Electrical Notes & Articles

Sharing Abstracts,Notes on various Electrical Engineering Topics.

Analysis the Truth behind Household Power Savers

FEBRUARY 9, 2012 8 COMMENTS (HTTPS://ELECTRICALNOTES.WORDPRESS.COM/2012/02/09/ANALYSIS-THE-TRUTH-BEHIND-


HOUSEHOLD-POWER-SAVERS/#COMMENTS)

Introduction:

A House hold power saving devices has recently received a lot of a ention from both consumers and manufacturers. It is generally used in
residential homes to save energy and to reduce electricity bills. It is a small device which is to be plugged in any of the AC sockets in the house
(Mostly near Energy Meter). Moreover, some of the companies claim that their power savers save up to 40% of the energy.

(h ps://electricalnotes.files.wordpress.com/2012/02/1.png)
Many people believe that the claims made by the power saver manufacturing companies are false. Almost all people who buy power savers do it
to reduce their electricity bills. Many people who have used these power savers said that they could reduce their electricity bills with the
devices; however the reduction was not as much as they had expected. Moreover, they could not figure out if the reduction in electricity bills
was due to the power savers or because of their efforts to reduce their electrical usage. There have been several serious discussions about the
genuineness of the device. In This Note, We will try to find the real truth behind these power savers which claim to save as much as 40% of
energy.

Working Principle of Power Saver as per Manufacture:

A Power Saver is a device which plugs in to power socket. Apparently just by keeping the device connected it will immediately reduce your
power consumption. Typical claims are savings between 25% and 40%.
It is known that the electricity that comes to our homes is not stable in nature. There are many fluctuations, raise and falls, and surges/Spikes in
this current. This unstable current cannot be used by any of the household appliances. Moreover, the fluctuating current wastes the electric
current from the circuit by converting electrical energy into heat energy. This heat energy not only gets wasted to the atmosphere, but also
harms the appliances and wiring circuit.

(h ps://electricalnotes.files.wordpress.com/2012/02/11.png)

Power Saver stores the electricity inside of it using a system of capacitorsand they release it in a smoother way to normal without the spikes.
The systems also automatically remove carbon from the circuit which also encourages a smoother electrical flow. This means that we will have
less power spikes. More of the electricity flowing around circuit can be used to power appliances than before.
Basically it is claimed that Power savers work on the principle of surge protection technology. Power savers work on straightening this
unstable electric current to provide a smooth and constant output. The fluctuation in voltage is unpredictable and cannot be controlled.
However, the power savers utilize current fluctuation to provide a usable power by acting like a filter and allowing only smooth current to
pass through the circuit. Power savers use capacitors for this purpose. When there is a surge of current in the circuit, the capacitor of the
power saver stores the excess current and releases it when there is a sudden drop. Thus only smooth output current comes out of the device.
Moreover, a power saver also removes any type of carbon in the system, which facilitates further smoother flow. The main advantage of
power savers is not that they provide a backup system in times of low current, but that it protects the household appliances. It is known that
a sudden rise in the power can destroy the electrical appliance. Thus, the power saver not only protects the appliance but also increases its
life. Moreover, they also reduce the energy consumption and thus the electricity bills.
The amount of power saved by a power saver depends on the number of appliances on the circuit. Also, the system takes at least a week to
adapt itself fully to the circuit, before it starts showing its peak performance. The maximum amount of voltage savings will be seen in areas
where in the current fluctuation is the highest.

House Hold Power Saver Scam Review:

Power Factor Correction for residential customers (home owners) is a scam? At most, each unit is worth as an investment. Power factor
correction does make sense for some commercial / industrial customers.
Many Companies promoting and advertise that their Power Saver unit are able to save domestic residential power consumption by employing
an “active power factor correction” method on the supply line. The concept seems pre y impressive as the concept is true and legally accepted.
But practically, we will find that it’s not feasible.
To support above statement First we need to understand three terms.

1. Type of Electrical Load of House,


2. Basic Power Terminology (KW, KVA, KVAR).
3. Electrical Tariff method of Electricity Company for Household Consumer and Industrial Consumer.

There are basically two kinds of load that exists in every house: one that is resistive like incandescent lamps, heaters etc. and the other that’s
capacitive or inductive like ACs, refrigerators, computers, etc.
The power factor of a Resistive Load like toaster or ordinary incandescent light bulb is 1 (one). Devices with coils or capacitors (like pumps, fans
and florescent light bulb ballasts)-Reactive Load have power factors less than one. When the power factor is less than 1, the current and voltage
are out of phase. This is due to energy being stored and released into inductors (motor coil) or capacitors on every AC cycle (usually 50 or 60
times per second).
There are three terms need to be understand when dealing with alternating (AC) power.

1. First Term is kilowa (kW) and it represents Real power. Real power can perform work. Utility meters on the side of House measure this
quantity (Real Power) and Power Company charge for it.
2. The second term is reactive power, measured in KVAR. Unlike kW, it cannot perform work. Residential customers do not pay for KVAR, and
utility meters on houses do not record it too.
3. The third term is apparent power, referred to as KVA. By use of multi meters we can measure current and voltage and then multiply the
readings together we get apparent power in VA.

(h ps://electricalnotes.files.wordpress.com/2012/02/2.png)

Power Factor = Real Power (Wa s) /Apparent Power (VA),


Therefore, Real Power (Wa s) = Apparent Power × PF = Voltage × Ampere × PF.
Ideally a PF = 1, or unity, for an appliance defines a clean and a desired power consumption mostly Household Equipments (The dissipated
output power becomes equal to the applied input power).
In the above formula we can see that if PF is less than 1, the amperes (current consumption) of the appliances increase, and vice verse.
With AC Resistive Load, the voltage is always in phase with the current and constitutes an ideal power factor equal to 1. However, with
inductive or capacitive loads, the current waveform lags behind the voltage waveform and is not in tandem. This happens due to the inherent
properties of these devices to store and release energy with the changing AC waveform, and this causes an overall distorted wave form,
lowering the net PF of the appliance.
Manufacture claim that the above problem may be solved by installing a well-calculated inductor/capacitor network and switching it
automatically and appropriately to correct these fluctuations. A power saver unit is designed exactly for this purpose. This correction is able to
bring the level of PF very close to unity, thus improving the apparent power to a great extent. An improved apparent power would mean less
CURRENT consumption by all the domestic appliances. So far everything looks fine, but what’s the use of the above correction? The Utility
Bill Which We pay is never based on Apparent Power (KVA) but it is based on Real Power (KW). The utility bill that we pay is never for the
Apparent Power- it’s for the Real Power.
By Reducing Current Consumption Does Not Reduce Power Bills of Household Consumer.

Study of Power Saver in Domestic Load


Let us try to study Household’s Reactive-Resistive Electrical Load and Voltage Spike Characteristic by example.

(1) Power Saver in Reactive Load of Home:

Let’s take One Example for reactive Load: A refrigerator having a rated Real Power of 100 wa s at 220 V AC has a PF = 0.6. So Power=Volt X
Ampere X P.F becomes 100 = 220 × A × 0.6 Therefore, A = 0.75 Ampere
Now suppose after Installing Power Saver if the PF is brought to about 0.9, the above result will now show as: 100 = 220 × A × 0.9 And A = 0.5
Ampere
In the second expression we clearly show that a reduction in current consumption by the refrigerator, but interestingly in both the above cases,
the Real Power remains the same, i.e. the refrigerator continues to consume 100 wa s, and therefore the utility bill remains the same. This
simply proves that although the PF correction done by an energy saver may decrease the Amperage of the appliances, it can never bring down
their power consumption and the electric Bill amount.
Reactive power is not a problem for a Reactive Load of Home appliances like A.C, Freeze, motor for its operation. It is a problem for the electric
utility company when they charge for KW only. If two customers both use the same amount of real energy but one has a power factor of 0.5,
then that customer also draws double the current. This increased current requires the Power Company to use larger transformers, wiring and
related equipment. To recover these costs Power Company charged a Penalty to industrial customers for their Low power factors and give them
benefits if they improve their Power Factor in. Residential customers (homes) are never charged extra for their reactive Power.

(2) Power Saver in Resistive Load of Home:

Since a resistive load does not carry a PF so there is not any issue regarding filtering of Voltage and Current, So Power = Voltage X Current.

(3) In Voltage Spike/Fluctuation condition of Household Appliances:

In above discussion simply proves that as long as the voltage and the current are constant, the consumed power will also be constant. However,
if there’s any rise in the input voltage because of a fluctuation, then as explained above your appliances will be forced to consume a
proportionate amount of power. This becomes more apparent because current, being a function of voltage, also rises proportionately. However,
this rise in the power consumption will be negligibly small; the following simple math will prove this.
Consider a bulb consuming 100 wa s of power at 220 volts. This simply means at 240 volts it will use up about 109 wa s of power. The rise is
just of around 9% and since such fluctuations are pre y seldom, this value may be furthermore reduced to less than 1%, and that is negligible.
Thus the above discussions convincingly prove that energy savers can never work and the concept is not practically feasible.

What happens when Power Saver is installed?

The Fig shows the result of using Power Saver. The air conditioner (which has a large compressor motor) is still consuming reactive power but it
is being supplied by a nearby capacitor (which is what is in those “KVAR” boxes). If you were to mount it at the air conditioner and switch it on
with the air conditioner plus you sized the capacitor perfectly, then there would be no reactive power on the line going back to the fuse panel. If
the wire between your fuse panels is very long and undersized, reducing the current would result in it running cooler and having a higher
voltage at the air conditioner. These savings due to cooler wiring is minimal.

(h ps://electricalnotes.files.wordpress.com/2012/02/3.png)

A further complication is that if you install the “KVAR” unit at the fuse panel, it does nothing for the heat losses except for the two feet of huge
wire between the fuse panel and the utility meter. Many KVAR units are marketed as boxes that you install at a single location. If your power
factor box is too large, then it will be providing reactive power for something else, perhaps your neighbor.
Conclusion:

Power factor correction devices improve power quality but do not generally improve energy efficiency (meaning they would not reduce your
energy bill). There are several reasons why their energy efficiency claims could be exaggerated.
First, residential customers are not charged for KVA- hour usage, but by kilowa -hour usage. This means that any savings in energy demand
will not directly result in lowering a residential user’s utility bill.
Second, the only potential for real power savings would occur if the product were only put near in the circuit while a reactive load (such as a
motor) were running, and taken out of the circuit when the motor is not running. This is impractical, given that there are several motors in a
typical home that can come on at any time (refrigerator, air conditioner, HVAC blower, vacuum cleaner, etc.), but the Power Saver itself is
intended for permanent, una ended connection near the house breaker panel. And certainly not in the way the manufacturers recommend that
they be installed, that is, permanently connecting them at the main panel. Doing that drags the power factor capacitive when the inductive
motors are off and could create some real problems with ringing voltages.
The KVAR needs to be sized perfectly to balance the inductive loads. Since our motors cycle on and off and we don’t use the air conditioner in
the winter, there is no way to get it sized properly unless we have something to monitor the line and switch it on and off capacity (capacitors) as
necessary.
Adding a capacitor can increase the line voltage to dangerous levels because it interacts with the incoming power transmission lines.
Adding a capacitor to a line that has harmonic frequencies (created by some electronic equipment) on it can result in unwanted resonance and
high currents.
For commercial facilities, power factor correction will rarely be cost-effective based on energy savings alone. The bulk of cost savings power
factor correction can offer is in the form of avoided utility charges for low power factor. Energy savings are usually below 1% and always
below 3% of load, the higher percentage occurring where motors are a large fraction of the overall load of a facility. Energy savings alone do not
make an installation cost effective.

FILED UNDER UNCATEGORIZED

About Jignesh.Parmar (B.E,Mtech,MIE,FIE,CEng)


Jignesh Parmar has completed M.Tech (Power System Control), B.E(Electrical). He is member of Institution of Engineers (MIE) and CEng,India.
Membership No:M-1473586.He has more than 16 years experience in Transmission -Distribution-Electrical Energy theft detection-Electrical
Maintenance-Electrical Projects (Planning-Designing-Technical Review-coordination -Execution). He is Presently associate with one of the leading
business group as a Deputy Manager at Ahmedabad,India. He has published numbers of Technical Articles in “Electrical Mirror”, “Electrical
India”, “Lighting India”,”Smart Energy”, “Industrial Electrix”(Australian Power Publications) Magazines. He is Freelancer Programmer of Advance
Excel and design useful Excel base Electrical Programs as per IS, NEC, IEC,IEEE codes. He is Technical Blogger and Familiar with English, Hindi,
Gujarati, French languages. He wants to Share his experience & Knowledge and help technical enthusiasts to find suitable solutions and updating
themselves on various Engineering Topics.

8 Responses to Analysis the Truth behind Household Power Savers

sakawat Hossain says:


February 9, 2012 at 7:06 pm
Good Idea

Reply
santosh malani says:
February 10, 2012 at 4:15 am
Very good article , i full agree with ur principal

Reply
Manish says:
February 19, 2012 at 6:10 pm
very good article – indeed you helped me to know the truth behind power savers.
I enjoy reading each and every article of yours. pls. keep up the good work.
keep writing.

Reply
Ghanshyam Tiwari says:
March 23, 2012 at 6:44 am
Excellant coverage on topic.

Reply
Nilesh says:
May 6, 2012 at 7:03 am
Excellent Analysis
Reply
Ranjit says:
August 16, 2012 at 3:37 pm
I really appreciate your taking the trouble to get to the ni y gri ies of the subject and you have done a truly marvelous job of it.
The fact of the ma er remains that most power utility providers under supply on the designed and standard P.D or Voltage. The norm being 10-
15 % short. KWh unit measurement hence compensates with increased Ampereage draw from appliances as a result. What we therefore need to
compensate for the shortfall is a multi tap mini transformer is the shortfall is constant and be er still, a servo controlled stabiliser/transformer.
Its a pity though that these are not manufactured or rather mass produced, as a nation we would save a lot collectively just by addressing this
one detail.
I would love to hear from you about my two paise comment.
Thanks again for a job well done.

Reply
saijd rasheed says:
October 19, 2012 at 11:30 am
sajid rasheed.
plz sir inform me about full detail about power saver device what used in device

Reply
C L Bhagat says:
May 11, 2017 at 8:03 am
A very correct technical and convincing analysis for a layman following domestic power savers to save energy bills . keep it up !

Reply