Data sheet 6ES7158-3AD10-0XA0

SIMATIC PN/PN Coupler for deterministic data exchange between max.4 PN-
Controller per subnet, also from subnet to subnet, PROFIsafe data exchange, I/O-,
MSI-, MSO- and data record communication, redundant power supply, PN-
connection via SIMATIC BusAdapter (BA), delivery w/o BusAdapter

General information
Product type designation PN/PN coupler
Firmware version
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No; For operation on isochronous bus
● Tool changer Yes; Docking station and docking unit
● Local coupling, IO data Yes
— Number of coupling modules 16
— Number of coupling submodules per module 4; 1x write, 3x read
● Local coupling, data records Yes
— Number of coupling modules 16
— Number of coupling submodules per module 4; 1x write, 3x read
— Record length, max. 4 096 byte
— FIFO depth in storage mode 8
Engineering with
● STEP 7 TIA Portal configurable/integrated from version STEP 7 V15.1 or higher
● PROFINET from GSD version/GSD revision V2.3
Installation type/mounting
Mounting Mounting rail 7.5 mm and 15 mm
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Mains buffering
● Mains/voltage failure stored energy time 10 ms
Input current
Current consumption, max. 360 mA; For 19.2 V input voltage at the right-hand supply terminal, including 2
plugged BA 2x LC
Inrush current, max. 1.6 A
I²t 0.031 A²·s
from supply voltage 1L+, max. 320 mA; For 19.2 V input voltage at the left-hand supply terminal, including 2
plugged BA 2x LC
Power loss
Power loss, typ. 4 W; For 24 V input voltage and 2 plugged BA 2x RJ45 If BusAdapters with an
optical interface are plugged, there is an additional 750 mW per optical
interface (3 W with 2 plugged BA 2x LC)
Address area
Address space per module

6ES71583AD100XA0 Subject to change without notice


2/21/2024
Page 1/3 © Copyright Siemens
● Address space per module, max. 254 byte; max. 254 bytes of input data and 253 bytes of output data
Address space per station
● Address space per station, max. 1 440 byte; per input / output
Hardware configuration
Submodules
● Number of submodules per station, max. 116
Interfaces
Number of PROFINET interfaces 2; One PROFINET interface per line side
Optical interface Yes; Via SIMATIC BusAdapter
Transmission rate, max. 100 Mbit/s
1. Interface
Interface types
● Number of ports 2; via BusAdapter
● integrated switch Yes
● BusAdapter (PROFINET) Yes; Compatible BusAdapter: BA 2x RJ45, BA 2x FC, BA 2x SCRJ, BA SCRJ /
RJ45, BA SCRJ / FC, BA 2x LC, BA LC / RJ45, BA LC / FC
Protocols
● PROFINET IO Device Yes
● Open IE communication Yes
● Media redundancy Yes; As MRP or MRPD client; max. 50 or 30 devices in the ring
2. Interface
Interface types
● Number of ports 2; via BusAdapter
● integrated switch Yes
Protocols
● PROFINET IO Device Yes
● Open IE communication Yes
● Media redundancy Yes; As MRP or MRPD client; max. 50 or 30 devices in the ring
Interface types
RJ 45 (Ethernet)
● Transmission procedure PROFINET with 100 Mbit/s full duplex (100BASE-TX)
● 10 Mbps No
● 100 Mbps Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX)
● Autonegotiation Yes
● Autocrossing Yes
Protocols
Supports protocol for PROFINET IO Yes
Protocols (Ethernet)
● TCP/IP Yes
● SNMP Yes
● LLDP Yes
● ping Yes
● ARP Yes
PROFINET IO Device
Services
— IRT Yes
— PROFIenergy No
— Prioritized startup Yes
— Shared device Yes
— Number of IO Controllers with shared device, max. 4; per line side
Redundancy mode
● PROFINET system redundancy (S2) Yes; NAP S2 acc. to IEC
● H-Sync forwarding Yes
Media redundancy
— MRP Yes
— MRPD Yes
Open IE communication
● TCP/IP Yes
● SNMP Yes
● LLDP Yes

6ES71583AD100XA0 Subject to change without notice


2/21/2024
Page 2/3 © Copyright Siemens
Interrupts/diagnostics/status information
Status indicator Yes
Alarms Yes
Diagnostics function Yes; Parameterizable
Diagnostics indication LED
● RUN LED Yes; green LED
● ERROR LED Yes; red LED
● MAINT LED Yes; Yellow LED
● LINK LED Yes; 2x green link LEDs on BusAdapter
● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
Potential separation
between supply voltage and electronics Yes; to power input 2
between Ethernet and electronics Yes
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Network loading class 3
Ambient conditions
Ambient temperature during operation
● min. -30 °C; From FS05
● max. 60 °C; = Tmax for horizontal installation; for vertical installation Tmax = 50 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; restrictions for installation altitudes > 2 000 m, see section "Climatic
and mechanical environmental conditions"
Mechanics/material
Strain relief Yes; Optional, for RJ45 and FC BusAdapter only
Dimensions
Width 100 mm; Minimized with good handling
Height 117 mm
Depth 74 mm; with mounting rail
Weights
Weight, approx. 200 g; without BusAdapter