Data Sheet
FieldIT
PF 900-NR Power Feed Module
Features and Benefits
■ 24 V DC supply voltage
■ Supply current ≤ 4 A
■ Bus access via terminals
■ Redundant supply
■ Fault signal output with adjustable
mode of operation
■ EMC acc. to NAMUR NE 21
Function
The power feed module supplies the Power Rail with a voltage of
24 V DC and a maximum current of 4 A.
FieldIT PF 900-NR Power Feed Module
Functionality
General
The power feed module supplies the Power Rail with a voltage of 24 V DC and a maximum current of 4 A.
The dual designed power feed terminals 8+ and 11+ or 9- and 12- have the ability to loop the supply (up to a
max. of 10 A). The integrated fault evaluation detects shorts and possible collective error messages. In a
fault condition, the relays switch closed (terminals 7 and 10) and the fault is indicated by means of a red
LED on the front panel. The mode of operation can be adjusted with a plug-in jumper. The terminals 13 and
15 are for the bus connection (only with Power Rail PR 900-N). The terminal 14 is the measuring point for
the collective error message (only planned for inspection or test, may not be wired into the system).
Power feed module 1 Power feed module 2
Power Rail
Power supply 1 Power supply 2
Two power feed modules can be used on a Power Rail as a redundant supply through the reverse diode "R".
Connection
Supply Bus
8+ 11+ 9- 12- 13 14 15
4A
R
green
≥1
red
1
I II
+ -
7 10
Output Power Fault
supply signal
Bus
Power Rail
2 3BDD011868R101
FieldIT PF 900-NR Power Feed Module
Indicating and operating elements
Front view
Dimensions
Adjustment of the jumpers
115
Width = 20 mm
114.5
Power Rail supply and bus
I 1
II
The jumper is visible on the circuit board after removing the cover and the left component.
The mode of operation can be adjusted with a jumper (see connection diagram).
3BDD011868R101 3
FieldIT PF 900-NR Power Feed Module
Technical data
Connection terminals 11+, 12-
terminals 8+, 9-
Rated voltage 20 ... 30 V DC
Supply
The maximum rated operational voltage of the devices plugged
onto the Power Rail must not be exceeded.
Power loss 2.4 W
Power Rail feed output current: ≤ 4 A
Fault signal relay output: NO (normally open)
Output
Contact loading 24 V AC, 1 A/ 24 V DC, 1 A
Energised/De-energised delay approx. 20 ms / approx. 20 ms
Conformity Protection degree IEC 60529
Ambient temperature -25 ... 50 °C (248 ... 323 K)
Storage temperature -40 ... 85 °C (233 ... 358 K)
Ambient conditions
Relative humidity < 95 % non-condensing
Degree of soiling max. 2, according to IEC 60664
Protection degree IP20
Mass approx. 100 g
Mechanical Dimensions 20 x 118 x 115 mm (0.8 x 4.6 x 4.5 in)
specifications Connection type terminals
Core cross-section up to 2.5 mm2
Mounting DIN rail mounting
For more information on FieldIT, contact us at [email protected]
For the latest information on ABB visit us on the World Wide Web at http://www.abb.com
3BDD011868R101 Printed in Germany June 2005
Copyright © 2005 by ABB, All Rights Reserved
® Registered Trademark of ABB
™ Trademark of ABB
Automation Technologies Automation Technologies Automation Technologies
Wickliffe, Ohio, USA Västerås, Sweden Mannheim, Germany
http://www.abb.com/controlsystems http://www.abb.com/controlsystems http://www.abb.de/controlsystems
email:
[email protected] email:
[email protected] email:
[email protected]