Ground Resistance Measurement Guide
Ground Resistance Measurement Guide
Ground
Resistance
2
Measurement methods
Measurement procedure
(1) Disconnect the grounding electrode you wish to measure from from the
power supply system.
(2) Insert the auxiliary grounding electrode S (P) into the ground a distance of E (C1) S (P) H (C2)
10 m away.
(3) Insert the auxiliary grounding electrode H (C) into the ground another 10 m
away.
(4) Connect the earth tester’s E terminal, S (P) terminal, and H (C) terminal to > 10 m > 10 m
I1
Efficiency improvement by not having to disconnecting the R3
a [m]
R2 R1
grounding electrode using the MEC function* (FT6041 only)
I3 I2 I1 I = I1 + I2 + I3
A clamp sensor is used to measure current flowing to the grounding elec-
trode. This approach allows the grounding electrode to be measured while it
remains connected to the power supply system. R1 = V
I1
*MEC stands for “measuring earth with a clamp.”
Measurement principle
Prepare two clamps, one for applying/injecting a voltage and the other for sensing/measuring the current. If you attach the voltage injec-
tion clamp to the ground resistance Rx you wish to measure, current will flow to all multiple grounds. If you measure the current flowing to
Rx with the current measurement sensor, you will have measured the current as in the following equation:
Rx + 1/[(1/R1) + (1/R2) + (1/R3) + (1/R4) + ...] = V/I
If there are numerous connections, the value within the square brackets above will be extremely small, with the result that Rx ≈ V / I.
1
What method will you use to make measurements?
4-pole method 3-pole method 2-pole method Clamp method
5 Long cables causing long testing times?
The most typical ground resistance measurement method is the 3-pole Measuring ground resistance involves using long measurement cables
method, but the clamp measurement method is well suited to measuring that are dozens of meters in length. As a result, not only measurement
ground resistance when there are multiple grounds. Alternately, you’ll itself, but also set-up and clean-up take time. Check for features that
need an instrument that’s capable of 4-pole measurement if you need to help streamline work, such as reels that let you quickly rewind mea-
measure soil resistivity. Choose an earth tester that can accommodate surement cables.
the measurement method you plan to use.
It takes time to drive elec- Make measurements With this earth nets mod-
trodes deep into the ground. without inserting auxiliary ule, simply open and pour
Electrodes can’t be used at grounding electrodes water on it, and you can
all in some locations. deep into the ground. measure on soil or hard
surfaces like concrete.
5
Comparison chart
Choosing the right instrument for your application will help ensure stable measurement while streamlining your work.
Two-pole method -
Ground potential -
0 to 30.0 V RMS 0 to 30.0 V RMS 0 to 30.0 V RMS
Measurement range
2 (ground resistance)
3 Ω to 300 kΩ 20 Ω to 2000 Ω 10 Ω to 1000 Ω 0.20 Ω to 1600 Ω
3 Measuring frequency 94, 105, 111, 128, 55 Hz 128 Hz 575, 600 Hz 2375 Hz
5 Cord winders -
‒25℃ to 65℃ ‒25℃ to 65℃ 0℃ to 40℃ ‒10℃ to 50℃
Operating temperature
(-13℉ to 149℉) (-13℉ to 149℉) (32℉ to 104℉) (14℉ to 122℉)
IP40
6 Dustproof and waterproof IP67 IP67 IP40
with jaws closed
1 m above concrete 1 m above concrete
Drop-proof - -
(with protector attached) (with protector attached)
Support for GENNECT Cross
7 (storage of measured values) -
Clamp measurement method
(with optional sensor)
8 (maximum measurable conductor
diameter) φ 52 mm (2.05 in.)
- -
φ 32 mm (1.26 in.)
78 mm (3.07 in.) × 20 mm (0.79 in.) busbar
WIRELESS ADAPTER
Z3210 (option)
GENNECT Cross is a free app. The iOS version can be downloaded from the App Store®, while the Android version can be downloaded from Google Play™.
Search for “GENNECT Cross” on Google Play™ or the App Store® or scan the QR code below.
6
EARTH TESTER
FT6041
Field-capable
Fast-working
Extensive measurement functionality
Accuracy guaranteed for 1 year
Product warranty for 3 years
Extensive measurement functionality: choose the right measurement method for any application
> 10 m > 10 m
E (C1)
V
S (P) H (C)
I1 E(C1)
a [m]
R3 R2 R1 ES(P1) S(P2) H(C2)
I3 I2 I1 I = I1 + I2 + I3
R1 = V
I1
Current
measurement I
Rn R2 R1 R
In I2 I1 I
R= V -
1 ~ V Clips up to 28 mm (1.10 in.)
I 1 + 1 + ... + 1
R1 R2 Rn
I Small enough to affix to a busbar
Shorter
work times
Allowable resistance
IP67
With protector attached
Operating temperature range Drop-proof design
-25°C to 65°C 1m
Dirt, sand, and rain resistance Extreme cold, extreme heat. The FT6041 Withstands being dropped onto concrete
IP67 dust and water protection won’t fail, even during extended operation. from a height of 1 m
Since the Earth Tester FT6041 is designed to The instrument, which is designed to be used Use the FT6041 outdoors with peace of mind
keep dust and dirt out of its enclosure, you can outdoors for extended periods of time, features thanks to a tough design that’s built to with-
use it in the field without worrying about mud or a design resilient to extreme temperatures that stand being dropped from a height of 1 m
dust. If it gets dirty, simply rinse it off with water. allows use in a broad temperature range. during use.
Basic specifications
• Ground resistance measurement: 4-pole method, 3-pole method, 2-pole method, MEC function, clamp-on measurement (two clamps)
Measurement
• Soil resistivity measurement: 4-pole method • Low-resistance measurement: 4-terminal method, 2-terminal method
parameters
• Ground potential measurement
Ground potential 0 to 30.0 V RMS, accuracy: ±2.3% rdg. ±8 dgt. (50/60 Hz), ±1.3% rdg. ±4 dgt. (DC)
Live wire warning, auto power save, soil resistivity display (4-pole method only), zero-adjustment, auto-hold, continuous measurement mode,
Functions wireless communication (only when Z3210 is connected), buzzer sound, comparator, switching the display, ground potential overload display
(when measuring ground resistance)
Operating temperature
-25℃ to 65℃*1 (non-condensing)
and humidity
Storage temperature
-25°C to 65°C: 80% RH or less (non-condensing)
and humidity
Dustproof and
IP65/IP67 (EN60529)
waterproof
Applicable standards EN 61010 (safety), EN 61326 (EMC), EN61557-1/EN61557-10/EN61557-14 (low-resistance measurement, earth testers), EN61557-5 (earth testers)
Power supply HR6 nickel-metal hydride battery x 4 or LR03 alkaline battery × 4
Number of measurements 500 times (3-pole method, without Z3210 installed)
per battery charge*2 400 times (3-pole method, with Z3210 installed and using wireless communication)
Dimensions and mass Approx. 189 mm (7.44 in.)W × 148 mm (5.83 in.) H × 48 mm (1.89 in.) D, approx. 765 g (26.98 oz.) (including battery, protector)
EARTH TESTER
FT6041
Qty. Note
Included accessories AUXILIARY EARTHING ROD L9840 2 270 mm (10.63 in.), stainless steel, set of 2
MEASUREMENT CABLE L9845-31 1 Yellow, 25 m (82.02 ft.), equipped with winder
MEASUREMENT CABLE L9845-33 1 Blue, 25 m (82.02 ft.), equipped with winder
MEASUREMENT CABLE L9845-52 1 Red, 50 m (164.04 f.t), equipped with winder
MEASUREMENT CABLE L9841 1 Black alligator clip, 4 m (13.12 ft.) long
TEST LEAD L9787 1 Bundled with line/ground lead, aligator clip, 1.2 m (3.94 ft.) long
EARTH NETS MODULE L9846 2 Use with measuring cord set, built-in grounding/earth nets
CARRYING CASE C0208 1 For storing FT6041 and clamp sensors, hard type
CARRYING CASE C0209 1 For storing measurment cables, soft type
Protector 1 Attaches to and protect FT6041
LR6 Alkaline battery 4
Instruction manual 1
Operating precautions 1
FT6041-91 set FT6041 and included accessories, also includes clamps FT9847 and CT9848
Products included
in FT6041-91 Qty. Note
For signal induction, including resistance
SIGNAL INDUCTION
1 check loop, φ52 mm (2.05 in.) or less,
CLAMP FT9847
78 mm (3.07 in.) × 20 mm (0.79 in.) bus-bar
OLAMP ON SENSOR For detection, φ52 mm (2.05 in.) or less,
1
CT9848 78 mm (3.07 in.) × 20 mm (0.79 in.) bus-bar
FT6041 and included accessories FT9847 CT9848
Options for FT6041 sold separately To ensure safety, use the separately sold Test Lead L9787 when making measurements using the two-pole method.
SIGNAL INDUCTION CLAMP CLAMP ON SENSOR WIRELESS ADAPTER Z3210 AUXILIARY EARTHING ROD MEASUREMENT CABLE MEASUREMENT CABLE MEASUREMENT CABLE
FT9847 (for signal induction) CT9848 Bluetooth® communication L9840 L9841 L9842-11 L9842-22
Including resistance check (for detection) will be possible by 2 piece set, stainless steel Alligator clip, black, Yellow 10 m (32.81 ft.) long, Red 20 m (65.62 ft.) long,
loop attaching to the FT6041 4 m (13.12 ft.) long equipped with winder equipped with winder
TEST LEAD L9787 PIN TYPE LEAD 9772 LARGE CLIP TYPE LEAD 9467 EARTH NETS 9050 CARRYING CASE C0208 CARRYING CASE
Bundled with line/ground For low-resistance For low-resistance 2 sheets in set For storing FT6041 and C0209
lead, aligator clip, 1.2 m measurement by measurement by clamps, hard type For storing measurment
(3.94 ft.) long 4-terminal method 4-terminal method cables, soft type
9
EARTH TESTER
FT6031-50
IP67
Dustproof and waterproof enclosure for Accurately measures 5 Ω Excellent noise resistance
robust performance in the field High precision & zero-adjustment Allowable ground potential: 25.0 V RMS
Since the FT6031-50’s enclosure is designed to The FT6031-50 delivers high accuracy of ±1.5% Even in an environment where the ground
keep out dust, it can be used with peace of mind rdg. ±8 dgt. The zero-adjustment function aids in potential is 25 V RMS, stable ground resistance
in settings where it would be exposed to mud delivering even better accuracy by canceling the can be measured.
and dust. And if the instrument gets dirty, it can wiring resistance of long measurement cable runs.
be rinsed clean with water.
WIRELESS ADAPTER
Z3210 (sold separately)
Single
insertion
The tolerance for the supplemental Tangle- and twist-free measurement cord Add wireless communication capability by
grounding electrode’s resistance: 50 kΩ winders connecting Wireless Adapter Z3210
It eliminates the inconvenience of reinserting the Measurement cord retrieval is a time-consuming Transfer measurements to your phone or tablet.
auxiliary grounding rod over and over again due part of ground resistance measurement. The Generate reports with site photos and drawings
to increased soil resistance of dry soil or other FT6031-50's newly developed winders allow cords with the free app GENNECT Cross
non-optimal conditions, saving working time. The to be rewound about twice as quickly as with
grounding rod is thin making it easier to insert conventional reels.
and remove, and is made of hard, rust-resistant
stainless steel.
Basic specifications
Measurement system Two-pole method or three-pole method
Measurement range 20 Ω (0 to 20.00 Ω) 200 Ω (0 to 200.0 Ω) 2000 Ω (0 to 2000 Ω)
Accuracy ±1.5% rdg. ±8 dgt. ±1.5% rdg. ±4 dgt. ±1.5% rdg. ±4 dgt.
0 to 30.0 V RMS
Ground potential Accuracy: ±2.3% rdg. ±8 dgt. (50/60 Hz), ±1.3% rdg. ±4 dgt. (DC)
Allowable ground potential 25.0 V RMS (DC or sine wave)
Operating temperature and humidity -25℃ to 65℃*1 (non-condensing)
Storage temperature and humidity -25°C to 65°C (-13℉ to 149℉): 80 % RH or less (non-condensing)
Dustproof and waterproof IP65/IP67 (EN60529)
Applicable standards Safety: EN 61010 (main unit), EN 61010 (measuring circuit); EMC: EN 61326; earth testers: EN 61557
LR6 alkaline battery ×4, possible number of measurements for one set of batteries: 500 times (measurement
Power supply conditions: three-pole method, measuring 10 Ω at 10-second intervals without Z3210 installed)
185 mm (7.28 in.) W × 111 mm (4.37 in.) H × 44 mm (1.73 in.) D, 570 g (20.1 oz.) (including batteries and
Dimensions and mass protector, excluding terminal covers and other accessories)
*1: -25℃ to 40℃, -13℉ to 104℉ (80% RH or less), 40℃ to 45℃, 104℉ to 113℉ (60 % RH or less), 45℃ to 50℃, 113℉ to 122℉ (50% RH or less), 50℃ to 55℃, 122℉ to 131℉ (40% RH or less),
55℃ to 60℃, 131℉ to 140℉ (30% RH or less), 60℃ to 65℃, 140℉ to 149℉ (25% RH or less)
See p. 12 for included accessories and options sold separately
10
Current
Clamp-on measurement CAT IV 600 V GENNECT Cross
Accuracy guaranteed for 1 year method True RMS (with Z3210)
Product warranty for 3 years
22 mm
(0.87 in.)
32 mm 20 mm
(1.26 in.) (0.79 in.)
Alarm Function
Set the alarm to audibly and visually
notify yourself that the resistance or Large storage capacity
current value exceeds the threshold. (up to 2,000 values)
You can store up to 2,000 measurement
values in the field and utilize them in
your office later.
Cloud E-mail
Applications
Multiple grounds can be easily checked with the clamps.
Hazardous Transmission
storage tanks towers
Measurement precaution
In measuring ground resistance of poles for multi-grounded systems, the number of ground poles influences the accuracy of measurement.
If there are few ground poles, the ground resistance of that pole will be measured as higher than the actual value. On the other hand, the
more poles there are, the closer the measured value of that pole will be to its actual value. It is up to the skilled technician to take all of these
factors into account to accurately measure the ground poles for multi-grounded systems.
Measured value Measured value Measured value
20 Ω 15 Ω 12 Ω
10 Ω 10 Ω 10 Ω 10 Ω 10 Ω 10 Ω 10 Ω 10 Ω 10 Ω 10 Ω 10 Ω
Basic specifications
Instrument has two cores for voltage injection and current measurement. The total circuit loop resistance is calculated
from the defined voltage and measured current.
Measurement principle
Note: It is for multi-grounded systems only. In a multi-grounded system, the larger the number of ground poles, the more
accurate the measured value.
Ground resistance 0.20 Ω (0.01 Ω resolution) to 1600 Ω (20 Ω resolution), 10 ranges; zero suppression: less than 0.02 Ω; accuracy: ±1.5%
range rdg. ±0.02 Ω
20.00 mA (0.01 mA resolution) to 60.0 A (0.1 A resolution), 5 ranges; zero suppression: less than 0.05 mA; accuracy:
AC current range
±2.0% rdg. ±0.05 mA (30 to 400 Hz, true RMS); crest factor: 5.0 or less (for the 60 A range, 1.7 or less)
Maximum input current 100 A AC continuous, 200 A AC for 2 minutes or shorter (at 50/60 Hz, requires derating at frequency)
(current measurement)
Maximum rated
terminal-to-ground 600 V AC measurement category IV (anticipated transient overvoltage 8000 V)
voltage
Memory function 2000 values
Alarm function It beeps when measured value is less than or greater than threshold (resistance/current measurement)
Current harmonic levels up to 30th, content factor, total harmonic distortion ratio
Harmonic levels
(harmonics can be displayed with our free app GENNECT Cross when the Z3210 installed.)
Other functions Data hold, backlight, filter, auto power save, wireless communication (with Z3210 installed)
Dust-proof and IP40 (EN60529) with jaws closed
waterproof
Applicable standards Safety: EN61010; EMC: EN61326
Power supply LR6 alkaline battery × 2
Continuous operating Approx. 40 hours (25 Ω measurement, backlight off, without Z3210 installed)
time per battery set Approx. 35 hours (25 Ω measurement, backlight off, with Z3210 installed and using wireless communications)
Dimensions and mass Approx. 73 mm (2.78 in.) W × 218 mm (8.58 in.) H × 43 mm (1.69 in.) D, approx. 620 g (21.87 oz.) (except for the battery)
Read from the scale Green bar = within allowable resistance of auxiliary
grounding electrode
Basic specifications
Dramatically faster set-up and break-down
Measurement AC potential difference detection method
method (Two-pole method or three-pole method)
Measurement range 10 Ω (0 to 11.5 Ω) 100 Ω (0 to 115 Ω) 1000 Ω (0 to 1150 Ω) Prep Cleanup
Nominal Deviation ±0.25 Ω ±2.5 Ω ±25 Ω
Ground potential
0 to 30 V; nominal deviation: ±3.0% f.s.
measurement
Operating temperature 0°C to 40°C (32°F to 104°F),
and humidity 80 % rh or less (non-condensing)
Storage temperature -10°C to 50°C (14°F to 122°F),
and humidity 80% RH or less (non-condensing)
Dustproof and waterproof IP40 (EN60529) Easy to drive into the ground Tangle- and twist-free
Applicable Safety (instrument/measurementcircuitry): EN 61010; The auxiliary grounding rod is Easily rewind measurement
standards EMC: EN 61326; earth testers: EN 61557
thin (for easier penetration), cords, even if they’re 20 m long
LR6 (AA) alkaline battery ×6, 1100 times operation
(at 30 sec. measurement and 30 sec. rest cycle, 575
hard, and rust-resistant stainless
Power supply steel. (Variations in the thickness
Hz mode, 100 Ω at auxiliary electrode, measuring 10
Ω in 1 Ω range of auxiliary grounding rods
Dimensions and 164 mm (6.46 in.) W × 119 mm (4.69 in.) H × 88 mm (3.46 cause almost no change in their
mass in.) D, 760 g (26.8 oz.) ground resistance.)
Common to FT6031-50 and FT3151 To ensure safety, use the separately sold Test Lead L9787 when making measurements using the two-pole method.
The Bluetooth® word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks by HIOKI E.E. CORPORATION is under license.
Note: company names and product names appearing in this brochure are trademarks or registered trademarks of various companies.
DISTRIBUTED BY
HEADQUARTERS
81 Koizumi,
Ueda, Nagano 386-1192 Japan
https://www.hioki.com/
All information correct as of Mar. 26, 2024. Contents are subject to change without notice. series_EarthTesterE2-43E