Session 2 Cooling Systems
Cooling Systems
Session 2 Cooling Systems
Nominal Capacity: 300 GPM
300 300 300
N= 300 GPM NN+2N
+N1:
1=300
300GPM,
GPM,Redundant
Redundant
(gallons per minute)
150 150 150 150 150
N + 1= 300 GPM, Redundant
Basic Redundant
22
Session 2 Cooling Systems
Single Distribution Path
Basic
Capacity
N= 300 GPM
Redundant
Components
Session 2 Cooling Systems
Redundant Distribution Path
Concurrently
Maintainable
N= 300 GPM
23
Session 2 Cooling Systems
Redundant Distribution Path
A A A A A A
Fault
Tolerant
N= 300 GPM
A A A A A A
au·ton·o·mous: (adj.) Not controlled by others or outside forces; independent
Session 2 Cooling Systems
Compromised Distribution Path
A A A A A A
Basic
Capacity
N= 330 GPM
A A A A A A
24
Session 2 Cooling Systems
Valves are a Risk
• A common “rule of
thumb” is to avoid
valves whenever
possible
› Engineers for nuclear
power plants and
submarines minimize
valves where possible
• Both nuclear plants and
submarines are shut
down for an extended
period on a regular
basis for maintenance
(Tier II equivalent)
Tier III and Tier IV data centers are NOT shut down on
a regular basis for maintenance!
Session 2 Cooling Systems
Dual Distribution Path
Concurrently
Maintainable
N= 300 GPM
System A System B
25
Session 2 Cooling Systems
Dual Distribution Path
Compartmentalization
Fault
Tolerant
N= 300 GPM
System A System B
Session 2 Cooling Systems
Basic Capacity (Tier I)
Computer Room Cooling
26
Session 2 Cooling Systems
Redundant Components (Tier II)
Computer Room Cooling
Session 2 Cooling Systems
Concurrently Maintainable (Tier III)
Computer Room Cooling
27
Session 2 Cooling Systems
Concurrently Maintainable (Tier III)
Computer Room Cooling
Session 2 Cooling Systems
Concurrently Maintainable (Tier III)
Computer Room Cooling
Concurrently Maintainable Dual-Coil
28
Session 2 Cooling Systems
Concurrently Maintainable (Tier III)
Computer Room Cooling
Concurrently Maintainable 4-Pipe
Session 2 Cooling Systems
Fault Tolerant (Tier IV)
Computer Room Cooling
29
Session 2 Cooling Systems
Fault Tolerant (Tier IV)
Chilled Water Distribution
• The topology may look like Tier III solutions
• Tier IV must autonomously respond to failures— such as leaky
valves or fittings—to prevent further impact to the site
• Compartmentalization of chilled water pipes and control
elements outside the computer room is required
Session 2 Cooling Systems
Concurrently Maintainable (Tier III)
Chilled Water System
30
Session 2 Cooling Systems
Fault Tolerant (Tier IV)
Chilled Water System
Session 2 Cooling Systems
Tie Valves in a Chilled Water System
Compliant
31
Session 2 Cooling Systems
Glycol Systems
CRAC CRAC CRAC
Session 2 Cooling Systems
Glycol System Tier Progression
Basic Capacity N Components
CRAC
32
Session 2 Cooling Systems
Glycol System Tier Progression
Redundant
Components CRAC CRAC N+1 Components
Session 2 Cooling Systems
Glycol System Tier Progression
Concurrently
Maintainable CRAC CRAC N+1 Components
33
Session 2 Cooling Systems
Glycol System Tier Progression
Add Capacity
Larger Capacity
Pumps
Concurrently
Maintainable CRAC CRAC CRAC N+1 Components
Session 2 Cooling Systems
Split-System CRAC Cooling
• Avoids issues of multiple
valves and piping systems
• Integrity of power sources
is a significant design and
Certification consideration
(Session 3)
• Ambient (outdoor) design
temperatures have a large
affect on capacity (Session
5) CRAC CRAC
• Continuous Cooling,
required for
Tier IV, has proven difficult
to achieve
34
Session 2 Cooling Systems
Continuous Cooling
• Continuous Cooling is the capability to maintain steady state in
the critical environments without site power until the mechanical
system is providing rated cooling at the extreme ambient
conditions
> Computer rooms, network rooms, UPS rooms. . .
• To complement uninterrupted power for IT devices
• Continuous Cooling is required to meet Tier IV criteria
> Part of the Uptime Institute Tier Standard
Session 2 Cooling Systems
Why Continuous Cooling?
• Provides IT devices thermal stability without site power until the
mechanical system is providing rated cooling to the IT devices at
the extreme ambient conditions
• Lockouts occur frequently
› Chillers/CRACs /Switchgear relays
› Consider a UPS battery plant is often designed for 15 minutes or more
• “Normal” Sequence of Operations can take several minutes
› Programmed engine-generator start delay
› Start and parallel sequence
› Switchgear transfer
› Chiller or CRAC restart sequence
35
Session 2 Cooling Systems
Continuous Cooling Case Study
ASHRAE 2011 Recommendations
• Recommended operating envelope for IT equipment
› Temperature
64.4‒80.6°F dry bulb
(18‒27°C)
› Temperature Rate-of-Change
9°F per hour
(5°C)
› Moisture
≤ 60% relative humidity (RH) and
41.9‒59°F dew point
(5.5‒15°C)
Session 2 Cooling Systems
Continuous Cooling Case Study
ASHRAE 2015 Recommendations
• Recommended operating envelope for IT equipment
› Temperature
64.4‒80.6°F dry bulb
(18‒27°C)
› Temperature Rate-of-Change
32°F per hour
(20°C, but no more than 5°C in any 15 minutes)
› Moisture
≤ 60% relative humidity (RH) and
15.8‒59°F dew point
(-9°C – 15°C)
36
Session 2 Cooling Systems
Temperature Rate-of-Change Test
Test Protocol
• Steady state configuration and conditions
› Load = 250 cabinets at 6 kW average or 1,500 kW
› Temperature sensors indicate ≤ 80°F (27°C)
› Power and cooling system normal
• Shut down all (14) CRAH units
• Record temperature rate-of-rise to 90°F (32°C)
• Recover
Session 2 Cooling Systems
Temperature Rate-of-Change Results
• First Data Point ~ 1 Minute
› Temperature sensor at 7 feet AFF = 90°F (32°C)
› Temperature sensor at ceiling = 110°F (43°C)
Owner aborts test!
• Last Data Point ~ 20 Minutes
› Temperature sensor at 7 feet AFF returns to 78°F (25.5°C)
37
Session 2 Cooling Systems
Tier IV Continuous Cooling
• Cooling technology drives the solution
• Requires, as appropriate for cooling solution
> Uninterruptible power for cooling fans
> Uninterruptible power secondary chilled water pumps or glycol system
pumps
> Thermal storage or uninterruptible refrigeration
• Uninterruptible CRAC-based Continuous Cooling is conceivable
Session 2 Cooling Systems
Noncritical Functions
• Some facility infrastructure components do not directly impact
availability of critical environments
• These systems may be isolated on failure or for maintenance for
extended periods
• Duration of “extended period” is equivalent to on-site stores of
engine-generator fuel and makeup water
38
Session 2 Cooling Systems
Common Noncritical Functions
• Building pressurization (makeup air systems)
• Humidification
• Fuel polishing (fuel storage filtration systems)
• Reverse-osmosis systems
• “Free cooling” or economizer systems
• Building automation (Tier I, Tier II, Tier III)
• Support area comfort HVAC
• Battery room ventilation
Session 2 Cooling Systems
Unintended Impacts
• Noncritical system connections to critical systems may create
noncompliant topology
• Cautions
∅ Chilled water connections for building air handlers
∅ Free cooling heat exchanger integration
∅ Fuel polishing system isolation
39
Session 2 Cooling Systems
Utility Sources
• Tier I‒IV data center systems must be able to autonomously
respond to a loss of external cooling generation, such as district
cooling
• This is similar to how engine generators must be able to
autonomously respond to loss of utility power from the grid
Session 2 Cooling Systems
Cooling Systems Recap
• Chilled water and glycol systems require careful attention to
piping and valve configurations
• Direct expansion (DX) systems simplify (avoid) piping
challenges, but require careful attention to power and
Continuous Cooling solutions
• Integration of noncritical systems can create
Concurrent Maintainability and Fault Tolerance discrepancies
40