Astesj 020124
Astesj 020124
1, 197-205 (2017)
ASTESJ
www.astesj.com
ISSN: 2415-6698
Special Issue on Computer Systems, Information Technology, Electrical and Electronics
Engineering
1. Introduction protectors, are devices that are connected between each electrical
conductor in power and communications systems and the earth [2].
A lightning protector also referred to as a lightning arrestor is a These prevent the flow of the normal power or signal current to
device used on electrical power systems and telecommunications ground, but provide a path over which high voltage lightning
systems to protect the insulation and conductors of the system current flows, bypassing the connected equipment. The purpose
from the damaging effects of lightning. The typical lightning is to limit the rise voltage when a communications or power line
protector, depending on the sizes, has a high voltage terminal and is struck by lightning or being close to a lightning strike. If
a ground terminal. When a lightning surge travels along the power protection fails or is absent, lightning that strikes the electrical
line to the protector, the current from the surge is diverted through system introduces thousands of kilovolts that may damage the
the arrestor, in most cases to earth [1]. transmission lines, and can also cause damage to transformers and
In telegraphy and telephony, a lightning protector is placed other electrical and electronic devices including home appliances
where wires enter a structure, preventing damage to electronic [2-4].
instruments within and ensuring the safety of individuals nearby. Also exceeding the capability of an arrester will crack or
Smaller versions of lightning protectors, also called surge puncture the metal-oxide disk(s), in effect reduce the arrester
*
Corresponding Author: Mbunwe Muncho Josephine, Department of Electrical internal electrical resistance, thus, the condition will limit the
Engineering, University of Nigeria Nsukka, +2348036675952;
E-mail: [email protected] arrester’s ability to survive future system conditions. This
www.astesj.com 197
https://dx.doi.org/10.25046/aj020124
M.M. Josephine et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 2, No. 1, 197-205 (2017)
condition does not jeopardize the insulation protection provided strokes, the stroke travels in both directions from the point where
by the arrester, but in an unlikely case of complete failure of an the stroke originated. Wave velocity is an inverse function of the
arrester, a line-ground arc will develop and pressure will build up surge impedance. Waves travel on an overhead line at
inside the housing of the arrester. This pressure will be safely approximately 1000 ft. per microsecond, in cables about 300 –
vented to the outside and an external arc will be established 600 ft. per microsecond and in a buried conductor about 300 ft.
provided the fault current is within the pressure relief fault current per microsecond. The velocity internal to a rotating machine may
capability of the arrester. This low-voltage arc maintains be only 25ft. per microsecond [4-8].
equipment protection. Once an arrester has safely vented, it no
longer possesses its pressure relief/fault current capability and The current resulting from a traveling wave is equal to the
should be replaced immediately. For a given application, the voltage divided by the impedance, E . Wave current is
Z
arrester selected should have a pressure/fault current capability approximately two to four amps per kilovolt of surge voltage.
greater than maximum short-circuit current available at the Lightning waves on overhead lines gradually attenuate with travel.
intended arrester location. This rating of arrester capability should When the wave runs into a change in impedance (transformer,
include appropriate allowances for future growth in the system [3- another line, etc.), the wave continues in the same direction at a
7]. different magnitude. It will also reflect back in the direction from
which it came. When a wave 𝐸𝐸1 traveling on surge impedance 𝑍𝑍1
Surge arresters when installed are exposed to many physical
factors on the earth. These factors that such arresters are exposed encounters surge impedance𝑍𝑍2 , the voltage on the new wave 𝑍𝑍2
to when they are in operation are expected to affect them in one becomes:
way or the other. These factors are temperature, spacing of the
arresters and earth resistance. The villages around the Donga E = E 2Z 2
(1)
Matung Division of North West Province of Cameroon have the
2
E +E
1
1 2
highest annual average number of lightning storms in the Note: as the new surge impedance 𝑍𝑍2 approaches infinity,
Cameroon. On average, between 40 and 90 thunderstorms hit the
representative of an open line, 𝐸𝐸2 = 2𝐸𝐸1 .
areas along the Binshua each year, while Nkambe and some
villages along the Donga border have an average of less than 10 The reflected wave will actually double in magnitude in its
per year. So, it is easy to understand that surge protection of return in the opposite direction. Unless the wave is discharged to
electrical equipment is a very important part of the electrical ground (lightning arrester connected to ground), the reflected
system design. Lightning strikes are not the only sources of wave can severely damage electrical equipment. Surges produced
voltage surges in the electrical system. The following are a few of by lightning have high magnitudes, but their durations are very
the more frequently encountered causes of transient voltage short. The lightning discharge may reach its crest value in
surges: approximately 1 to 20 microseconds and produce conduction
flashover voltages of 5 to 20 times normal in 1 microsecond or
• Surge voltages associated with switching capacitors; less. The wave shape is customarily expressed by two intervals
• Surge voltages due to a failure in equipment insulation associated with the wave geometry. The first time interval is
resulting in a short circuit on the distribution system; between a virtual zero and crest; the second time interval is
• Surge voltages associated with the discharge of lightning between the virtual zero and the half crest value on the wave tail.
arresters at other locations within the facility. The wave is defined if the crest value is added to the two time
When capacitors are switched in and out of the circuit, it is interval designations. For example, a 20000 amp 10 x 20
possible to get a re-strike when interrupting the capacitor circuit microsecond current wave rises to a crest of 20000 amperes in10
current. A steep-front voltage excursion may be created from each microseconds after virtual zero and decays to 10000 amperes in
re-strike. These voltage excursions may be high enough to 20microseconds after virtual zero.
damage rotating machines applied at the same voltage. A surge
capacitor applied at the motor terminals can change the steepness In addition to component failures, it can cause system upset,
of the wave front enough to protect the motor. A short circuit can lost data, erroneous signals and false system operations. Thus,
cause a voltage surge in excess of 3 times the normal line to surge arresters should be designed for all bus systems and system
neutral crest value. The magnitude and steepness of the wave front configuration to maintain system reliability regardless of the
is not as severe as that of a lightning strike, but can cause damage cause or magnitude of these transients. Surge arrester products
or weaken motor windings that do not have the higher Basic should be invaluable to any business when planning for protection
Impulse Insulation Level (BIL) ratings of other equipment. from unforeseen occurrences [3, 5, 9]. There are different series
of surge arrester and where they can be applied in electrical
When lightning, discharges through an arrester, surge currents engineering. Below is the list:
are discharged into the grounding terminal. It is very important
that substations and overhead lines be protected with well- • Low-voltage surge arrestor
grounded shield wires. It is also equally important that the ground • Distribution arrestor
system between pieces of equipment be bonded together with • The station type of common valve arrestor
interconnected ground wires dedicated to the grounding system. • Magnetic blow valve station arrestor
When a surge is released on a line by direct strokes or induced
www.astesj.com 198
M.M. Josephine et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 2, No. 1, 197-205 (2017)
• Protection of rotating machine using magnetic blow
valve arrester: • Metal Oxide Varistor (MOV)
• Line Magnetic blow valve arrester: A metal oxide varistor consists of a bulk semiconductor
• DC or blowing valve-type arrester: material (typically sintered granular zinc oxide) that can conduct
• Neutral protection arrester: large currents (effectively short-circuits) when presented with a
• Fiber-tube arrester: voltage above its rated voltage. MOVs typically limit voltages to
• Plug-in Signal Arrester: about 3 to 4 times the normal circuit voltage by diverting surge
• High-frequency feeder arrester: current elsewhere than the protected load. MOVs may be
• Receptacle-type surge arrester: connected in parallel to increase current capability and life
• Signal Arrester: expectancy, providing they are matched sets (unmatched MOVs
• Network arrester: have a tolerance of approximately ±20% on voltage ratings, which
• Coaxial cable lightning arrester [5-7]. is not sufficient). MOVs have finite life expectancy and "degrade"
when exposed to a few large transients, or many smaller
transients. As a MOV degrades, its triggering voltage falls lower
2. Related Work
and lower. If the MOV is being used to protect a low-power signal
2.1. Principles of Surge Arresters (Heading 2) line, the ultimate failure mode typically is a partial or complete
short circuit of the line, terminating normal circuit operation.
Though there are different types and classes of surge arresters, When used in power applications, MOVs usually are thermal
they all work on the same general principle. Surge arrester works fused or otherwise protected to avoid persistent short circuits and
by conducting excess voltages from a signal or power-carrying other fire hazards. In a typical power strip, the visible circuit
conductor to ground. breaker is distinct from the internal thermal fuse, which is not
normally visible to the end user. The circuit breaker has no
2.1. Surge Arrester Specification
function related to disconnecting an MOV. A thermal fuse or
Most electrical equipment is rated for traveling wave voltage some equivalent solution protects from MOV generated hazards.
surge capability by the Impulse Test. The Impulse Test is most • Transient voltage suppression (TVS) diode
common and consists of applying a full-wave voltage surge of a A TVS diode is a type of Zener diode, also called an avalanche
specified crest value to the insulation of the equipment involved diode or silicon avalanche diode (SAD), which can limit voltage
[6]. The crest value of the wave is called the Basic Impulse spikes. These components provide the fastest limiting action of
Insulation Level (BIL) of the equipment. Each type of electrical protective components (theoretically in picoseconds), but have a
equipment has a standard BIL rating. Lightning arresters are relatively low energy absorbing capability. Voltages can be
coordinated with standard electrical equipment insulation levels clamped to less than twice the normal operation voltage. If current
so that they will protect the insulation against lightning over impulses remain within the device ratings, life expectancy is
voltages [7]. This coordination is obtained by having an arrester exceptionally long. If component ratings are exceeded, the diode
that will discharge at a lower voltage level than the voltage may fail as a permanent short circuit; in such cases, protection
required to break down the electrical equipment insulation. may remain but normal circuit operation is terminated in the case
Equipment has certain applicable impulse levels or BIL as defined of low-power signal lines. Due to their relatively-limited current
in industry standards [8]. Follow Current, Discharge current and capacity, TVS diodes are often restricted to circuits with smaller
voltage - The follow current is the current which flows from current spikes. TVS diodes are also used where spikes occur
connected supply sources through lightning arrester following the significantly more often than once a year, since this component
passage of discharge current [11]. From the discharged current, will not degrade when used within its ratings. A unique type of
the surge current flows through the arrester after the spark over, TVS diode (trade names Transzorb or Transil) contains reversed
while the discharge voltage is the peak value of the voltage paired series avalanche diodes for bi-polar operation.TVS diodes
appearing between the line terminals and ground, during the are often used in high-speed but low power circuits, such as occur
passage of the discharge current [5, 9-11]. in data communications. These devices can be paired in series
2.2. Surge Arresters Characteristics with another diode to provide low capacitance as required in
The following types of electrical or electronic devices can be communication circuits.
used to reduce or limit voltage surges. Some surge suppression • Thyristor Surge Protection Device (TSPD)
systems use multiple technologies, since each method has its A Trisil is a type of thyristor surge protection device (TSPD), a
strong and weak points. The first six types listed operate primarily specialized solid-state electronic device used in crowbar circuits
by diverting unwanted surge energy away from the protected load, to protect against overvoltage conditions. A SIDACtor is another
through a protective component connected in a parallel (or thyristor type of device used for similar protective purposes.
shunted) topology. The last two methods also block unwanted These thyristor-family devices can be viewed as having
energy by using a protective component connected in series with characteristics much like a spark gap or a gas discharged tube
the power fed to the protected load, and additionally may shunt (GDT), but can operate much faster. They are related to TVS
the unwanted energy like the earlier systems. Among the diodes, but can "breakover" to a low clamping voltage analogous
numerous types are [6]: to an ionized and conducting spark gap. After triggering, the low
www.astesj.com 199
M.M. Josephine et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 2, No. 1, 197-205 (2017)
clamping voltage allows large current surges to flow while arresters and earth resistance. Figure 1 below shows the effect of
limiting heat dissipation in the device. temperature.
3. Methodology Z P ( Z 1 + Z 2 )V
V1= (3)
( Z P Z 1 + Z P Z 2 + Z 1Z 2)
3.1. Presentation of methods for assessing surge arrester
performance
3.3. Selection of lightning arrester
The choice for selecting the arresters is determined by the
parameters: The lightning arresters are designated by the crest magnitude of
the discharge current having 10 × 20𝜇𝜇𝜇𝜇 wave shape which the
• Surge arrester ratings. arrester can safely pass without causing damage. The lightning
• Impedance division under normal and abnormal arresters are designated as 8, 10, 20 KA and can safely discharge
conditions to determine whether it will act as low these current crests. The discharge current from the arrester varies
resistive unit under abnormal conditions. from a few hundred amperes to kilo-amperes Maximum discharge
• Selecting station class for its protection capability and voltage (crest value) and discharge factor for the arrester is
distribution class for its restoration capability. defined as the maximum value of voltage which appears across
• Also the location of the arrester, determined by the the arrester terminals at the time of discharging if rated current
terminal point of the protected equipment. determines its impulse level of protection. The discharge factor is
3.2. Application and Selection of Surge Arrester given as in equation 5, to get a result that falls within 2.4 to 3.0:
The objective of arrester selection is to select the lowest rated DF = v da (4)
surge arrester which will provide adequate overall protection of v ra
www.astesj.com 201
M.M. Josephine et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 2, No. 1, 197-205 (2017)
Where, v da
= discharge voltage of the arrester • Specification of Lightning Arrester for Incoming Side
Incoming side of residential, the specifications of lightning
arrester are as follow.
v ra
= rated voltage of the arrester System nominal voltage = 0.415kV
Rated normal Voltage = 0.415 × 1.1 = 45.65kV
The above ratio for arresters manufactured by different companies Continuous Operating Voltage (kV) rms = 48.0kV
varies from 1.6 to 1.8, so, the average value may be taken as 1.7 Normal Discharge Current (8 /20μs) kA = 10kA
E rated arrester voltage KV (R.M.S value) and LS as the minimum 1/50 Impulse Spark over Voltage = 163.5kV
impulse insulation level in kV (crest valve) with value after Frequency (Hz) = 50Hz
allowing 10% as tolerance factor and 25% as margin factor can be Type = outdoor
obtained.
• Specifications of Lightning Arrester for Outgoing Side
The followings are the specifications of lightning arrester for
1.25 × 1.1 × 1.7 × 2
L S
=
0.8
E = 4.13E (5) outgoing side of residential.
System nominal voltage = 0.220kV
Rated normal Voltage = 0.22 × 1.1 = 24.20kVkV
In a case of Extra High Voltage (EHV) system, the maximum Continuous Operating Voltage (kV) rms = 24kV
impulse LP in kV implies: Normal Discharge Current (8 /20μs) (kA) = 10kA
LP = 2.3 × power frequency withstand voltage in kV (RMS) Frequency (Hz) = 50Hz
Type = outdoor
= 2.3 EL (6)
• Intermediate class arrester
For 75% arrester, Application is based upon the maximum continuous operation
voltage, line to neutral, at the arrester location. For grounded
LP = 2.37 EL (7) neutral systems (GNS), this is computed as:
For 80% arrester,
GNS = sv m (9)
LP=2.53EL (8) 3
3.4. Surge current ratings
Where, sv m
= maximum system voltage.
For historical comparison, the maximum continuous operating
The surge current normally is the largest single surge that a device voltage is 81% of the conventional 71% arrester installed on an
can withstand without damage, should exceed the largest surge effectively grounded neutral system.
that SPD would experience in service. This work uses the largest • Earthing system and Lightning earthing
surge that can be expected at the service entrance as resistance to The frame of every generator, stationary motor, portable motor,
multiple 3 kA (8/20𝜇𝜇𝜇𝜇) surge for panel protectors. At the service and metallic parts of all transformers and the regulating and
entrance SPD rate the surge current per phase which can be controlling apparatus connected with supply shall be earthed by
calculated by adding the surge current from individual modes of separate and distinct connection with earth. Every conductor used
protection L-N and L-G. Thus, surge current ratings for residential on earthing shall be of stranded solid copper or suitable copper
should fall within 10 kA to 70 kA per phase with test waveforms alloy, and shall be protected wherever liable to mechanical
other than 8/20 𝜇𝜇𝜇𝜇 also acceptable. This work uses surge current damage. Also, against corrosion, particular attention being given
ratings of 20 kA to 70 kA (8/20𝜇𝜇𝜇𝜇) per phase. For high-lightning in these respects to the earthing leads at its point of connection
area, like Binshua, SPDs with higher surge current ratings in the with the earth electrode. The coefficient of earthing is below 80
range of 40 kA to 120 kA is used in order to provide a longer percent. With earthing coefficient less than 80% in this case, on
service life and higher reliability. four wire distribution systems, the transformer neutral is solidly
grounded at every voltage level. On high voltage transmission
3.5. Lightning Arrester Design systems the coefficient of earthing does not exceed 75%. In
A station class and intermediate surge arresters are used. The earthing system, lightning arresters with PVC coated wire and
system voltage is 0.415kV and maximum continuous cable lug are used.
operation voltage is 48 kV rms. The duty cycle rating is 60 kV •
415V Lighting Arrester (70mm2 PVC Coated Wire) =
rms and maximum discharge current is 10 kA. 50’’
•
220V Lighting Arrester (70mm2 PVC Coated Wire) =
1. Maximum 0.5μs discharge voltage = 163.5 kV 100’’
2. Maximum switching surge protective level=116.4 kV •
70mm2 Cable Lug = 2
3. Maximum discharge voltage using an 8/20=148.8 kV 3.5.1. Design Data
Current wave-kV For incoming side and outgoing side, the discharge voltage,
The maximum discharge voltage for a10kA impulse current insulation level, minimum impulse insulation level and power
wave produces a voltage wave cresting in 0.5μs. frequency withstand voltage base on 100% arrester are as shown
www.astesj.com 202
M.M. Josephine et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 2, No. 1, 197-205 (2017)
in Table.1. Ground voltage peak value and switching surge
withstand voltage are also shown in Table.1.
Where, v Hrms
= highest rms voltage of healthy line to earth
www.astesj.com 203
M.M. Josephine et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 2, No. 1, 197-205 (2017)
The lists arrester ratings, from a manufacturer, that would 3.6. Designing a Home Surge Arrester System
normally be applied on systems of various line-to-line voltages The design of any surge arrester comes under the same
are as shown in Table 2 [12]. principle which is to ground any excess voltage that comes into
the electrical or electronic system. This could be achieved by
Table 2: Typical Arrester Ratings for System Voltage
considering the circuit diagram as shown in Figure 5.
Arrester Rating (kV)
Norminal System Grounded High Impedance
L-L Voltage Neutral Circuits Grounded,
(kV) Ungrounded or
Temporarily
Ungrounded
4.5 4.5
5.1
--- 6.0 From the Figure 4, MOVs are connected in parallel to increase
6.9 6.0 --- current capability and life expectancy, which, when exposed to a
few large transients, or many smaller transients. The MOV
--- 7.5 degrades, when its triggering voltage falls lower and lower.
--- 8.5 When used in power applications, MOVs usually are thermal
fused or otherwise protected to avoid persistent short circuits and
12.47 9.0 ---
other fire hazards. In a typical power strip, the visible circuit
10 --- breaker is distinct from the internal thermal fuse, which is not
normally visible to the end user. The circuit breaker has no
--- 12
function related to disconnecting an MOV. A thermal fuse or
--- 15 some equivalent solution protects from MOV generated hazards.
13.2, 13.8 10 --- 3.7. Modes of Protection
4. Conclusion
In this paper, the basis theory of lightning, lightning shielding
and design of lightning arrester are presented. Station class and
intermediate arresters are used. The type of arrester is outdoor
type. The rated voltages of arresters are 46kV and 25kV, the
maximum discharge current is 10kA and MCOV are 48kVrms
and 24kVrms. The lightning arrester in this paper is provided for
overvoltage protection in a high-lightning area. This paper will
help and give the electrical knowledge of the protection system in
6(a) high-lightning area which coach to the technicians, the
professional engineers, the students who are facing the
overvoltage condition and protection coordination in high-
lightning area.
Conflict of Interest
References
[1] J. Hernandez, GE Specification Engineer; “Lightning Arresters: A Guide to
Selection and application”.
[2] Lightning arrester. From Wikipedia, the free encyclopedia
www.wikipedia.com.
[3] J.G. Anderson, “Transmission line Reference Book, 345Kv and above”, 2nd
edition. EPRI, Palo Alto, CA (1982)
6(c) [4] Allan Greenwood, “Electrical transients in power system”, Wiley, 1971
- Technology & Engineering - 544 pages
Figure 6. A simplified surge protection device (SPD) circuit [5] Surge arrestor. From Wikipedia, the free encyclopedia www.wikipedia.com.
[6] L. Pryor, P.E., GE, Sr. Specification Engineer; “The Application and
3.8. Installation of Home Surge Arrester Selection of Lightning Arresters”.
[7] Surge arrester, G31-A75X-X809. www.epcos.com
Today’s modern homes are filled to the brim with technology
[8] DEHN + SÖHNE, “Lightning protection guide”, 3rd updated edition as of
products -- from personal music players, e-readers and laptops to December 2014 www.dehn-international.com
HDTVs to hi-tech refrigerators and washing machines. These [9] A. Piantini, “Lightning Protection of overhead power distribution lines”, 29th
appliances and electronics feature delicate circuitry that can easily international conference on lightning protection June 2008; Uppsala,
Sweden.
be destroyed by a simple fluctuation in the home’s voltage. This [10] D. Donovan, “Whole-House Surge Arrester: DIY Installation Guide”.
can be caused by lightening or a surge in the power grid. http://www.stevejenkins.com/
[11] N. K. Htwe, “Analysis and Design Selection of Lightning Arrester for
In order to protect these sensitive items, we usually plug their Distribution Substation”, World Academy of Science, Engineering and
Technology 48 2008.
power cords into surge protectors. But, as more electronics [12] ANSI/ IEEE 1989, “IEEE Standard for Gapped Silicon-Carbide Surge
become further integrated into our daily lives, we find ourselves Arresters for AC Power Circuit”.
having to protect all of them, which makes having surge
protectors for every piece of electronics a problem. One way to
www.astesj.com 205