Ahri 140-2023 (I-P)
Ahri 140-2023 (I-P)
Evaluation of
Air-conditioning and Heating
Equipment Test Stands
©Copyright 2023, by Air-Conditioning, Heating, and Refrigeration Institute
Printed in U.S.A.
IMPORTANT
SAFETY DISCLAIMER
AHRI does not set safety standards and does not certify or guarantee the safety of any products,
components or systems designed, tested, rated, installed or operated in accordance with this
standard/guideline. It is strongly recommended that products be designed, constructed, assembled,
installed, and operated in accordance with nationally recognized safety standards and code requirements
appropriate for products covered by this standard/guideline.
AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted
industry practices. AHRI does not certify or guarantee that any tests conducted under its
standards/guidelines will be non-hazardous or free from risk.
Note:
AHRI Standards are developed independently of AHRI Certification activities and can have scopes that include
products that are not part of the AHRI Certification Program. The scope of the applicable AHRI Certification
Program can be found on AHRI’s website at www.ahrinet.org.
Intent
This standard is intended for the guidance of the industry, including manufacturers, engineers, installers, efficiency
regulators, contractors, and users.
2023 Edition
This edition of AHRI Standard 140-2023 (I-P), Evaluation of Air-conditioning and Heating Equipment Test Stands,
was prepared by the Unitary Small Equipment Standards Technical Committee. The standard was published by the
Unitary Standards Subcommittee on 12 June 2023.
This is the initial publication of AHRI Standard 140-2023 (I-P), Evaluation of Air-conditioning and Heating
Equipment Test Stands. AHRI Standard 140-2023 (I-P) was developed to:
The Unitary Small Equipment (USE) Standards Technical Committee is responsible for the development and
maintenance of AHRI standards and guidelines pertaining to Unitary Air-conditioning and Air-source Heat Pump
Equipment, Mini-Split (1:1) Air-conditioning and Heat Pump Equipment, and Demand Response through Variable
Capacity HVAC Systems in Residential and Small Commercial Applications.
The following product types are out of scope for this STC: Packaged Terminal AC/HP, Commercial or Industrial
AC/HP, Furnaces, Variable Refrigerant Systems (VRF), Geothermal and Water Source HP, Single Package Vertical
Unit (SPVU), and Performance Rating of Zoning products.
The scope of the Unitary Standards Subcommittee is standards and guidelines related to the end products that are part
of the AHRI Unitary Industry Sector. (The definition of and list of products associated with each sector are found on
AHRI’s website.)
These lists represent the membership at the time the Standards Technical Committee and Standards Subcommittee
were balloted on the final text of this edition. Since that time, changes in the membership may have occurred.
Membership on these committees shall not in and of itself constitute an endorsement by the committee members or
their employers of any document developed by the committee on which the member serves.
TABLE OF CONTENTS
PAGE
SECTIONS
FIGURES
TABLES
Section 1. Purpose
1.1 Purpose. The purpose of this standard is to establish for Test Stands: definitions; test requirements; rating
requirements; minimum data requirements for Published Ratings; nomenclature; and conformance conditions.
Section 2. Scope
2.1 Scope. This standard applies to Test Stands used for performance testing for the following equipment types:
1) Unitary Air-conditioning and Air-source Heat Pump Equipment within the scope of AHRI Standard
210/240.
2) Commercial and Industrial Unitary Air-conditioning and Heat Pump Equipment within the scope of
AHRI Standard 340/360.
3) Computer and Data Processing Room Air Conditioners within the scope of AHRI Standard 1360.
4) Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment within the
scope of AHRI Standard 1230.
5) Single Package Vertical Air-conditioners and Heat Pumps within the scope of AHRI Standard 390.
6) Packaged Terminal Air-conditioners and Heat Pumps within the scope of AHRI Standard 310/380.
2.2 Exclusions. Qualification procedures for water-cooled and evaporatively cooled equipment are not covered by
this standard.
Section 3. Definitions
All terms in this document follow the standard industry definitions in the ASHRAE Terminology website unless
otherwise defined in this section.
3.1 Airflow Measurement Apparatus. A device for determining the volume rate of air passing through the UUT.
Commonly referred to as “code tester” within the industry.
3.2 Air Side Capacity Measurement System. The equipment used to determine UUT capacity including inlet
psychrometric air properties, outlet psychrometric air properties, and the Air Flow Measurement Apparatus.
3.3 Baseline Test. A test conducted in accordance with a Reference Rating Standard on a Correlation Sample at a
Reference Test Stand.
3.4 Correlation Sample. A sample with documented performance data from a Reference Test Stand
3.5 Cyclic Test. A test where all or part of the system is turned on and off in a cycle.
3.6 Drain Trap. A plumbing drain fixture designed to retain a small amount of the draining water to seal the pipe
and prevent any gases from flowing through the pipe.
3.7 Electric Heat Box. Test apparatus used to supply a known quantity of heat to the air stream.
1
__________________________________________________________ AHRI Standard 140-2023 (I-P)
3.8 Error. The difference between the true value of the quantity measured or calculated and the observed value.
All errors in experimental data can be classified as one of two types: systematic (fixed) errors or random
(precision) errors. The terms accuracy and precision are often used to distinguish between systematic and
random errors.
3.8.2 Random Error. An error that causes readings to take random values on either side of a mean value. The
random error is quantified based on how well an instrument can reproduce subsequent readings for an
unchanging input. Random errors cannot be corrected through calibration.
3.8.3 Systematic Error. An error that persists and cannot be deemed as due entirely to chance. Systematic error can
be corrected through calibration
3.9 External Static Pressure Drop Verification. The percent difference between the exact coil only ASHRAE duct
configuration baseline pressure and the corresponding test measured value from either conventional or
alternative psychometric testing configuration divided by the corresponding test measured value from either
conventional or alternative psychometric testing configuration.
3.10.1 Latent Heat Balance. The percent difference between the latent heat calculated from the measured condensate
flow rate and the measured psychrometric latent capacity, qlci.
3.10.2 Sensible Heat Balance. The percent difference between the measured psychrometric sensible heat and
measured electric heat added to the system.
3.11 Indoor Blower. The fan used to move air through the indoor side of the UUT.
3.13 Leakage Rate. The volume of air entering or leaving the Test Stand between the UUT outlet connection and
the Nozzle Plate location.
3.14 Measured Airflow Difference. The deviation between two different Air Flow Measurement Apparatus nozzle
size combination readings at the same airflow in CFM.
3.15 Nozzle Chamber. Apparatus containing the air flow measurement nozzles. Part of the Airflow Measurement
Apparatus.
3.16 Nozzle Plate. A plate designed to seal the cross-sectional area of a duct with nozzles attached to allow air to
pass through. Part of the Nozzle Chamber.
3.17 Passive Pressure Drop Device. A custom-built assembly, constructed without internal insulation, sealed to
prevent any external or internal air leakage, and sized to provide a designated external static pressure over a
range of airflow as shown in Appendix C.
3.18 Qualified Facility. A test laboratory that meets all of the requirements of the AHRI Standard 140.
3.19 Reference Rating Standard. The standard used to rate the UUT.
3.20 Reference Test Stand. A Test Stand that has been proven through data collection to provide baseline
measurements.
3.21.1 “Shall” or “shall not”. Indicate mandatory requirements to strictly conform to the standard and where
deviation is not permitted.
2
__________________________________________________________ AHRI Standard 140-2023 (I-P)
3.21.2 “Should” or “should not”. Express recommendations rather than requirements. In the negative form, a
recommendation is the expression that a suggested possible choice or course of action is not preferred but
not prohibited.
3.22 Test Stand. Facility constructed for the purpose of testing or developing ratings in accordance with a Reference
Rating Standard.
3.22.1 Indoor Room. A portion of the facility used to maintain a controlled environment for the indoor test rating
conditions in accordance with the Reference Rating Standard.
3.22.2 Outdoor Room. A portion of the facility used to maintain a controlled environment for the outdoor test rating
conditions in accordance with the Reference Rating Standard.
3.23 Test Type. A specific test within this standard to verify a particular function of the Test Stand. Test Types are
listed in Section 4.
3.24 Uncertainty. An estimated value for the error in a measurement or calculation, that can be the result of both
Systematic and Random Error.
3.25 Unit Under Test (UUT). The Correlation Sample used to validate the Test Stand. Each UUT is rated in
accordance with a Reference Rating Standard.
3.26 Validation. The process of evaluating if a system accomplishes its purpose or intent.
3.27 Verification. The process of determining if a Test Stand is built according to specifications provided in a design,
drawing, statement of work, or other document.
4.1 Test Requirements. All testing shall be conducted in accordance with the test methods and procedures as
described in this standard and its appendices. Each Test Stand is tested in accordance with the Reference Rating
Standard. Refer to Table 1 below for Test Types required per Reference Rating Standard. If the Test Stand is
not able to meet these criteria, adjustments shall be made to resolve the issue.
3
__________________________________________________________ AHRI Standard 140-2023 (I-P)
1. If only one test facility exists, correlate between multiple indoor rooms. Run a complete set of tests with
Room A and Room B. Then repeat the tests by swapping units between Room A and Room B. As an
alternative, if only one room exists completely disassemble and reassemble the setup at a different date. This
will show repeatability.
4.1.1 Data Acquisition. All test data shall be recorded in accordance with Appendix D.
4.1.2 Instrumentation Calibration. All measurement equipment should be calibrated in accordance with Appendix
E.
4.1.3 Uncertainty Analysis. An Uncertainty analysis shall be completed. An example is shown in Appendix F.
5.1 Qualification Requirements. Each Test Stand shall be qualified as defined in Section 5 within the tolerances
shown in Table 2
4
__________________________________________________________ AHRI Standard 140-2023 (I-P)
5.2 Table 2.
5.2.1 Reference Rating Standard. Each Test Stand shall be qualified in accordance with at least one Reference
Rating Standard. Where more than one Reference Rating Standard applies, each Test Stand shall be qualified
separately for each Reference Rating Standard.
5.2.2 Validation Checks. Each Test Stand shall be qualified using the validation checks defined in this Section.
Ratings related to airflow measurement are provided for a specific Airflow Measurement Apparatus.
5.2.2.1 Air Flow Measurement Apparatus Leakage. Test Stand air flow leakage shall be verified for a given Nozzle
Chamber and ductwork configuration by measuring Leakage Rates at the following locations within the
measurement apparatus system:
1) Nozzle Plate
2) Airflow Measurement Apparatus, including all permanent ductwork components from
Nozzle Plate to UUT connection point.
Leakage Rates at each location are established at the target static pressure setpoints
5.2.2.2 Zero Load. Test Stand instrument induced error shall be verified for a given Nozzle Chamber across a range
of airflow by the following:
1) Sensible Error
2) Latent Error
3) Pressure Transducer Zero Error
These deviations are established by comparing the total sensible and latent heat input of the UUT to the
sensible and latent heat measured at a zero-load condition.
5.2.2.3 Air Flow Measurement Apparatus Verification. Test Stand air flow measurement shall be verified for a
given Nozzle Chamber across a range of its nozzle configurations. Airflow measurements are verified by
comparing two different Air Flow Measurement Apparatus nozzle size combinations at the same pressure
drop using the Passive Pressure Drop Device.
5.2.2.4 Sensible Heat Measurement. Test Stand sensible heat measurements shall be verified for a given Capacity
Measurement System by confirming Sensible Heat Balance.
Sensible Heat Balance is verified by comparing the total sensible heat input of the UUT to the sensible
heat measured at Minimum Airflow, Mean of Minimum and Maximum Airflow, and Maximum Airflow.
5.2.2.5 Mixing Efficiency. Test Stand Mixing Efficiency shall be verified by comparing the difference between the
maximum and minimum recorded temperatures on the outlet temperature grid with the difference between
the average outlet and average inlet temperatures.
5.2.2.6 Instrument Induced Humidity Ratio Verification. Instrument induced humidity ratio verification is the
measure of accuracy of the latent measurement equipment during sensible heat measurement tests where
no latent change is expected.
5.2.2.7 Latent Heat Measurement. Test Stand latent heat measurement shall be verified for a given Capacity
Measurement System by confirming the Latent Heat Balance.
Latent Heat Balance is verified by comparing the latent heat calculated from measured air properties
against the latent heat calculated from measured condensate draining from the indoor coil of the system.
5.2.2.8 External Static Pressure Measurement. Test Stand external static pressure measurement shall be verified
by comparing ANSI/ASHRAE Standard 37 duct configurations to ANSI/ASHRAE Standard 116 duct
configurations.
5
__________________________________________________________ AHRI Standard 140-2023 (I-P)
5.2.2.9 Thermal Energy Storage Effect for CD Rating. Test Stand thermal energy storage effect shall be determined
for CD testing by cycling the heater in the Electric Heater Box. The result shall be used in accordance with
Section 9.2 of ANSI/ASHRAE Standard 116.
5.2.2.10 Full System Psychrometric Round Robin Testing. Test Stand overall measurement accuracy shall be
verified by correlation testing with one or more Reference Test Stands
5.2.2.11 Large Unitary Sensible Heat Measurement. Sensible heat measurement specific to Large Unitary devices.
5.2.3 Test Stand Limits of Operation. Test Stand minimum and maximum operational limits, as defined in Table
3, shall be established at the standard rating conditions specified by the Reference Rating Standard.
5.2.4 Uncertainty of Measurement. Uncertainty for all measurements (such as capacity, power, efficiency, pressure
drop) shall be calculated.
6
__________________________________________________________ AHRI Standard 140-2023 (I-P)
7
__________________________________________________________ AHRI Standard 140-2023 (I-P)
- Minimum Power 3% -
Maximum Cooling
- 3% -
Capacity
Maximum Heating
- 3% -
Capacity
- Maximum Power 3% -
6.1 Minimum Data Requirements for Qualified Facilities. Table 3 provides minimum data requirements to publish
Test Stand qualification.
All claims to qualification within the scope of this standard shall include the statement “Qualified in accordance
with AHRI Standard 140 for performance testing in accordance with [Reference Rating Standard].”, where
“[Reference Rating Standard]” shall be replaced by the Reference Rating Standard used to rate the Test Stand in the
following format of [Publisher] [Number]-[Publication Year] [(units)] (for example: AHRI 210/240-2017 (I-P).
All claims to qualifications outside the scope of the standard shall include the statement “Outside the scope of AHRI
Standard ####.”
8
__________________________________________________________ AHRI Standard 140-2023 (I-P)
9
__________________________________________________________ AHRI Standard 140-2023 (I-P)
7.1 Conformance. While conformance with this standard is voluntary, conformance shall not be claimed or implied
for Test Stands within the standard’s Purpose (Section 1) and Scope (Section 2) unless such claims meet all of
the requirements of the standard and all of the testing and qualification requirements are measured and reported
in complete compliance with the standard. Any Test Stand that has not met all the requirements of the standard
cannot reference, state, or acknowledge the standard in any written, oral, or electronic communication.
10
__________________________________________________________ AHRI Standard 140-2023 (I-P)
A1.1. AHRI Standard 210/240-2017 (with Addendum 1), Unitary Air-Conditioning and Air-Source Heat
Pump Equipment, 2019, Air Conditioning, Heating and Refrigeration Institute, 2311 Wilson
Boulevard, Suite 400, Arlington, VA 22201, U.S.A.
A1.2. AHRI 310/380-2017, Packaged Terminal Air-Conditioners and Heat Pumps, 2017, Air
Conditioning, Heating and Refrigeration Institute, 2311 Wilson Boulevard, Suite 400, Arlington,
VA 22201, U.S.A.
A1.3. AHRI 340/360-2019, Performance Rating of Commercial and Industrial Unitary Air-conditioning
and Heat Pump Equipment, 2019, Air Conditioning, Heating and Refrigeration Institute, 2311
Wilson Boulevard, Suite 400, Arlington, VA 22201, U.S.A.
A1.4. AHRI 390-2021 (I-P), Single Package Vertical Air-Conditioners and Heat Pumps, 2021, Air
Conditioning, Heating and Refrigeration Institute, 2311 Wilson Boulevard, Suite 400, Arlington,
VA 22201, U.S.A.
A1.5. AHRI 1230-2021 (I-P), Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat
Pump Equipment, 2021, Air Conditioning, Heating and Refrigeration Institute, 2311 Wilson
Boulevard, Suite 400, Arlington, VA 22201, U.S.A.
A1.6. AHRI 1360-2017, Computer and Data Processing Room Air Conditioners, 2017, Air Conditioning,
Heating and Refrigeration Institute, 2311 Wilson Boulevard, Suite 400, Arlington, VA 22201,
U.S.A.
A1.7. ANSI/ASHRAE Standard 37, 2009 Methods of Testing for Rating Electrically Driven Unitary Air-
Conditioning and Heat Pump Equipment, 2009, American Society of Heating, Refrigerating and
Air-Conditioning Engineers, Inc. 1791 Tullie Circle NE, Atlanta, GA 30329, U.S.A.
A1.8. ANSI/ASHRAE Standard 116, 2010 Methods of Testing for Rating Seasonal Efficiency of Unitary
Air Conditioners and Heat Pumps, 2010, American Society of Heating, Refrigerating and Air-
Conditioning Engineers, Inc. 1791 Tullie Circle NE, Atlanta, GA 30329, U.S.A.
11
__________________________________________________________ AHRI Standard 140-2023 (I-P)
B1.1. ASHRAE Handbook – Fundamentals: 2017, ASHRAE,. 180 Technology Parkway NW, Peachtree
Corners, GA 30092, U.S.A.
B1.2. ASME PTC 19.1-2013, Test Uncertainty, The American Society of Mechanical Engineers, Two
Park Avenue, New York, NY 10016, USA
C2.1. Passive Pressure Drop Device. Construct the assembly as detailed in Table 4 based on the Test
Stand minimum and maximum airflow. A graphical representation of a Passive Pressure Drop
Device is shown in Figure 1.
C2.2. Design of Restriction Plate. The restriction plate can be made with several different hole
combinations. Holes can be covered during testing to achieve required pressure drop.
12
__________________________________________________________ AHRI Standard 140-2023 (I-P)
C2.3. Electric Heat Box. Shall be constructed with low thermal mass wire wound heater elements split
into two sections side by side. Each heater element shall have the capacity to provide a minimum
10°F increase in air temperature at maximum Test Stand airflow. Heater shall be positioned in duct
in such a way as be out of the line of sight of any sensors. See Figure 2. The Electric Heat Box shall
have all joints and seams taped or sealed (internally and externally as required) for all tests to
eliminate air from leaking past the heater.
13
__________________________________________________________ AHRI Standard 140-2023 (I-P)
C3. Test Requirements. All Test Stand tests shall be conducted in accordance with the Reference Rating Standard.
Setup. Specified leakage nozzle shall be sized to measure 1%- 2% of the minimum
air flow.
Procedure.
14
__________________________________________________________ AHRI Standard 140-2023 (I-P)
• Use nozzle, or insert a nozzle plug with a leakage nozzle to allow the CFM
to be measured. See Figure 3.
• If inlet side of the nozzles is not accessible, a cap with a leakage nozzle can
be used. See Figure 4
• Slowly run blower up to the target static pressure setpoint per Table 5 –
minimum 90 seconds duration
• Measure and record the target static pressure setpoint pressure and the
leakage airflow at intervals of no greater than 10 seconds.
• For an additional 90 seconds, measure flow rate through small nozzle.
• Overall system leakage as measured using the small nozzle shall be less
than value specified in Table 2.
15
__________________________________________________________ AHRI Standard 140-2023 (I-P)
Recorded Data. Before nozzle, nozzle delta P, and airflow data shall be recorded for
this Test Type.
16
__________________________________________________________ AHRI Standard 140-2023 (I-P)
Data Analysis. Overall system leakage shall be compared to the Test Stand Minimum
Air Flow as shown in Equation 1.
𝑄𝑙𝑚𝑎𝑥 = 𝑄𝑚𝑖𝑛 ∙ 0.01 1
Where:
Qmin = Test stand minimum airflow rate.
Qlmax = Maximum allowed leakage
Qn = Measured leakage airflow
n = Test points 2, 3, or 4 as defined in Table 5.
Selection of Equipment.
C3.2.1.1. The UUT and Electric Heater Box, or both are not required for
this test. However, if UUT and Electric Heater Box, or both are installed,
these shall be turned off and the UUT drain pan shall be dry.
Setup.
C3.2.2.1. Temperatures. Average inlet and outlet dry bulb and wet bulb
temperatures shall be measured.
Procedure. Only nozzle combinations approved through the Air Flow Measurement
Apparatus Verification shall be used in this test.
C3.2.3.2. Test Type. The Electric Heat Box power supply shall not be
energized.
17
__________________________________________________________ AHRI Standard 140-2023 (I-P)
Recorded Data. Inlet and outlet dry bulb and wet bulb temperatures, airflow, nozzle
delta pressure, before nozzle pressure, and external static pressure.
Selection of Equipment. A Passive Pressure Drop Device shall be used to conduct the
test.
Set up. Passive Pressure Drop Device shall be setup in the Test Stand as if it were a
UUT.
Procedure.
C3.3.3.2. Test Points. The Passive Pressure Drop Device shall be tested,
at the six (6) conditions, show in in Table 7, using the smallest and largest
nozzle combination at each target airflow and static pressure setpoint.
Each test shall be run over a minimum 5-minute period.
18
__________________________________________________________ AHRI Standard 140-2023 (I-P)
Recorded Data. Pressure drop across the Passive Pressure Drop Device, inlet dry
bulb temperature, inlet humidity, inlet barometric pressure, air flow, nozzle delta
pressure, and the nozzle combination.
Data Analysis. Each test (1, 2, or 3) will produce a flow rate measurement for each
nozzle combination (A and B) that shall be compared as shown in Equation 3.
𝑄𝐴 − 𝑄B
∆𝑄𝑛 = [ ] ∙ 100
𝑄A + 𝑄B
2 𝑛
3
Where:
Selection of Equipment. The UUT and Electric Heat Box can be installed for this test.
19
__________________________________________________________ AHRI Standard 140-2023 (I-P)
C3.4.3.2. Electric Heat Box Air Temperature. Over the tested airflow
rates, the voltage to the Electric Heat Box shall be maintained in order to
maintain a stable differential temperature across the Electric Heat Box
between 10⁰F and 20⁰F.
C3.4.3.3.1. During this test, the UUT blower shall not be energized, and the Electric Heat Box
shall be energized. The heater shall be powered to a level that maintains the capacity to
meet the requirements of C3.4.3.2.
The temperature measured by each of the grid thermocouples shall meet the
requirements of Equation 4.
𝑇 = 𝑇𝐴𝑣𝑒𝑟𝑎𝑔𝑒 ± 0.75℉ 4
C3.4.3.4. Test Conditions. The UUT and Electric Heat Box shall be
operated, at the three (3) conditions shown in Table 8.
3. For each test, the Target Airflow shall be selected based on the Test Stand Minimum and Maximum
airflow range.
a. Minimum target is (Test Stand Minimum up to 1.1 * Test Stand Minimum)
b. Maximum target is (Test Stand Maximum down to 0.9 * Test Stand Maximum)
c. Mean target is ((Test Stand Maximum – Test Minimum) / 2) +/- 10%
4. Electric Heat Box power supply shall have a maximum deviation of 100 W per 1000 SCFM measured.
5. The average airflow deviation shall be less than 1.0% or 5 SCFM of target value whichever is greater.
Recorded Data. Electric Heater Power, entering dry bulb temperature, leaving dry
bulb temperature, entering wet bulb temperature, leaving wet bulb temperature, total
capacity, sensible capacity, latent capacity, and airflow.
20
__________________________________________________________ AHRI Standard 140-2023 (I-P)
𝑞𝑠𝑟𝑖 −𝑞𝑡ℎ𝑖
𝐵𝑆𝐻𝑛 = [ ] ∙ 100 5
𝑞𝑠𝑟𝑖 𝑛
Where:
n = Test condition.
𝑞𝑠𝑟𝑖 = 𝐸ℎ ∙ 3.412
Where:
𝐸ℎ = Electric heat 6
Selection of Equipment. The Electric Heat Box shall be constructed in such a way as
to allow one half of the flow to be heated, forcing a temperature differential to be
created side to side. See Figure 5.
21
__________________________________________________________ AHRI Standard 140-2023 (I-P)
Setup.
22
__________________________________________________________ AHRI Standard 140-2023 (I-P)
Recorded Data. Electric Heater Power, inlet thermocouple grid, outlet thermocouple grid, entering
dry bulb temperature, leaving dry bulb temperature, entering wet bulb temperature, leaving wet bulb
temperature, total capacity, sensible capacity, latent capacity, and airflow.
Calculation of Mixing Efficiency. For each mixing test, calculate the efficiency as
shown in Equation 7. Verify the mixing efficiency is between 0 and 0.1.
∆𝑇𝑜𝑢𝑡𝑙𝑒𝑡
𝜂𝑚𝑖𝑥𝑖𝑛𝑔 = 7
𝑇𝑜𝑢𝑡𝑙𝑒𝑡 −𝑇𝑖𝑛𝑙𝑒𝑡
Where:
Selection of Equipment. The UUT and Electric Heat Box can be installed for this test.
Setup.
C3.6.2.1. Methodology. Using the sensible heat test set up to verify the
accuracy of the latent measurement equipment at a zero latent load
condition.
23
__________________________________________________________ AHRI Standard 140-2023 (I-P)
Where:
Informative Note: At an inlet condition of 70⁰F and outlet condition of 82⁰F and
1000 SCFM airflow at 1 atmosphere, a difference at either limit of the
tolerance indicates a wet bulb error of 0.19⁰F.
Selection of Equipment. The cooling system of UUT(s) used to conduct the Sensible
Heat Measurement Test at the Test Stand shall be selected to operate at 80⁰F dry
bulb/67⁰F wet bulb.
Setup.
Procedure. Only setups approved through the Air Flow Measurement Apparatus
Verification shall be used in this test.
C3.7.3.1. Test Points. The UUT shall be tested, at the two conditions,
shown in Table 10.
C3.7.3.2. Condensate Mass Flow Rate. The condensate mass flow rate
draining off of the indoor coil shall be measured for three consecutive
periods for each test.
C3.7.3.2.1. Measurement. At a minimum, measure the weight or volume at the beginning and
at the end of each individual test (± 10 seconds). Calculate the difference and divide it by
the total time to obtain the condensate mass flow rate in lbs/hr.
C3.7.3.2.2. Stability Criteria. Single test condensate mass flow rate shall be with ± 6% of the
mean of all three consecutive periods for each test.
24
__________________________________________________________ AHRI Standard 140-2023 (I-P)
Full-load cooling
Mean of Minimum and
Lowest setting at standard rating
1 Maximum total
test condition. condition Reference
capacity ± 25%
Rating Standard
Notes:
1. Thetest shall be run over three (3) consecutive minimum 10-minute
periods.
Recorded Data. Entering and leaving dry bulb and wet bulb temperatures, air flow
rate, and condensate flow rate shall be recorded.
Data Analysis.
C3.7.5.1. Latent Heat Balance. Calculate the Latent Heat Balance based
on the measured condensate flow rate, 𝑤𝑐 and measured latent capacity,
𝑞𝑙𝑐𝑖 using Equation 9:
𝑞𝑙𝑐𝑐 − 𝑞𝑙𝑐𝑖
𝐵𝐿𝐻 𝑛 = [ ] ∙ 100 9
𝑞𝑙𝑐𝑐 𝑛
Where:
n = Test condition.
𝑞𝑙𝑐𝑐 = 1061 · 𝑤𝑐
Selection of Equipment. A Passive Pressure Drop Device shall be used to conduct the
test in accordance with Section C2.1.
Setup. Passive Pressure Drop Device shall be setup in the Test Stand as if it were a
UUT in the following duct configurations:
25
__________________________________________________________ AHRI Standard 140-2023 (I-P)
C3.8.3.2. Test Points. The Passive Pressure Drop Device shall be tested
at the six conditions shown in Table 11. The three additional points
specified in Test 3 shall be run if needed to qualify the Alternative
Psychrometric Testing Configuration.
26
__________________________________________________________ AHRI Standard 140-2023 (I-P)
Recorded Data. Air flow rate and static pressure drop shall be recorded.
Data Analysis.
∆𝑃𝑠𝑡𝐸 − ∆𝑃𝑠𝑡𝑀
𝐵𝑆𝑇 = [ ] ∙ 100 10
∆𝑃𝑠𝑡𝑀 𝑛
Where:
Selection of Equipment. The UUT and Electric Heat Box shall match those used in
the Sensible Heat Measurement testing (Section C3.4).
Setup. Test setup shall match the requirements of Section C3.4 testing with the
following additional requirements.
27
__________________________________________________________ AHRI Standard 140-2023 (I-P)
Procedure.
C3.9.3.1. Indoor Blower Off. The Indoor Blower motor shall be left
unpowered.
C3.9.3.2. Indoor Room Air. Inlet conditions shall be 70⁰F dry bulb.
C3.9.3.4.1. Radiant Heat Affect. To confirm that the leaving thermocouple grid is not affected
by the radiant heat coming from the heater element, conduct a ten-minute test comparing
the leaving thermocouple grid and the outlet RTD. If the thermocouple grid is greater than
the RTD by more than 0.75⁰F, then shield the thermocouple grid to prevent radiant heat
affect.
C3.9.3.4.2. Cyclic. During the test the Electric Heat Box is cycled a minimum of four on and
off cycles as defined in Table 12.
Recorded Data. The entering and leaving air dry bulb temperatures, air flow rate, the
electric heater power, and the thermal mass thermocouple temperatures.
28
__________________________________________________________ AHRI Standard 140-2023 (I-P)
Data Analysis. This test is measuring qcyc,h, qcyc,hoff, and qts to determine the mcpm term.
𝑞𝑡𝑠 = 𝑞𝑐𝑦𝑐,ℎ𝑜𝑓𝑓 11
𝜃2
𝛤𝑚 = ∫ [𝑡𝑚 (𝜃)]𝑑𝜃
𝜃1
12
Where:
𝜃1,2 = Test time from the start (𝜃1 ) to the stop (𝜃2 ) of each
ON cycle
Integrated change in temperature (thermal storage potential) for the ON portion of each of
the last three cycles shall not vary by more than 0.3°F using the average of the last three
cycles.
Report the mean of mcpm for all cycles, use last three cycles for
calculation of Equation 14.
mcpm(µ) = ∑mcpm / 3 14
If mcpm(µ) > 4.0 Btu/°F, thermocouples shall remain on the device with the greatest thermal
energy storage effect and adjustment made to all Cyclic Test Stand tests as per the
following.
C3.9.5.4.1. Cooling—Cyclic. Equation 15, Equation 16, Equation 17, Equation 18, Equation
19, Equation 20, Equation 21, and Equation 22 shall be used to determine the cyclic
cooling capacity for a dry coil:
29
__________________________________________________________ AHRI Standard 140-2023 (I-P)
Θt
where tm(0) is the temperature of the thermal storage device at the beginning
of the cycle ON period and tm(t) is the temperature at the end of time I.
For units without an indoor fan, qcyc shall have a fan correction. The fan
correction shall be for a period for I, whose definition source is indicated
above. The fan-corrected qcyc shall be the correct capacity value to be used
with the Cyclic Test.
C3.9.5.4.2. Heating, Steady-State. The total heating capacity based on indoor-side data shall
be calculated as showing in Equation 23
30
__________________________________________________________ AHRI Standard 140-2023 (I-P)
These relationships shall be used for the low-temperature test and the high-
temperature test or tests in the case of two-speed, two-compressor, or
variable-speed units. For units without an indoor fan, both the capacity and
power shall be corrected as defined in specific test procedures.
Informative Note: During the heat on cycle, the thermal mass, the mixer, will take on
heat. This heat is not measured by the thermocouple grid causing a higher C D.
During the no-heat cycle, the thermal mass will give off heat. This procedure
is used to create an estimate of this effect.
Selection of Equipment. In order to qualify the Test Stand for both cooling and
heating, a UUT that operates in cooling and heating shall be selected within the scope
of the Reference Rating Standard and within the cooling and heating capacity
limitations of the Test Stand.
Informative Note: Each lab should select a unit that best meets that lab’s
individual needs. Selecting a single unit and testing it in multiple rooms
will provide the most useful data for trend analysis and correlation
between rooms, but little information about the lab’s operating range.
Selecting different units of different capacities can provide useful data
across the lab’s operating range, but little data for trend analysis or
correlation.
Setup.
For Single Package Units, the outdoor air enthalpy method as outlined in ANSI/ASHRAE
Standard 37 Section 7.3 shall be used for the secondary Heat Balance.
31
__________________________________________________________ AHRI Standard 140-2023 (I-P)
If outdoor air enthalpy will be utilized for a split system, then outdoor air enthalpy method
equipment shall be verified simultaneously.
Procedure. Only nozzle combinations approved through the Air Flow Measurement
Apparatus Verification shall be used in this test.
Data Analysis. Each Test Type will produce a sensible capacity, latent capacity, and
power measurement.
𝑞̅𝑠𝑐𝑖 − 𝑞𝑠𝑐𝑖
∆𝑞𝑠𝑐𝑖 = ∙ 100
𝑞̅𝑠𝑐𝑖 + 𝑞𝑠𝑐𝑖
2
23
Where:
𝑞̅𝑙𝑐𝑖 − 𝑞𝑙𝑐𝑖
∆𝑞𝑖𝑐𝑖 = ∙ 100
𝑞̅𝑙𝑐𝑖 + 𝑞𝑙𝑐𝑖
2
24
Where:
𝑞̅𝑙𝑐𝑖 = Average latent capacity of all round robin test results of the
same UUT at the same test condition.
𝐸̅𝑖 − 𝐸𝑖
∆𝐸𝑖 = ∙ 100
𝐸̅𝑖 + 𝐸𝑖
2
25
32
__________________________________________________________ AHRI Standard 140-2023 (I-P)
Where:
𝐸̅𝑖 = Average power of all round robin test results of the same UUT
at the same test condition.
𝐸𝑖 = power
Selection of Equipment. The UUT and Electric Heat Box shall match those used in
the Zero Load testing. This alternative sensible heat measurement shall be used when
evaluating systems greater than 5 tons and the Electric Heat Box cannot meet full
capacity range. A cooling sample shall be used simultaneously with the Electric Heat
Box to allow the air flow to be cooled and then partially reheated to measure sensible
heat accuracy. The Heat Box shall be able to provide heating of at least 10% of the
cooling capacity of the cooling sample. An ASHRAE duct shall not be required to
perform this test.
Setup. Setup shall match the Zero Load Test with the addition of the cooling sample
and the ability to measure power supplied to the Electric Heat Box separately from
the power supplied to the cooling sample.
Procedure. Only nozzle combinations approved through the Air Flow Measurement
Apparatus Verification shall be used in this test.
C3.11.3.2. Electric Heat Box Air Temperature. Over the tested airflow
rates, the voltage to the Electric Heat Box shall be controlled in order to
maintain a stable power output from the Electric Heat Box.
C3.11.3.3.1. Cooling Full Load. During this test, the sample cooling unit shall be run at its low,
medium and high-speed settings with the Electric Heat Box 100% on and 100% off. See
Table 13.
C3.11.3.3.2. Mixing Efficiency. During this test, the cooling sample shall be run at its rated
minimum airflow with the cooling turned off and the Electric Heater turned 100% ON
with the Left Side Only, the Right Side only, and the entire heater.
Any of the nine grid thermocouples shall conform to the uniform flow tolerance
calculated by equation 26:
𝑇 = 𝑇𝑎𝑣𝑔 ± 0.75°𝐹 26
Test Conditions. The UUT and Electric Heat Box shall be operated, at the nine
conditions shown in Table 13
33
__________________________________________________________ AHRI Standard 140-2023 (I-P)
4. Temperature measurements shall be taken with the heater turned on and the heater turned off. The
sensible heat difference shall be calculated and compared to the heater input.
Recorded Data. Refer to C3.4.4 for test conditions 1-6. Refer to 3.5.1 for test
conditions 7-9.
34
__________________________________________________________ AHRI Standard 140-2023 (I-P)
D2. Requirements. All Test Stand tests shall be conducted in accordance with the Reference Rating Standard.
D2.1. Time Period. Steady-state operating conditions and performance shall be maintained for a minimum
test period of 30 minutes, such that measurement parameters and test results are within both the
operating condition tolerances and test tolerances set forth in the Reference Rating Standard.
D2.2. Simultaneous Measurement. All measurements should be taken simultaneously. Software or other
recording methods shall be used to capture time-stamped data points over the duration of the test
time period.
D2.3. Sampling Rate. A minimum of 30 data point measurements shall be collected and recorded for each
parameter at uniform time intervals. Intervals between time stamps shall not vary more than ± 5%
from the average time interval for all data points.
D2.4. Measured Values. Measurement values including temperature, pressure, flow, and power shall be
calculated as the mean of all measured data over the test time period.
D2.5. Test Results. Test results including capacity, efficiency, and pressure drop shall be calculated using
the Measured Values.
D2.6. Period on Conditions. All tests shall be on conditions for 30 minutes prior to starting data interval.
35
__________________________________________________________ AHRI Standard 140-2023 (I-P)
E2. Requirements. All Test Stand tests should be conducted with calibrated instrumentation in accordance with
the Reference Rating Standard.
E2.1. Calibrated Systems. Data acquisition systems should be either calibrated as a system, or all
individual component calibrations should be documented in a manner that demonstrates the
measurement system meets the accuracy requirements specified in the Reference Rating Standard.
E2.2. Minimum Calibrated Points. Calibrations should include no less than four points compared to a
calibration standard. Calibration standards should be traceable to NIST or laboratories that
participate in inter-laboratory audits.
E2.3. Calibrated Range. All instruments and measurement systems should be calibrated over a range
that meets or exceeds the range of Test Stand data acquisition. For each instrument device in a
measurement system, the calibration process should identify the range where the Reference Rating
Standard required accuracy can be achieved. All measurements should be taken within the
calibrated range for each instrument device measurement. For a given type of measurement,
multiple instruments may be required to cover a wide range of testing conditions for a given Test
Stand.
To determine the calibrated range a linear regression analysis should be performed on the
calibration data.
E2.3.1. Linear Regression Analysis. To complete this analysis, calibration data is plotted to show
the residual errors versus the calibration reference standard. The standard error of
estimate should be calculated for the measurement system indicated values (post
calibration) versus the calibration reference standard, then using Equation 27 plot a 95%
prediction interval (α=5%) on both sides of the curve fit. The point(s) where the
prediction interval curve exceeds the required accuracy should be the limit(s) of the
range. Table 14 and Equation 28, Equation 29, Equation 30, Equation 31, Equation 32,
and Equation 33 explain the method of calculating the prediction interval. See example
using sample data in Figure 7 and Figure 8, where the specified accuracy is ±1% of
reading, and the useable range is from 100 to 13.4, or Turn Down Ratio of 7.5:1.
E2.4. Electrical Measurements. Accuracy of electrical measurements should include all devices in the
measurement system such as power meter or power analyzer, potential transformers, current
transformers, and data acquisition signals. UUT that utilize power-altering equipment, such as
variable frequency drive or inverter, may require appropriate isolation and precautions to confirm
that accurate power measurements are obtained. UUT that utilize power-altering equipment may
require the use of instrumentation that is capable of accurately measuring signals containing high
frequency and high crest factors, or both. In these cases, the instrumentation used should have
bandwidth and crest factor specifications, or both to confirm the electrical power input
measurement errors are within the accuracy requirements of the Reference Rating Standard for the
quantity measured.
36
__________________________________________________________ AHRI Standard 140-2023 (I-P)
x1 − ŷ ± PI(x1 )
𝑦1 x1 x1 − ŷ ± PI(x1 )
𝑥1
x1 − ŷ ± PI(x2 )
Calibration Data
𝑦2 x2 x2 − ŷ ± PI(x2 )
x2
x1 − ŷ ± PI(x3 )
𝑦3 x3 x3 − ŷ ± PI(x3 )
x3
x1 − ŷ ± PI(xn )
𝑦n xn xn − ŷ ± PI(xn )
x𝑛
continuous curve
continuous curve
x̂ − ŷ ± PI(x̂ )
Regression
𝑥̅ sε
Statistics
x̂ − ŷ ± PI(x̂ )
SSx varying x̂ from x̂
varying x̂ from
min to max
min to max
values of xj
values of xj
Notes:
1. Reference Standard Value is the actual value determined or measured by the calibration standard.
2. Corrected Indicated Value is the value of the measured quantity given directly by a measuring system on
the basis of its calibration curve (“as left” when the calibration process has been completed, not “as found”
at the beginning of the calibration process).
1 (x̂ − 𝑥̅ )2
𝑃𝐼(x̂) = 𝑠𝜀 ∙ 𝑡𝛼.𝑛−2 ∙ √1 + +
2 𝑛 𝑆𝑆𝑥
27
n
1
x̅ = ∑(xj )
n
j=1
28
𝑛
𝑆𝑆𝑥 = ∑(𝑥𝑗 − 𝑥̅ )2
𝑗=1
29
37
__________________________________________________________ AHRI Standard 140-2023 (I-P)
ŷ = m ∙ x̂ + c
33
38
__________________________________________________________ AHRI Standard 140-2023 (I-P)
39
__________________________________________________________ AHRI Standard 140-2023 (I-P)
F2. Methodology.
F2.1. Goal. Uncertainty analysis (referred to as error analysis) is outlined in ASME 19.1. The goal of
the Uncertainty analysis is to bound the reported test results such that the true values lie within the
specified range with 95% confidence. The Uncertainty of the reported results is found by
propagation of error sources in the measurement system.
F2.2. Overall Uncertainty. The error analysis applied in this standard is intended for steady state
measurements taken from a single system over a period long enough to encompass all system
variations. The first step is to assign the Uncertainty in each of the measured variables as shown in
Equation 34:
𝑈𝑥 = √𝐵𝑥2 + (𝑡𝑆𝑥 )2
34
Where:
2
𝐵𝑥2 = ∑𝐵𝑥,𝑗
35
F2.4. Mean and Standard Deviation. A sequence of measurements made over time of a particular
quantity often exhibit random variations or Random Errors. The standard deviation in Equation 36
is a measure of the magnitude of the Random Error and is most meaningful if data is collected on
a time scale longer than any naturally occurring variations in the system. The average and standard
deviation for each measured variable is calculated by Equation 36 and Equation 37.
𝐽
1
𝑥̅ = ∑ 𝑥𝑗
𝐽
𝑗=1
36
40
__________________________________________________________ AHRI Standard 140-2023 (I-P)
𝐽 1⁄2
1 2
𝑆𝑥̅ = [ ∑(𝑥𝑗 − 𝑥̅ ) ]
𝐽−1
𝑗=1
37
𝑌 = 𝑌(𝑋1 , 𝑋2 , … , 𝑋𝑖 ) where 𝑋 = 𝑥̅
38
The Uncertainty in the computed quantity Y can be estimated as shown in Equation 39 from where
the partial derivatives represent the sensitivities of the computed quantity Y to variations in the
individual (averaged) measurements X_i.
2 2 2 2 1⁄2
𝜕𝑌 𝜕𝑌 𝜕𝑌 𝜕𝑌
𝑈𝑌 = [( 𝑈𝑋1 ) + ( 𝑈𝑋2 ) + ⋯ + ( 𝑈𝑋𝑖 ) + ⋯ + ( 𝑈𝑋𝑀 ) ]
𝜕𝑋1 𝜕𝑋2 𝜕𝑋𝑖 𝜕𝑋𝑀
39
𝜕𝑌
In the following equations, partial derivatives are represented as = 𝜃𝑋𝑖
𝜕𝑋𝑖
F3. Assumptions. The following assumptions are made for uncertainties calculated in accordance with this standard.
• Air, water, and refrigerant properties are known perfectly (negligible Uncertainty) when using
formulations consistent with those in the Reference Rating Standard.
• As defined in ASHRAE 37, power measurement devices for fans and compressor are accurate within ±
2%.
• As defined in ASHRAE 37, power measurement devices for electric heaters are accurate within ± 1%.
F4. Requirements. .
41
__________________________________________________________ AHRI Standard 140-2023 (I-P)
60𝑄𝑚𝑖 (𝐶𝑝𝑎1 𝑡𝑎1 − 𝐶𝑝𝑎2 𝑡𝑎2 ) 60𝑄𝑚𝑖 𝐶𝑝𝑎1 𝑡𝑎1 − 60𝑄𝑚𝑖 𝐶𝑝𝑎2 𝑡𝑎2
𝑞𝑠𝑐𝑖 = =
𝑣𝑛′ (1 + 𝑊𝑛 ) 𝑣𝑛′ + 𝑣𝑛′ 𝑊𝑛
40
2 2 2
(𝜃𝑄𝑚𝑖 𝑈𝑄𝑚𝑖 ) + (𝜃𝐶𝑝𝑎1 𝑈𝐶𝑝𝑎1 ) + (𝜃𝑡𝑎1 𝑈𝑡𝑎1 ) +
𝑈𝑞𝑠𝑐𝑖 = √ 2 2 2 2
(𝜃𝐶𝑝𝑎2 𝑈𝐶𝑝𝑎2 ) + (𝜃𝑡𝑎2 𝑈𝑡𝑎2 ) + (𝜃𝑣𝑛′ 𝑈𝑣𝑛′ ) + (𝜃𝑊𝑛 𝑈𝑊𝑛 )
2 2 2 𝑈 2 2 𝑈 2 2 𝑈 2
𝑄𝑚𝑖 𝑈𝑄𝑚𝑖 𝐶𝑝𝑎1 𝐶𝑝𝑎1 𝑡𝑎1 𝑡𝑎1 𝐶𝑝 𝐶𝑝
( 𝜃𝑄𝑚𝑖 ) ( ) +( 𝜃𝐶𝑝𝑎1 ) ( ) +( 𝜃𝑡𝑎1 ) ( ) + ( 𝑎2 𝜃𝐶𝑝𝑎2 ) ( 𝑎2 )
𝑈𝑞𝑠𝑐𝑖 𝑞𝑠𝑐𝑖 𝑄𝑚𝑖 𝑞𝑠𝑐𝑖 𝐶𝑝𝑎1 𝑞𝑠𝑐𝑖 𝑡𝑎1 𝑞𝑠𝑐𝑖 𝐶𝑝𝑎2
= 2 2
𝑞𝑠𝑐𝑖 𝑡𝑎2 2 𝑈 2
𝑡𝑣 ′ 2
𝑈𝑣′ 𝑊𝑛 2
𝑈𝑊
𝑡𝑎2
+( 𝜃𝑡𝑎2 ) ( ) + ( 𝑛 𝜃𝑣𝑛′ ) ( ′𝑛 ) + ( 𝜃𝑊𝑛 ) ( 𝑛 )
√ 𝑞𝑠𝑐𝑖 𝑡𝑎2 𝑞𝑠𝑐𝑖 𝑣𝑛 𝑞𝑠𝑐𝑖 𝑊𝑛
Where:
42
__________________________________________________________ AHRI Standard 140-2023 (I-P)
2 2 2
𝑈𝑄𝑚𝑖 = √(𝜃𝐶 𝑈𝐶 )2 + (𝜃𝐴𝑛 𝑈𝐴𝑛 ) + (𝜃𝑃𝑉 𝑈𝑃𝑉 ) + (𝜃𝑣𝑛′ 𝑈𝑣𝑛′ )
2 𝑈 ′ 2
𝑈𝑄𝑚𝑖 𝐶 2
𝑈𝐶 2 𝐴𝑛 2
𝑈𝐴 2 𝑃𝑉 2
𝑈𝑃 2 𝑣𝑛′ 𝑣
= √( 𝜃𝐶 ) ( ) + ( 𝜃𝐴𝑛 ) ( 𝑛 ) + ( 𝜃𝑃𝑉 ) ( 𝑉 ) + ( 𝜃𝑣𝑛′ ) ( ′𝑛 )
𝑄𝑚𝑖 𝑄𝑚𝑖 𝐶 𝑄𝑚𝑖 𝐴𝑛 𝑄𝑚𝑖 𝑃𝑉 𝑄𝑚𝑖 𝑣𝑛
𝑈𝐴𝑛 = √(𝜃𝐷 𝑈𝐷 )2 = 𝜃𝐷 𝑈𝐷
𝑈𝐴𝑛 𝜃𝐷 𝑈𝐷
=
𝐴𝑛 𝐴𝑛
𝜋𝐷
𝜃𝐷 =
18
2
𝑈𝑣𝑛′ 𝑣𝑛 2 𝑈
𝑣 𝑊𝑛 2
𝑈𝑊 2
= √( ′ 𝜃𝑣𝑛 ) ( 𝑛 ) + ( ′ 𝜃𝑊𝑛 ) ( 𝑛 )
𝑣𝑛′ 𝑣𝑛 𝑣𝑛 𝑣𝑛 𝑊𝑛
1
𝜃𝑣𝑛 =
1 + 𝑊𝑛
𝑣𝑛
𝜃𝑊𝑛 = −
(1 + 𝑊𝑛 )2
43
__________________________________________________________ AHRI Standard 140-2023 (I-P)
0.370486 ∙ 𝑡𝑛 ∙ (1 + 1.607858𝑊𝑛 )
𝑣𝑛 =
𝑃𝑛
2 2 2
𝑈𝑣𝑛 = √(𝜃𝑡𝑛 𝑈𝑡𝑛 ) + (𝜃𝑊𝑛 𝑈𝑊𝑛 ) + (𝜃𝑃𝑛 𝑈𝑃𝑛 )
2
𝑈𝑣𝑛 𝑡𝑛 2 𝑈
𝑡 𝑊𝑛 2
𝑈𝑊 2 𝑃𝑛 2
𝑈𝑃 2
= √( 𝜃𝑡𝑛 ) ( 𝑛 ) + ( 𝜃𝑊𝑛 ) ( 𝑛 ) + ( 𝜃𝑃𝑛 ) ( 𝑛 )
𝑣𝑛 𝑣𝑛 𝑡𝑛 𝑣𝑛 𝑊𝑛 𝑣𝑛 𝑃𝑛
0.370486(1.607858𝑊𝑛 + 1)
𝜃𝑡𝑛 =
𝑃𝑛
0.595688879𝑡𝑛
𝜃𝑊𝑛 =
𝑃𝑛
0.370486𝑡𝑛 (1.607858𝑊𝑛 + 1)
𝜃𝑃𝑛 = −
𝑃𝑛 2
leaving UUT:
𝐶𝑝𝑎2 = 0.24 + 0.444𝑊2
2
𝑈𝐶𝑝𝑎2 = √(𝜃𝑊2 𝑈𝑊2 ) = 𝜃𝑊2 𝑈𝑊2
𝑈𝐶𝑝𝑎2 𝜃𝑊2 𝑈𝑊2
=
𝐶𝑝𝑎2 𝐶𝑝𝑎2
𝜃𝑊2 = 0.444
44
__________________________________________________________ AHRI Standard 140-2023 (I-P)
2 2 2
𝑈𝑊𝑛 = √(𝜃𝑊𝑠𝑛
∗ 𝑈𝑊 ∗ ) + (𝜃𝑡 ∗ 𝑈𝑡 ∗ ) + (𝜃𝑡 𝑈𝑡 )
𝑠𝑛 𝑛 𝑛 𝑛 𝑛
∗ 2 2 2 𝑈 ∗ 2 2 𝑈 2
𝑈𝑊𝑛 𝑊𝑠𝑛 𝑈𝑊𝑠𝑛
∗ 𝑡𝑛∗ 𝑡𝑛 𝑡𝑛 𝑡𝑛
= √( 𝜃𝑊𝑠𝑛
∗ ) ( ) + ( 𝜃 ∗ ) ( ) + ( 𝜃 ) ( )
𝑊𝑛 𝑊𝑛 ∗
𝑊𝑠𝑛 𝑊𝑛 𝑡𝑛 𝑡𝑛∗ 𝑊𝑛 𝑡𝑛 𝑡𝑛
1093 − 0.556𝑡𝑛∗
𝜃𝑊𝑠𝑛
∗ =
1093 + 0.444𝑡𝑛 − 𝑡𝑛∗
∗
1093𝑊𝑠𝑛 0.556𝑡𝑛∗ 𝑊𝑠𝑛
∗
𝜃𝑡𝑛∗ = −
(1093 + 0.444𝑡𝑛 − 𝑡𝑛∗ )2 (1093 + 0.444𝑡𝑛 − 𝑡𝑛∗ )2
∗
0.556𝑊𝑠𝑛 0.240𝑡𝑛∗
− +
1093 + 0.444𝑡𝑛 − 𝑡𝑛∗ (1093 + 0.444𝑡𝑛 − 𝑡𝑛∗ )2
0.240
+
1093 + 0.444𝑡𝑛 − 𝑡𝑛∗
∗
1093𝑊𝑠𝑛 − 0.24𝑡𝑛 − 0.556𝑡𝑛∗ 𝑊𝑠𝑛
∗
+ 0.240𝑡𝑛∗
𝜃𝑡𝑛∗ =
(1093 + 0.444𝑡𝑛 − 𝑡𝑛∗ )2
∗
−0.556𝑊𝑠𝑛 + 0.240
+
1093 + 0.444𝑡𝑛 − 𝑡𝑛∗
0.240
𝜃𝑡𝑛 =−
1093 + 0.444𝑡𝑛 − 𝑡𝑛∗
∗
0.444(1093𝑊𝑠𝑛 − 0.24𝑡𝑛 + 0.24𝑡𝑛∗ − 0.556𝑊𝑠𝑛
∗ ∗
𝑡𝑛
−
(1093 + 0.444𝑡𝑛 − 𝑡𝑛∗ )2
entering UUT:
∗
1093𝑊𝑠1 − 0.556𝑡1∗ 𝑊𝑠1
∗
− 0.240𝑡1 + 0.240𝑡1∗
𝑊1 =
1093 + 0.444𝑡1 − 𝑡1∗
2 2 2
𝑈𝑊1 = √(𝜃𝑊𝑠1
∗ 𝑈𝑊 ∗ ) + (𝜃𝑡 ∗ 𝑈𝑡 ∗ ) + (𝜃𝑡 𝑈𝑡 )
𝑠1 1 1 1 1
2
𝑈𝑊1 𝑊𝑠1∗ 2
𝑈𝑊𝑠1
∗ 𝑡1∗ 2
𝑈𝑡1∗ 2 𝑡1 2 𝑈
𝑡1
2
= √( 𝜃𝑊𝑠1
∗ ) ( ) + ( 𝜃 𝑡 ∗) ( ) + ( 𝜃𝑡 ) ( )
𝑊1 𝑊1 𝑊𝑠1∗ 𝑊1 1 𝑡1∗ 𝑊1 1 𝑡1
1093 − 0.556𝑡1∗
𝜃𝑊𝑠1
∗ =
1093 + 0.444𝑡1 − 𝑡1∗
∗
1093𝑊𝑠1 − 0.24𝑡1 − 0.556𝑡1∗ 𝑊𝑠1
∗
+ 0.240𝑡1∗ −0.556𝑊𝑠1 ∗
+ 0.240
𝜃𝑡1∗ = ∗ +
(1093 + 0.444𝑡1 − 𝑡1 ) 2 1093 + 0.444𝑡1 − 𝑡1∗
0.240
𝜃𝑡1 = −
1093 + 0.444𝑡1 − 𝑡1∗
∗
0.444(1093𝑊𝑠1 − 0.24𝑡1 + 0.24𝑡1∗ − 0.556𝑊𝑠1
∗ ∗
𝑡1
−
(1093 + 0.444𝑡1 − 𝑡1∗ )2
leaving UUT:
∗
1093𝑊𝑠2 − 0.556𝑡2∗ 𝑊𝑠2
∗
− 0.240𝑡2 + 0.240𝑡2∗
𝑊2 =
1093 + 0.444𝑡2 − 𝑡2∗
45
__________________________________________________________ AHRI Standard 140-2023 (I-P)
2 2 2
𝑈𝑊2 = √(𝜃𝑊𝑠2
∗ 𝑈𝑊 ∗ ) + (𝜃𝑡 ∗ 𝑈𝑡 ∗ ) + (𝜃𝑡 𝑈𝑡 )
𝑠2 2 2 2 2
2
𝑈𝑊2 𝑊𝑠2∗ 2
𝑈𝑊𝑠2
∗ 𝑡2∗ 2
𝑈𝑡2∗ 2 𝑡2 2 𝑈
𝑡2
2
= √( 𝜃𝑊𝑠2
∗ ) ( ) + ( 𝜃 ∗ ) ( ) + ( 𝜃 ) ( )
𝑊2 𝑊2 𝑊𝑠2∗ 𝑊2 𝑡2 𝑡2∗ 𝑊2 𝑡2 𝑡2
1093 − 0.556𝑡2∗
𝜃𝑊𝑠2
∗ =
1093 + 0.444𝑡2 − 𝑡2∗
∗
1093𝑊𝑠2 − 0.24𝑡2 − 0.556𝑡2∗ 𝑊𝑠2
∗
+ 0.240𝑡2∗ −0.556𝑊𝑠2 ∗
+ 0.240
𝜃𝑡2∗ = +
(1093 + 0.444𝑡2 − 𝑡2∗ )2 1093 + 0.444𝑡2 − 𝑡2∗
0.240
𝜃𝑡2 = −
1093 + 0.444𝑡2 − 𝑡2∗
∗
0.444(1093𝑊𝑠2 − 0.24𝑡2 + 0.24𝑡2∗ − 0.556𝑊𝑠2
∗ ∗
𝑡2
− ∗ 2
(1093 + 0.444𝑡2 − 𝑡2 )
∗
0.621945 ∙ 𝑝𝑤𝑠(𝑡𝑛∗)
𝑊𝑠𝑛 =
𝑃𝑛 − 𝑝𝑤𝑠(𝑡𝑛∗)
2 2
∗ = √(𝜃𝑝
𝑈𝑊𝑠𝑛 𝑈 ) + (𝜃𝑃𝑛 𝑈𝑃𝑛 )
𝑤𝑠(𝑡∗ ) 𝑝𝑤𝑠(𝑡∗ )
𝑛 𝑛
2
𝑈𝑊𝑠𝑛
∗ 𝑝𝑤𝑠(𝑡𝑛∗) 2 𝑈𝑝 𝑃𝑛 2
𝑈𝑃𝑛 2
𝑤𝑠(𝑡∗𝑛 )
= √ ( 𝜃𝑝 ∗ ) ( ) + ( 𝜃𝑃 ) ( )
∗
𝑊𝑠𝑛 𝑊𝑠𝑛∗ 𝑤𝑠(𝑡𝑛 ) 𝑝𝑤𝑠(𝑡𝑛∗) 𝑊𝑠𝑛∗ 𝑛
𝑃𝑛
0.621945𝑝𝑤𝑠(𝑡𝑛∗ ) 0.621945
𝜃𝑝𝑤𝑠(𝑡∗ ) = 2 +
𝑛
(𝑃𝑛 − 𝑝𝑤𝑠(𝑡𝑛∗ ) ) 𝑃𝑛 − 𝑝𝑤𝑠(𝑡𝑛∗)
0.621945𝑝𝑤𝑠(𝑡𝑛∗ )
𝜃𝑃𝑛 = − 2
(𝑃𝑛 − 𝑝𝑤𝑠(𝑡𝑛∗ ) )
entering UUT:
∗
0.621945 ∙ 𝑝𝑤𝑠(𝑡1∗)
𝑊𝑠1 =
𝑃1 − 𝑝𝑤𝑠(𝑡1∗)
46
__________________________________________________________ AHRI Standard 140-2023 (I-P)
2 2
∗ = √(𝜃𝑝
𝑈𝑊𝑠1 𝑈 ) + (𝜃𝑃1 𝑈𝑃1 )
𝑤𝑠(𝑡∗ ) 𝑝𝑤𝑠(𝑡∗ )
1 1
2
𝑈𝑊𝑠1
∗ 𝑝𝑤𝑠(𝑡1∗) 2 𝑈𝑝𝑤𝑠(𝑡∗ )
𝑃1
2
𝑈𝑃 2
= √( 𝜃𝑝𝑤𝑠(𝑡∗ ) ) ( 1
) + ( ∗ 𝜃𝑃1 ) ( 1 )
𝑊𝑠1∗ 𝑊𝑠1∗ 1 𝑝𝑤𝑠(𝑡1∗) 𝑊𝑠1 𝑃1
0.621945𝑝𝑤𝑠(𝑡1∗) 0.621945
𝜃𝑝𝑤𝑠(𝑡∗ ) = 2 +
1
(𝑃1 − 𝑝𝑤𝑠(𝑡1∗) ) 𝑃1 − 𝑝𝑤𝑠(𝑡1∗)
0.621945𝑝𝑤𝑠(𝑡1∗)
𝜃𝑃𝑛1 = − 2
(𝑃1 − 𝑝𝑤𝑠(𝑡1∗) )
leaving UUT:
∗
0.621945 ∙ 𝑝𝑤𝑠(𝑡2∗)
𝑊𝑠2 =
𝑃2 − 𝑝𝑤𝑠(𝑡2∗)
2 2
∗ = √(𝜃𝑝
𝑈𝑊𝑠2 𝑈 ) + (𝜃𝑃2 𝑈𝑃2 )
𝑤𝑠(𝑡∗ ) 𝑝𝑤𝑠(𝑡∗ )
2 2
2
𝑈𝑊𝑠2
∗ 𝑝𝑤𝑠(𝑡2∗) 2 𝑈𝑝𝑤𝑠(𝑡∗ )
𝑃2
2
𝑈𝑃 2
= √( 𝜃𝑝𝑤𝑠(𝑡∗ ) ) ( 2
) + ( ∗ 𝜃𝑃2 ) ( 2 )
𝑊𝑠2∗ 𝑊𝑠2∗ 2 𝑝𝑤𝑠(𝑡2∗) 𝑊𝑠2 𝑃2
0.621945𝑝𝑤𝑠(𝑡2∗) 0.621945
𝜃𝑝𝑤𝑠(𝑡∗ ) = 2 +
2
(𝑃2 − 𝑝𝑤𝑠(𝑡2∗) ) 𝑃2 − 𝑝𝑤𝑠(𝑡2∗)
0.621945𝑝𝑤𝑠(𝑡2∗)
𝜃𝑃𝑛2 = − 2
(𝑃2 − 𝑝𝑤𝑠(𝑡2∗) )
47
___________________________________________________________________________________________ AHRI Standard 140-202x (I-P)
−10440.397 ∗ +1.289036∗10−5 ∗𝑡 ∗ 2
∗ −11.29465−0.027022355∗𝑡𝑛 𝑛
[ 𝑡𝑛 ]
3
𝑝𝑤𝑠(𝑡𝑛∗ ) = 𝑒 −2.4780681∗10−9 ∗𝑡𝑛
∗ +6.5459673∗ln (𝑡 ∗ )
𝑛
2
𝑈𝑝𝑤𝑠(𝑡∗ ) = √(𝜃𝑡𝑛∗ 𝑈𝑡𝑛∗ ) = (𝜃𝑡𝑛∗ 𝑈𝑡𝑛∗ )
𝑛
entering UUT:
−10440.397 2
−11.29465−0.027022355∗𝑡1∗ +1.289036∗10−5 ∗𝑡1∗
[ 𝑡1∗ ]
−2.4780681∗10 −9 ∗𝑡 ∗ 3 +6.5459673∗ln (𝑡 ∗ )
𝑝𝑤𝑠(𝑡1∗ ) = 𝑒 1 1
2
𝑈𝑝𝑤𝑠(𝑡∗ ) = √(𝜃𝑡1∗ 𝑈𝑡1∗ ) = (𝜃𝑡1∗ 𝑈𝑡1∗ )
1
leaving UUT:
48
___________________________________________________________________________________________ AHRI Standard 140-202x (I-P)
−10440.397 2
−11.29465−0.027022355∗𝑡2∗ +1.289036∗10−5 ∗𝑡2∗
[ 𝑡2∗ ]
−2.4780681∗10 −9 ∗𝑡 ∗ 3 +6.5459673∗ln (𝑡 ∗ )
𝑝𝑤𝑠(𝑡2∗ ) = 𝑒 2 2
2
𝑈𝑝𝑤𝑠(𝑡∗ ) = √(𝜃𝑡2∗ 𝑈𝑡1∗ ) = (𝜃𝑡2∗ 𝑈𝑡2∗ )
2
−10440.397
−11.29465−0.027022355∗𝑡𝑛 +1.289036∗10−5 ∗𝑡𝑛 2
[ 𝑡𝑛 ]
𝑝𝑤𝑠(𝑡𝑛 ) = 𝑒 −2.4780681∗10−9 ∗𝑡𝑛 3 +6.5459673∗ln (𝑡𝑛 )
2
𝑈𝑝𝑤𝑠(𝑡𝑛) = √(𝜃𝑡𝑛 𝑈𝑡𝑛 ) = (𝜃𝑡𝑛 𝑈𝑡𝑛 )
𝑈𝑝𝑤𝑠(𝑡𝑛) (𝜃𝑡𝑛 𝑈𝑡𝑛 )
=
𝑝𝑤𝑠(𝑡𝑛) 𝑝𝑤𝑠(𝑡𝑛)
10440.397
−0.027022355∗𝑡𝑛 +6.5459673∗𝑙𝑛(𝑡𝑛 )− +0.00001289036∗𝑡𝑛 2 −11.29465
[ 𝑡𝑛 ] 6.5459673
𝜃𝑡𝑛 = 𝑒 −0.0000000024780681∗𝑡𝑛 3 × (0.00002578072 ∗ 𝑡𝑛 +
𝑡𝑛
10440.397
+ − 0.0000000074342043𝑡𝑛 2 − 0.027022355
𝑡𝑛 2
entering UUT:
49
___________________________________________________________________________________________ AHRI Standard 140-202x (I-P)
−10440.397
−11.29465−0.027022355∗𝑡1 +1.289036∗10−5 ∗𝑡1 2
[ 𝑡1 ]
𝑝𝑤𝑠(𝑡1 ) = 𝑒 −2.4780681∗10−9 ∗𝑡1 3 +6.5459673∗ln (𝑡1 )
2
𝑈𝑝𝑤𝑠(𝑡1) = √(𝜃𝑡1 𝑈𝑡1 ) = (𝜃𝑡1 𝑈𝑡1 )
𝑈𝑝𝑤𝑠(𝑡1) (𝜃𝑡1 𝑈𝑡1 )
=
𝑝𝑤𝑠(𝑡1) 𝑝𝑤𝑠(𝑡1)
10440.397
−0.027022355∗𝑡1 +6.5459673∗𝑙𝑛(𝑡1 )− +0.00001289036∗𝑡1 2 −11.29465
[ 𝑡1 ] 6.5459673
𝜃𝑡1 = 𝑒 −0.0000000024780681∗𝑡1 3 × (0.00002578072 ∗ 𝑡1 +
𝑡1
10440.397
+ − 0.0000000074342043𝑡1 2 − 0.027022355
𝑡1 2
leaving UUT:
−10440.397
−11.29465−0.027022355∗𝑡2 +1.289036∗10−5 ∗𝑡2 2
[ 𝑡2 ]
−2.4780681∗10 −9 ∗𝑡 3 +6.5459673∗ln (𝑡 )
𝑝𝑤𝑠(𝑡2 ) = 𝑒 2 2
2
𝑈𝑝𝑤𝑠(𝑡2) = √(𝜃𝑡2∗ 𝑈𝑡2 ) = (𝜃𝑡2 𝑈𝑡2 )
𝑈𝑝𝑤𝑠(𝑡2) (𝜃𝑡2 𝑈𝑡2 )
=
𝑝𝑤𝑠(𝑡2) 𝑝𝑤𝑠(𝑡2)
10440.397
−0.027022355∗𝑡2 +6.5459673∗𝑙𝑛(𝑡2 )− +0.00001289036∗𝑡2 2 −11.29465
[ 𝑡2 ] 6.545967
𝜃𝑡2 = 𝑒 −0.0000000024780681∗𝑡2 3 × (0.00002578072 ∗ 𝑡2 +
𝑡2
10440.397
+ − 0.0000000074342043𝑡2 2 − 0.027022355
𝑡2 2
F4.2. Total Cooling Capacity. As defined in ASHRAE 37, sensible cooling capacity (𝑞𝑡𝑐𝑖 ) can be calculated as shown in Equation 42.
Where:
𝑞𝑙𝑐𝑖 = 63600𝑄𝑚𝑖 (𝑊𝑖1 − 𝑊𝑖2 )/[𝑣𝑛′ (1 + 𝑊𝑛 )]
50
___________________________________________________________________________________________ AHRI Standard 140-202x (I-P)
Where:
2 2 2 2 2
𝑈𝑞𝑙𝑐𝑖 = √(𝜃𝑄𝑚𝑖 𝑈𝑄𝑚𝑖 ) + (𝜃𝑊𝑖1 𝑈𝑊𝑖1 ) + (𝜃𝑊𝑖2 𝑈𝑊𝑖2 ) + (𝜃𝑣𝑛′ 𝑈𝑣𝑛′ ) + (𝜃𝑊𝑛 𝑈𝑊𝑛 )
63600(𝑊𝑖1 − 𝑊𝑖2 )
𝜃𝑄𝑚𝑖 =
𝑣𝑛′ (1 + 𝑊𝑛 )
63600𝑄𝑚𝑖
𝜃𝑊𝑖1 = ′
𝑣𝑛 (1 + 𝑊𝑛 )
63600𝑄𝑚𝑖
𝜃𝑊𝑖2 = − ′
𝑣𝑛 (1 + 𝑊𝑛 )
63600𝑄𝑚𝑖 (𝑊𝑖1 − 𝑊𝑖2 )
𝜃𝑣𝑛′ = −
𝑣𝑛′ 2 (𝑊𝑛 + 1)
63600𝑄𝑚𝑖 (𝑊𝑖1 − 𝑊𝑖2 )
𝜃𝑊𝑛 = −
(𝑊𝑛 + 1)2 𝑣𝑛′
51
___________________________________________________________________________________________ AHRI Standard 140-202x (I-P)
2 2 2
𝑈𝑄𝑚𝑖 = √(𝜃𝐶 𝑈𝐶 )2 + (𝜃𝐴𝑛 𝑈𝐴𝑛 ) + (𝜃𝑃𝑉 𝑈𝑃𝑉 ) + (𝜃𝑣𝑛′ 𝑈𝑣𝑛′ )
2 𝑈 ′ 2
𝑈𝑄𝑚𝑖 𝐶 2
𝑈𝐶 2 𝐴𝑛 2
𝑈𝐴 2 𝑃𝑉 2
𝑈𝑃 2 𝑣𝑛′ 𝑣
= √( 𝜃𝐶 ) ( ) + ( 𝜃𝐴𝑛 ) ( 𝑛 ) + ( 𝜃𝑃𝑉 ) ( 𝑉 ) + ( 𝜃𝑣𝑛′ ) ( ′𝑛 )
𝑄𝑚𝑖 𝑄𝑚𝑖 𝐶 𝑄𝑚𝑖 𝐴𝑛 𝑄𝑚𝑖 𝑃𝑉 𝑄𝑚𝑖 𝑣𝑛
𝑈𝐴𝑛 = √(𝜃𝐷 𝑈𝐷 )2 = 𝜃𝐷 𝑈𝐷
52
___________________________________________________________________________________________ AHRI Standard 140-202x (I-P)
𝑈𝐴𝑛 𝜃𝐷 𝑈𝐷
=
𝐴𝑛 𝐴𝑛
𝜋𝐷
𝜃𝐷 =
18
2
𝑈𝑣𝑛′ 𝑣𝑛 2 𝑈
𝑣 𝑊𝑛 2
𝑈𝑊 2
= √( ′ 𝜃𝑣𝑛 ) ( 𝑛 ) + ( ′ 𝜃𝑊𝑛 ) ( 𝑛 )
𝑣𝑛′ 𝑣𝑛 𝑣𝑛 𝑣𝑛 𝑊𝑛
1
𝜃𝑣𝑛 =
1 + 𝑊𝑛
𝑣𝑛
𝜃𝑊𝑛 = −
(1 + 𝑊𝑛 )2
0.370486 ∙ 𝑡𝑛 ∙ (1 + 1.607858𝑊𝑛 )
𝑣𝑛 =
𝑃𝑛
2 2 2
𝑈𝑣𝑛 = √(𝜃𝑡𝑛 𝑈𝑡𝑛 ) + (𝜃𝑊𝑛 𝑈𝑊𝑛 ) + (𝜃𝑃𝑛 𝑈𝑃𝑛 )
2
𝑈𝑣𝑛 𝑡𝑛 2 𝑈
𝑡 𝑊𝑛 2
𝑈𝑊 2 𝑃𝑛 2
𝑈𝑃 2
= √( 𝜃𝑡𝑛 ) ( 𝑛 ) + ( 𝜃𝑊𝑛 ) ( 𝑛 ) + ( 𝜃𝑃𝑛 ) ( 𝑛 )
𝑣𝑛 𝑣𝑛 𝑡𝑛 𝑣𝑛 𝑊𝑛 𝑣𝑛 𝑃𝑛
53
___________________________________________________________________________________________ AHRI Standard 140-202x (I-P)
0.370486(1.607858𝑊𝑛 + 1)
𝜃𝑡𝑛 =
𝑃𝑛
0.595688879𝑡𝑛
𝜃𝑊𝑛 =
𝑃𝑛
0.370486𝑡𝑛 (1.607858𝑊𝑛 + 1)
𝜃𝑃𝑛 = −
𝑃𝑛 2
∗
1093𝑊𝑠𝑛 − 0.556𝑡𝑛∗ 𝑊𝑠𝑛
∗
− 0.240𝑡𝑛 + 0.240𝑡𝑛∗
𝑊𝑛 =
1093 + 0.444𝑡𝑛 − 𝑡𝑛∗
2 2 2
𝑈𝑊𝑛 = √(𝜃𝑊𝑠𝑛
∗ 𝑈𝑊 ∗ ) + (𝜃𝑡 ∗ 𝑈𝑡 ∗ ) + (𝜃𝑡 𝑈𝑡 )
𝑠𝑛 𝑛 𝑛 𝑛 𝑛
∗ 2 2 2 𝑈 ∗ 2 2 𝑈 2
𝑈𝑊𝑛 𝑊𝑠𝑛 𝑈𝑊𝑠𝑛
∗ 𝑡𝑛∗ 𝑡𝑛 𝑡𝑛 𝑡𝑛
= √( 𝜃𝑊𝑠𝑛
∗ ) ( ) + ( 𝜃 ∗ ) ( ) + ( 𝜃 ) ( )
𝑊𝑛 𝑊𝑛 ∗
𝑊𝑠𝑛 𝑊𝑛 𝑡𝑛 𝑡𝑛∗ 𝑊𝑛 𝑡𝑛 𝑡𝑛
1093 − 0.556𝑡𝑛∗
𝜃𝑊𝑠𝑛
∗ =
1093 + 0.444𝑡𝑛 − 𝑡𝑛∗
∗
1093𝑊𝑠𝑛 0.556𝑡𝑛∗ 𝑊𝑠𝑛∗
0.556𝑊𝑠𝑛 ∗
0.240𝑡𝑛∗ 0.240
𝜃𝑡𝑛∗ = ∗ 2
− ∗ 2
− ∗
+ ∗ 2
+
(1093 + 0.444𝑡𝑛 − 𝑡𝑛 ) (1093 + 0.444𝑡𝑛 − 𝑡𝑛 ) 1093 + 0.444𝑡𝑛 − 𝑡𝑛 (1093 + 0.444𝑡𝑛 − 𝑡𝑛 ) 1093 + 0.444𝑡𝑛 − 𝑡𝑛∗
∗
1093𝑊𝑠𝑛 − 0.24𝑡𝑛 − 0.556𝑡𝑛∗ 𝑊𝑠𝑛∗
+ 0.240𝑡𝑛∗ −0.556𝑊𝑠𝑛 ∗
+ 0.240
𝜃𝑡𝑛∗ = ∗ 2
+
(1093 + 0.444𝑡𝑛 − 𝑡𝑛 ) 1093 + 0.444𝑡𝑛 − 𝑡𝑛∗
∗
0.240 0.444(1093𝑊𝑠𝑛 − 0.24𝑡𝑛 + 0.24𝑡𝑛∗ − 0.556𝑊𝑠𝑛
∗ ∗
𝑡𝑛
𝜃𝑡𝑛 = − −
1093 + 0.444𝑡𝑛 − 𝑡𝑛∗ (1093 + 0.444𝑡𝑛 − 𝑡𝑛∗ )2
entering UUT:
∗ ∗
1093𝑊𝑠𝑖1 − 0.556𝑡1∗ 𝑊𝑠𝑖1 − 0.240𝑡1 + 0.240𝑡1∗
𝑊𝑖1 =
1093 + 0.444𝑡1 − 𝑡1∗
54
___________________________________________________________________________________________ AHRI Standard 140-202x (I-P)
2 2 2
𝑈𝑊𝑖1 = √(𝜃𝑊𝑠𝑖1
∗ 𝑈𝑊 ∗ ) + (𝜃𝑡 ∗ 𝑈𝑡 ∗ ) + (𝜃𝑡 𝑈𝑡 )
𝑠𝑖1 1 1 1 1
2
𝑈𝑊𝑖1 ∗
𝑊𝑠𝑖1 2 𝑈 ∗
𝑊𝑠𝑖1 𝑡1∗ 2
𝑈𝑡1∗ 2 𝑡1 2 𝑈
𝑡1
2
= √( 𝜃𝑊𝑠𝑖1
∗ ) ( ) + ( 𝜃 ∗ ) ( ) + ( 𝜃 ) ( )
𝑊𝑖1 𝑊𝑖1 ∗
𝑊𝑠𝑖1 𝑊𝑖1 𝑡1 𝑡1∗ 𝑊𝑖1 𝑡1 𝑡1
1093 − 0.556𝑡1∗
𝜃𝑊𝑠𝑖1
∗ =
1093 + 0.444𝑡1 − 𝑡1∗
∗ ∗ ∗
1093𝑊𝑠𝑖1 − 0.24𝑡1 − 0.556𝑡1∗ 𝑊𝑠𝑖1 + 0.240𝑡1∗ −0.556𝑊𝑠𝑖1 + 0.240
𝜃𝑡1∗ = +
(1093 + 0.444𝑡1 − 𝑡1∗ )2 1093 + 0.444𝑡1 − 𝑡1∗
∗ ∗ ∗
0.240 0.444(1093𝑊𝑠𝑖1 − 0.24𝑡1 + 0.24𝑡1∗ − 0.556𝑊𝑠𝑖1 𝑡1
𝜃𝑡1 = − ∗ − ∗ 2
1093 + 0.444𝑡1 − 𝑡1 (1093 + 0.444𝑡1 − 𝑡1 )
leaving UUT:
∗ ∗
1093𝑊𝑠𝑖2 − 0.556𝑡2∗ 𝑊𝑠𝑖2 − 0.240𝑡2 + 0.240𝑡2∗
𝑊𝑖2 =
1093 + 0.444𝑡2 − 𝑡2∗
2 2 2
𝑈𝑊𝑖2 = √(𝜃𝑊𝑠𝑖2
∗ 𝑈𝑊 ∗ ) + (𝜃𝑡 ∗ 𝑈𝑡 ∗ ) + (𝜃𝑡 𝑈𝑡 )
𝑠𝑖2 2 2 2 2
2
𝑈𝑊𝑖2 ∗
𝑊𝑠𝑖2 2 𝑈 ∗
𝑊𝑠𝑖2 𝑡2∗ 2
𝑈𝑡2∗ 2 𝑡2 2 𝑈
𝑡2
2
= √( 𝜃𝑊𝑠𝑖2
∗ ) ( ) + ( 𝜃 ∗ ) ( ) + ( 𝜃 ) ( )
𝑊𝑖2 𝑊𝑖2 ∗
𝑊𝑠𝑖2 𝑊𝑖2 𝑡2 𝑡2∗ 𝑊𝑖2 𝑡2 𝑡2
1093 − 0.556𝑡2∗
𝜃𝑊𝑠𝑖2
∗ =
1093 + 0.444𝑡2 − 𝑡2∗
∗ ∗ ∗
1093𝑊𝑠𝑖2 − 0.24𝑡2 − 0.556𝑡2∗ 𝑊𝑠𝑖2 + 0.240𝑡2∗ −0.556𝑊𝑠𝑖2 + 0.240
𝜃𝑡2∗ = ∗ +
(1093 + 0.444𝑡2 − 𝑡2 )2 1093 + 0.444𝑡2 − 𝑡2∗
∗ ∗ ∗
0.240 0.444(1093𝑊𝑠𝑖2 − 0.24𝑡2 + 0.24𝑡2∗ − 0.556𝑊𝑠𝑖2 𝑡2
𝜃𝑡2 = − ∗ − ∗ 2
1093 + 0.444𝑡2 − 𝑡2 (1093 + 0.444𝑡2 − 𝑡2 )
F4.3. Power. As defined in ASHRAE 37, total input power (𝐸𝑡 ) can be calculated as shown in Equation 43.
55
___________________________________________________________________________________________ AHRI Standard 140-202x (I-P)
Where:
Where:
2
𝑈𝑊𝑖𝑛𝑝𝑢𝑡 = √𝐵𝑊𝑖𝑛𝑝𝑢𝑡 2 + (𝑡𝑆𝑊𝑖𝑛𝑝𝑢𝑡 )
2
𝑈𝑃𝐼𝐹 = √𝐵𝑃𝐼𝐹 2 + (𝑡𝑆𝑊𝑖𝑛𝑝𝑢𝑡 )
2
𝑈𝑃𝑖𝑛𝑑𝑜𝑜𝑟 = √𝐵𝑃𝑖𝑛𝑑𝑜𝑜𝑟 2 + (𝑡𝑆𝑃𝑖𝑛𝑑𝑜𝑜𝑟 )
Where:
𝐵𝑊𝑖𝑛𝑝𝑢𝑡 = 𝐵𝑃𝐼𝐹 = 𝐵𝑃𝑖𝑛𝑑𝑜𝑜𝑟 = 0.02 OR Value specified by measurement device
𝑡 = 1.96
F4.4. Efficiency. As defined in ASHRAE 37, steady-state energy-efficiency ratio (𝐸𝐸𝑅𝑠𝑠 ) can be calculated as shown in Equation 44.
2 2
1 𝑞𝑡𝑐𝑖
𝑈𝐸𝐸𝑅𝑠𝑠 = √( 𝑈𝑞𝑡𝑐𝑖 ) + ( 2 𝑈𝐸𝑡 )
𝐸𝑡 𝐸𝑡
56
___________________________________________________________________________________________ AHRI Standard 140-202x (I-P)
F4.5. Pressure Drop. Pressure Drop (ΔP) is defined as Inlet Pressure (P1) minus Outlet Pressure (P2). Pressure Drop Uncertainty can be calculated as
shown in Equation 45:
Where:
Where:
57