IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.

xlsx

Revision Description of the modification Sheet By Company Date Base Line


A1-0 Creation All Lawrence Ong NEJV 23-Nov-17
A1-1 ICSS.BMS.1
A1-0-D7 AMENDMENT (AS PER ICSS COMMENTS) ALL BMS 201 GRDI 28-Feb-18
Amended attribute descrtiption for Distribution Board (Type 3) as per
A1-0-D17 ICSS.BMS.1 (ELS) SY202 NEJV 5-Nov-18
DADS IO LIST REV.A1-1-D2
A1-0-D18 all razif GRDI 6-Dec-18
updated severity
A1-0-D19 all razif/kschong GRDI/NEJV 7-Dec-18
updated character limit
combine all ecs subsytem
28-Jan-19
remove all shutter and maintanin only one roller shutter
A1-0-D20 all razif GRDI
add noise barrier lighting
Combine lift and escalator under VTS
Delete/ Remove of Duplicate IO Class ICSS.BMS.1 (Air System)
Add new class for External Lighthing according to the revised IO List with
Eqpt_Code "EXTL"
Incomer Breaker (Type 4) Eqpt_Code update to "IBN4"
ICSS.BMS.1 (ELS)
Update "Lift Roller Shutter" to "Roller Shutter" accoding to the revised IO
List.
Add new class for noise barried lighted with Eqpt_Code "NBL_"
Udpate sub (system) from SSV_ to DRS_
ICSS.BMS.1 (SP)
A1-0-D21 Change tab name from ICSS.BMS.1 (SP) to ICSS.BMS.1 (DRS) according SY202 NEJV 25-Jan-18
ICSS.BMS.1 (DRS)
to the revised IO List.
Update/Add LMCP-RWCP with Eqpt_Code "LCPR" ICSS.BMS.1 (CWS)
Additional two IO Class for LMCP-FDPS (Type 1) for "low level alarm" and
ICSS.BMS.1 (FDPS)
"high level alarm" according to the revised IO List
Add New class for all Item with Eqpt_Code. ICSS.BMS.1 (SSV)
Update LMCP-ECS from "Incoming Breaker On Status" to "Incoming
Breaker Status " to sync with ICSS.VRV ICSS.BMS.1 (ECS)
Add new class "Exhaust Air Fan (Type 8)" for different severity
A2-0 Baseline for Final Design Solution All SY202 NEJV 13/2/2019 Yes
Additional Class for DB7B and DB7C according the IO List
A2-1 ICSS.BMS.1 (ELE) SY202 NEJV 30/4/2019
Additional Class for UPS1 and UPS2 according the IO List
ICSS.BMS.1 (ELE)
A2-2 Additional Class for Lighting Grouping ICSS.ECS BMS 201 GRDI 12/2/2020 A2-1
ICSS.BMS.1 (BMS)
1. Update Eqpt_Code for BMS Mode Selector "BMSS"
2. Change BMS Field Controller (DDC) to DDC Enclosure
3. Update Eqpt_Code for DDC Enclosure "DDC_" to "ENCL"
4. Add new class for Cold Water Tank with Eqpt_Code "CWTK" ICSS.BMS.1 (ELE)
5. Add new class for Rain Water Tank (Type 1) with Eqpt_Code "RWT_" ICSS.BMS.1 (CWS)
A2-3 6. add new class for Hose Reel Tank with Eqpt_Code "HRTK" ICSS.BMS.1 (BMS) BMS 201 GRDI 21/2/2020 A2-2
7. Update Eqpt_Code for Stabling Yard Lighting Zone "SYL" to "SYLG" ICSS.BMS.1 (FPS)
8. Remove v0_Severity form all FCU type due to placing error ICSS.BMS.1 (ECS)
9. Remove EXF3 and EXF9 due to same attribute with EXF1 and EXF7
10. Remove Class UVR2, DCCH, DCC1,DCC2, INB4, IMB4, INC1,
SPD1,INC2,SPD2
1. Add new class Cold Water Tank (Type 2) with Eqpt_Code "CWT2"
A2-4 2. Add Submersible Pump Control Panel (Type 3) with Eqpt_Code "LEP2" ICSS.BMS.1 (CWS) BMS 201 GRDI 27/2/2020 A2-3
3. 2. Add Hose Reel Tank with Eqpt_Code "HRTC"
A2-5 1. Update Combined List Combined BMS 201 GRDI 4/3/2020 A2-4
1. Added back SSB - Incomer Breaker (Type 4)
ICSS.BMS.1 (ELE)
2. Added new class Fresf Air Fan (Type 1), Noise Barrier Lighting (Type 2),
A2-6 ICSS.BMS.1 (ECS) BMS 201 GRDI 6/4/2020 A2-5
SSB - Incomer Breaker (Type 5), 3 Distribution Board (Type 4) Classes,
SSB - Outgoing Breaker (Type 3)
1. Update ICSS_Code for SSB - Outgoing Breaker (Type 3) & Distribution
Board (Type 4)
A2-7 ICSS.BMS.1 (ELE) BMS 202 GRDI 2/5/2020 A2-6
2. Update Attribute_Description on UVR3 & UVR4
3. Added Local Motor Control Panel (Type 13)
1. Revert back Attribute_Description for UVR3 & UVR4
2. Added SSB - Outgoing Breaker (Type 4), MSB - DC Supply Voltage
(Type 2) & Noise Barrier Lighting (Type 3)
A2-8 ICSS.BMS.1 (ELE) BMS 202 GRDI 19/5/2020 A2-7
3. Updated DPM-1 & DPM-2
4. Updated SSB - Outgoing Breaker (Type 3) v0_label(0), v0_label(1)
&v1_Severity
1. Revert back MSB - Undervoltage Relay (Type 2), MSB - Incomer
ICSS.BMS.1 (ELE)
A2-9 Breaker (Type 4) BMS 202 GRDI 21/5/2020 A2-8
2. Added Local Motor Control Panel (Type 14)
ICSS.BMS.1 (ECS)
A2-10 1. Added new class Rain Water Tank (Type 3) with Eqpt_Code RWT1 ICSS.BMS.1 (CWS) BMS 202 GRDI 23/7/2020 A2-9
A2-11 1. Added new class MSB - AC Supply Voltage ICSS.BMS.1 (ELE) BMS 202 GRDI 3/8/2020 A2-10
ICSS.BMS.1 (ELE)
1. Added new class UPS3 & UPS4
A3-0 ICSS.BMS.1 (BMS) BMS 203 GRDI 3/12/2020 A2-11
2. Remove MSB - Bus Section ACB Trip
ICSS.BMS.1 (FPS)
1. Modify Value_UPPER_Limit(iii), Add DAC_Scaling_Factor and
Corrective Maintenance for Room Temperature
A4-0 2. Modify Corrective Maintenance for Open/Close status for incomer ICSS.BMS.1 (ECS) ICSS.BMS.1 (ELE) SY202 NEJV 26/4/2022 Yes
breaker

Revision Register
IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings-Alarm/Event[DI]/Control[DO] Analogue_Type_Meanings_Alarm/E General_Control_Requirements

Value_Out_of_Range_
Meaningful_Min_valu

Severity_of_Range<(i)
Transition_Interval_(s
Other_bits_meanings
WPC_Data_Type

Scaling Factor
v4_label(100)

v5_label(101)

v6_label(110)

v7_label(111)
v2_label(10)

v3_label(11)
v0_Severity

v1_Severity

v2_Severity

v3_Severity

v4_Severity

v5_Severity

v6_Severity

v7_Severity
v0_label(0)

v1_label(1)

HIGH(iv)
Initial_Condition(s Return_Condition( Corrective
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit

ec)
initCond_TO ReturnCond_TO Comments

e
)_before_Ctl s)_after_Ctl Maintenance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC/ICSS WPC/ICSS WPC/ICSS WPC/ICSS WPC/ICSS WPC
BMS_ BMS_ SREL BMS Server Health/Fault Status DI Healthy 0 Faulty 1 Y
BMS_ BMS_ CTLR BMS Controller Health/Fault Status DI Healthy 0 Faulty 1 Y
BMS_ BMS_ ENCL DDC Enclosure Health/Fault Status DI Healthy 0 Faulty 1 Y
BMS_ BMS_ BMSS BMS Mode Selector BMS/ICSS DI BMS ICSS

ICSS.BMS.1 (BMS) Page 1


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings-Alarm/Event[DI]/Control[DO] Analogue_Type_Meanings_Alarm/Event[AI]

Value_Out_of_Range_
Meaningful_Min_valu
Transition_Interval_(s

Severity_of_Range<(i)
Other_bits_meanings
WPC_Data_Type

Scaling Factor
v2_label(10)
v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

LOW(i)
Corrective
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit

ec)

e
Maintenance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
BMS_ DRS_ LECP Submersible Pump Control Panel Mode Auto DI Manual 3 Auto N
BMS_ DRS_ LECP Submersible Pump Control Panel Incoming Breaker (Off/On) DI Off 3 On N
Submersible Pump Control Panel
BMS_ DRS_ LECP High Water Level Alarm DI Normal Alert 2 N
(Type 1)
Submersible Pump Control Panel
BMS_ DRS_ LECP High High Water Level Alarm DI Normal Alarm 1 Y
(Type 1)
Submersible Pump Control Panel
BMS_ DRS_ LEP1 Mode Auto DI Manual 3 Auto N
(Type 2)
Submersible Pump Control Panel
BMS_ DRS_ LEP1 Incoming Breaker (Off/On) DI Off 3 On N
(Type 2)
Submersible Pump Control Panel
BMS_ DRS_ LEP2 Mode Auto DI Manual 3 Auto N
(Type 3)
Submersible Pump Control Panel
BMS_ DRS_ LEP2 Incoming Breaker (Off/On) DI Off 3 On N
(Type 3)
Submersible Pump Control Panel
BMS_ DRS_ LEP2 Undervoltage Relay DI Normal Alarm 2 Y
(Type 3)
Submersible Pump Control Panel
BMS_ DRS_ LEP2 High Water Level Alarm DI Normal Alert 2 N
(Type 3)
Submersible Pump Control Panel
BMS_ DRS_ LEP2 High High Water Level Alarm DI Normal Alarm 1 Y
(Type 3)
BMS_ DRS_ LESP Submersible Pump On/Off Status DI Off On N
BMS_ DRS_ LESP Submersible Pump Trip Fault Alarm DI Normal Trip 2 Y
BMS_ DRS_ SSP_ Sewerage Submersible Pump On/Off Status DI Off On N
BMS_ DRS_ SSP_ Sewerage Submersible Pump Trip Fault Alarm DI Normal Trip 2 Y

ICSS.BMS.1 (DRS) Page 1


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_InformatiOn Attribute_InformatiOn(Internal_Variable,IV) Discrete_Type_Meanings-Alarm/Event[DI]/COntrol[DO] Analogue_Type_Meanings_Alarm/E

Meaningful_Min
WPC_Data_Type

TransitiOn_Inter

Value_Out_of_R

Severity_of_Ran
Other_bits_mea

Scaling Factor
ange_LOW(i)
v2_label(10)
v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

val_(sec)

_value
Corrective

ge<(i)
nings
System (S_ub)S_yS_tem Eqpt_Code Eqpt_DescriptiOn Attribute_DescriptiOn unit
Maintenance

WPC WC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC

BMS_ CWS_ LCP_ Cold Water Pump Control Panel Mode Auto DI Manual 3 Auto N

BMS_ CWS_ LCP_ Cold Water Pump Control Panel Incoming Breaker (Off/On) DI Off On N
BMS_ CWS_ CWTK Cold Water Tank (Type 1) High Water Level Alarm DI Normal High 2 N
BMS_ CWS_ CWTK Cold Water Tank (Type 1) Low Water Level Alarm DI Normal Low 2 Y
BMS_ CWS_ CWT2 Cold Water Tank (Type 2) Tank Leakage Alarm DI Normal Alarm 2 Y
BMS_ CWS_ CWT2 Cold Water Tank (Type 2) High Water Level Alarm DI Normal High 2 N
BMS_ CWS_ CWT2 Cold Water Tank (Type 2) Low Water Level Alarm DI Normal Low 2 Y
BMS_ CWS_ CWP_ Cold Water Pump On/Off Status DI Off On N
BMS_ CWS_ CWP_ Cold Water Pump Trip/Fault Alarm DI Normal Trip 2 Y
RWH Pump Control Panel (Type
BMS_ CWS_ LCPR Mode Auto DI Manual 3 Auto N
1)
RWH Pump Control Panel (Type
BMS_ CWS_ LCPR Incoming Breaker (Off/On) DI Off On N
1)
BMS_ CWS_ RWT_ Rain Water Tank (Type 1) Tank Leakage Alarm DI Normal Alarm 2 Y
BMS_ CWS_ RWT_ Rain Water Tank (Type 1) High Water Level Alarm DI Normal High 2 N
BMS_ CWS_ RWT_ Rain Water Tank (Type 1) Low Water Level Alarm DI Normal Low 2 Y
RWH Pump Control Panel (Type
BMS_ CWS_ LCP1 Mode Auto DI Manual 3 Auto N
2)
RWH Pump Control Panel (Type
BMS_ CWS_ LCP1 Incoming Breaker (Off/On) DI Off On N
2)
BMS_ CWS_ LCP1 Rain Water Tank (Type 2) Tank 1 Leakage Alarm DI Normal Alarm 2 Y
BMS_ CWS_ LCP1 Rain Water Tank (Type 2) Tank 2 Leakage Alarm DI Normal Alarm 2 Y
BMS_ CWS_ LCP1 Rain Water Tank (Type 2) High Water Level Alarm DI Normal High 2 N
BMS_ CWS_ LCP1 Rain Water Tank (Type 2) Low Water Level Alarm DI Normal Low 2 Y
BMS_ CWS_ RWT1 Rain Water Tank (Type 3) Tank Leakage Alarm DI Normal Alarm 2 Y
BMS_ CWS_ RWT1 Rain Water Tank (Type 3) High Water Level Alarm 1 DI Normal High 2 N
BMS_ CWS_ RWT1 Rain Water Tank (Type 3) Low Water Level Alarm 1 DI Normal Low 2 Y
BMS_ CWS_ RWT1 Rain Water Tank (Type 3) High Water Level Alarm 2 DI Normal High 2 N
BMS_ CWS_ RWT1 Rain Water Tank (Type 3) Low Water Level Alarm 2 DI Normal Low 2 Y
BMS_ CWS_ RWHP Rain Water Harvesting Pump On/Off Status DI Off On N
BMS_ CWS_ RWHP Rain Water Harvesting Pump Trip/Fault Alarm DI Normal Trip 2 Y
BMS_ CWS_ HRTC Hose Reel Tank Tank Leakage Alarm DI Normal Alarm 2 Y

ICSS.BMS.1 (CWS) Page 1


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings-Alarm/Event[DI]/Control[DO] Analogue_Type_Meanings_Alar

Value_Out_of_Range_

Severity_of_Range<(i)
Meaningful_Min_valu
Transition_Interval_(s
Other_bits_meanings
WPC_Data_Type

Scaling Factor
v2_label(10)
v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

LOW(i)
Corrective
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit

ec)

e
Maintenance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
Hose Reel Pump Control Panel
BMS_ FPS_ LMCP Supply Healthy Status DI Normal Alarm 2 Y Y
(Type 1)
Hose Reel Pump Control Panel
BMS_ FPS_ LMCP Incoming Breaker (Off/On) DI Off On N N
(Type 1)
Hose Reel Pump Control Panel
BMS_ FPS_ LMCP Incoming Breaker Trip DI Normal Trip 2 Y Y
(Type 1)
BMS_ FPS_ HRTK Hose Reel Tank High Water Level Alarm DI Normal High 3 N
BMS_ FPS_ HRTK Hose Reel Tank Low Water Level Alarm DI Normal Low 2 Y
BMS_ FPS_ LMCW Wet Riser Pump Control Panel Supply Healthy Status DI Normal Alarm 2 Y Y
BMS_ FPS_ LMCW Wet Riser Pump Control Panel Incoming Breaker (Off/On) DI Off On N N
BMS_ FPS_ LMCW Wet Riser Pump Control Panel Incoming Breaker Trip DI Normal Trip 2 Y Y
BMS_ FPS_ LMCW Wet Riser Pump Control Panel High Water Level Alarm DI Normal High 3 N
BMS_ FPS_ LMCW Wet Riser Pump Control Panel Low Water Level Alarm DI Normal Low 2 Y
Hose Reel Pump Control Panel
BMS_ FPS_ LMCB Supply Healthy Status DI Normal Alarm 2 Y
(Type 2)
Hose Reel Pump Control Panel
BMS_ FPS_ LMCB Incoming Breaker (Off/On) DI Off On N
(Type 2)
Hose Reel Pump Control Panel
BMS_ FPS_ LMCB High Water Level Alarm DI Normal High N
(Type 2)
Hose Reel Pump Control Panel
BMS_ FPS_ LMCB Low Water Level Alarm DI Normal Low Y
(Type 2)
BMS_ FPS_ SPCP Sprinkler Pump Control Panel Supply Healthy Status DI Normal Alarm 2 Y
BMS_ FPS_ SPCP Sprinkler Pump Control Panel Incoming Breaker (Off/On) DI Off On N
BMS_ FPS_ SPCP Sprinkler Pump Control Panel Incoming Breaker Trip DI Normal Trip Y
BMS_ FPS_ SPCP Sprinkler Pump Control Panel High Water Level Alarm DI Normal High N
BMS_ FPS_ SPCP Sprinkler Pump Control Panel Low Water Level Alarm DI Normal Low Y
BMS_ FPS_ HPCP Hydrant Pump Control Panel Supply Healthy Status DI Normal Alarm 2 Y
BMS_ FPS_ HPCP Hydrant Pump Control Panel Incoming Breaker (Off/On) DI Off On N
BMS_ FPS_ HPCP Hydrant Pump Control Panel Incoming Breaker Trip DI Normal Trip Y
BMS_ FPS_ HPCP Hydrant Pump Control Panel High Water Level Alarm DI Normal High N
BMS_ FPS_ HPCP Hydrant Pump Control Panel Low Water Level Alarm DI Normal Low Y
BMS_ FPS_ SPTA Sprinkler Tank High Water Level Alarm DI Normal High 3 N
BMS_ FPS_ SPTA Sprinkler Tank Low Water Level Alarm DI Normal Low 2 Y
BMS_ FPS_ HYTA Hydrant Tank High Water Level Alarm DI Normal High 3 N
BMS_ FPS_ HYTA Hydrant Tank Low Water Level Alarm DI Normal Low 2 Y
BMS_ FPS_ WRTA Wet Riser Tank High Water Level Alarm DI Normal High 3 N
BMS_ FPS_ WRTA Wet Riser Tank Low Water Level Alarm DI Normal Low 2 Y
BMS_ FPS_ SPHP Sprinkler Hose Pump Mode Auto DI Manual Auto N
BMS_ FPS_ SPHP Sprinkler Hose Pump Fault Alarm DI Normal Alarm 2 Y
BMS_ FPS_ SPHP Sprinkler Hose Pump Run/Stop Status DI Stop Run N
BMS_ FPS_ HYPU Fire Hydrant Pump Mode Auto DI Manual Auto N
BMS_ FPS_ HYPU Fire Hydrant Pump Fault Alarm DI Normal Alarm Y
BMS_ FPS_ HYPU Fire Hydrant Pump Run/Stop Status DI Stop Run N
BMS_ FPS_ WRPU Wet Riser Pump Mode Auto DI Manual 3 Auto N
BMS_ FPS_ WRPU Wet Riser Pump Fault Alarm DI Normal Alarm 2 Y

ICSS.BMS.1 (FPS) Page 1


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings-Alarm/Event[DI]/Control[DO] Analogue_Type_Meanings_Alar

Value_Out_of_Range_

Severity_of_Range<(i)
Meaningful_Min_valu
Transition_Interval_(s
Other_bits_meanings
WPC_Data_Type

Scaling Factor
v2_label(10)
v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

LOW(i)
Corrective
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit

ec)

e
Maintenance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
BMS_ FPS_ WRPU Wet Riser Pump Run/Stop Status DI Stop Run N
BMS_ FPS_ HOP1 Hose Reel Pump (Type 1) Mode Auto DI Manual 3 Auto N
BMS_ FPS_ HOP1 Hose Reel Pump (Type 1) Fault Alarm DI Normal Alarm 2 Y
BMS_ FPS_ HOP1 Hose Reel Pump (Type 1) Supply Healthy Status DI Normal Alarm 2 Y
BMS_ FPS_ HOP1 Hose Reel Pump (Type 1) Run/Stop Status DI Stop Run N
BMS_ FPS_ HORP Hose Reel Pump (Type 2) Mode Auto DI Manual 3 Auto N
BMS_ FPS_ HORP Hose Reel Pump (Type 2) Fault Alarm DI Normal Alarm 2 Y
BMS_ FPS_ HORP Hose Reel Pump (Type 2) Run/Stop Status DI Stop Run N
BMS_ FPS_ FAPL Fire Alarm Panel Supply Healthy Status DI Normal Alarm 2 Y
BMS_ FPS_ FISP Sub-Fire Alarm Panel Supply Healthy Status DI Normal Alarm 2 Y
BMS_ FPS_ FAPH Main Fire Alarm Panel Supply Healthy Status DI Normal Alarm 2 Y
BMS_ FPS_ FMSY FM200 Panel Mode Auto DI Manual 3 Auto N
BMS_ FPS_ FMSY FM200 Panel Gas Discharge DI Normal Discharged 1 Y
BMS_ FPS_ FMSY FM200 Panel Fault Alarm DI Normal Alarm 2 Y
BMS_ FPS_ REPL Fire Alarm Repeater Panel Supply Healthy Status DI Normal Alarm 2 Y

ICSS.BMS.1 (FPS) Page 2


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings-Alarm/Event[DI]/Control[DO] Analogue_Type_Meanings_Alarm/E

Meaningful_Max_valu

Value_Out_of_Range_

Severity_of_Range>(iv
Transition_Interval_(s
Other_bits_meanings
WPC_Data_Type

Scaling Factor
v4_label(100)

v5_label(101)

v6_label(110)

v7_label(111)
v2_label(10)

v3_label(11)
v0_Severity

v1_Severity

v2_Severity

v3_Severity

v4_Severity

v5_Severity

v6_Severity

v7_Severity
v0_label(0)

v1_label(1)
Corrective

LOW(i)
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit Maintenanc

ec)

)
e

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
BMS_ VTS_ ESC_ Escalator Panel Local/Remote Status DI Local 3 Remote N
BMS_ VTS_ ESC_ Escalator On/Off Status DI Off On N
BMS_ VTS_ ESC_ Escalator Up/Forward Direction DI Off Forward N
BMS_ VTS_ ESC_ Escalator Down/Backwards Direction DI Off Backwards N
BMS_ VTS_ ESC_ Escalator Run/Stop Status DI Stop Run N
BMS_ VTS_ ESC_ Escalator Maintenance On/Off Status DI Off On N
BMS_ VTS_ ESC_ Escalator Fault/Trip Alarm DI Normal Alarm 2 Y
BMS_ VTS_ ESC_ Escalator Pit Flooding Alarm DI Normal Alarm 2 Y
BMS_ VTS_ LIFT Lift Panel Local/Remote Status DI Local 3 Remote N
BMS_ VTS_ LIFT Lift Power On/Off Status DI Off On N
BMS_ VTS_ LIFT Lift Operation On/Off Status DI Off On N
BMS_ VTS_ LIFT Lift Maintenance On/Off Status DI Off On N
BMS_ VTS_ LIFT Lift Up/Forward Direction DI Off Up N
BMS_ VTS_ LIFT Lift Down/Backwards Direction DI Off Down N
BMS_ VTS_ LIFT Lift Fault/Trip/Warning Alarm DI Normal Alarm 2 Y
BMS_ VTS_ LIFT Lift Summary Alarm DI Normal Alarm 2 N
BMS_ VTS_ LIFT Lift Door Alarm DI Normal Alarm 2 Y
BMS_ VTS_ LIFT Lift Emergency Alarm DI Normal Alarm 2 Y
BMS_ VTS_ LIFT Lift Special Operation Mode DI Off On N

ICSS.BMS.1 (VTS) Page 1


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings- Analogue_Type_Meanings_Alarm/Event[AI]

Meaningful_Max_valu

Severity_of_Range>(iv
Value_Out_of_Range_

Value_Out_of_Range_
Value_LOWER_Limit(ii

Value_UPPER_Limit(iii

Severity_of_Range<(i)
Meaningful_Min_valu

Severity_of_Range(iii-
Transition_Interval_(s

Severity_of_Range(i)-
Other_bits_meanings
WPC_Data_Type

Scaling Factor
v2_label(10)
v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

HIGH(iv)
LOW(i)
Corrective
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit

ec)

(ii)

iv)
e
e

)
Maintenance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
BMS_ ELE_ ACB_ MSB - Incomer ACB Open/Close DI Off On Y
BMS_ ELE_ ACB_ MSB - Incomer ACB Trip DI Normal Trip 1 Y
BMS_ ELE_ ACB2 MSB - Incomer ACB (Type 2) Open/Close DI Off On Y
BMS_ ELE_ ACB3 MSB - Incomer ACB No. 1 Open/Close DI Off On Y
BMS_ ELE_ ACB3 MSB - Incomer ACB No. 1 Trip DI Normal Trip 1 Y
BMS_ ELE_ ACB4 MSB - Incomer ACB No. 2 Open/Close DI Off On Y
BMS_ ELE_ ACB4 MSB - Incomer ACB No. 2 Trip DI Normal Trip 1 Y
BMS_ ELE_ BACB MSB - Bus Section ACB Open/Close DI Off On N
BMS_ ELE_ BACB MSB - Bus Section ACB Trip DI Normal Trip 1 Y
BMS_ ELE_ CAPB MSB - Capacitor Bank Open/Close DI Off On N
BMS_ ELE_ CAPB MSB - Capacitor Bank Trip DI Normal Trip 1 Y
BMS_ ELE_ DPM_ MSB - Digital Power Meter Current-R A AI 0.1 N
BMS_ ELE_ DPM_ MSB - Digital Power Meter Current-Y A AI 0.1 N
BMS_ ELE_ DPM_ MSB - Digital Power Meter Current-B A AI 0.1 N
BMS_ ELE_ DPM_ MSB - Digital Power Meter Voltage-RY V AI 0.1 N
BMS_ ELE_ DPM_ MSB - Digital Power Meter Voltage-YB V AI 0.1 N
BMS_ ELE_ DPM_ MSB - Digital Power Meter Voltage-BR V AI 0.1 N
BMS_ ELE_ DPM_ MSB - Digital Power Meter Power KW AI 0.1 N
BMS_ ELE_ DPM_ MSB - Digital Power Meter Power Factor AI 0 0.85 1 0.001 N
BMS_ ELE_ DPM1 MSB - Digital Power Meter-1 Current-R A AI 0.1 N
BMS_ ELE_ DPM1 MSB - Digital Power Meter-1 Current-Y A AI 0.1 N
BMS_ ELE_ DPM1 MSB - Digital Power Meter-1 Current-B A AI 0.1 N
BMS_ ELE_ DPM1 MSB - Digital Power Meter-1 Voltage-RY V AI 0.1 N
BMS_ ELE_ DPM1 MSB - Digital Power Meter-1 Voltage-YB V AI 0.1 N
BMS_ ELE_ DPM1 MSB - Digital Power Meter-1 Voltage-BR V AI 0.1 N
BMS_ ELE_ DPM1 MSB - Digital Power Meter-1 Power KW AI 0.1 N
BMS_ ELE_ DPM1 MSB - Digital Power Meter-1 Power Factor AI 0 0.85 1 0.001 N
BMS_ ELE_ DPM2 MSB - Digital Power Meter-2 Current-R A AI 0.1 N
BMS_ ELE_ DPM2 MSB - Digital Power Meter-2 Current-Y A AI 0.1 N
BMS_ ELE_ DPM2 MSB - Digital Power Meter-2 Current-B A AI 0.1 N
BMS_ ELE_ DPM2 MSB - Digital Power Meter-2 Voltage-RY V AI 0.1 N
BMS_ ELE_ DPM2 MSB - Digital Power Meter-2 Voltage-YB V AI 0.1 N
BMS_ ELE_ DPM2 MSB - Digital Power Meter-2 Voltage-BR V AI 0.1 N
BMS_ ELE_ DPM2 MSB - Digital Power Meter-2 Power KW AI 0.1 N
BMS_ ELE_ DPM2 MSB - Digital Power Meter-2 Power Factor AI 0 0.85 1 0.001 N
MSB - Undervoltage Relay (Type
BMS_ ELE_ UVR1 Undervoltage DI Normal Alarm 2 Y
1)
MSB - Undervoltage Relay (Type
BMS_ ELE_ UVR2 Failure DI Normal Failure 2 Y
2)
BMS_ ELE_ UVR3 MSB - Undervoltage Relay-1 Undervoltage DI Normal Alarm 2 Y
BMS_ ELE_ UVR4 MSB - Undervoltage Relay-2 Undervoltage DI Normal Alarm 2 Y
BMS_ ELE_ SPD_ MSB - Surge Protection Device Surge Alarm Protection Status DI Normal Alarm 2 Y

ICSS.BMS.1 (ELE) Page 1


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings- Analogue_Type_Meanings_Alarm/Event[AI]

Meaningful_Max_valu

Severity_of_Range>(iv
Value_Out_of_Range_

Value_Out_of_Range_
Value_LOWER_Limit(ii

Value_UPPER_Limit(iii

Severity_of_Range<(i)
Meaningful_Min_valu

Severity_of_Range(iii-
Transition_Interval_(s

Severity_of_Range(i)-
Other_bits_meanings
WPC_Data_Type

Scaling Factor
v2_label(10)
v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

HIGH(iv)
LOW(i)
Corrective
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit

ec)

(ii)

iv)
e
e

)
Maintenance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
BMS_ ELE_ SPD1 SSB - Surge Protection Device Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ SPD4 MSB - Surge Protection Device-1 Surge Alarm Protection Status DI Normal Alarm 2 Y

BMS_ ELE_ SPD5 MSB - Surge Protection Device-2 Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ DCV_ MSB - DC Supply Voltage Undervoltage DI Normal Alarm 2 Y
BMS_ ELE_ ACV_ MSB - AC Supply Voltage Undervoltage DI Normal Alarm 2 Y
MSB - DC Supply Voltage (Type
BMS_ ELE_ DCV1 Undervoltage 1 DI Normal Alarm 2 Y
2)
MSB - DC Supply Voltage (Type
BMS_ ELE_ DCV1 Undervoltage 2 DI Normal Alarm 2 Y
2)
MSB - 110 DC Charger Summary
BMS_ ELE_ DCCH Common Alarm DI Normal Alarm 2 Y
Alarm
MSB - 110 DC Charger Summary
BMS_ ELE_ DCC1 Common Alarm DI Normal Alarm 2 Y
Alarm 1
MSB - 110 DC Charger Summary
BMS_ ELE_ DCC2 Common Alarm DI Normal Alarm 2 Y
Alarm 2
BMS_ ELE_ UPS_ Uninterruptible Power Supply Supply A Breaker Open/Close DI Off On N
BMS_ ELE_ UPS_ Uninterruptible Power Supply Supply B Breaker Open/Close DI Off On N
BMS_ ELE_ UPS_ Uninterruptible Power Supply Supply A Breaker Trip DI Normal Trip 1 Y
BMS_ ELE_ UPS_ Uninterruptible Power Supply Supply B Breaker Trip DI Normal Trip 1 Y
BMS_ ELE_ UPS_ Uninterruptible Power Supply External Bypass On/Off DI Off On N
BMS_ ELE_ UPS_ Uninterruptible Power Supply Battery Charging/Discharging DI Charging Discharging Y
BMS_ ELE_ UPS_ Uninterruptible Power Supply Battery Common Alarm DI Normal Alarm 2 Y
BMS_ ELE_ UPS_ Uninterruptible Power Supply Fan Failure/Alarm Status DI Normal Alarm 2 Y
BMS_ ELE_ UPS_ Uninterruptible Power Supply UPS On / Emergency Shutdown DI Off On N
BMS_ ELE_ UPS_ Uninterruptible Power Supply Summary Alarm DI Normal Alarm 2 Y
BMS_ ELE_ UPS_ Uninterruptible Power Supply UPS Online Status DI Off On N
BMS_ ELE_ UPS_ Uninterruptible Power Supply UPS On Battery Status DI Off On 1 N
BMS_ ELE_ UPS_ Uninterruptible Power Supply UPS On Static Bypass status DI Off On 1 N
BMS_ ELE_ UPS_ Uninterruptible Power Supply UPS On Maintenance Bypass DI Off On 3 N
BMS_ ELE_ UPS_ Uninterruptible Power Supply Rectifier/Inverter Fault Alarm DI Normal Alarm 2 Y
BMS_ ELE_ UPS_ Uninterruptible Power Supply UPS Battery Low Alarm DI Normal Alarm 1 Y
BMS_ ELE_ UPS_ Uninterruptible Power Supply Incoming Voltage-RY V AI N
BMS_ ELE_ UPS_ Uninterruptible Power Supply Incoming Voltage-YB V AI N
BMS_ ELE_ UPS_ Uninterruptible Power Supply Incoming Voltage-BR V AI N
BMS_ ELE_ UPS_ Uninterruptible Power Supply Incoming Current-R A AI N
BMS_ ELE_ UPS_ Uninterruptible Power Supply Incoming Current-Y A AI N
BMS_ ELE_ UPS_ Uninterruptible Power Supply Incoming Current-B A AI N
BMS_ ELE_ UPS_ Uninterruptible Power Supply Outgoing Voltage-RY V AI N
BMS_ ELE_ UPS_ Uninterruptible Power Supply Outgoing Voltage-YB V AI N

ICSS.BMS.1 (ELE) Page 2


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings- Analogue_Type_Meanings_Alarm/Event[AI]

Meaningful_Max_valu

Severity_of_Range>(iv
Value_Out_of_Range_

Value_Out_of_Range_
Value_LOWER_Limit(ii

Value_UPPER_Limit(iii

Severity_of_Range<(i)
Meaningful_Min_valu

Severity_of_Range(iii-
Transition_Interval_(s

Severity_of_Range(i)-
Other_bits_meanings
WPC_Data_Type

Scaling Factor
v2_label(10)
v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

HIGH(iv)
LOW(i)
Corrective
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit

ec)

(ii)

iv)
e
e

)
Maintenance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
BMS_ ELE_ UPS_ Uninterruptible Power Supply Outgoing Voltage-BR V AI N
BMS_ ELE_ UPS_ Uninterruptible Power Supply Outgoing Current-R A AI N
BMS_ ELE_ UPS_ Uninterruptible Power Supply Outgoing Current-Y A AI N
BMS_ ELE_ UPS_ Uninterruptible Power Supply Outgoing Current-B A AI N
BMS_ ELE_ UPS1 Uninterruptible Power Supply External Bypass On/Off DI Off On N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Battery Charging/Discharging DI Charging Discharging Y
BMS_ ELE_ UPS1 Uninterruptible Power Supply Battery Common Alarm DI Normal Alarm 2 Y
BMS_ ELE_ UPS1 Uninterruptible Power Supply Fan Failure/Alarm Status DI Normal Alarm 2 Y
BMS_ ELE_ UPS1 Uninterruptible Power Supply UPS On / Emergency Shutdown DI Off On N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Summary Alarm DI Normal Alarm 2 Y
BMS_ ELE_ UPS1 Uninterruptible Power Supply UPS Online Status DI Off On N
BMS_ ELE_ UPS1 Uninterruptible Power Supply UPS On Battery Status DI Off On 1 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply UPS On Static Bypass status DI Off On 1 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply UPS On Maintenance Bypass DI Off On 3 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Rectifier/Inverter Fault Alarm DI Normal Alarm 2 Y
BMS_ ELE_ UPS1 Uninterruptible Power Supply UPS Battery Low Alarm DI Normal Alarm 1 Y
BMS_ ELE_ UPS1 Uninterruptible Power Supply Incoming Voltage-RY V AI 0.1 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Incoming Voltage-YB V AI 0.1 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Incoming Voltage-BR V AI 0.1 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Incoming Current-R A AI 0.1 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Incoming Current-Y A AI 0.1 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Incoming Current-B A AI 0.1 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Outgoing Voltage-RY V AI 0.1 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Outgoing Voltage-YB V AI 0.1 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Outgoing Voltage-BR V AI 0.1 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Outgoing Current-R A AI 0.1 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Outgoing Current-Y A AI 0.1 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Outgoing Current-B A AI 0.1 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Input Power R KW AI 0.1 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Input Power Y KW AI 0.1 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Input Power B KW AI 0.1 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Output Power R KW AI 0.1 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Output Power Y KW AI 0.1 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Output Power B KW AI 0.1 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Input Fequency Hz AI 0.1 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Output Frequency Hz AI 0.1 N
BMS_ ELE_ UPS1 Uninterruptible Power Supply Output Active Power KW AI 0.1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Supply A Breaker Open/Close DI Off On N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Supply B Breaker Open/Close DI Off On N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Supply A Breaker Trip DI Normal Trip 1 Y
BMS_ ELE_ UPS2 Uninterruptible Power Supply Supply B Breaker Trip DI Normal Trip 1 Y

ICSS.BMS.1 (ELE) Page 3


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings- Analogue_Type_Meanings_Alarm/Event[AI]

Meaningful_Max_valu

Severity_of_Range>(iv
Value_Out_of_Range_

Value_Out_of_Range_
Value_LOWER_Limit(ii

Value_UPPER_Limit(iii

Severity_of_Range<(i)
Meaningful_Min_valu

Severity_of_Range(iii-
Transition_Interval_(s

Severity_of_Range(i)-
Other_bits_meanings
WPC_Data_Type

Scaling Factor
v2_label(10)
v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

HIGH(iv)
LOW(i)
Corrective
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit

ec)

(ii)

iv)
e
e

)
Maintenance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
BMS_ ELE_ UPS2 Uninterruptible Power Supply External Bypass On/Off DI Off On N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Battery Charging/Discharging DI Charging Discharging Y
BMS_ ELE_ UPS2 Uninterruptible Power Supply Battery Common Alarm DI Normal Alarm 2 Y
BMS_ ELE_ UPS2 Uninterruptible Power Supply Fan Failure/Alarm Status DI Normal Alarm 2 Y
BMS_ ELE_ UPS2 Uninterruptible Power Supply UPS On / Emergency Shutdown DI Off On N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Summary Alarm DI Normal Alarm 2 Y
BMS_ ELE_ UPS2 Uninterruptible Power Supply UPS Online Status DI Off On N
BMS_ ELE_ UPS2 Uninterruptible Power Supply UPS On Battery Status DI Off On 1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply UPS On Static Bypass status DI Off On 1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply UPS On Maintenance Bypass DI Off On 3 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Rectifier/Inverter Fault Alarm DI Normal Alarm 2 Y
BMS_ ELE_ UPS2 Uninterruptible Power Supply UPS Battery Low Alarm DI Normal Alarm 1 Y
BMS_ ELE_ UPS2 Uninterruptible Power Supply Incoming Voltage-RY V AI 0.1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Incoming Voltage-YB V AI 0.1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Incoming Voltage-BR V AI 0.1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Incoming Current-R A AI 0.1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Incoming Current-Y A AI 0.1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Incoming Current-B A AI 0.1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Outgoing Voltage-RY V AI 0.1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Outgoing Voltage-YB V AI 0.1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Outgoing Voltage-BR V AI 0.1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Outgoing Current-R A AI 0.1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Outgoing Current-Y A AI 0.1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Outgoing Current-B A AI 0.1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Input Power R KW AI 0.1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Input Power Y KW AI 0.1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Input Power B KW AI 0.1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Output Power R KW AI 0.1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Output Power Y KW AI 0.1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Output Power B KW AI 0.1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Input Fequency Hz AI 0.1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Output Frequency Hz AI 0.1 N
BMS_ ELE_ UPS2 Uninterruptible Power Supply Output Active Power KW AI 0.1 N
BMS_ UPS3 Uninterruptible Power Supply Supply A Breaker Open/Close DI Off On N
BMS_ UPS3 Uninterruptible Power Supply Supply A Breaker Trip DI Normal Trip 1 Y
BMS_ UPS3 Uninterruptible Power Supply Supply B Breaker Open/Close DI Off On N
BMS_ UPS3 Uninterruptible Power Supply Supply B Breaker Trip DI Normal Trip 1 Y
BMS_ UPS3 Uninterruptible Power Supply External Bypass On/Off DI Off On N
BMS_ UPS3 Uninterruptible Power Supply Battery Charging/Discharging DI Charging Discharging Y
BMS_ UPS3 Uninterruptible Power Supply Battery Common Alarm DI Normal Alarm 2 Y
BMS_ UPS3 Uninterruptible Power Supply Fan Failure/Alarm Status DI Normal Alarm 2 Y

ICSS.BMS.1 (ELE) Page 4


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings- Analogue_Type_Meanings_Alarm/Event[AI]

Meaningful_Max_valu

Severity_of_Range>(iv
Value_Out_of_Range_

Value_Out_of_Range_
Value_LOWER_Limit(ii

Value_UPPER_Limit(iii

Severity_of_Range<(i)
Meaningful_Min_valu

Severity_of_Range(iii-
Transition_Interval_(s

Severity_of_Range(i)-
Other_bits_meanings
WPC_Data_Type

Scaling Factor
v2_label(10)
v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

HIGH(iv)
LOW(i)
Corrective
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit

ec)

(ii)

iv)
e
e

)
Maintenance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
BMS_ UPS3 Uninterruptible Power Supply UPS On / Emergency Shutdown DI Off On N
BMS_ UPS3 Uninterruptible Power Supply Summary Alarm DI Normal Alarm 2 Y
BMS_ UPS3 Uninterruptible Power Supply UPS Online Status DI Off On N
BMS_ UPS3 Uninterruptible Power Supply UPS On Battery Status DI Off On 1 N
BMS_ UPS3 Uninterruptible Power Supply UPS On Static Bypass status DI Off On 1 N
BMS_ UPS3 Uninterruptible Power Supply UPS On Maintenance Bypass DI Off On 3 N
BMS_ UPS3 Uninterruptible Power Supply Rectifier/Inverter Fault Alarm DI Normal Alarm 2 Y
BMS_ UPS3 Uninterruptible Power Supply UPS Battery Low Alarm DI Normal Alarm 1 Y
BMS_ UPS3 Uninterruptible Power Supply Incoming Voltage V AI 0.1 N
BMS_ UPS3 Uninterruptible Power Supply Incoming Current A AI 0.1 N
BMS_ UPS3 Uninterruptible Power Supply Outgoing Voltage V AI 0.1 N
BMS_ UPS3 Uninterruptible Power Supply Outgoing Current A AI 0.1 N
BMS_ UPS3 Uninterruptible Power Supply Input Power KW AI 0.1 N
BMS_ UPS3 Uninterruptible Power Supply Output Power KW AI 0.1 N
BMS_ UPS3 Uninterruptible Power Supply Input Fequency Hz AI 0.1 N
BMS_ UPS3 Uninterruptible Power Supply Output Frequency Hz AI 0.1 N
BMS_ UPS3 Uninterruptible Power Supply Output Active Power KW AI 0.1 N
BMS_ UPS4 Uninterruptible Power Supply External Bypass On/Off DI Off On N
BMS_ UPS4 Uninterruptible Power Supply Battery Charging/Discharging DI Charging Discharging Y
BMS_ UPS4 Uninterruptible Power Supply Battery Common Alarm DI Normal Alarm 2 Y
BMS_ UPS4 Uninterruptible Power Supply Fan Failure/Alarm Status DI Normal Alarm 2 Y
BMS_ UPS4 Uninterruptible Power Supply UPS On / Emergency Shutdown DI Off On N
BMS_ UPS4 Uninterruptible Power Supply Summary Alarm DI Normal Alarm 2 Y
BMS_ UPS4 Uninterruptible Power Supply UPS Online Status DI Off On N
BMS_ UPS4 Uninterruptible Power Supply UPS On Battery Status DI Off On 1 N
BMS_ UPS4 Uninterruptible Power Supply UPS On Static Bypass status DI Off On 1 N
BMS_ UPS4 Uninterruptible Power Supply UPS On Maintenance Bypass DI Off On 3 N
BMS_ UPS4 Uninterruptible Power Supply Rectifier/Inverter Fault Alarm DI Normal Alarm 2 Y
BMS_ UPS4 Uninterruptible Power Supply UPS Battery Low Alarm DI Normal Alarm 1 Y
BMS_ UPS4 Uninterruptible Power Supply Incoming Voltage V AI 0.1 N
BMS_ UPS4 Uninterruptible Power Supply Incoming Current A AI 0.1 N
BMS_ UPS4 Uninterruptible Power Supply Outgoing Voltage V AI 0.1 N
BMS_ UPS4 Uninterruptible Power Supply Outgoing Current A AI 0.1 N
BMS_ UPS4 Uninterruptible Power Supply Input Power KW AI 0.1 N
BMS_ UPS4 Uninterruptible Power Supply Output Power KW AI 0.1 N
BMS_ UPS4 Uninterruptible Power Supply Input Fequency Hz AI 0.1 N
BMS_ UPS4 Uninterruptible Power Supply Output Frequency Hz AI 0.1 N
BMS_ UPS4 Uninterruptible Power Supply Output Active Power KW AI 0.1 N
BMS_ ELE_ INB1 SSB - Incomer Breaker (Type 1) Open/Close DI Off On N
BMS_ ELE_ INB1 SSB - Incomer Breaker (Type 1) Trip DI Normal Trip 1 Y

ICSS.BMS.1 (ELE) Page 5


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings- Analogue_Type_Meanings_Alarm/Event[AI]

Meaningful_Max_valu

Severity_of_Range>(iv
Value_Out_of_Range_

Value_Out_of_Range_
Value_LOWER_Limit(ii

Value_UPPER_Limit(iii

Severity_of_Range<(i)
Meaningful_Min_valu

Severity_of_Range(iii-
Transition_Interval_(s

Severity_of_Range(i)-
Other_bits_meanings
WPC_Data_Type

Scaling Factor
v2_label(10)
v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

HIGH(iv)
LOW(i)
Corrective
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit

ec)

(ii)

iv)
e
e

)
Maintenance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
BMS_ ELE_ IMB1 MSB - Incomer Breaker (Type 1) Open/Close DI Off On Y

BMS_ ELE_ IMB1 MSB - Incomer Breaker (Type 1) Trip DI Normal Trip 1 Y
BMS_ ELE_ INBK SSB - Incomer Breaker (Type 2) Open/Close DI Off On Y
BMS_ ELE_ INB3 SSB - Incomer Breaker (Type 3) Open/Close DI Off On Y
BMS_ ELE_ INB3 SSB - Incomer Breaker (Type 3) Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ IN1A SSB - Incomer Breaker 1 Open/Close DI Off On Y
BMS_ ELE_ IN1A SSB - Incomer Breaker 1 Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ IN1A SSB - Incomer Breaker 1 Trip DI Normal Trip 1 Y
BMS_ ELE_ IN2B SSB - Incomer Breaker 2 Open/Close DI Off On Y
BMS_ ELE_ IN2B SSB - Incomer Breaker 2 Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ IN2B SSB - Incomer Breaker 2 Trip DI Normal Trip 1 Y
BMS_ ELE_ INB4 SSB - Incomer Breaker (Type 4) Open/Close DI Off On Y
BMS_ ELE_ INB4 SSB - Incomer Breaker (Type 4) Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ INB4 SSB - Incomer Breaker (Type 4) Trip DI Normal Trip 1 Y
BMS_ ELE_ INB5 SSB - Incomer Breaker (Type 5) Open/Close 1 DI Off On Y
BMS_ ELE_ INB5 SSB - Incomer Breaker (Type 5) Open/Close 2 DI Normal Alarm 2 Y
BMS_ ELE_ INB5 SSB - Incomer Breaker (Type 5) Trip DI Normal Trip 1 Y
BMS_ ELE_ IN1C SSB - Incomer Breaker 1 Open/Close DI Off On Y
BMS_ ELE_ IN1C SSB - Incomer Breaker 1 Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ IN2D SSB - Incomer Breaker 2 Open/Close DI Off On Y
BMS_ ELE_ IN2D SSB - Incomer Breaker 2 Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ IMB4 MSB - Incomer Breaker (Type 4) Open/Close DI Off On Y

BMS_ ELE_ IMB4 MSB - Incomer Breaker (Type 4) Surge Alarm Protection Status DI Normal Alarm 2 Y

BMS_ ELE_ IMB4 MSB - Incomer Breaker (Type 4) Trip DI Normal Trip 1 Y
BMS_ ELE_ INCB MSB - Incomer MCCB Open/Close DI Off On Y
BMS_ ELE_ INCB MSB - Incomer MCCB Trip DI Normal Trip 1 Y
BMS_ ELE_ INC1 SSB - Incomer MCCB 1 Open/Close DI Off On Y
BMS_ ELE_ INC1 SSB - Incomer MCCB 1 Trip DI Normal Trip 1 Y
BMS_ ELE_ SPD2 SSB - Surge Protection Device 1 Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ INC2 SSB - Incomer MCCB 2 Open/Close DI Off On Y
BMS_ ELE_ INC2 SSB - Incomer MCCB 2 Trip DI Normal Trip 1 Y
BMS_ ELE_ SPD3 SSB - Surge Protection Device 2 Surge Alarm Protection Status DI Normal Alarm 2 Y
CPP - Incomer Breaker To UPS
BMS_ ELE_ IBUB Open/Close DI Off On N
Board

ICSS.BMS.1 (ELE) Page 6


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings- Analogue_Type_Meanings_Alarm/Event[AI]

Meaningful_Max_valu

Severity_of_Range>(iv
Value_Out_of_Range_

Value_Out_of_Range_
Value_LOWER_Limit(ii

Value_UPPER_Limit(iii

Severity_of_Range<(i)
Meaningful_Min_valu

Severity_of_Range(iii-
Transition_Interval_(s

Severity_of_Range(i)-
Other_bits_meanings
WPC_Data_Type

Scaling Factor
v2_label(10)
v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

HIGH(iv)
LOW(i)
Corrective
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit

ec)

(ii)

iv)
e
e

)
Maintenance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
CPP - Incomer Breaker To UPS
BMS_ ELE_ IBUB Trip DI Normal Trip 1 Y
Board
CPP - Incomer Breaker 1 To UPS
BMS_ ELE_ IBU1 Open/Close DI Off On N
Board
CPP - Incomer Breaker 1 To UPS
BMS_ ELE_ IBU1 Trip DI Normal Trip 1 Y
Board
CPP - Incomer Breaker 2 To UPS
BMS_ ELE_ IBU2 Open/Close DI Off On N
Board
CPP - Incomer Breaker 2 To UPS
BMS_ ELE_ IBU2 Trip DI Normal Trip 1 Y
Board
BMS_ ELE_ FOHL FOH Station Lighting Zone 33% On/Off Control DO Off On N
BMS_ ELE_ FOHL FOH Station Lighting Zone 66% On/Off Control DO Off On N
BMS_ ELE_ FOHL FOH Station Lighting Zone 100% On/Off Control DO Off On N
BMS_ ELE_ BOHL BOH Station Lighting Zone Operation Hours DO Off On N
BMS_ ELE_ BOHL BOH Station Lighting Zone Before Dawn/Night Only DO Off On N
BMS_ ELE_ BOHL BOH Station Lighting Zone Non-Operation Hours DO Off On N
BMS_ ELE_ ENTL Entrance Lighting Zone 50% On/Off Control DO Off On N
BMS_ ELE_ ENTL Entrance Lighting Zone 100% On/Off Control DO Off On N
BMS_ ELE_ SYLG Stabling Yard Lighting Zone 50% On/Off Control DO Off On N
BMS_ ELE_ SYLG Stabling Yard Lighting Zone 100% On/Off Control DO Off On N
BMS_ ELE_ TOSL Toilet/Surau On/Off Control DO Off On N
BMS_ ELE_ SIGN Signage On/Off Control DO Off On N
BMS_ ELE_ DB1_ Distribution Board (Type 1) Open/Close DI Off On N
BMS_ ELE_ DB2_ Distribution Board (Type 2) Open/Close DI Off On N
BMS_ ELE_ DB2_ Distribution Board (Type 2) Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ DB3A Distribution Board (Type 3) Open/Close DI Off On N
BMS_ ELE_ DB3A Distribution Board (Type 3) Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ DB3A Distribution Board (Type 3) On/Off Control 1 DO Off On N
BMS_ ELE_ DB3E Distribution Board (Type 3) Open/Close DI Off On N
BMS_ ELE_ DB3E Distribution Board (Type 3) Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ DB3E Distribution Board (Type 3) On/Off Control 1 DO Off On N
BMS_ ELE_ DB3E Distribution Board (Type 3) On/Off Control 2 DO Off On N
BMS_ ELE_ DB3D Distribution Board (Type 3) Open/Close DI Off On N
BMS_ ELE_ DB3D Distribution Board (Type 3) Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ DB3D Distribution Board (Type 3) On/Off Control 1 DO Off On N
BMS_ ELE_ DB3D Distribution Board (Type 3) On/Off Control 2 DO Off On N
BMS_ ELE_ DB3D Distribution Board (Type 3) On/Off Control 3 DO Off On N
BMS_ ELE_ DB3C Distribution Board (Type 3) Open/Close DI Off On N
BMS_ ELE_ DB3C Distribution Board (Type 3) Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ DB3C Distribution Board (Type 3) On/Off Control 1 DO Off On N
BMS_ ELE_ DB3C Distribution Board (Type 3) On/Off Control 2 DO Off On N
BMS_ ELE_ DB3C Distribution Board (Type 3) On/Off Control 3 DO Off On N

ICSS.BMS.1 (ELE) Page 7


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings- Analogue_Type_Meanings_Alarm/Event[AI]

Meaningful_Max_valu

Severity_of_Range>(iv
Value_Out_of_Range_

Value_Out_of_Range_
Value_LOWER_Limit(ii

Value_UPPER_Limit(iii

Severity_of_Range<(i)
Meaningful_Min_valu

Severity_of_Range(iii-
Transition_Interval_(s

Severity_of_Range(i)-
Other_bits_meanings
WPC_Data_Type

Scaling Factor
v2_label(10)
v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

HIGH(iv)
LOW(i)
Corrective
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit

ec)

(ii)

iv)
e
e

)
Maintenance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
BMS_ ELE_ DB3C Distribution Board (Type 3) On/Off Control 4 DO Off On N
BMS_ ELE_ DB3H Distribution Board (Type 3) Open/Close DI Off On N
BMS_ ELE_ DB3H Distribution Board (Type 3) Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ DB3H Distribution Board (Type 3) On/Off Control 1 DO Off On N
BMS_ ELE_ DB3H Distribution Board (Type 3) On/Off Control 2 DO Off On N
BMS_ ELE_ DB3H Distribution Board (Type 3) On/Off Control 3 DO Off On N
BMS_ ELE_ DB3H Distribution Board (Type 3) On/Off Control 4 DO Off On N
BMS_ ELE_ DB3H Distribution Board (Type 3) On/Off Control 5 DO Off On N
BMS_ ELE_ DB3B Distribution Board (Type 3) Open/Close DI Off On N
BMS_ ELE_ DB3B Distribution Board (Type 3) Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ DB3B Distribution Board (Type 3) On/Off Control 1 DO Off On N
BMS_ ELE_ DB3B Distribution Board (Type 3) On/Off Control 2 DO Off On N
BMS_ ELE_ DB3B Distribution Board (Type 3) On/Off Control 3 DO Off On N
BMS_ ELE_ DB3B Distribution Board (Type 3) On/Off Control 4 DO Off On N
BMS_ ELE_ DB3B Distribution Board (Type 3) On/Off Control 5 DO Off On N
BMS_ ELE_ DB3B Distribution Board (Type 3) On/Off Control 6 DO Off On N
BMS_ ELE_ DB3G Distribution Board (Type 3) Open/Close DI Off On N
BMS_ ELE_ DB3G Distribution Board (Type 3) Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ DB3G Distribution Board (Type 3) On/Off Control 1 DO Off On N
BMS_ ELE_ DB3G Distribution Board (Type 3) On/Off Control 2 DO Off On N
BMS_ ELE_ DB3G Distribution Board (Type 3) On/Off Control 3 DO Off On N
BMS_ ELE_ DB3G Distribution Board (Type 3) On/Off Control 4 DO Off On N
BMS_ ELE_ DB3G Distribution Board (Type 3) On/Off Control 5 DO Off On N
BMS_ ELE_ DB3G Distribution Board (Type 3) On/Off Control 6 DO Off On N
BMS_ ELE_ DB3G Distribution Board (Type 3) On/Off Control 7 DO Off On N
BMS_ ELE_ DB3I Distribution Board (Type 3) Open/Close DI Off On N
BMS_ ELE_ DB3I Distribution Board (Type 3) Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ DB3I Distribution Board (Type 3) On/Off Control 1 DO Off On N
BMS_ ELE_ DB3I Distribution Board (Type 3) On/Off Control 2 DO Off On N
BMS_ ELE_ DB3I Distribution Board (Type 3) On/Off Control 3 DO Off On N
BMS_ ELE_ DB3I Distribution Board (Type 3) On/Off Control 4 DO Off On N
BMS_ ELE_ DB3I Distribution Board (Type 3) On/Off Control 5 DO Off On N
BMS_ ELE_ DB3I Distribution Board (Type 3) On/Off Control 6 DO Off On N
BMS_ ELE_ DB3I Distribution Board (Type 3) On/Off Control 7 DO Off On N
BMS_ ELE_ DB3I Distribution Board (Type 3) On/Off Control 8 DO Off On N
BMS_ ELE_ DB3F Distribution Board (Type 3) Open/Close DI Off On N
BMS_ ELE_ DB3F Distribution Board (Type 3) Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ DB3F Distribution Board (Type 3) On/Off Control 1 DO Off On N
BMS_ ELE_ DB3F Distribution Board (Type 3) On/Off Control 2 DO Off On N
BMS_ ELE_ DB3F Distribution Board (Type 3) On/Off Control 3 DO Off On N
BMS_ ELE_ DB3F Distribution Board (Type 3) On/Off Control 4 DO Off On N
BMS_ ELE_ DB3F Distribution Board (Type 3) On/Off Control 5 DO Off On N

ICSS.BMS.1 (ELE) Page 8


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings- Analogue_Type_Meanings_Alarm/Event[AI]

Meaningful_Max_valu

Severity_of_Range>(iv
Value_Out_of_Range_

Value_Out_of_Range_
Value_LOWER_Limit(ii

Value_UPPER_Limit(iii

Severity_of_Range<(i)
Meaningful_Min_valu

Severity_of_Range(iii-
Transition_Interval_(s

Severity_of_Range(i)-
Other_bits_meanings
WPC_Data_Type

Scaling Factor
v2_label(10)
v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

HIGH(iv)
LOW(i)
Corrective
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit

ec)

(ii)

iv)
e
e

)
Maintenance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
BMS_ ELE_ DB3F Distribution Board (Type 3) On/Off Control 6 DO Off On N
BMS_ ELE_ DB3F Distribution Board (Type 3) On/Off Control 7 DO Off On N
BMS_ ELE_ DB3F Distribution Board (Type 3) On/Off Control 8 DO Off On N
BMS_ ELE_ DB3F Distribution Board (Type 3) On/Off Control 9 DO Off On N
BMS_ ELE_ DB3M Distribution Board (Type 3) Open/Close DI Off On N
BMS_ ELE_ DB3M Distribution Board (Type 3) Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ DB3M Distribution Board (Type 3) On/Off Control 1 DO Off On N
BMS_ ELE_ DB3M Distribution Board (Type 3) On/Off Control 2 DO Off On N
BMS_ ELE_ DB3M Distribution Board (Type 3) On/Off Control 3 DO Off On N
BMS_ ELE_ DB3M Distribution Board (Type 3) On/Off Control 4 DO Off On N
BMS_ ELE_ DB3M Distribution Board (Type 3) On/Off Control 5 DO Off On N
BMS_ ELE_ DB3M Distribution Board (Type 3) On/Off Control 6 DO Off On N
BMS_ ELE_ DB3M Distribution Board (Type 3) On/Off Control 7 DO Off On N
BMS_ ELE_ DB3M Distribution Board (Type 3) On/Off Control 8 DO Off On N
BMS_ ELE_ DB3M Distribution Board (Type 3) On/Off Control 9 DO Off On N
BMS_ ELE_ DB3M Distribution Board (Type 3) On/Off Control 10 DO Off On N
BMS_ ELE_ DB3L Distribution Board (Type 3) Open/Close DI Off On N
BMS_ ELE_ DB3L Distribution Board (Type 3) Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ DB3L Distribution Board (Type 3) On/Off Control 1 DO Off On N
BMS_ ELE_ DB3L Distribution Board (Type 3) On/Off Control 2 DO Off On N
BMS_ ELE_ DB3L Distribution Board (Type 3) On/Off Control 3 DO Off On N
BMS_ ELE_ DB3L Distribution Board (Type 3) On/Off Control 4 DO Off On N
BMS_ ELE_ DB3L Distribution Board (Type 3) On/Off Control 5 DO Off On N
BMS_ ELE_ DB3L Distribution Board (Type 3) On/Off Control 6 DO Off On N
BMS_ ELE_ DB3L Distribution Board (Type 3) On/Off Control 7 DO Off On N
BMS_ ELE_ DB3L Distribution Board (Type 3) On/Off Control 8 DO Off On N
BMS_ ELE_ DB3L Distribution Board (Type 3) On/Off Control 9 DO Off On N
BMS_ ELE_ DB3L Distribution Board (Type 3) On/Off Control 10 DO Off On N
BMS_ ELE_ DB3L Distribution Board (Type 3) On/Off Control 11 DO Off On N
BMS_ ELE_ DB3K Distribution Board (Type 3) Open/Close DI Off On N
BMS_ ELE_ DB3K Distribution Board (Type 3) Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ DB3K Distribution Board (Type 3) On/Off Control 1 DO Off On N
BMS_ ELE_ DB3K Distribution Board (Type 3) On/Off Control 2 DO Off On N
BMS_ ELE_ DB3K Distribution Board (Type 3) On/Off Control 3 DO Off On N
BMS_ ELE_ DB3K Distribution Board (Type 3) On/Off Control 4 DO Off On N
BMS_ ELE_ DB3K Distribution Board (Type 3) On/Off Control 5 DO Off On N
BMS_ ELE_ DB3K Distribution Board (Type 3) On/Off Control 6 DO Off On N
BMS_ ELE_ DB3K Distribution Board (Type 3) On/Off Control 7 DO Off On N
BMS_ ELE_ DB3K Distribution Board (Type 3) On/Off Control 8 DO Off On N
BMS_ ELE_ DB3K Distribution Board (Type 3) On/Off Control 9 DO Off On N
BMS_ ELE_ DB3K Distribution Board (Type 3) On/Off Control 10 DO Off On N
BMS_ ELE_ DB3K Distribution Board (Type 3) On/Off Control 11 DO Off On N

ICSS.BMS.1 (ELE) Page 9


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings- Analogue_Type_Meanings_Alarm/Event[AI]

Meaningful_Max_valu

Severity_of_Range>(iv
Value_Out_of_Range_

Value_Out_of_Range_
Value_LOWER_Limit(ii

Value_UPPER_Limit(iii

Severity_of_Range<(i)
Meaningful_Min_valu

Severity_of_Range(iii-
Transition_Interval_(s

Severity_of_Range(i)-
Other_bits_meanings
WPC_Data_Type

Scaling Factor
v2_label(10)
v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

HIGH(iv)
LOW(i)
Corrective
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit

ec)

(ii)

iv)
e
e

)
Maintenance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
BMS_ ELE_ DB3K Distribution Board (Type 3) On/Off Control 12 DO Off On N
BMS_ ELE_ DB3N Distribution Board (Type 3) Open/Close DI Off On N
BMS_ ELE_ DB3N Distribution Board (Type 3) Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ DB3N Distribution Board (Type 3) On/Off Control 1 DO Off On N
BMS_ ELE_ DB3N Distribution Board (Type 3) On/Off Control 2 DO Off On N
BMS_ ELE_ DB3N Distribution Board (Type 3) On/Off Control 3 DO Off On N
BMS_ ELE_ DB3N Distribution Board (Type 3) On/Off Control 4 DO Off On N
BMS_ ELE_ DB3N Distribution Board (Type 3) On/Off Control 5 DO Off On N
BMS_ ELE_ DB3N Distribution Board (Type 3) On/Off Control 6 DO Off On N
BMS_ ELE_ DB3N Distribution Board (Type 3) On/Off Control 7 DO Off On N
BMS_ ELE_ DB3N Distribution Board (Type 3) On/Off Control 8 DO Off On N
BMS_ ELE_ DB3N Distribution Board (Type 3) On/Off Control 9 DO Off On N
BMS_ ELE_ DB3N Distribution Board (Type 3) On/Off Control 10 DO Off On N
BMS_ ELE_ DB3N Distribution Board (Type 3) On/Off Control 11 DO Off On N
BMS_ ELE_ DB3N Distribution Board (Type 3) On/Off Control 12 DO Off On N
BMS_ ELE_ DB3N Distribution Board (Type 3) On/Off Control 13 DO Off On N
BMS_ ELE_ DB3J Distribution Board (Type 3) Open/Close DI Off On N
BMS_ ELE_ DB3J Distribution Board (Type 3) Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ DB3J Distribution Board (Type 3) On/Off Control 1 DO Off On N
BMS_ ELE_ DB3J Distribution Board (Type 3) On/Off Control 2 DO Off On N
BMS_ ELE_ DB3J Distribution Board (Type 3) On/Off Control 3 DO Off On N
BMS_ ELE_ DB3J Distribution Board (Type 3) On/Off Control 4 DO Off On N
BMS_ ELE_ DB3J Distribution Board (Type 3) On/Off Control 5 DO Off On N
BMS_ ELE_ DB3J Distribution Board (Type 3) On/Off Control 6 DO Off On N
BMS_ ELE_ DB3J Distribution Board (Type 3) On/Off Control 7 DO Off On N
BMS_ ELE_ DB3J Distribution Board (Type 3) On/Off Control 8 DO Off On N
BMS_ ELE_ DB3J Distribution Board (Type 3) On/Off Control 9 DO Off On N
BMS_ ELE_ DB3J Distribution Board (Type 3) On/Off Control 10 DO Off On N
BMS_ ELE_ DB3J Distribution Board (Type 3) On/Off Control 11 DO Off On N
BMS_ ELE_ DB3J Distribution Board (Type 3) On/Off Control 12 DO Off On N
BMS_ ELE_ DB3J Distribution Board (Type 3) On/Off Control 13 DO Off On N
BMS_ ELE_ DB3J Distribution Board (Type 3) On/Off Control 14 DO Off On N
BMS_ ELE_ DB3J Distribution Board (Type 3) On/Off Control 15 DO Off On N
BMS_ ELE_ DB3J Distribution Board (Type 3) On/Off Control 16 DO Off On N
BMS_ ELE_ DB3O Distribution Board (Type 3) Open/Close DI Off On N
BMS_ ELE_ DB3O Distribution Board (Type 3) Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ DB3O Distribution Board (Type 3) On/Off Control 1 DO Off On N
BMS_ ELE_ DB3O Distribution Board (Type 3) On/Off Control 2 DO Off On N
BMS_ ELE_ DB3O Distribution Board (Type 3) On/Off Control 3 DO Off On N
BMS_ ELE_ DB3O Distribution Board (Type 3) On/Off Control 4 DO Off On N
BMS_ ELE_ DB3O Distribution Board (Type 3) On/Off Control 5 DO Off On N
BMS_ ELE_ DB3O Distribution Board (Type 3) On/Off Control 6 DO Off On N

ICSS.BMS.1 (ELE) Page 10


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings- Analogue_Type_Meanings_Alarm/Event[AI]

Meaningful_Max_valu

Severity_of_Range>(iv
Value_Out_of_Range_

Value_Out_of_Range_
Value_LOWER_Limit(ii

Value_UPPER_Limit(iii

Severity_of_Range<(i)
Meaningful_Min_valu

Severity_of_Range(iii-
Transition_Interval_(s

Severity_of_Range(i)-
Other_bits_meanings
WPC_Data_Type

Scaling Factor
v2_label(10)
v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

HIGH(iv)
LOW(i)
Corrective
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit

ec)

(ii)

iv)
e
e

)
Maintenance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
BMS_ ELE_ DB3O Distribution Board (Type 3) On/Off Control 7 DO Off On N
BMS_ ELE_ DB3O Distribution Board (Type 3) On/Off Control 8 DO Off On N
BMS_ ELE_ DB3O Distribution Board (Type 3) On/Off Control 9 DO Off On N
BMS_ ELE_ DB3O Distribution Board (Type 3) On/Off Control 10 DO Off On N
BMS_ ELE_ DB3O Distribution Board (Type 3) On/Off Control 11 DO Off On N
BMS_ ELE_ DB3O Distribution Board (Type 3) On/Off Control 12 DO Off On N
BMS_ ELE_ DB3O Distribution Board (Type 3) On/Off Control 13 DO Off On N
BMS_ ELE_ DB3O Distribution Board (Type 3) On/Off Control 14 DO Off On N
BMS_ ELE_ DB3O Distribution Board (Type 3) On/Off Control 15 DO Off On N
BMS_ ELE_ DB3O Distribution Board (Type 3) On/Off Control 16 DO Off On N
BMS_ ELE_ DB3O Distribution Board (Type 3) On/Off Control 17 DO Off On N
BMS_ ELE_ DB3O Distribution Board (Type 3) On/Off Control 18 DO Off On N
BMS_ ELE_ DB3O Distribution Board (Type 3) On/Off Control 19 DO Off On N
BMS_ ELE_ DB3O Distribution Board (Type 3) On/Off Control 20 DO Off On N
BMS_ ELE_ DB3O Distribution Board (Type 3) On/Off Control 21 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) Open/Close DI Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 1 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 2 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 3 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 4 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 5 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 6 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 7 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 8 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 9 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 10 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 11 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 12 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 13 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 14 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 15 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 16 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 17 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 18 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 19 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 20 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 21 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 22 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 23 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 24 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 25 DO Off On N

ICSS.BMS.1 (ELE) Page 11


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings- Analogue_Type_Meanings_Alarm/Event[AI]

Meaningful_Max_valu

Severity_of_Range>(iv
Value_Out_of_Range_

Value_Out_of_Range_
Value_LOWER_Limit(ii

Value_UPPER_Limit(iii

Severity_of_Range<(i)
Meaningful_Min_valu

Severity_of_Range(iii-
Transition_Interval_(s

Severity_of_Range(i)-
Other_bits_meanings
WPC_Data_Type

Scaling Factor
v2_label(10)
v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

HIGH(iv)
LOW(i)
Corrective
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit

ec)

(ii)

iv)
e
e

)
Maintenance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 26 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 27 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 28 DO Off On N
BMS_ ELE_ DB3P Distribution Board (Type 3) On/Off Control 29 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) Open/Close DI Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 1 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 2 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 3 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 4 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 5 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 6 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 7 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 8 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 9 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 10 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 11 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 12 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 13 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 14 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 15 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 16 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 17 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 18 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 19 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 20 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 21 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 22 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 23 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 24 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 25 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 26 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 27 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 28 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 29 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 30 DO Off On N
BMS_ ELE_ DB3Q Distribution Board (Type 3) On/Off Control 31 DO Off On N
BMS_ ELE_ DB4A Distribution Board (Type 4) Open/Close DI Off On N
BMS_ ELE_ DB4A Distribution Board (Type 4) On/Off Control 1 DO Off On N
BMS_ ELE_ DB4C Distribution Board (Type 4) Open/Close DI Off On N
BMS_ ELE_ DB4C Distribution Board (Type 4) On/Off Control 1 DO Off On N
BMS_ ELE_ DB4C Distribution Board (Type 4) On/Off Control 2 DO Off On N

ICSS.BMS.1 (ELE) Page 12


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings- Analogue_Type_Meanings_Alarm/Event[AI]

Meaningful_Max_valu

Severity_of_Range>(iv
Value_Out_of_Range_

Value_Out_of_Range_
Value_LOWER_Limit(ii

Value_UPPER_Limit(iii

Severity_of_Range<(i)
Meaningful_Min_valu

Severity_of_Range(iii-
Transition_Interval_(s

Severity_of_Range(i)-
Other_bits_meanings
WPC_Data_Type

Scaling Factor
v2_label(10)
v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

HIGH(iv)
LOW(i)
Corrective
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit

ec)

(ii)

iv)
e
e

)
Maintenance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
BMS_ ELE_ DB4D Distribution Board (Type 4) Open/Close DI Off On N
BMS_ ELE_ DB4D Distribution Board (Type 4) On/Off Control 1 DO Off On N
BMS_ ELE_ DB4D Distribution Board (Type 4) On/Off Control 2 DO Off On N
BMS_ ELE_ DB4D Distribution Board (Type 4) On/Off Control 3 DO Off On N
BMS_ ELE_ DB4B Distribution Board (Type 4) Open/Close DI Off On N
BMS_ ELE_ DB4B Distribution Board (Type 4) On/Off Control 1 DO Off On N
BMS_ ELE_ DB4B Distribution Board (Type 4) On/Off Control 2 DO Off On N
BMS_ ELE_ DB4B Distribution Board (Type 4) On/Off Control 3 DO Off On N
BMS_ ELE_ DB4B Distribution Board (Type 4) On/Off Control 4 DO Off On N
BMS_ ELE_ DB4F Distribution Board (Type 4) Open/Close DI Off On N
BMS_ ELE_ DB4F Distribution Board (Type 4) On/Off Control 1 DO Off On N
BMS_ ELE_ DB4F Distribution Board (Type 4) On/Off Control 2 DO Off On N
BMS_ ELE_ DB4F Distribution Board (Type 4) On/Off Control 3 DO Off On N
BMS_ ELE_ DB4F Distribution Board (Type 4) On/Off Control 4 DO Off On N
BMS_ ELE_ DB4F Distribution Board (Type 4) On/Off Control 5 DO Off On N
BMS_ ELE_ DB4G Distribution Board (Type 4) Open/Close DI Off On N
BMS_ ELE_ DB4G Distribution Board (Type 4) On/Off Control 1 DO Off On N
BMS_ ELE_ DB4G Distribution Board (Type 4) On/Off Control 2 DO Off On N
BMS_ ELE_ DB4G Distribution Board (Type 4) On/Off Control 3 DO Off On N
BMS_ ELE_ DB4G Distribution Board (Type 4) On/Off Control 4 DO Off On N
BMS_ ELE_ DB4G Distribution Board (Type 4) On/Off Control 5 DO Off On N
BMS_ ELE_ DB4G Distribution Board (Type 4) On/Off Control 6 DO Off On N
BMS_ ELE_ DB4E Distribution Board (Type 4) Open/Close DI Off On N
BMS_ ELE_ DB4E Distribution Board (Type 4) On/Off Control 1 DO Off On N
BMS_ ELE_ DB4E Distribution Board (Type 4) On/Off Control 2 DO Off On N
BMS_ ELE_ DB4E Distribution Board (Type 4) On/Off Control 3 DO Off On N
BMS_ ELE_ DB4E Distribution Board (Type 4) On/Off Control 4 DO Off On N
BMS_ ELE_ DB4E Distribution Board (Type 4) On/Off Control 5 DO Off On N
BMS_ ELE_ DB4E Distribution Board (Type 4) On/Off Control 6 DO Off On N
BMS_ ELE_ DB4E Distribution Board (Type 4) On/Off Control 7 DO Off On N
BMS_ ELE_ DB5_ Distribution Board (Type 5) Open/Close DI Off On N
BMS_ ELE_ DB5_ Distribution Board (Type 5) Trip DI Normal Trip 1 Y
BMS_ ELE_ DB6F Distribution Board (Type 6) Open/Close DI Off On N
BMS_ ELE_ DB6F Distribution Board (Type 6) Trip DI Normal Trip 1 Y
BMS_ ELE_ DB6F Distribution Board (Type 6) On/Off Control 1 DO Off On N
BMS_ ELE_ DB6_ Distribution Board (Type 6) Open/Close DI Off On N
BMS_ ELE_ DB6_ Distribution Board (Type 6) Trip DI Normal Trip 1 Y
BMS_ ELE_ DB6_ Distribution Board (Type 6) On/Off Control 1 DO Off On N
BMS_ ELE_ DB6_ Distribution Board (Type 6) On/Off Control 2 DO Off On N
BMS_ ELE_ DB6D Distribution Board (Type 6) Open/Close DI Off On N
BMS_ ELE_ DB6D Distribution Board (Type 6) Trip DI Normal Trip 1 Y
BMS_ ELE_ DB6D Distribution Board (Type 6) On/Off Control 1 DO Off On N

ICSS.BMS.1 (ELE) Page 13


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings- Analogue_Type_Meanings_Alarm/Event[AI]

Meaningful_Max_valu

Severity_of_Range>(iv
Value_Out_of_Range_

Value_Out_of_Range_
Value_LOWER_Limit(ii

Value_UPPER_Limit(iii

Severity_of_Range<(i)
Meaningful_Min_valu

Severity_of_Range(iii-
Transition_Interval_(s

Severity_of_Range(i)-
Other_bits_meanings
WPC_Data_Type

Scaling Factor
v2_label(10)
v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

HIGH(iv)
LOW(i)
Corrective
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit

ec)

(ii)

iv)
e
e

)
Maintenance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
BMS_ ELE_ DB6D Distribution Board (Type 6) On/Off Control 2 DO Off On N
BMS_ ELE_ DB6D Distribution Board (Type 6) On/Off Control 3 DO Off On N
BMS_ ELE_ DB6C Distribution Board (Type 6) Open/Close DI Off On N
BMS_ ELE_ DB6C Distribution Board (Type 6) Trip DI Normal Trip 1 Y
BMS_ ELE_ DB6C Distribution Board (Type 6) On/Off Control 1 DO Off On N
BMS_ ELE_ DB6C Distribution Board (Type 6) On/Off Control 2 DO Off On N
BMS_ ELE_ DB6C Distribution Board (Type 6) On/Off Control 3 DO Off On N
BMS_ ELE_ DB6C Distribution Board (Type 6) On/Off Control 4 DO Off On N
BMS_ ELE_ DB6G Distribution Board (Type 6) Open/Close DI Off On N
BMS_ ELE_ DB6G Distribution Board (Type 6) Trip DI Normal Trip 1 Y
BMS_ ELE_ DB6G Distribution Board (Type 6) On/Off Control 1 DO Off On N
BMS_ ELE_ DB6G Distribution Board (Type 6) On/Off Control 2 DO Off On N
BMS_ ELE_ DB6G Distribution Board (Type 6) On/Off Control 3 DO Off On N
BMS_ ELE_ DB6G Distribution Board (Type 6) On/Off Control 4 DO Off On N
BMS_ ELE_ DB6G Distribution Board (Type 6) On/Off Control 5 DO Off On N
BMS_ ELE_ DB6E Distribution Board (Type 6) Open/Close DI Off On N
BMS_ ELE_ DB6E Distribution Board (Type 6) Trip DI Normal Trip 1 Y
BMS_ ELE_ DB6E Distribution Board (Type 6) On/Off Control 1 DO Off On N
BMS_ ELE_ DB6E Distribution Board (Type 6) On/Off Control 2 DO Off On N
BMS_ ELE_ DB6E Distribution Board (Type 6) On/Off Control 3 DO Off On N
BMS_ ELE_ DB6E Distribution Board (Type 6) On/Off Control 4 DO Off On N
BMS_ ELE_ DB6E Distribution Board (Type 6) On/Off Control 5 DO Off On N
BMS_ ELE_ DB6E Distribution Board (Type 6) On/Off Control 6 DO Off On N
BMS_ ELE_ DB6H Distribution Board (Type 6) Open/Close DI Off On N
BMS_ ELE_ DB6H Distribution Board (Type 6) Trip DI Normal Trip 1 Y
BMS_ ELE_ DB6H Distribution Board (Type 6) On/Off Control 1 DO Off On N
BMS_ ELE_ DB6H Distribution Board (Type 6) On/Off Control 2 DO Off On N
BMS_ ELE_ DB6H Distribution Board (Type 6) On/Off Control 3 DO Off On N
BMS_ ELE_ DB6H Distribution Board (Type 6) On/Off Control 4 DO Off On N
BMS_ ELE_ DB6H Distribution Board (Type 6) On/Off Control 5 DO Off On N
BMS_ ELE_ DB6H Distribution Board (Type 6) On/Off Control 6 DO Off On N
BMS_ ELE_ DB6H Distribution Board (Type 6) On/Off Control 7 DO Off On N
BMS_ ELE_ DB6B Distribution Board (Type 6) Open/Close DI Off On N
BMS_ ELE_ DB6B Distribution Board (Type 6) Trip DI Normal Trip 1 Y
BMS_ ELE_ DB6B Distribution Board (Type 6) On/Off Control 1 DO Off On N
BMS_ ELE_ DB6B Distribution Board (Type 6) On/Off Control 2 DO Off On N
BMS_ ELE_ DB6B Distribution Board (Type 6) On/Off Control 3 DO Off On N
BMS_ ELE_ DB6B Distribution Board (Type 6) On/Off Control 4 DO Off On N
BMS_ ELE_ DB6B Distribution Board (Type 6) On/Off Control 5 DO Off On N
BMS_ ELE_ DB6B Distribution Board (Type 6) On/Off Control 6 DO Off On N
BMS_ ELE_ DB6B Distribution Board (Type 6) On/Off Control 7 DO Off On N
BMS_ ELE_ DB6B Distribution Board (Type 6) On/Off Control 8 DO Off On N

ICSS.BMS.1 (ELE) Page 14


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings- Analogue_Type_Meanings_Alarm/Event[AI]

Meaningful_Max_valu

Severity_of_Range>(iv
Value_Out_of_Range_

Value_Out_of_Range_
Value_LOWER_Limit(ii

Value_UPPER_Limit(iii

Severity_of_Range<(i)
Meaningful_Min_valu

Severity_of_Range(iii-
Transition_Interval_(s

Severity_of_Range(i)-
Other_bits_meanings
WPC_Data_Type

Scaling Factor
v2_label(10)
v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

HIGH(iv)
LOW(i)
Corrective
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit

ec)

(ii)

iv)
e
e

)
Maintenance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
BMS_ ELE_ DB6A Distribution Board (Type 6) Open/Close DI Off On N
BMS_ ELE_ DB6A Distribution Board (Type 6) Trip DI Normal Trip 1 Y
BMS_ ELE_ DB6A Distribution Board (Type 6) On/Off Control 1 DO Off On N
BMS_ ELE_ DB6A Distribution Board (Type 6) On/Off Control 2 DO Off On N
BMS_ ELE_ DB6A Distribution Board (Type 6) On/Off Control 3 DO Off On N
BMS_ ELE_ DB6A Distribution Board (Type 6) On/Off Control 4 DO Off On N
BMS_ ELE_ DB6A Distribution Board (Type 6) On/Off Control 5 DO Off On N
BMS_ ELE_ DB6A Distribution Board (Type 6) On/Off Control 6 DO Off On N
BMS_ ELE_ DB6A Distribution Board (Type 6) On/Off Control 7 DO Off On N
BMS_ ELE_ DB6A Distribution Board (Type 6) On/Off Control 8 DO Off On N
BMS_ ELE_ DB6A Distribution Board (Type 6) On/Off Control 9 DO Off On N
BMS_ ELE_ DB7_ Distribution Board (Type 7) On/Off Control 1 DO Off On N
BMS_ ELE_ DB7_ Distribution Board (Type 7) On/Off Control 2 DO Off On N
BMS_ ELE_ DB7A Distribution Board (Type 7) Open/Close DI Off On N
BMS_ ELE_ DB7A Distribution Board (Type 7) Open Control DO - Open N
BMS_ ELE_ DB7A Distribution Board (Type 7) Close Control DO - Close N
BMS_ ELE_ DB7B Distribution Board (Type 7) Open/Close DI Off On N
BMS_ ELE_ DB7B Distribution Board (Type 7) Open Control 1 DO - Open N
BMS_ ELE_ DB7B Distribution Board (Type 7) Close Control 1 DO - Close N
BMS_ ELE_ DB7B Distribution Board (Type 7) Open Control 2 DO - Open N
BMS_ ELE_ DB7B Distribution Board (Type 7) Close Control 2 DO - Close N
BMS_ ELE_ DB7B Distribution Board (Type 7) Open Control 3 DO - Open N
BMS_ ELE_ DB7B Distribution Board (Type 7) Close Control 3 DO - Close N
BMS_ ELE_ DB7C Distribution Board (Type 7) Open/Close DI Off On N
BMS_ ELE_ DB7C Distribution Board (Type 7) Open Control 1 DO - Open N
BMS_ ELE_ DB7C Distribution Board (Type 7) Close Control 1 DO - Close N
BMS_ ELE_ DB7C Distribution Board (Type 7) Open Control 2 DO - Open N
BMS_ ELE_ DB7C Distribution Board (Type 7) Close Control 2 DO - Close N
BMS_ ELE_ DB7C Distribution Board (Type 7) Open Control 3 DO - Open N
BMS_ ELE_ DB7C Distribution Board (Type 7) Close Control 3 DO - Close N
BMS_ ELE_ DB7C Distribution Board (Type 7) Open Control 4 DO - Open N
BMS_ ELE_ DB7C Distribution Board (Type 7) Close Control 4 DO - Close N
BMS_ ELE_ DB9_ Distribution Board (Type 9) On/Off Status DI Off On N
BMS_ ELE_ DB9_ Distribution Board (Type 9) Open/Close DI Off On N
BMS_ ELE_ DB9_ Distribution Board (Type 9) Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ DB9_ Distribution Board (Type 9) On/Off Control 1 DO Off On N
BMS_ ELE_ DB10 Distribution Board (Type 10) On/Off Control 1 DO Off On N
BMS_ ELE_ DB11 Distribution Board (Type 11) Open/Close DI Off On N
BMS_ ELE_ DB11 Distribution Board (Type 11) Surge Alarm Protection Status DI Normal Alarm 2 Y
BMS_ ELE_ DB11 Distribution Board (Type 11) Auto Status DI Manual 3 Auto N
BMS_ ELE_ DB11 Distribution Board (Type 11) On/Off Status 1 DI Off On N
BMS_ ELE_ DB11 Distribution Board (Type 11) On/Off Control 1 DO Off On N

ICSS.BMS.1 (ELE) Page 15


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings- Analogue_Type_Meanings_Alarm/Event[AI]

Meaningful_Max_valu

Severity_of_Range>(iv
Value_Out_of_Range_

Value_Out_of_Range_
Value_LOWER_Limit(ii

Value_UPPER_Limit(iii

Severity_of_Range<(i)
Meaningful_Min_valu

Severity_of_Range(iii-
Transition_Interval_(s

Severity_of_Range(i)-
Other_bits_meanings
WPC_Data_Type

Scaling Factor
v2_label(10)
v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

HIGH(iv)
LOW(i)
Corrective
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit

ec)

(ii)

iv)
e
e

)
Maintenance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
BMS_ ELE_ DB12 Distribution Board (Type 12) Open/Close DI Off On N
BMS_ ELE_ DB12 Distribution Board (Type 12) Trip DI Normal Trip 1 Y
BMS_ ELE_ DB12 Distribution Board (Type 12) Auto Status DI Manual 3 Auto Y
BMS_ ELE_ DB12 Distribution Board (Type 12) On/Off Status 1 DI Off On N
BMS_ ELE_ DB12 Distribution Board (Type 12) On/Off Status 2 DI Off On N
BMS_ ELE_ DB12 Distribution Board (Type 12) On/Off Control 1 DO Off On N
BMS_ ELE_ DB12 Distribution Board (Type 12) On/Off Control 2 DO Off On N
BMS_ ELE_ NBL_ Noise Barrier Lighting Trip DI Normal Trip 1 Y
BMS_ ELE_ NBL_ Noise Barrier Lighting On/Off Control 1 DO Off On N
BMS_ ELE_ NBL1 Noise Barrier Lighting (Type 2) Open/Close DI Off On N
BMS_ ELE_ NBL1 Noise Barrier Lighting (Type 2) Trip DI Normal Trip 1 Y
BMS_ ELE_ NBL1 Noise Barrier Lighting (Type 2) On/Off Control 1 DO Off On N
BMS_ ELE_ NBL2 Noise Barrier Lighting (Type 3) Trip 1 DI Normal Trip 1 Y
BMS_ ELE_ NBL2 Noise Barrier Lighting (Type 3) On/Off Control 1 DO Off On N
BMS_ ELE_ NBL2 Noise Barrier Lighting (Type 3) Trip 2 DI Normal Trip 1 Y
BMS_ ELE_ NBL2 Noise Barrier Lighting (Type 3) On/Off Control 2 DO Off On N
BMS_ ELE_ ESS_ Roller Shutter Open Control DO - Open N
BMS_ ELE_ ESS_ Roller Shutter Close Control DO - Close N
BMS_ ELE_ COUP Coupler Open/Close DI Off On N
BMS_ ELE_ COUP Coupler Trip DI Normal Trip 1 Y
BMS_ ELE_ OTBR SSB - Outgoing Breaker (Type 1) Open/Close DI Off On N

BMS_ ELE_ OTBR SSB - Outgoing Breaker (Type 1) Trip DI Normal Trip 1 Y

BMS_ ELE_ OTB2 SSB - Outgoing Breaker (Type 2) Open/Close DI Off On N

BMS_ ELE_ OTB4 SSB - Outgoing Breaker (Type 3) Open/Close 1 DI Off On N

BMS_ ELE_ OTB4 SSB - Outgoing Breaker (Type 3) Open/Close 2 DI Off On N

BMS_ ELE_ OTB5 SSB - Outgoing Breaker (Type 4) Open/Close 1 DI Off On N

BMS_ ELE_ OTB5 SSB - Outgoing Breaker (Type 4) Open/Close 2 DI Off On N

BMS_ ELE_ OTB5 SSB - Outgoing Breaker (Type 4) Open/Close 3 DI Off On N

BMS_ ELE_ OTB3 MSB - Outgoing Breaker (Type 2) Open/Close DI Off On N


BMS_ ELE_ EXTL SSB - External Lighting Open/Close DI Off On N

ICSS.BMS.1 (ELE) Page 16


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings- Analogue_Type_Meanings_Alarm/Event[AI]

WPC_Data_Type

Meaningful_Min

Value_LOWER_L
Value_Out_of_R

Value_Out_of_R

Severity_of_Ran

Severity_of_Ran

Severity_of_Ran

Severity_of_Ran
Value_UPPER_Li
Other_bits_mea

Transition_Inter

Meaningful_Ma

ange_HIGH(iv)

Scaling Factor
ange_LOW(i)
Correc

v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

val_(sec)

ge(iii-iv)
ge(i)-(ii)
x_value

ge>(iv)
imit(ii)

mit(iii)
_value
tive

ge<(i)
nings
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit
Mainte
nance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
Local Motor Control Panel (Type
BMS_ ECS_ LMC1 Auto Status DI Manual 3 Auto N
1)
Local Motor Control Panel (Type
BMS_ ECS_ LMC1 Incoming Breaker Status DI Off On N
1)
Local Motor Control Panel (Type
BMS_ ECS_ LMC1 Room Temperature °C AI 0 28 50 3 1 3 N
1)
Local Motor Control Panel (Type
BMS_ ECS_ LMC2 Auto Status DI Manual 3 Auto N
2)
Local Motor Control Panel (Type
BMS_ ECS_ LMC2 Incoming Breaker Status DI Off On N
2)
Local Motor Control Panel (Type
BMS_ ECS_ LMC3 Incoming Breaker Status DI Off On N
3)
Local Motor Control Panel (Type
BMS_ ECS_ LMC3 Room Temperature °C AI 0 28 50 3 1 3 N
3)
Local Motor Control Panel (Type
BMS_ ECS_ LMC4 Incoming Breaker Status DI Off On N
4)
Local Motor Control Panel (Type
BMS_ ECS_ LMC5 Auto Status DI Manual 3 Auto N
5)
Local Motor Control Panel (Type
BMS_ ECS_ LMC5 Damper Fully Closed Status DI Open Close N
5)
Local Motor Control Panel (Type
BMS_ ECS_ LMC6 Auto Status DI Manual 3 Auto N
6)
Local Motor Control Panel (Type
BMS_ ECS_ LMC6 Damper Fully Closed Status DI Open Close N
6)
Local Motor Control Panel (Type
BMS_ ECS_ LMC6 Incoming Breaker Status DI Off On N
6)
Local Motor Control Panel (Type
BMS_ ECS_ LMC6 Room Temperature °C AI 0 28 50 3 1 3 N
6)
Local Motor Control Panel (Type
BMS_ ECS_ LMC7 Auto Status DI Remote Auto N
7)
Local Motor Control Panel (Type
BMS_ ECS_ LMC7 Incoming Breaker Status DI Off On N
7)
Local Motor Control Panel (Type
BMS_ ECS_ LMC7 Run/Stop Command DO Stop Run N
7)
Local Motor Control Panel (Type
BMS_ ECS_ LMC8 Auto Status DI Manual 3 Auto N
8)
Local Motor Control Panel (Type
BMS_ ECS_ LMC8 Room Temperature °C AI 0 28 50 3 1 3 N
8)
Local Motor Control Panel (Type
BMS_ ECS_ LMC9 Damper Fully Closed Status DI Open Close N
9)
Local Motor Control Panel (Type
BMS_ ECS_ LMC9 Incoming Breaker Status DI Off On N
9)
Local Motor Control Panel (Type
BMS_ ECS_ LMC9 Room Temperature °C AI 0 28 50 3 1 3 N
9)
Local Motor Control Panel (Type
BMS_ ECS_ LM10 Auto Status DI Manual 3 Auto N
10)
Local Motor Control Panel (Type
BMS_ ECS_ LM10 Incoming Breaker Status DI Off On N
10)
Local Motor Control Panel (Type
BMS_ ECS_ LM10 Room Temperature °C AI 0 40 50 3 1 3 N
10)

ICSS.BMS.1 (ECS) Page 1


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings- Analogue_Type_Meanings_Alarm/Event[AI]

WPC_Data_Type

Meaningful_Min

Value_LOWER_L
Value_Out_of_R

Value_Out_of_R

Severity_of_Ran

Severity_of_Ran

Severity_of_Ran

Severity_of_Ran
Value_UPPER_Li
Other_bits_mea

Transition_Inter

Meaningful_Ma

ange_HIGH(iv)

Scaling Factor
ange_LOW(i)
Correc

v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

val_(sec)

ge(iii-iv)
ge(i)-(ii)
x_value

ge>(iv)
imit(ii)

mit(iii)
_value
tive

ge<(i)
nings
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit
Mainte
nance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
Local Motor Control Panel (Type
BMS_ ECS_ LM11 Incoming Breaker Status DI Off On N
11)
Local Motor Control Panel (Type
BMS_ ECS_ LM11 Room Temperature °C AI 0 36 50 3 1 3 N
11)
Local Motor Control Panel (Type
BMS_ ECS_ LM12 Auto Status DI Manual 3 Auto N
12)
Local Motor Control Panel (Type
BMS_ ECS_ LM12 Room Temperature °C AI 0 36 50 3 1 3 N
12)
Local Motor Control Panel (Type
BMS_ ECS_ LM13 Room Temperature °C AI 0 36 50 3 1 3 N
13)
Local Motor Control Panel (Type
BMS_ ECS_ LM14 Room Temperature °C AI 0 28 50 3 1 3 N
14)
BMS_ ECS_ FCU1 Fan Coil Unit (Type 1) On/Off Status DI Off On N
BMS_ ECS_ FCU1 Fan Coil Unit (Type 1) Trip Fault Alarm DI Normal Trip 2 Y
BMS_ ECS_ FCU2 Fan Coil Unit (Type 2) On/Off Status DI Off On N
BMS_ ECS_ FCU2 Fan Coil Unit (Type 2) Trip Fault Alarm DI Normal Trip 2 Y
BMS_ ECS_ FCU2 Fan Coil Unit (Type 2) Run/Stop Command DO Stop Run N
BMS_ ECS_ FCU2 Fan Coil Unit (Type 2) Room Temperature °C AI 0 28 50 3 1 3 N
BMS_ ECS_ FCU3 Fan Coil Unit (Type 3) On/Off Status DI Off On N
BMS_ ECS_ FCU3 Fan Coil Unit (Type 3) Trip Fault Alarm DI Normal Trip 2 Y
BMS_ ECS_ FCU3 Fan Coil Unit (Type 3) Run/Stop Command DO Stop Run N
BMS_ ECS_ FCU3 Fan Coil Unit (Type 3) Room Temperature °C AI 0 28 50 3 1 3 Y
BMS_ ECS_ FCU4 Fan Coil Unit (Type 4) On/Off Status DI Off On N
BMS_ ECS_ FCU4 Fan Coil Unit (Type 4) Trip Fault Alarm DI Normal Trip 2 Y
BMS_ ECS_ FCU4 Fan Coil Unit (Type 4) Room Temperature °C AI 0 28 50 3 1 3 N
BMS_ ECS_ FCU5 Fan Coil Unit (Type 5) On/Off Status DI Off On N
BMS_ ECS_ FCU5 Fan Coil Unit (Type 5) Trip Fault Alarm DI Normal Trip 2 Y
BMS_ ECS_ FCU5 Fan Coil Unit (Type 5) Run/Stop Command DO Stop Run N
BMS_ ECS_ FCU6 Fan Coil Unit (Type 6) On/Off Status DI Off On N
BMS_ ECS_ FCU6 Fan Coil Unit (Type 6) Trip Fault Alarm DI Normal 2 Trip 2 Y
BMS_ ECS_ FCU7 Fan Coil Unit (Type 7) On/Off Status DI Off On N
BMS_ ECS_ FCU7 Fan Coil Unit (Type 7) Trip Fault Alarm DI Normal Trip 3 Y
BMS_ ECS_ FCU7 Fan Coil Unit (Type 7) Run/Stop Command DO Stop Run N
BMS_ ECS_ FCU7 Fan Coil Unit (Type 7) Room Temperature °C AI 0 28 50 3 1 3 N
BMS_ ECS_ FCU8 Fan Coil Unit (Type 8) On/Off Status DI Off On N
BMS_ ECS_ FCU8 Fan Coil Unit (Type 8) Trip Fault Alarm DI Normal Trip 3 Y
BMS_ ECS_ FCU9 Fan Coil Unit (Type 9) On/Off Status DI Off On N
BMS_ ECS_ FCU9 Fan Coil Unit (Type 9) Trip Fault Alarm DI Normal Trip 3 Y
BMS_ ECS_ FCU9 Fan Coil Unit (Type 9) Room Temperature °C AI 0 28 50 3 1 3 N
BMS_ ECS_ MFD1 Motorized Fire Damper (Type 1) Damper Fully Closed Status DI Open Close N

BMS_ ECS_ MFD2 Motorized Fire Damper (Type 2) Damper Fully Opened Status DI Close Open N
BMS_ ECS_ MDFO Motorised Damper Damper Fully Opened Status DI Close Open N
BMS_ ECS_ MDFC Motorised Damper Damper Fully Closed Status DI Open Close N
BMS_ ECS_ AVRF Air-Conditioning- VRF (Outdoor) Incoming Breaker On Status DI Off On N

BMS_ ECS_ AVRF Air-Conditioning- VRF (Outdoor) Trip Fault Alarm DI Normal Trip Y
BMS_ ECS_ ACCU VRF Condensing Unit Trip Fault Alarm DI Normal Trip 2 Y

ICSS.BMS.1 (ECS) Page 2


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings- Analogue_Type_Meanings_Alarm/Event[AI]

WPC_Data_Type

Meaningful_Min

Value_LOWER_L
Value_Out_of_R

Value_Out_of_R

Severity_of_Ran

Severity_of_Ran

Severity_of_Ran

Severity_of_Ran
Value_UPPER_Li
Other_bits_mea

Transition_Inter

Meaningful_Ma

ange_HIGH(iv)

Scaling Factor
ange_LOW(i)
Correc

v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

val_(sec)

ge(iii-iv)
ge(i)-(ii)
x_value

ge>(iv)
imit(ii)

mit(iii)
_value
tive

ge<(i)
nings
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit
Mainte
nance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
BMS_ ECS_ HVLS High Volume Low Speed Fan On/Off Status DI Off On N
BMS_ ECS_ HVLS High Volume Low Speed Fan Run/Stop Command DO Stop Run N
BMS_ ECS_ SSF_ Smoke Spill Fan On/Off Status DI Off On N
BMS_ ECS_ SSF_ Smoke Spill Fan Emergency Stop Lock DI Run Stop N
BMS_ ECS_ SSF_ Smoke Spill Fan Damper Fully Opened Status DI Close Open N
BMS_ ECS_ EXF1 Exhaust Air Fan (Type 1) On/Off Status DI Off On N
BMS_ ECS_ EXF1 Exhaust Air Fan (Type 1) Trip Fault Alarm DI Normal Trip 2 Y
BMS_ ECS_ EXF2 Exhaust Air Fan (Type 2) On/Off Status DI Off On N
BMS_ ECS_ EXF2 Exhaust Air Fan (Type 2) Trip Fault Alarm DI Normal Trip 2 Y
BMS_ ECS_ EXF2 Exhaust Air Fan (Type 2) Run/Stop Command DO Stop Run N
BMS_ ECS_ EXF3 Exhaust Air Fan (Type 3) On/Off Status DI Off On N
BMS_ ECS_ EXF3 Exhaust Air Fan (Type 3) Trip Fault Alarm DI Normal Trip 2 Y
BMS_ ECS_ EXF4 Exhaust Air Fan (Type 4) On/Off Status DI Off On N
BMS_ ECS_ EXF4 Exhaust Air Fan (Type 4) Emergency Stop Lock DI Run Stop N
BMS_ ECS_ EXF5 Exhaust Air Fan (Type 5) On/Off Status DI Off On N
BMS_ ECS_ EXF5 Exhaust Air Fan (Type 5) Run/Stop Command DO Stop Run N
BMS_ ECS_ EXF6 Exhaust Air Fan (Type 6) On/Off Status DI Off On N
BMS_ ECS_ EXF6 Exhaust Air Fan (Type 6) Emergency Stop Lock DI Off On N
BMS_ ECS_ EXF7 Exhaust Air Fan (Type 7) On/Off Status DI Off On N
BMS_ ECS_ EXF7 Exhaust Air Fan (Type 7) Trip Fault Alarm DI Normal Trip 3 Y
BMS_ ECS_ EXF8 Exhaust Air Fan (Type 8) On/Off Status DI Off On N
BMS_ ECS_ EXF8 Exhaust Air Fan (Type 8) Trip Fault Alarm DI Normal Trip 3 Y
BMS_ ECS_ EXF8 Exhaust Air Fan (Type 8) Run/Stop Command DO Stop Run N
BMS_ ECS_ FAF1 Fresf Air Fan (Type 1) On/Off Status DI Off On N
BMS_ ECS_ FAF1 Fresf Air Fan (Type 1) Trip Fault Alarm DI Normal Trip 2 Y
BMS_ ECS_ EXF9 Exhaust Air Fan (Type 9) On/Off Status DI Off On N
BMS_ ECS_ EXF9 Exhaust Air Fan (Type 9) Trip Fault Alarm DI Normal Trip 3 Y
BMS_ ECS_ SPU1 Split Unit (Type 1) Trip Alarm DI Normal Trip Y
BMS_ ECS_ SPU1 Split Unit (Type 1) Run/Stop Command DO Stop Run N
BMS_ ECS_ SPU1 Split Unit (Type 1) Room Temperature °C AI 0 28 50 3 1 3 Y
BMS_ ECS_ SPU2 Split Unit (Type 2) On/Off Status DI Off On N
BMS_ ECS_ SPU2 Split Unit (Type 2) Trip Fault Alarm DI Normal Trip Y
BMS_ ECS_ SPU2 Split Unit (Type 2) Damper Fully Closed Status DI Open Close N
BMS_ ECS_ SPU2 Split Unit (Type 2) Run/Stop Command DO Stop Run N
BMS_ ECS_ SPU2 Split Unit (Type 2) Room Temperature °C AI 0 28 50 3 1 3 Y
BMS_ ECS_ Logic Selector Control BMS/ICSS Mode DI BMS ICSS 3 Y
BMS_ ECS_ Logic Schedule output Run/Stop Schedule DO Stop On N

ICSS.BMS.1 (ECS) Page 3


Value_Out_of_Range_HIGH(iv)
IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Meaningful_Min_value

Severity_of_Range<(i)
Other_bits_meanings
Equipment_InformatiOn Attribute_InformatiOn(Internal_Variable,IV) Discrete_Type_Meanings- Analogue_Type_Meanings_Alar

WPC_Data_Type

TransitiOn_Inter

Scaling Factor
v0_Severity

v1_Severity
v0_label(0)

v1_label(1)

val_(sec)
Corrective
System (S_ub)S_yS_tem Eqpt_Code Eqpt_DescriptiOn Attribute_DescriptiOn unit
Maintenance

WPC WC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
BMS_ SSV_ MCC_ SSTS MCC Open/Close DI Open Close N
BMS_ SSV_ MCC_ SSTS MCC Trip/Fault Alarm DI Normal Trip 2 Y
BMS_ SSV_ MCC_ SSTS MCC Auto Mode DI Manual 3 Auto N
BMS_ SSV_ INPL SSTS Control Panel Open/Close DI Open Close N
BMS_ SSV_ INPL SSTS Control Panel High Water Level Alarm DI Normal Alert 2 N
BMS_ SSV_ INPL SSTS Control Panel High High Water Level Alarm DI Normal Alarm 1 Y
BMS_ SSV_ PMP1 SSTS Pump 1 On/Off Status DI Off On N
BMS_ SSV_ PMP1 SSTS Pump 1 Trip/Fault Alarm DI Normal Trip 2 Y
BMS_ SSV_ PMP2 SSTS Pump 2 On/Off Status DI Off On N
BMS_ SSV_ PMP2 SSTS Pump 2 Trip/Fault Alarm DI Normal Trip 2 Y
BMS_ SSV_ ABLW Air Blower On/Off Status DI Off On N
BMS_ SSV_ ABLW Air Blower Trip/Fault Alarm DI Normal Trip 2 Y

ICSS.BMS.1 (SSV) Page 1


IO CLASS_SY202_(ICSS.BMS.1)_REV_A4-0.xlsx

Value_Out_of_Range_LOW(i)
Equipment_Information Attribute_Information(Internal_Variable,IV) Discrete_Type_Meanings-Alarm/Event[DI]/Control[DO] Analogue_Type_Meanings_Alarm/Event[AI]

Meaningful_Min_value
Transition_Interval_(s

Severity_of_Range<(i)
Other_bits_meanings
WPC_Data_Type

Scaling Factor
v0_Severity
v0_label(0)

v1_label(1)
Corrective
System (Sub)System Eqpt_Code Eqpt_Description Attribute_Description unit

ec)
Maintenance

WPC WPC ICSS WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC WPC
BMS_ CAS_ AICO Air Compressor Local/Remote Switch Mode DI Local Remote N
BMS_ CAS_ AICO Air Compressor On/Off DI Off On N
BMS_ CAS_ AICO Air Compressor Trip/Fault DI Normal Trip Y
BMS_ CAS_ AICO Air Compressor Water/Air/Flow DI Normal Alarm N
BMS_ CAS_ AICO Air Compressor Start/stop DI Stop Start N
BMS_ CAS_ AID1 Air Dryer (Type 1) Local/Remote Switch Mode DI Local Remote N
BMS_ CAS_ AID1 Air Dryer (Type 1) On/Off DI Off On N
BMS_ CAS_ AID1 Air Dryer (Type 1) Trip/Fault DI Normal Trip Y
BMS_ CAS_ AID1 Air Dryer (Type 1) High Temperature DI Low High Y
BMS_ CAS_ AID1 Air Dryer (Type 1) Start/stop DI Stop Start N
BMS_ CAS_ AID2 Air Dryer (Type 2) Local/Remote Switch Mode DI Local Remote N
BMS_ CAS_ AID2 Air Dryer (Type 2) On/Off DI Off On N
BMS_ CAS_ AID2 Air Dryer (Type 2) Trip/Fault DI Normal Trip Y
BMS_ CAS_ AID2 Air Dryer (Type 2) Water/Air/Flow DI Normal Alarm Y
BMS_ CAS_ AID2 Air Dryer (Type 2) Start/stop DI Stop Start N
BMS_ CAS_ AIRR Air Receiver High Air Pressure Level Alarm DI Normal High N
BMS_ CAS_ AIRR Air Receiver Low Air Pressure Level Alarm DI Normal Low Y

ICSS.BMS.1 (AIR SYSTEM) Page 1