Diode Block
Diode Block
ize
p a ct S
Power Supply Input P-0R-24-20-S1 Com 8 mm
4
ize
p a ct S
Com 8 mm
4
SCREW CONNECTOR TYPE
DIODE BLOCK UNIT
ize
p a ct S
Power Supply Input P-0R-24-20-S3 Com 8 mm
4
ize
p a ct S
Com 8 mm
4
SCHEMATIC BLOCK DIAGRAM TO USE DIODE BLOCK
FOR BOTH DETACHABLE & SCREW TYPE CONNECTOR
NC CO NC CO
1 2 3 4
INPUT INPUT
SUPPLY-A SUPPLY-B
+ +
+VE -VE
POWER POWER
SUPPLY-A SUPPLY-B
-VE +VE
+VE
+VE
-VE
-VE
TO LOAD
This Diode Block Unit has one Seriers diode in the +ve & ve supply line in the unit. This isolates both +ve & -ve Power
Supply lines with the other power supplies.
To create power supply redundancy through these units the output of each of power supply is connected at the input
of each of these Diode Block Unit with right ploarity & output from these units are connected in parallel i.e +ve
terminal to +ve terminal & -ve terminal to -ve terminal at the output of each Diode Block Unit.
PI. Note: One Diode Block Unit is required for each one of the power supplies. There are two types of diode block
available screw type connector & Detachable type connector.
OR-ING DIODE BLOCK
SCREW TYPE
General Information
The OR-ING unit combines two or more power sources to create
redundant power source preserving the output power supply in case
one of the input sources fails. In this situation of input power failure,
the next power supply feeds the power quickly to prevent the system
bus voltage from failing and bus collapse. The power supply failure
signal is given by relay N/C contact
Overload - 10%max.
Drop - 0.65 volts max DC at 20A
R1
Input
PS1
Indicators :
Input power supply - 1 green LED for each power supply
Output power supply - 1 green LED for output
output - 1N/C Relay Contact
Rated 5A @ 24VDC & 5A @ 230VAC in
case of failure of any one of the Input
35
power supply
131
Conductor cross section - 0.2-4.02mm solid
0.2-2.52solid
AWG 24-12
NO CO NC
NO CO NC
24 VDC.40
OUTPUT
INPUT
24 VDC
168
14
20
Approvals
OR-ING DIODE BLOCK
SCREW TYPE
Model No.: P-OR-24-5-S3
Model No.: P-OR-24-10-S3
Model No.: P-OR-24-20-S3
General Information
The OR-ING unit combines two or more power sources to create
redundant power source preserving the output power supply in case
one of the input sources fails. In this situation of input power failure,
the next power supply feeds the power quickly to prevent the system
bus voltage from failing and bus collapse. The power supply failure
signal is given by relay N/C contact
Overload - 10%max.
Drop - 0.65 volts max DC at 5A,10A & 20A
R1
131
Output
Indicators :
Input power supply - 1 green LED for each power supply
Output power supply - 1 green LED for output
35 output - 1N/C Relay Contact
131 Rated 5A @ 24VDC & 5A @ 230VAC in
case of failure of any one of the Input
power supply
NO CO NC
NO CO NC
POWER SUPPLY
24 VDC.10A
OUTPUT
INPUT
24 VDC
14
48
20
Approvals
OR-ING DIODE BLOCK
DETACHABLE TYPE
Model No.:P-0R-24-05-S1
Model No.:P-0R-24-10-S1
Model No.:P-0R-48-05-S1
Model No.:P-0R-48-10-S1
General Information
The Diode Block unit comprises of power supply isolating diodes in
positive and negative supply lines of the input power supply.
for redundancy in the power supply to the control unit the output of two
or more such units are connected in parallel. In the situation where
input to one of the oring unit power supply fails, the next power supply
connected will feed the power quickly to prevent the system bus
voltage from failing and bus collapse. 1N/C relay contact is brought
out from each oring unit for supply failure alarm.
Overload - 10%max.
Drop - 0.65 volts max DC at 5A / 10A
R1
Input
Ps1
Output
Indicators :
Input power supply - 1 green LED for each power supply
Output power supply - 1 green LED for output
35
131 output - 1N/C Relay Contact
Rated 5Amps @ 24VDC/230VAC
incase of failure of the input
power supply.
NO CO
Weight - 0.5Kg.Approx
POWER SUPPLY
24 VDC.10A
OUTPUT
INPUT
24 VDC
14
48
20
Approvals
OR-ING DIODE BLOCK
DETACHABLE TYPE
Model No.:P-0R-24-20-S1
Model No.:P-0R-48-20-S1
General Information
The Diode Block unit comprises of power supply isolating diodes in
positive and negative supply lines of the input power supply.
for redundancy in the power supply to the control unit the output of two
or more such units are connected in parallel. In the situation where
input to one of the oring unit power supply fails, the next power supply
connected will feed the power quickly to prevent the system bus
voltage from failing and bus collapse. 1N/C relay contact is brought
Overload - 10%max.
Drop - 0.65 volts max DC at 20A
R1
Input
PS1
Output
Indicators :
Input power supply - 1 green LED for each power supply
Output power supply - 1 green LED for output
output - 1N/C Relay Contact
Rated 5Amps @ 24VDC/230VAC
35
incase of failure of the input
131
power supply.
NO CO
NO CO
POWER SUPPLY
48
20
Approvals