- Reserved
30.-- Reserved
31.-- DC voltage A Actual value = value displayed × 10
32.-- DC voltage B Actual value = value displayed × 10
33.-- Reserved
Table continued on next page …

47
Table 5-2.5: System check (continued)

DSP1
Parameters displayed on DSP2 Remarks
content
34.-- Address of VIP indoor unit
35.-- Reserved
36.-- Reserved
37.-- Refrigerant quantity Refer to Note 7
38.-- Reserved
39.-- Power mode Refer to Note 8
“--“ is displayed if no error or protection events
40.-- Most recent error or protection code
have occurred since start-up
-- -- End
Notes:
1. Outdoor unit capacity setting:
 0: 8HP; 1: 10HP; 2: 12HP; 3: 14HP; 4: 16HP; 5: 18HP; 6: 20HP; 7: 22HP; 8: 24HP; 9: 26HP; A: 28HP; B: 30HP; C: 30HP.
2. Operating mode:
 0: off; 2: cooling; 3: null; 4: forced cooling.
3. The fan speed index is related to the fan speed in rpm and can take any integer value in the range 1 (slowest) to 37 (fastest).
4. 480P: steps = value displayed × 4; 3000P: steps = value displayed × 24.
5. Silent mode:
 0: night silent time 6h/10h; 1: night silent time 6h/12h; 2: night silent time 8h/10h; 3: night silent time 8h/12h; 4: no silent mode; 5: silent mode 1; 6:
silent mode 2; 7: silent mode 3; 8: super silent mode 1; 9: super silent mode 2; 10: super silent mode 3; 11: super silent mode 4.
6. Static pressure mode:
 0: standard static pressure; 1: low static pressure; 2: medium static pressure; 3: high static pressure; 4: super high static pressure.
7. Refrigerant quantity:
 0: normal; 1: slightly excessive; 2: significantly excessive; 3: slightly insufficient; 4: significantly insufficient; 5: critically insufficient.
8. Power mode:
 0: 100% capacity output; 1: 90% capacity output; 2: 80% capacity output; 3: 70% capacity output; 4: 60% capacity output; 5: 50% capacity output; 6:
40% capacity output; 10: auto power save mode, 100% capacity output; 11: auto power save mode, 90% capacity output; 12: auto power save
mode, 80% capacity output; 13: auto power save mode, 70% capacity output; 14: auto power save mode, 60% capacity output; 15: auto power save
mode, 50% capacity output; 16: auto power save mode, 40% capacity output;

Digital display output


Table 5-2.6: Digital display output in different operating states

Outdoor unit state Parameters displayed on DSP1 Parameters displayed on DSP2


The number of indoor units in
Standby Unit's address DSP1
communication with the outdoor units
For single Running speed of the compressor in
--
Normal compressor units rotations per second
operation For dual Running speed of compressor A in Running speed of compressor B in
compressor units rotations per second rotations per second
Error or protection -- or placeholder Error or protection code
DSP2
In menu mode Refer to Table 5-2.3 Refer to Table 5-2.3
System check Refer to Table 5-2.5 Refer to Table 5-2.5

48
3 Compressor Inverter Module
3.1 Ports
Figure 5-3.1: Compressor inverter module ports

Table 5-3.1: Compressor inverter module PCB ports


Label Port code Content Port voltage
1 CN6\CN7\CN11 3-phase power supply port to inverter module 380V AC
2 CN12\CN13\CN14 Inverter module power output port to compressor U V W /
3 CN20 Fan module power output port 18-22V DC
4 CN2\CN3 Inverter module control port 220V AC
Inverter module operating indicator LED1
5 LED1\LED2 0-3.3V DC (varying)
Inverter module error indicator LED2
6 CN8\CN9 Communication port to main board 0-5V DC (varying)
7 CN38 Power supply port to fan module IPM 485-645V DC
8 CN1\CN5 Connect to reactor /

49
3.2 Layout
Figure 5-3.2: Compressor inverter module components

LED indicators LED1 and LED2


Table 5-3.2: LED indicators LED1 and LED2

Indicator LED indicator function and status

Inverter module operating indicator. Continuously on if the compressor is running normally and
LED 1
flashing if an inverter module error has occurred1.

LED 2 Inverter module error indicator. Continuously on if an inverter module error has occurred1.

Note:
1. If an inverter module error occurs, refer to Part 6, “Xh4 Troubleshooting”. The error code is displayed on the digital display.

Dial switch S7 setting


Dial switch S7 is used to set compressor inverter module A/B address. The compressor inverter module A/B location refers
to the wiring diagram.
S7 on inverter module Inverter module address

0 for compressor inverter module A

1 for compressor inverter module B

50
4 Fan Module
4.1 Ports
Figure 5-4.1: Fan module ports

Table 5-4.1: Fan module PCB ports


Label in Port code Content Port voltage
1 CN6 Power supply port to fan module control part 18-22V DC
2 CN5 Power supply port to fan module control part 18-22V DC
3 CN2 Program upgrade port /
4 CN1 Communication port to main board 0-5V DC (varying)
5 CN4 Communication port to main board 0-5V DC (varying)
6 CN7 Power supply port ”N” to fan module IPM Voltage between P and N is 485-645V
7 CN8 Power supply port ”P” to fan module IPM Voltage between P and N is 485-645V
8 CN3 Connect to fan motor /
9 SW1 Fan module address dial switch1 Note 1
10 LED2 Fan module error indicator /
11 LED1 Fan module operating indicator /
Notes:
1. This dial switch is used to set fan module A/B address. The fan module A/B location refers to the wiring diagram.
Dial switch on fan module Fan module address

0 for fan module A

1 for fan module B

51
8-16HP

RA_A

CN6
CN1
5 Wiring Diagrams

RA_A
Figure 5-5.1: 8-16HP wiring diagram

CN11

CN2(CN3)
CN12 CN13 CN14

EEVA

CN70
EEVA
L1’ L2’ L3’ RA_A
ENC1 ENC2

52
CN82
N-ON
NUM_S POWER CN30
DSP1 DSP2

CN18
S12 ENC3

H-PRO
ON

L-PRO MENU DOWN UP OK Alarm CN80

CN19
123 Alarm

L-PRO
IN_NUM
HEATB

CN3
TF1
TF1
CN67 HEATB
HEATB

CN4
T7C1 CN67_1
Main board HEATB

T7C1
HEATA HEATA/HEATB Crankcase heater
CN66 HEATA Alarm Alarm output
H-YL1

CN17
HEATA

H-YL1
CN66_1 HEATA

T4

CN1
SV7 CN46 SV7

T4 T3
T3

SV4 CN43 SV4

CN26 CN27 CN9


O-C O-FAN

SV2 CN41 SV2


USB UPGRADE

X Y E P Q E O A E H1 H2 E CN91

ON/OFF SWITCH
XT1 (for priority mode )
L1 L2 L3 N

To To To
To indoor outdoor
centrali- kilowatt-
units hour units com-
zed communi- munication
controller cation meter bus
bus
Power in
18-30HP

RA_A RA_B

CN6 CN6

RA_A RA_B

CN11 CN11
Figure 5-5.2: 18-30HP wiring diagram

CN2(CN3)
CN2(CN3)
Note
CN12 CN13 CN14 CN12 CN13 CN14

Note:Cable of COMP B has one more belt than COMP A

EEVA

CN70
EEVA
RA_A/RA_B
ENC1 ENC2

53
CN82
N-ON
NUM_S POWER
DSP1 DSP2 CN30
S12 ENC3

CN18
H-PRO
ON

MENU DOWN UP OK

CN19
L-PRO 123 Alarm

L-PRO
CN80 Alarm
IN_NUM

CN3
TF1

TF1
HEATB
CN67 HEATB

TF2
TF2

CN13
HEATB

CN4
T7C1 CN67_1
Main board HEATB
HEATA/HEATB Crankcase heater
HEATA

CN5
T7C2 CN66 HEATA Alarm Alarm output

T7C1 T7C2
HEATA

CN17
H-YL1 CN66_1 HEATA

T4

CN1
SV7 CN46 SV7
T3 H-YL1 T4 T3

SV4 CN43 SV4


CN26 CN27

CN9
O-C O-FAN

SV2 CN41 SV2


USB UPGRADE

X Y E P Q E O A E H1 H2 E CN91

ON/OFF SWITCH
XT1 (for priority mode )
L1 L2 L3 N

To To To
To indoor outdoor
centrali- kilowatt-
units hour units com-
zed communi- munication
controller cation meter bus
bus
Power in
Part 6
Diagnosis and
Troubleshooting
1 Error Code Table .................................................................................... 55

2 Troubleshooting .................................................................................... 56

3 Appendix to Part 6 .............................................................................. 107

54
1 Error Code Table
Table 6-1.1: Error code table

Error Manual re-start


Content Remarks
code1 required2
Only displayed on the slave unit
E0 Communication error between outdoor units No
with the error
E2 Communication error between indoor and master unit Only displayed on the master unit No
Outdoor heat exchanger temperature sensor (T3) error or
E4 Displayed on the unit with the error No
outdoor ambient temperature sensor (T4) error
E5 Abnormal power supply voltage Displayed on the unit with the error No
Compressor top or discharge pipe temperature sensor
E7 Displayed on the unit with the error Yes
(T7C1/T7C2) error
E8 Outdoor unit address error Displayed on the unit with the error Yes
xE9 EEPROM mismatch Displayed on the unit with the error Yes
xF1 DC bus voltage error Displayed on the unit with the error No
Displayed on the unit with the error
XF6 Electronic expansion valve connection error Yes
Refer to Note 3
Communication error between main control chip and inverter
xH0 Displayed on the unit with the error No
driver chip
H2 Number of slave units detected by master unit has decreased Only displayed on the master unit No
H3 Number of slave units detected by master unit has increased Only displayed on the master unit No
xH4 Inverter module protection Displayed on the unit with the error Yes
H5 P2 protection appears three times in 60 minutes Displayed on the unit with the error Yes
H6 P4 protection appears three times in 100 minutes Displayed on the unit with the error Yes
Number of indoor units detected by master unit not same as
H7 Only displayed on the master unit No
number set on main PCB
H8 High pressure sensor error Displayed on the unit with the error No
xH9 P9 protection appears ten times in 120 minutes Displayed on the unit with the error Yes
yHd Slave unit malfunction Only displayed on the master unit No
C7 PL protection appears three times in 100 minutes Displayed on the unit with the error Yes
P1 Discharge pipe high pressure protection Displayed on the unit with the error No
P2 Suction pipe low pressure protection Displayed on the unit with the error No
P4 Discharge temperature protection Displayed on the unit with the error No
P5 Outdoor heat exchanger temperature protection Displayed on the unit with the error No
xP9 Fan module protection Displayed on the unit with the error No
Table continued on next page …

55
Table 6-1.1: Error code table (continued)

Error Manual re-start


Content Remarks
code1 required2
PL Inverter module temperature protection Displayed on the unit with the error No
PP Compressor discharge insufficient superheat protection Displayed on the unit with the error No
xL0 Inverter module protection Displayed on the unit with the error Yes
xL1 DC bus low voltage protection Displayed on the unit with the error Yes
xL2 DC bus high voltage protection Displayed on the unit with the error Yes
xL4 MCE error Displayed on the unit with the error Yes
xL5 Zero speed protection Displayed on the unit with the error Yes
xL7 Phase sequence error Displayed on the unit with the error Yes
Compressor frequency variation greater than 15Hz within one
xL8 Displayed on the unit with the error Yes
second protection
Actual compressor frequency differs from target frequency by
xL9 Displayed on the unit with the error Yes
more than 15Hz protection
Notes:
1. 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1 representing compressor system A and 2
representing compressor system B. 'y' is a placeholder for the address (1 or 2) of the slave unit with the error.
2. For some error codes, a manual restart is required before the system can resume operation.
3. Once the EXV has been connected properly, the error code will flash to indicate that the connection has been re-established. A manual restart is then
required before the system can resume operation.

2 Troubleshooting
2.1 Warning

Warning

 All electrical work must be carried out by competent and suitably qualified, certified and
accredited professionals and in accordance with all applicable legislation (all national, local and other laws,
standards, codes, rules, regulations and other legislation that apply in a given situation).
 Power-off the outdoor units before connecting or disconnecting any connections or wiring, otherwise electric
shock (which can cause physical injury or death) may occur or damage to components may occur.

56
2.2 E0: Communication error between outdoor units
Digital display output

Description
 Communication error between outdoor units.
 All units stop running.
 Error code is only displayed on the slave unit with the error.

Trigger / recover condition


 Trigger condition: Slave unit cannot receive signal from master unit for 60s.
 Recover condition: Slave unit can receive signal from master unit.
 Reset method: Resume automatically.

Possible causes
 Incorrect outdoor unit address setting.
 Communication wires between outdoor units not connected properly.
 Loosened wiring within electric control box.
 Damaged main PCB or electric control box communication terminals block.

57
Procedure

E0

ODU addresses on switch ENC1 are set Yes Set the ODU addresses correctly
incorrectly1
No

Ensure the communication wires are


Communication wires between ODUs are Yes three-core shielded cable and are
not connected properly2
connected properly
No

Wires between outdoor main PCB and


electric control box communication Yes Ensure the wires are connected properly
terminals block are loose
No

Replacing outdoor main PCB resolves the


error
No

Replace electric control box


communication terminals block

Notes:
1. The master unit address should be set as 0, slave units addresses should be set from 1 to 2, and the addresses should not be repeated within one system.
2. All the wires for H1, H2, E connections should be three-core shielded cable, the wiring should be connected according to polarity (H1 to H1, etc), the wiring
should not be open or short circuited.

58
2.3 E2: Communication error between indoor and master unit
Digital display output

Description
 Communication error between indoor and master unit.
 All units stop running.
 Error code is only displayed on the master unit.

Trigger / recover condition


 Trigger condition: Indoor units and outdoor units cannot communication for 2 minutes after the system power on 20
minutes.
 Recover condition: Communication go back to normal.
 Reset method: Resume automatically.

Possible causes
 Communication wires between indoor and outdoor units not connected properly.
 Indoor unit power supply abnormal.
 Loosened wiring within electric control box.
 Interference from high voltage wires or other sources of electromagnetic radiation.
 Communication wire too long.
 Damaged main PCB or electric control box communication terminals block.

59
Procedure

E2

Communication wires P Q E have short Yes Reconnect the communication wires


circuited or disconnected1
No

Communication wires P Q E are not Yes Connect the communication wires in a


connected in a daisy chain daisy chain
No

IDU power supply is abnormal Yes Ensure normal power supply

No

Wires between outdoor main PCB and


electric control box communication Yes Ensure the wires are connected properly
terminals block are loose
No

Interference from high voltage (220V or Yes Ensure the communication wires and
higher) wires high voltage wires are separated
No

Communication wires are close to a Remove the source of interference, or


source of electromagnetic radiation such Yes add additional shielding to the
as transformer or strong fluorescent lamp communication wires
No

The length of communication wire is over Yes Reduce the wire length to less than
1200m 1200m or strengthen the signal
No

Replacing outdoor main PCB resolves the


error
No

Replace electric control box


communication terminals block

Notes:
1. Measure the resistance among P, Q and E. The normal resistance between P and Q is 120Ω, between P and E is infinite, between Q and E is infinite.

60
2.4 E4: Temperature sensor (T3/T4) error
Digital display output

Description
 Outdoor heat exchanger temperature sensor (T3) error or outdoor ambient temperature sensor (T4) error.
 All units stop running.
 Error code is only displayed on the unit with the error.

Trigger / recover condition


 Trigger condition: The main control board cannot receive the feedback signal of temperature sensor T3 or T4.
 Recover condition: The main control board can receive the feedback signal of temperature sensor T3 or T4.
 Reset method: Resume automatically.

Possible causes
 Temperature sensor not connected properly or has malfunctioned.
 Damaged main PCB.

61
Procedure

E4

Temperature sensor connection on main Yes Ensure the sensor is connected properly
PCB is loose1
No

Temperature sensor has short-circuited Yes Replace the sensor


or failed2
No

Replace outdoor main PCB

Notes:
1. Outdoor ambient temperature sensor (T4) and heat exchanger temperature sensor (T3) connection is port CN1 on the main PCB (labeled 11 in Figure 5-2.1
in Part 5, 2.1 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Table 6-3.1 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”.

62
2.5 E5: Abnormal power supply voltage
Digital display output

Description
 Abnormal power supply voltage.
 All units stop running.
 Error code is only displayed on the unit with the error.

Trigger / recover condition


 Trigger condition: Outdoor unit power supply phase voltage < 165V.
 Recover condition: Outdoor unit power supply phase voltage is > 180V.
 Reset method: Resume automatically.

Possible causes
 Outdoor unit power supply voltage is abnormal or a phase is missing.
 Loosened wiring within electric control box.
 High voltage circuit error.
 Main PCB damaged.

63
Procedure

E5

ODU power supply is abnormal or a Yes Provide normal power supply


phase is missing1
No

Wires between outdoor main PCB, AC


filter boards and electric control box Yes Ensure the wires are connected properly
power supply terminals are loose
No

High voltage circuit error has occurred,


such as the compressor has
malfunctioned2, the fan motor has Yes Replace or repair the relevant parts
short-circuited3, or the inverter module
has short-circuited4
No

Replace outdoor main PCB

Notes:
1. The normal voltage between A and N, B and N, and C and N is 198-242V.
2. The normal resistances of the inverter compressor are 0.7-1.5Ω among U V W and infinite between each of U V W and ground. If any of the resistances
differ from these specifications, the compressor has malfunctioned.
3. The normal resistances of the fan motor coil among U V W are less than 10Ω. If a measured resistance is 0Ω, the fan motor has short-circuited.
4. Set a multi-meter to buzzer mode and test any two terminals of P N U V W of the inverter module. If the buzzer sounds, the inverter module has
short-circuited.

Figure: Inverter module terminals

64
2.6 E7: Temperature sensor (T7C1/2) error
Digital display output

Description
 A compressor top temperature sensor or discharge pipe temperature sensor (T7C1/2) error.
 All units stop running.
 Error code is only displayed on the unit with the error.

Trigger / recover condition


 Trigger condition: Discharge pressure ≥ 3MPa and discharge temperature < 15oC for 2 minutes.
 Recover condition: Discharge pressure and temperature go back to normal.
 Reset method: Manually restart.

Possible causes
 Temperature sensor not connected properly or has malfunctioned.
 Damaged main PCB.

65
Procedure

E7

Temperature sensor connection on main Yes Ensure the sensor is connected properly
PCB is loose1
No

Temperature sensor has short-circuited Yes Replace the sensor


or failed2
No

Replace outdoor main PCB

Notes:
1. Compressor top temperature sensor and discharge pipe temperature sensor connections are ports CN4 and CN5 on the main PCB (labeled 3 and 4,
respectively, in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Table 6-3.2 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”.

66
2.7 E8: Outdoor unit address error
Digital display output

Description
 Outdoor unit address error.
 All units stop running.
 Error code is only displayed on the unit with the error.

Trigger / recover condition


 Trigger condition: Outdoor unit address is set more than 2.
 Recover condition: Outdoor unit addresses are set from 0 to 2.
 Reset method: Manually restart.

Possible causes
 Invalid outdoor unit address.
 Main PCB damaged.

67
Procedure

E8

The ODU's address is not in the valid Yes Slave units addresses should be set from
range1 1 to 2
No

Replace the outdoor main PCB

Notes:
1. The master unit address should be set as 0, slave units addresses should be set from 1 to 2, and the addresses should not be repeated within one system.

68
2.8 xE9: EEPROM mismatch
Digital display output

In the error code, 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1
representing compressor system A and 2 representing compressor system B.

Description
 1E9 indicates a compressor A EEPROM mismatch.
 2E9 indicates a compressor B EEPROM mismatch.
 All units stop running.
 Error code is only displayed on the unit with the error.

Trigger / recover condition


 Trigger condition: Compressor drive parameter is mismatch.
 Recover condition: Compressor drive parameter is match.
 Reset method: Manually restart.

Possible causes
 Outdoor unit was powered on immediately after being powered off.
 Main PCB damaged.

69
Procedure

xE9

Power off the unit and wait for the digital


The outdoor unit was powered on Yes display to turn off before restarting the
immediately after being powered off1
unit
No

Replace outdoor main PCB

Notes:
1. When performing a manual restart of an outdoor unit, once the unit has been powered off it should not be powered on again until the digital display has
turned off.

70
2.9 xF1: DC bus voltage error
Digital display output

'x' is a placeholder for the compressor system (compressor and related electrical components), with 1 representing
compressor system A and 2 representing compressor system B.

Description
 1F1 indicates compressor A DC bus voltage error; 2F1 indicates compressor B DC bus voltage error.
 All units stop running.
 Error code is only displayed on the unit with the error.

Trigger / recover condition


 Trigger condition: DC bus voltage < 350V or DC bus voltage > 700V continuously for 10 seconds.
 Recover condition: DC bus voltage goes back to normal.
 Reset method: Restart automatically.

Possible causes
 Loosened wiring of the compressor inverter module.
 Incorrect wiring of the reactor and DC bus wire.
 Abnormal power supply.
 Inverter module damaged.

Procedure

F1 error

Compressor inverter module wiring is Yes Reconnect cables based on


loosened wiring diagram

No

Yes Check the power supply


The power supply is abnormal 1
equipment

No

Replace the inverter module

71
2.10 F6: Electronic expansion valve connection error
Digital display output

Description
 Electronic expansion valve connection error.
 All units stop running.
 Error code is only displayed on the unit with the error.

Trigger / recover condition


 Trigger condition: The main control board cannot receive the feedback signal of EXV.
 Recover condition: The main control board can receive the feedback signal of EXV.
 Reset method: When the main control board can receive the feedback signal of EXV, F6 flashes, a manual system
restart id required before the system can resume operation.

Possible causes
 Electronic expansion valve coil not connected properly or has malfunctioned.
 Damaged main PCB.

72
Procedure

F6

Electronic expansion valve coil Yes Ensure the sensor is connected properly
connection on main PCB is loose1
No

Electronic expansion valve coil has Yes Replace the sensor


malfunctioned2
No

Replace outdoor main PCB

Notes:
1. Electronic expansion valve coil connections is port CN70 on the main PCB (labeled 19 in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. The normal resistances between EXV coil wiring terminals RED and white / yellow / orange / blue are 40-50Ω. If any of the resistances differ from the value,
the EXV coil has malfunctioned.
Figure: EXV coil wiring terminals

73
2.11 xH0: Communication error
Digital display output

In the error code, 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1
representing compressor system A and 2 representing compressor system B.

Description
 1H0 indicates a communication error between the main control chip and the compressor A inverter driver chip.
 2H0 indicates a communication error between the main control chip and the compressor B inverter driver chip.
 All units stop running.
 Error code is only displayed on the unit with the error.

Trigger / recover condition


 Trigger condition: Main control chip and inverter driver chip cannot communication for 2 minutes.
 Recover condition: Communication go back to normal.
 Reset method: Resume automatically.

Possible causes
 Incorrect compressor inverter module address setting.  Bridge rectifier damaged.
 Loosened communication wiring from the main PCB to  Main PCB damaged.
the inverter module.  Compressor inverter module damaged.

Procedure

H0 error

Reset the compressor


Compressor inverter module address Yes inverter module address via
setting is incorrect dial switch S7 on inverter
module 1
No
Communication wire from outdoor Yes Reconnect the
main PCB CN26 to inverter module CN8/
communication wire
CN9 is loosened 2
No

Both LED1 and LED2 on inverter module Yes Check the power supply
are off when power on 3 circuit

No

Replace the outdoor main PCB, is the Yes


Normal
malfunction solved?

No

Replace the inverter module

74
Notes:
1. Compressor inverter module address is set through dial switch S7 on the inverter module. The compressor inverter module A/B location refers to the
wiring diagram.

S7 on inverter module Inverter module address

0 for compressor inverter module A

1 for compressor inverter module B

2. Communication wire from outdoor main PCB CN26 to inverter module CN8/CN9.
3. LED1/2 on inverter module

75
2.12 H2, H3: Slave units decreased/increased
Digital display output

Description
 H2 indicates that the number of slave units detected by master unit has decreased.
 H3 indicates that the number of slave units detected by master unit has increased.
 All units stop running.
 Error code is only displayed on the master unit.

Trigger / recover condition


 Trigger condition: Number of slave units detected by master unit has decreased or increased.
 Recover condition: Number of slave units detected by master unit goes back to normal.
 Reset method: Resume automatically.

Possible causes
 Some outdoor units are powered off.
 Power supply abnormal.
 Incorrect outdoor unit address setting.
 Communication wires between outdoor units not connected properly.
 Loosened wiring within electric control box.
 Damaged main PCB or electric control box communication terminals block.

76
Procedure

H2 / H3

Some outdoor units in the system are Yes Power on all the outdoor units
powered off
No

The power supply is abnormal Yes Check the power supply equipment

No

Troubleshoot as for an E0 error2

Notes:
1. See “E0 Troubleshooting”.

77
2.13 xH4: Inverter module protection
Digital display output

In the error code, 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1
representing compressor system A and 2 representing compressor system B.

Description
 1H4 indicates compressor A inverter module protection.
 2H4 indicates compressor B inverter module protection.
 All units stop running.
 Error code is only displayed on the unit with the error.

Trigger / recover condition


 Trigger condition: Compressor appears three inverter module protections.
 Recover condition: Inverter module goes back to normal.
 Reset method: Manually restart.

Possible causes
 Inverter module protection.
 DC bus low or high voltage protection.
 MCE error.
 Zero speed protection.
 Phase sequence error.
 Excessive compressor frequency variation.
 Actual compressor frequency differs from target frequency.

Specific error codes for xH4 inverter module protection


If an xH4 error code is displayed, enter menu mode “n31” (refer to Part 5, 2.2.3 “menu mode”) to check the history error
code to check the following specific error code: xL0, xL1, xL2, xL4, xL5, xL7, xL8, xL9.
Table 6-2.1: Specific error codes for error xH4
Specific error code1 Content
xL0 Inverter module protection
xL1 DC bus low voltage protection
xL2 DC bus high voltage protection
xL4 MCE error
xL5 Zero speed protection
xL7 Phase sequence error
xL8 Compressor frequency variation greater than 15Hz within one second protection
xL9 Actual compressor frequency differs from target frequency by more than 15Hz protection
Notes:
1. 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1 representing compressor system A and
2 representing compressor system B.

78
The specific error codes xL0, xL1, xL2 and xL4 can also be obtained from the inverter module LED indicators. If an inverter
module error has occurred, LED2 is continuously on and LED1 flashes.

Figure: LED indicators LED1 and LED2 on inverter module

Table 5-3.2: Errors indicated on LED1


LED1 flashing pattern Corresponding error
Flashes 8 times and stops for 1 second, then repeats xL0 - Inverter module protection
Flashes 9 times and stops for 1 second, then repeats xL1 - DC bus low voltage protection
Flashes 10 times and stops for 1 second, then repeats xL2 - DC bus high voltage protection
Flashes 12 times and stops for 1 second, then repeats xL4 - MCE error
Flashes 13 times and stops for 1 second, then repeats xL5- Zero speed protection
Flashes 15 times and stops for 1 second, then repeats xL7- Phase sequence error
Flashes 16 times and stops for 1 second, then repeats xL8-Compressor frequency variation greater than
15Hz within one second protection
Flashes 17 times and stops for 1 second, then repeats xL9-Actual compressor frequency differs from
target frequency by more than 15Hz protection

79
L0: Inverter module protection

L0 protection

The compressor wiring is connected Yes Reconnect the cables


incorrectly based on wiring diagram

No

Disconnect The resistance between 3 phases of Yes


the power compressor is over 5?
supply
No Replace the compressor

The insulation resistance of Yes


compressor is less than 100k?

No

The inverter module is not well heat Yes Yes Fasten IPM
The IPM screws is loosen
dissipation screws again

No No

Ensure enough Yes The compressor has less than 12 hours The silica gel is coated not Yes Coat with silica
preheating time preheating before initial operating well for heat radiation gel

No No

Switch on power again to detect No Replace the inverter


whether the compressor can start module

Yes

Refer to “P3 over current protection”

80
L1: DC bus low voltage protection

L1 protection

Yes Check the power supply


The power supply is abnormal
equipment

No

Yes
No output from bridge rectifier

No

1 Yes No Replace the


The DC bus voltage (P, N) is abnormal The reactor performs well
reactor

No
Yes
Replace the inverter module

Note:
1. The normal DC voltage between terminals P and N on inverter module should be 450-650V. When the voltage is lower than 350V, L1
protection will be appeared.
Figure: Inverter module terminals

81
L2: DC bus high voltage protection

L2 protection

Yes Check the power supply


The power supply is abnormal
equipment

No

1 Yes Replace the 3-phase bridge


The DC bus voltage (P, N) is abnormal
rectifier

No

Replace the inverter module

Note:
1. The normal DC voltage between terminals P and N on inverter module should be 450-650V. When the voltage is higher than 700V, L2
protection will be appeared.
Figure: Inverter module terminals

82
L4: MCE error

Notes:
1. Compressor inverter module address is set through dial switch S7 on the inverter module. The compressor inverter module A/B location refers to the
wiring diagram.

S7 on inverter module Inverter module address

0 for compressor inverter module A

1 for compressor inverter module B

83
L7: Phase sequence error

84
L8: Compressor frequency variation greater than 15Hz within one second protection
L9: Actual compressor frequency differs from target frequency by more than 15Hz protection

85
Compressor replacement procedure
Step 1: Remove faulty compressor and remove oil
 Remove the faulty compressor from the outdoor unit.
 Before removing the oil, shake the compressor so as to not allow impurities to remain settled at the bottom.
 Drain the oil out of the compressor and retain it for inspection. Normally the oil can be drained out from the
compressor discharge pipe.

Step 2: Inspect oil from faulty compressor


 The oil should be clear and transparent. Slightly yellow oil is not an indication of any problems. However, if the oil is
dark, black or contains impurities, the system has problems and the oil needs to be changed. If the compressor oil has
been spoiled, the compressor will not be being lubricated effectively. Abrasion will lead to a larger load and higher
current. More electric energy will get dissipated as heat and the temperature of the motor will become increasingly
high. Finally, compressor damage or burnout will result.

Step 3: Check oil in other compressors in the system


 If the oil drained from the faulty compressor is clean, go to Step 6.
 If the oil drained from the faulty compressor is only lightly spoiled, go to Step 4.
 If the oil drained from the faulty compressor is heavily spoiled, check the oil in the other compressors in the system.
Drain the oil from any compressors where the oil has been spoiled. Go to Step 4.

Step 4: Replace oil separator(s) and accumulator(s)


 If the oil from a compressor is spoiled (lightly or heavily), drain the oil from the oil separator and accumulator in that
unit and then replace them.

Step 5: Check filters(s)


 If the oil from a compressor is spoiled (lightly or heavily), check the filter between the gas stop valve and the 4-way
valve in that unit. If it is blocked, clean with nitrogen or replace.

Step 6: Replace the faulty compressor and re-fit the other compressors
 Replace the faulty compressor.
 If the oil had been spoiled and was drained from the non-faulty compressors in Step 3, use clean oil to clean them
before re-fitting them into the units. To clean, add oil into the compressor through the discharge pipe using a funnel,
shake the compressor, and then drain the oil. Repeat several times and then re-fit the compressors into the units.
(The discharge pipe is connected to the oil pool of the compressor by the inner oil balance pipe.)

Step 7: Add compressor oil


 Add 2.3L of oil to each of the compressors from which oil was drained in Step 3.
 Only use FV50S oil. Different compressors require different types of oil. Using the wrong type of oil leads to various
problems.
 Add additional oil to the accumulators such that the total amount of oil is 4L in 8-12HP units, 5L in 14-16HP units 6L in
18-22HP units and 9L in 24-30HP units.

Step 8: Vacuum drying and refrigerant charging


 Once all the compressors and other components have been fully connected, vacuum dry the system and recharge
refrigerant. Refer to the V6 Engineering Data Book, Part 3.

86
2.14 H7: Unmatched total number of indoor units
Digital display output

Description
 Number of indoor units detected by master unit not same as number set on main PCB.
 All units stop running.
 Error code is only displayed on the master unit.

Trigger / recover condition


 Trigger condition: Only one indoor unit cannot be detected by master unit for 8 hours or more than one indoor unit
cannot be detected by master unit for 3 minutes.
 Recover condition: Number of indoor units detected by master unit is same as number set on main PCB.
 Reset method: Resume automatically.

Possible causes
 Number of indoor units set on main PCB not same as actual number of indoor units.
 Some indoor units are powered off.
 Communication wires between indoor and outdoor units not connected properly.
 Indoor unit PCB damaged.
 Indoor unit without address or indoor unit address duplicated.
 Main PCB damaged.

87
Procedure

H7

Number of indoor units set on main PCB Change the setting on the PCB to be the
not same as actual number of indoor Yes same as the actual number of indoor
units1 units
No

Some indoor units are powered off Yes Power on all indoor units

No

After re-starting the ODUs and IDUs and Refer to indoor unit troubleshooting
then waiting 2 minutes, an IDU displays Yes guide. Resolving the indoor unit error
an E1 or FE error2 resolves the outdoor unit error
No

Two or more indoor units are assigned


No
the same address3
Yes

Setting the indoor units’ addresses No Replace outdoor main PCB


uniquely resolves the error

Notes:
1. The number of indoor units can be set on switches EN3 and S12 on the main PCB.
2. Indoor unit error code E1 indicates a communication error between indoor and master unit. Indoor unit error code FE indicates that an indoor unit has not
been assigned an address.
3. Indoor unit addresses can be checked and manually assigned using indoor unit remote/wired controllers. Alternatively, indoor unit addresses can be
automatically assigned by the master outdoor unit.

88
2.15 H8: High pressure sensor error
Digital display output

Description
 High pressure sensor error.
 All units stop running.
 Error code is only displayed on the unit with the error.

Trigger / recover condition


 Trigger condition: Discharge pressure ≤ 0.3MPa.
 Recover condition: Discharge pressure > 0.3MPa.
 Reset method: Resume automatically.

Possible causes
 Pressure sensor not connected properly or has malfunctioned.
 Insufficient refrigerant.
 Low pressure side blockage.
 Poor evaporator heat exchange.
 Main PCB damaged.

89
Procedure

H8

High pressure sensor connection on main Yes Ensure the sensor is connected properly
PCB is loose1
No

High pressure sensor has short-circuited Yes Replace the sensor


or failed2
No

Insufficient refrigerant caused by Yes Add refrigerant and inspect system for
refrigerant leakage3 leaks
No

The low pressure side is blocked, caused Inspect the system and fix the error. If the
by crushed or bent pipe, closed EXV or Yes filter is blocked by ice, the piping should
dirty filter4 be cleaned
No

The evaporator heat exchange is poor5 Yes Inspect the system and fix the error

No

Replace the outdoor main PCB

Notes:
1. High pressure sensor connection is port CN17 on the main PCB (labeled 7 in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure the resistance among the three terminals of the pressure sensor. If the resistance is of the order of mega Ohms or infinite, the pressure sensor
has failed.
3. An insufficiency of refrigerant causes compressor discharge temperature to be higher than normal, discharge and suction pressures to be lower than
normal and compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. These issues disappear once sufficient
refrigerant has been charged into the system. For normal system parameters refer to Table 6-3.4 in Part 6, 3.2 “Normal Operating Parameters of
Refrigerant System”.
4. A low pressure side blockage causes compressor discharge temperature to be higher than normal, suction pressure to be lower than normal and
compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. For normal system parameters refer to Table 6-3.4 in
Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
5. In cooling mode check indoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check outdoor heat exchangers, fans and air outlets
for dirt/blockages.

90
2.16 yHd: Slave unit malfunction
Digital display output

In the error code, 'y' is a placeholder for the address (1 or 2) of the slave unit with the error.

Description
 1Hd indicates an error on the slave unit with address 1.
 2Hd indicates an error on the slave unit with address 2.
 All units stop running.
 Error code is only displayed on the master unit.

Trigger / recover condition


 Trigger condition: Slave unit is malfunction.
 Recover condition: Slave unit goes back to normal.
 Reset method: Resume automatically.

Possible causes
 Slave unit malfunction.

91
Procedure

yHd

Check relevant slave unit

92
2.17 P1: Discharge pipe high pressure protection
Digital display output

Description
 All units stop running.
 Error code is only displayed on the unit with the error.

Trigger / recover condition


 Trigger condition: Discharge pressure ≥ 4.3MPa.
 Recover condition: Discharge pressure ≤ 4.0MPa for 2 minutes.
 Reset method: Resume automatically.

Possible causes
 Outdoor unit stop valves are closed.
 High pressure sensor not connected properly or has malfunctioned.
 Excess refrigerant.
 System contains air or nitrogen.
 High pressure side blockage.
 Poor condenser heat exchange.
 Main PCB damaged.

Procedure

P1

ODU stop valves are closed Yes Open the stop valves

No

High pressure sensor connection on main Yes Ensure the sensor is connected properly
PCB is loose1
No

High pressure sensor has failed2 Yes Replace the sensor

No

Flowchart continued on next page …

93
… flowchart continued from previous page

Yes Discharge part of the refrigerant. Add oil


Excess refrigerant3
if it leaks during discharge
No

Flush all refrigerant then vacuum the


System contains air or nitrogen 4 Yes system and recharge the refrigerant. Add
oil to the system if it leaks
No

The high pressure side is blocked, caused Yes Inspect the system and fix the error
by crushed or bent pipe or blocked EXV5
No

The condenser heat exchange is poor6 Yes Inspect the system and fix the error

No

Replace outdoor main PCB

Notes:
1. The high pressure sensor connection is port CN17 on the main PCB (labeled 7 in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure the resistance among the three terminals of the high pressure sensor. If the resistance is of the order of mega Ohms or infinite, the high pressure
sensor has failed.
3. Excess refrigerant causes discharge temperature to be lower than normal, discharge pressure to be higher than normal and suction pressure to be higher
than normal. For normal system parameters refer to Table 6-3.4 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
4. Air or nitrogen in the system causes discharge temperature to be higher than normal, discharge pressure to be higher than normal, compressor current to
be higher than normal, abnormal compressor noise and an unsteady pressure meter reading. For normal system parameters refer to Table 6-3.4 in Part 6,
3.2 “Normal Operating Parameters of Refrigerant System”.
5. High pressure side blockage causes discharge temperature to be higher than normal, discharge pressure to be higher than normal and suction pressure to
be lower than normal. For normal system parameters refer to Table 6-3.4 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
6. In cooling mode check outdoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check indoor heat exchangers, fans and air outlets
for dirt/blockages.

94
2.18 P2, H5: Suction pipe low pressure protection
Digital display output

Description
 All units stop running.
 Error code is only displayed on the unit with the error.

Trigger / recover condition


 Trigger condition:
For P2 protection: Suction pressure ≤ 0.05MPa.
For H5 protection: P2 protection appears three times in 60 minutes.
 Recover condition: Suction pressure ≥ 0.15MPa.
 Reset method:
For P2 protection: Resume automatically.
For H5 protection: Manually restart.

Possible causes
 Outdoor unit stop valves are closed.
 Insufficient refrigerant.
 Low pressure side blockage.
 Poor evaporator heat exchange.
 Main PCB damaged.

95
Procedure

P2 / H5

ODU stop valves are closed Yes Open the stop valves

No

Insufficient refrigerant caused by Yes Add refrigerant or inspect the system for
refrigerant leakage1 leaks
No

The low pressure side is blocked, caused Inspect the system and fix the error. If the
by crushed or bent pipe, blocked EXV, or Yes filter is blocked by ice, the piping should
dirty filter2 be cleaned
No

The evaporator heat exchange is poor5 Yes Inspect the system and fix the error

No

Replace outdoor main PCB

Notes:
1. An insufficiency of refrigerant causes compressor discharge temperature to be higher than normal, discharge and suction pressures to be lower than
normal and compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. These issues disappear once sufficient
refrigerant has been charged into the system. For normal system parameters refer to Table 6-3.4 in Part 6, 3.2 “Normal Operating Parameters of
Refrigerant System”.
2. A low pressure side blockage causes compressor discharge temperature to be higher than normal, suction pressure to be lower than normal and
compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. For normal system parameters refer to Table 6-3.4 in
Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
3. In cooling mode check indoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check outdoor heat exchangers, fans and air outlets
for dirt/blockages.

96
2.19 P4, H6: Discharge temperature protection
Digital display output

Description
 Discharge temperature protection.
 All units stop running.
 Error code is only displayed on the unit with the error.

Trigger / recover condition


 Trigger condition:
For P4 protection: Discharge temperature (T7C1/2) ≥ 120oC.
For H6 protection: P4 protection appears three times in 100 minutes.
 Recover condition: Discharge temperature (T7C1/2) ≤ 90 oC.
 Reset method:
For P4 protection: Resume automatically.
For H6 protection: Manually restart.

Possible causes
 Outdoor unit stop valves are closed.  Insufficient refrigerant.  System contains air or nitrogen.
 Temperature sensor/switch not connected  System blockage.  Poor condenser heat exchange.
properly or has malfunctioned.  Indoor load too large.  Main PCB damaged.

Procedure

P4 / H6

ODU stop valves are closed Yes Open the stop valves

No

Compressor top temperature sensor and


Yes Ensure the sensors and switch are
discharge pipe temperature sensor
connected properly
connections on main PCB are loose1
No

Compressor top temperature sensor


and/or discharge pipe temperature Yes Replace the faulty sensor(s)
sensor have short circuited or failed2
No
Flowchart continued on next page …

… flowchart continued from previous page

97
Insufficient refrigerant caused by Yes Add refrigerant and inspect the system
refrigerant leakage3 for leaks
No

Inspect the system and fix the error. If the


The system is blocked, caused by crushed Yes filter is blocked by ice, the piping should
or bent pipe, blocked EXV or dirty filter4
be cleaned
No

Yes Make sure the combination ratio is less


The indoor load is too large5
than 130%
No

Flush all refrigerant then vacuum the


System contains air or nitrogen6 Yes system and recharge refrigerant. Add oil
to the system if it leaks
No

The condenser heat exchange is poor7 Yes Inspect the system and fix the error

No

Replace outdoor main PCB

Notes:
1. Compressor top temperature sensor and discharge pipe temperature sensor connections are ports CN4 and CN5 on the main PCB (labeled 3 and 4,
respectively, in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Table 6-3.2 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”.
3. An insufficiency of refrigerant causes compressor discharge temperature to be higher than normal, discharge and suction pressures to be lower than
normal and compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. These issues disappear once sufficient
refrigerant has been charged into the system. For normal system parameters refer to Table 6-3.4 in Part 6, 3.2 “Normal Operating Parameters of
Refrigerant System”.
4. A low pressure side blockage causes compressor discharge temperature to be higher than normal, suction pressure to be lower than normal and
compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. For normal system parameters refer to Table 6-3.4 in
Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
5. An indoor load that is too large causes suction and discharge temperatures to be higher than normal. For normal system parameters refer to Table 6-3.4 in
Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
6. Air or nitrogen in the system causes discharge temperature to be higher than normal, discharge pressure to be higher than normal, compressor current to
be higher than normal, abnormal compressor noise and an unsteady pressure meter reading. For normal system parameters refer to Table 6-3.4 in Part 6,
3.2 “Normal Operating Parameters of Refrigerant System”.
7. In cooling mode check outdoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check indoor heat exchangers, fans and air outlets
for dirt/blockages.

98
2.20 P5: Outdoor heat exchanger temperature protection
Digital display output

Description
 Outdoor heat exchanger temperature protection.
 All units stop running.
 Error code is only displayed on the unit with the error.

Trigger / recover condition


 Trigger condition: Outdoor heat exchanger temperature (T3) ≥ 65oC.
 Recover condition: Outdoor heat exchanger temperature (T3) < 55 oC.
 Reset method: Resume automatically.

Possible causes
 Outdoor unit stop valves are closed.
 Temperature sensor not connected properly or has malfunctioned.
 Indoor load too large.
 System contains air or nitrogen.
 Poor condenser heat exchange.
 High pressure side blockage.
 Main PCB damaged.

99
Procedure

P5

ODU stop valves are closed Yes Open the stop valves

No

Outdoor heat exchanger temperature Yes Ensure the sensor is connected properly
sensor connection on main PCB is loose1
No

Outdoor heat exchanger temperature Yes Replace the sensor


sensor has short-circuited or failed2
No

Yes Make sure the combination ratio is less


The indoor load is too large3
than 130%
No

Flush all refrigerant then vacuum the


System contains air or nitrogen4 Yes system and recharge the refrigerant. Add
oil to the system if it leaks
No

The condenser heat exchange is poor5 Yes Inspect the system and fix the error

No

The high pressure side is blocked, caused Yes Inspect the system and fix the error
by crushed or bent pipe or blocked EXV6
No

Replace outdoor main PCB

Notes:
1. Outdoor heat exchanger temperature sensor connection is port CN1 on the main PCB (labeled 11 in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Table 6-3.1 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”
3. An indoor load that is too large causes suction and discharge temperatures to be higher than normal. For normal system parameters refer to Table 6-3.4 in
Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
4. Air or nitrogen in the system causes discharge temperature to be higher than normal, discharge pressure to be higher than normal, compressor current to
be higher than normal, abnormal compressor noise and an unsteady pressure meter reading. For normal system parameters refer to Table 6-3.4 in Part 6,
3.2 “Normal Operating Parameters of Refrigerant System”.
5. In cooling mode check outdoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check indoor heat exchangers, fans and air outlets
for dirt/blockages.
6. High pressure side blockage causes discharge temperature to be higher than normal, discharge pressure to be higher than normal and suction pressure to
be lower than normal. For normal system parameters refer to Table 6-3.4 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.

100
2.21 xP9, xH9: Fan module protection
Digital display output

;
'x' is a placeholder for the fan motor system (fan motor and related electrical components), with 1 representing fan motor
system A and 2 representing fan motor system B.

Description
 Fan module protection.
 All units stop running.
 Error code is only displayed on the unit with the error.

Trigger / recover condition


 Trigger condition:
For P9 protection: Fan speed is too low.
For H9 protection: P9 protection appears ten times in 120 minutes.
 Recover condition: Fan speed go back to normal.
 Reset method:
For P9 protection: Resume automatically; For H9 protection: Manually restart.

Possible causes
 Switch ENC2 incorrectly set.
 Power or communication wires not connected properly.
 Fan motor blocked or has failed.
 Power supply abnormal.
 AC filter board damaged.
 Fan module damaged.
 Main PCB damaged.

Procedure

xP9 / xH9

The capacity set on switch ENC2 on the Ensure the setting on switch ENC2
main PCB and the capacity given on the matches the unit capacity given on the
unit’s nameplate do not match unit’s nameplate
No

Some power wires or communication


Yes Ensure power and communication wires
wires of fan module are not connected
are connected properly
properly
No

101
… flowchart continued from previous page

Yes Remove obstruction or replace the fan


The fan motor is blocked or has failed
motor
No

The power supply is abnormal Yes Check the power supply equipment

No

Voltage between P and N on fan module Yes Replace AC filter board


is abnormal1
No

Replacing the fan module resolves the


error
No

Replace outdoor main PCB

Notes:
1. The normal voltage between P and N on the fan module is 540V DC.

Figure: Fan module P N terminals

102
2.22 PL, C7: Inverter module temperature protection
Digital display output

'x' is a placeholder for the compressor system (compressor and related electrical components), with 1 representing
compressor system A and 2 representing compressor system B.

Description
 1PL indicates inverter module A temperature protection.
 2PL indicates inverter module B temperature protection.
 All units stop running.
 Error code is only displayed on the unit with the error.

Trigger / recover condition


 Trigger condition:
For PL protection: Inverter module heat sink temperature (TF1/2) ≥ 80oC.
For C7 protection: PL protection appears three times in 100 minutes.
 Recover condition: Inverter module heat sink temperature (TF1/2) < 65oC
 Reset method:
For PL protection: Resume automatically.
For C7 protection: Manually restart.

Possible causes
 Blocked, dirty or loose heat sink.
 Temperature sensor not connected properly or has malfunctioned.
 Main PCB damaged.

103
Procedure

PL / C7

The inverter module heat sink is blocked Yes Clean or replace the heat sink
or dirty
No

The screws connecting the heat sink to Yes Tighten the screws and make sure the
the inverter module are loose heat sink is well-connected
No

Inverter module temperature sensor Yes Ensure the sensor is connected properly
connection on main PCB is loose1
No

Inverter module temperature sensor has Yes Replace the sensor


short circuited or failed2
No

Replace outdoor main PCB

Notes:
1. Inverter module temperature sensor connection is port CN3 and CN3_1 on the main PCB (labeled 5 and 6, respectively, in Figure 5-2.1 in Part 5, 2.1
“Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Table 6-3.3 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”.

104
2.23 PP: Compressor discharge insufficient superheat protection
Digital display output

Description
 Compressor discharge insufficient superheat protection.
 All units stop running.
 Error code is only displayed on the unit with the error.

Trigger / recover condition


 Trigger condition: Discharge gas superheat is ≤ 0oC for 20 minutes or ≤ 5oC for 60 minutes.
 Recover condition: Discharge gas superheat go back to normal value.
 Reset method: Resume automatically.

Possible causes
 Temperature sensor not connected properly or has malfunctioned.
 Poor temperature sensor heat insulation.
 Excess refrigerant.
 Discharge pressure too high.
 Main PCB damaged.

105
Procedure

PP

Compressor top temperature sensor


and/or discharge pipe temperature Yes Ensure the sensors are connected
sensor connections on main PCB are properly
loose1
No

Compressor top temperature sensor


and/or discharge pipe temperature Yes Replace the faulty sensor(s)
sensor have short circuited or failed2
No

Poor heat insulation of compressor top


temperature sensor resulting in Yes Ensure sufficient heat insulation for
temperature reading lower than actual compressor top temperature senor
temperature
No

Yes Discharge part of the refrigerant. Add oil


Excess refrigerant3
if it leaks during discharge
No

Discharge pressure is too high Yes Troubleshoot as for a P1 error4

No

Replace outdoor main PCB

Notes:
1. Compressor top temperature sensor and discharge pipe temperature sensor connections are ports CN4 and CN5 on the main PCB (labeled 3 and 4,
respectively, in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Table 6-3.2 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”.
3. Excess refrigerant causes discharge temperature to be lower than normal, discharge pressure to be higher than normal and suction pressure to be higher
than normal. For normal system parameters refer to Table 6-3.4 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
4. See “P1 Troubleshooting”.

106
3 Appendix to Part 6
3.1 Temperature Sensor Resistance Characteristics
Table 6-3.1: Outdoor ambient temperature sensor and outdoor heat exchanger temperature sensor resistance characteristics
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance
(°C) (kΩ) (°C) (kΩ) (°C) (kΩ) (°C) (kΩ)
-20 115.3 20 12.64 60 2.358 100 0.6297
-19 108.1 21 12.06 61 2.272 101 0.6115
-18 101.5 22 11.50 62 2.191 102 0.5939
-17 96.34 23 10.97 63 2.112 103 0.5768
-16 89.59 24 10.47 64 2.037 104 0.5604
-15 84.22 25 10.00 65 1.965 105 0.5445
-14 79.31 26 9.551 66 1.896 106 0.5291
-13 74.54 27 9.124 67 1.830 107 0.5143
-12 70.17 28 8.720 68 1.766 108 0.4999
-11 66.09 29 8.336 69 1.705 109 0.4860
-10 62.28 30 7.971 70 1.647 110 0.4726
-9 58.71 31 7.624 71 1.591 111 0.4596
-8 56.37 32 7.295 72 1.537 112 0.4470
-7 52.24 33 6.981 73 1.485 113 0.4348
-6 49.32 34 6.684 74 1.435 114 0.4230
-5 46.57 35 6.400 75 1.387 115 0.4116
-4 44.00 36 6.131 76 1.341 116 0.4006
-3 41.59 37 5.874 77 1.291 117 0.3899
-2 39.82 38 5.630 78 1.254 118 0.3796
-1 37.20 39 5.397 79 1.2133 119 0.3695
0 35.20 40 5.175 80 1.174 120 0.3598
1 33.33 41 4.964 81 1.136 121 0.3504
2 31.56 42 4.763 82 1.100 122 0.3413
3 29.91 43 4.571 83 1.064 123 0.3325
4 28.35 44 4.387 84 1.031 124 0.3239
5 26.88 45 4.213 85 0.9982 125 0.3156
6 25.50 46 4.046 86 0.9668 126 0.3075
7 24.19 47 3.887 87 0.9366 127 0.2997
8 22.57 48 3.735 88 0.9075 128 0.2922
9 21.81 49 3.590 89 0.8795 129 0.2848
10 20.72 50 3.451 90 0.8525 130 0.2777
11 19.69 51 3.318 91 0.8264 131 0.2708
12 18.72 52 3.192 92 0.8013 132 0.2641
13 17.80 53 3.071 93 0.7771 133 0.2576
14 16.93 54 2.959 94 0.7537 134 0.2513
15 16.12 55 2.844 95 0.7312 135 0.2451
16 15.34 56 2.738 96 0.7094 136 0.2392
17 14.62 57 2.637 97 0.6884 137 0.2334
18 13.92 58 2.540 98 0.6682 138 0.2278
19 13.26 59 2.447 99 0.6486 139 0.2223

107
Table 6-3.2: Compressor top temperature sensor and discharge pipe temperature sensor resistance characteristics
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance
(°C) (kΩ) (°C) (kΩ) (°C) (kΩ) (°C) (kΩ)

-20 542.7 20 68.66 60 13.59 100 3.702


-19 511.9 21 65.62 61 13.11 101 3.595
-18 483.0 22 62.73 62 12.65 102 3.492
-17 455.9 23 59.98 63 12.21 103 3.392
-16 430.5 24 57.37 64 11.79 104 3.296
-15 406.7 25 54.89 65 11.38 105 3.203
-14 384.3 26 52.53 66 10.99 106 3.113
-13 363.3 27 50.28 67 10.61 107 3.025
-12 343.6 28 48.14 68 10.25 108 2.941
-11 325.1 29 46.11 69 9.902 109 2.860
-10 307.7 30 44.17 70 9.569 110 2.781
-9 291.3 31 42.33 71 9.248 111 2.704
-8 275.9 32 40.57 72 8.940 112 2.630
-7 261.4 33 38.89 73 8.643 113 2.559
-6 247.8 34 37.30 74 8.358 114 2.489
-5 234.9 35 35.78 75 8.084 115 2.422
-4 222.8 36 34.32 76 7.820 116 2.357
-3 211.4 37 32.94 77 7.566 117 2.294
-2 200.7 38 31.62 78 7.321 118 2.233
-1 190.5 39 30.36 79 7.086 119 2.174
0 180.9 40 29.15 80 6.859 120 2.117
1 171.9 41 28.00 81 6.641 121 2.061
2 163.3 42 26.90 82 6.430 122 2.007
3 155.2 43 25.86 83 6.228 123 1.955
4 147.6 44 24.85 84 6.033 124 1.905
5 140.4 45 23.89 85 5.844 125 1.856
6 133.5 46 22.89 86 5.663 126 1.808
7 127.1 47 22.10 87 5.488 127 1.762
8 121.0 48 21.26 88 5.320 128 1.717
9 115.2 49 20.46 89 5.157 129 1.674
10 109.8 50 19.69 90 5.000 130 1.632
11 104.6 51 18.96 91 4.849
12 99.69 52 18.26 92 4.703
13 95.05 53 17.58 93 4.562
14 90.66 54 16.94 94 4.426
15 86.49 55 16.32 95 4.294
16 82.54 56 15.73 96 4.167
17 78.79 57 15.16 97 4.045
18 75.24 58 14.62 98 3.927
19 71.86 59 14.09 99 3.812

108
Table 6-3.3: Inverter module temperature sensor resistance characteristics
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance
(°C) (kΩ) (°C) (kΩ) (°C) (kΩ) (°C) (kΩ)

-30 971.4 10 109.0 50 19.70 90 5.000


-29 912.8 11 103.9 51 18.97 91 4.855
-28 858.2 12 99.02 52 18.26 92 4.705
-27 807.3 13 94.44 53 17.59 93 4.566
-26 759.7 14 90.11 54 16.94 94 4.431
-25 715.3 15 86.00 55 16.32 95 4.301
-24 673.6 16 82.09 56 15.73 96 4.176
-23 634.7 17 78.38 57 15.16 97 4.055
-22 598.2 18 74.87 58 14.62 98 3.938
-21 564.1 19 71.53 59 14.10 99 3.825
-20 532.2 20 68.36 60 13.60 100 3.716
-19 502.2 21 65.34 61 13.12 101 3.613
-18 474.1 22 62.47 62 12.65 102 3.514
-17 447.7 23 59.75 63 12.22 103 3.418
-16 423.0 24 57.17 64 11.79 104 3.326
-15 399.8 25 54.71 65 11.39 105 3.235
-14 378.0 26 52.36 66 10.99 106 3.148
-13 357.5 27 50.13 67 10.62 107 3.063
-12 338.2 28 48.01 68 10.25 108 2.982
-11 320.1 29 45.99 69 9.909 109 2.902
-10 303.1 30 44.07 70 9.576 110 2.826
-9 287.1 31 42.23 71 9.253 111 2.747
-8 272.0 32 40.48 72 8.947 112 2.672
-7 257.8 33 38.81 73 8.646 113 2.599
-6 244.4 34 37.23 74 8.362 114 2.528
-5 231.9 35 35.71 75 8.089 115 2.460
-4 220.0 36 34.27 76 7.821 116 2.390
-3 208.7 37 32.89 77 7.569 117 2.322
-2 198.2 38 31.58 78 7.323 118 2.256
-1 188.2 39 30.33 79 7.088 119 2.193
0 178.8 40 29.13 80 6.858 120 2.132
1 169.9 41 27.98 81 6.640 121 2.073
2 161.5 42 26.89 82 6.432 122 2.017
3 153.6 43 25.85 83 6.230 123 1.962
4 146.1 44 24.85 84 6.033 124 1.910
5 139.1 45 23.90 85 5.847 125 1.859
6 132.3 46 22.98 86 5.667
7 126.0 47 22.10 87 5.492
8 120.0 48 21.26 88 5.322
9 114.3 49 20.47 89 5.159

109
3.2 Normal Operating Parameters of Refrigerant System
Under the following conditions, the operating parameters given in Tables 6-3.4 should be observed:
 The master outdoor unit can detect all the indoor units.
 The number of indoor units displayed on DSP2 is steady and is equal to the actual number of indoor units installed.
 All stop valves are open and all indoor unit EXVs are connected to their unit’s PCB.
 If the combination ratio is 100% or less, all the indoor units are currently running and if the combination ratio is more
than 100%, indoor units with total capacity equal to the total capacity of the outdoor units are currently running.
 The system is being run in cooling mode with the following settings: temperature 17°C; fan speed high.
 The system has been running normally for more than 30 minutes.

Table 6-3.4: Outdoor unit cooling mode operating parameters


Outdoor ambient temperature °C < 10 10 to 26 26 to 31 31 to 41 > 41
Discharge temperature °C 60-76 62-78 65-82 67-92 69-92
Discharge superheat °C 17-30 17-33 17-34 17-36 10-32
Discharge pressure MPa 2.3-2.8 2.3-2.8 2.4-3.6 2.6-3.8 3.1-4.2
Suction pressure MPa 0.6-0.7 0.7-0.9 0.8-1.0 1.0-1.2 1.2-1.4

110

You might also like