New Features of IS-NT-SUS 1.3.

1 - page 1 of 12

New features of IS-NT-SUS 1.3.1

Firmware, default archives and documentation


IGS-NT-SUS software branch version 1.3.1 is based on IGS-NT standard software version 2.6.1. It is
distributed in IS-NT-SUS-1.3.1.igc and IG-NT-SUS-1.3.1.igc pack containing following files.

Firmware and archives


IS-NT-SUS-1.3.1.mhx IG-NT-SUS-1.3.1mhx
IS-NT-SUS-MINT-1.3 IG-NT-SUS-MINT-1.3
IS-NT-SUS-SPI-1.3 IG-NT-SUS-SPI-1.3
IS-NT-SUS-SPtM-1.3 IG-NT-SUS-SPtM-1.3
IS-NT-SUS-Combi-1.3 IG-NT-SUS-Combi-1.3
IS-NT-SUS-COX-1.3 IG-NT-SUS-COX-1.3

Available documentation
IGS-NT-2.6 Application Guide
IS-NT-MINT-2.6.pdf IGS-NT-2.6 Installation Guide
IS-NT-SPI-2.6.pdf InteliMonitor 2.7
IS-NT-SPtM-2.6.pdf GenConfig 2.6

Main changes in IGS-NT-SUS-1.3.1

Repairs

• Wrong records history – The records of values in history were incorrect/ nonsense.
The bug has been fixed.

Ap
om s.r.
C

o.

ComAp, spol. s r.o. Tel.: +420 246 012 111


Kundratka 2359/17 ISO 9001 Certified Fax: +420 266 316 647
180 00 Praha 8 E-mail: [email protected]
t

alit
Qu

en

Czech Republic y M a n a ge m Internet: http://www.comap.cz


New Features of IS-NT-SUS 1.3.1 - page 2 of 12

Main changes in IGS-NT-SUS-1.3

New features:

• Support for InteliGen-NT was added – SUS application is availlable for InteliGen hardware.

• Archive SPI and SPtM work without dongle

• archive MINT, Combi and COX work with SUS dongle (SUS + LSM+PMS) or with standard
dongle (LSM+PMS) –the function is the same for both dongles

• Changes at the screens of InteliVision 8 and InteliVision 5

- Main mettering screen of InteliVision 8 has been changed. The RPM gauge has been
replaced by operating values (apparent power, PF, GenV, water temp, fuel level, oil
press, etc.). Supported only in InteliVision v. 2.0 FW.
- Base colour of all label text in IV5 has been changed to white.
- Diagram of the site viewing states of the mains voltage, generator voltage and breakers
has been added into the status bar of InteliVision 8.

• Support of screen editor – function of screen editor of InteliVision 5 and InteliVisoin 8 has been
added in GenConfig 2.6. This function is supported in controller since IGS-NT-SUS 1.3.

• User defined buttons in Inteli Vision 5 and InteliVisoin 8 – user defined buttons in IV 5 and IV
8 support has been added (definition of user defined butons can be done via GenConfig 2.6 -
screen editor). Actions: Jump on any screen, definable name of button, set/reset/togle comand
for BI.

• Support of TIER IV icons has been implemented.

• Support for IB-NT (new Internet bridge) has been implemented.

• Changes of function Break through password prottection

- Break through password function can be ENABLED/DISABLED from the password


management window in InteliMonitor (initial status is DISABLED).
- Warning “PassInsertBlck” appears in alarm list when controller is blocked
- It is not allowed to insert the password in case that controller is blocked. There is
information that controller is blocked for next password attempt and time remaining till
the end of blocation instead of password input window at the terminal screen.
- The controller is locked for 5 minutes when the password is 3 times wrong entered (in
case of next 3 wrong attempts (correct password was not inserted at all) for 30, 60, 120,
240 minutes). Incorrect password message appears in the history of the controller when
the invalid password is used.

• Next Over Load Start function in MINT application has been changed. Level for starting of next
gen-set has been decrased to 90% of actual nominal power of all gen-sets on the bus. Start of
next gen-set is delayed for time OverldNextDel. This function prevents overloading of gen-sets in
case that no load reserve start level has not been set.

Ap
om s.r.
C

o.

ComAp, spol. s r.o. Tel.: +420 246 012 111


Kundratka 2359/17 ISO 9001 Certified Fax: +420 266 316 647
180 00 Praha 8 E-mail: [email protected]
t

alit
Qu

en

Czech Republic y M a n a ge m Internet: http://www.comap.cz


New Features of IS-NT-SUS 1.3.1 - page 3 of 12

• ECU binary values – all binary values read from ECU are reset to “zero” in case that
communication get lost.

• IS-NT, IG-NT HW and SW mismatch – application get not running in case of loading FW for IS-
NT into IG-NT HW and vice versa. Controller stays in Init mode.

• Setpoint changes

- AirGate Server (Comms settings group) - Setpoint has been renamed on AirGate.
Default value has been changed on ENABLED.
- IP addr mode (Comms settings group) - Default value of setpoint has been changed on
AUTOMATIC.
- AirGate IP (Comms settings group) – Default value has been set on airgate.comap.cz.
- 2Inom del (Gener protect group) – Range of setpoint has been changed to 600 s.
- Max+CylDifPmin, Max-CylDifPmin, Max+CylDifPnom, Max-CylDifPnom (Engine
protect Group – Range of setpoints has been limited for positive values (setpoints mean
absolute value of deviation).

• New LBO PeakShaveAct – the logical binary output is active when the gen-set is running due to
Peak Shaving (dependence on parameters PeakLevelStart, PeakLevelStop, PeakAutS/S del in
ProcessControl group, available in SPtM and COMBI application only).

• New Values – GL16, GL32 binary values has been added to the values of controller. Active bit
within the value means that corresponding controller has closed its GCB.

• Writing of shared setpoints – Shared setpoints of single controller (no other controller
communicating on CAN2) can be rewriten by Gen config (GenConfig 2.6). Shared setpoints can
not be rewriten in case, that any other controller is connected on CAN2.

• PLC functions

- Number of logical PLC blocks of IS-NT archive controller (all hardware variations) has
been increased. PLC logic can contain up to 100 AND/OR blocks and up to 100 XOR/RS
blocks.
- Number of available PLC blocks of standard IG-NT archive has been increased on
number of PLC blocks of IG-NT-mCHP except PLC blocks Regulators.

Table of PLC blocks available for IGS-NT controllers

IS-NT IG-NT
Group PLC Block
ver. 1.3 ver. 1.3
Logical function OR/AND 100 32
XOR/RS 100 32
Comparators Comp Hyst 16 4
Comp Time 8 4
Comp Win 16 4
Math operations Math Fc 16 2
Ext math Fc 8 2
Interpol Fc 2 1
Regulators PID Ana B 4

Ap
om s.r.
C

o.

ComAp, spol. s r.o. Tel.: +420 246 012 111


Kundratka 2359/17 ISO 9001 Certified Fax: +420 266 316 647
180 00 Praha 8 E-mail: [email protected]
t

alit
Qu

en

Czech Republic y M a n a ge m Internet: http://www.comap.cz


New Features of IS-NT-SUS 1.3.1 - page 4 of 12

PID Bin 4
Ramp functions Ramp 4 2
Up/Down 4 2
Inc/Dec 2 2
Mov Avg 2 1
Time functions Timer 4 1
Delay 24 8
Others Ana Switch 16 2
Force Hist 4 4
Force Prot 4 4
Jump 4 4
Mux Const. 4 4
Counter 4 1
Decomp 4 4
Convert 8 4

New features of IS-NT-SUS 1.2

Firmware, default archives and documentation


IS-NT-SUS software branch version 1.2 is based on IS-NT standard software version 2.5. It is distributed
in IS-NT-SUS-1.2. igc pack containing following files.

Firmware and archives


IS-NT-SUS-1.2.mhx
IS-NT-SUS-MINT-1.2
IS-NT-SUS-SPI-1.2
IS-NT-SUS-SPtM-1.2
IS-NT-SUS-Combi-1.2
IS-NT-SUS-COX-1.2

Available documentation
IGS-NT-2.4 Application Guide
IS-NT-MINT-2.5.pdf IGS-NT-2.5 Installation Guide
IS-NT-SPI-2.5.pdf InteliMonitor 2.6
IS-NT-SPtM-2.5.pdf GenConfig 2.5.1

Repaired Bugs
• The possibility to set the speed measurement based on generator frequency has been removed
as it is not applicable to SUS.
• Changed behaviour of UV coil. UV coil stayed active in the OFF mode and did not switch off even
if bus voltage was out of range. UV coil signal was not deactivated even if GCB fail alarm was
issued. Problem fixed – UV coil’s behaviour is now inversion of GCB OFF coil.

Ap
om s.r.
C

o.

ComAp, spol. s r.o. Tel.: +420 246 012 111


Kundratka 2359/17 ISO 9001 Certified Fax: +420 266 316 647
180 00 Praha 8 E-mail: [email protected]
t

alit
Qu

en

Czech Republic y M a n a ge m Internet: http://www.comap.cz


New Features of IS-NT-SUS 1.3.1 - page 5 of 12

• GCB opened after finishing countdown of the Min stab time when the GCB disable function was
active. Problem fixed.

General features of the SUS firmware:


• Prestart and Idle time shall be adjusted on all sets to same values, preferably to 0. This will
ensure the minimum waiting time for sets to excite their AVR.

• Parameter Power management: MinRunPower1 influences the number of sets which proceed to
successful SUS start. This parameter represents maximum expected load which will be applied to
gensets after SUS start. So in case this parameter is lower then Nominal power of any set, then it
can happen, that this single set will be loaded (AVR will be excited) and other sets will be refused
from SUS start. This can happen in a situation, when a set will have active BO: ReadyToExcite,
but the other sets not, and then because this set is supposed to cover all expected load, it is not
worth of waiting for other sets to get their RPM within adjusted window, to delay the load take over
from UPS. In such a situation all other sets with not active BO:ReadyToExcite will open their GCB
and their AVRs will be energized.

New features of IS-NT-SUS 1.1.1

Firmware, default archives and documentation

Firmware and archives


IS-NT-SUS-1.1.1.mhx
IS-NT-SUS-MINT-1.1
IS-NT-SUS-SPI-1.1
IS-NT-SUS-SPtM-1.1
IS-NT-SUS-Combi-1.1
IS-NT-SUS-COX-1.1

Available documentation

IS-NT-MINT-2.3.pdf IGS-NT-2.2 ApplicationGuide.pdf


IS-NT-SPI-2.3.pdf Inteli CommunicationGuide 06 2008.pdf
IS-NT-SPtM-2.3.pdf IGS-NT-2.2 TroubleshootingGuide.pdf
GenConfig 2.3., InteliMonitor 2.3

Repaired bugs
• In some cases the PLC module did not work properly depending on PLC configuration and
functions used. Affected functions were following: CmpT, MovAvg, PIDAna, PIDAnaBias,
PIDBin, Delay, Ramp, UpDown.

Ap
om s.r.
C

o.

ComAp, spol. s r.o. Tel.: +420 246 012 111


Kundratka 2359/17 ISO 9001 Certified Fax: +420 266 316 647
180 00 Praha 8 E-mail: [email protected]
t

alit
Qu

en

Czech Republic y M a n a ge m Internet: http://www.comap.cz


New Features of IS-NT-SUS 1.3.1 - page 6 of 12

New features of IS-NT-SUS 1.1

Firmware, default archives and documentation

IS-NT-SUS software branch version 1.1 is based on IS-NT standard software version 2.3. It is distributed
in IS-NT-SUS-1.1. igc pack containing following files.

Firmware and archives


IS-NT-SUS-1.1.mhx
IS-NT-SUS-MINT-1.1
IS-NT-SUS-SPI-1.1
IS-NT-SUS-SPtM-1.1
IS-NT-SUS-Combi-1.1
IS-NT-SUS-COX-1.1

Available documentation

IS-NT-MINT-2.3.pdf IGS-NT-2.2 ApplicationGuide.pdf


IS-NT-SPI-2.3.pdf Inteli CommunicationGuide 06 2008.pdf
IS-NT-SPtM-2.3.pdf IGS-NT-2.2 TroubleshootingGuide.pdf
GenConfig 2.3., InteliMonitor 2.3

Repaired bugs
• In version IS-NT-SUS 1.0, MINT application, could happen that not all the breakers close during the
SUS start procedure, although all the necessary conditions were fulfilled.
• Problem with current measurement stuck was repaired.

Ap
om s.r.
C

o.

ComAp, spol. s r.o. Tel.: +420 246 012 111


Kundratka 2359/17 ISO 9001 Certified Fax: +420 266 316 647
180 00 Praha 8 E-mail: [email protected]
t

alit
Qu

en

Czech Republic y M a n a ge m Internet: http://www.comap.cz


New Features of IS-NT-SUS 1.3.1 - page 7 of 12

New features of IS-NT-SUS 1.0

Firmware, default archives and documentation

IS-NT–SUS software branch version 1.0 is based on IS-NT standard software version 2.2.
It is distributed in IS-NT-SUS-1.0. igc pack containing following files.
IS-NT-SUS-1.0 firmware is compatible with GenConfig versions 2.2.1 and higher.

Firmware and archives


IS-NT-SUS-1.0.mhx
IS-NT-SUS-MINT-1.0
IS-NT-SUS-SPI-1.0
IS-NT-SUS-SPtM-1.0
IS-NT-SUS-Combi-1.0
IS-NT-SUS-COX-1.0

Available documentation

IS-NT-MINT-2.2.pdf IGS-NT-2.2 ApplicationGuide.pdf


IS-NT-SPI-2.2.pdf IGS-NT-2.2 CommunicationGuide.pdf
IS-NT-SPtM-2.2.pdf IGS-NT-2.2 TroubleshootingGuide.pdf
GenConfig 2.2., InteliMonitor 2.2

General description
IS-NT-SUS software branch is characterized by following features:

All applications:
− There are two modes of engine start: standard and start with GCB closed selected by a new setpoint
ProcessControl:GCBClosedStart
− Binary input StopExcitation must be active when the genset should start and run deexcited. It blocks the
voltage and frequency protections. Parallel contact from the AVR excitation control relay could be used.
− GCB closed start: If the engine speed is in the required window from the nominal speed (setpoint
ProcessControl:Excite window) for 1s (fixed delay), then the binary output ReadyToExcite closes.
− If the set does not reach the required speed within the given timeout Process control: Excite Timeout
from reaching the starting speed + Idle time, the GCB is opened, StopExcitation input must be
deactivated and standard start is performed.

Ap
om s.r.
C

o.

ComAp, spol. s r.o. Tel.: +420 246 012 111


Kundratka 2359/17 ISO 9001 Certified Fax: +420 266 316 647
180 00 Praha 8 E-mail: [email protected]
t

alit
Qu

en

Czech Republic y M a n a ge m Internet: http://www.comap.cz


New Features of IS-NT-SUS 1.3.1 - page 8 of 12

Successful GCB closed start


1. Succes
Nominal Excite
speed window

RPM

1s

ReadyToExcite

StopExcitation
Electric Act.
protections Deact.

Max stab time

GCB closed

Start

Unsuccessful GCB closed start

Nominal
2. Unsucc Excite
speed window

RPM
Starting
RPM

Standard starting
sequence (Crank
Idle time Excite timeout attempts times)
StopExcitation

GCB GCB
close/open opened
Start
− If the start of any set is unsuccessful, this set repeats the standard start with maximal number of
attempts given by the setpoint Engine params:Crank attempts.

Ap
om s.r.
C

o.

ComAp, spol. s r.o. Tel.: +420 246 012 111


Kundratka 2359/17 ISO 9001 Certified Fax: +420 266 316 647
180 00 Praha 8 E-mail: [email protected]
t

alit
Qu

en

Czech Republic y M a n a ge m Internet: http://www.comap.cz


New Features of IS-NT-SUS 1.3.1 - page 9 of 12

− If binary input StopExcitation is activated (in case of GCB closed), controller deactivates voltage and
frequency protections and the genset is running deexcited. On deactivation of binary input
StopExcitation the voltage and frequency protections are activated again with Engine params:Max stab
time delay.

GCB closed

StopExcitation

Electric Act.
protectionsDeact.

Max stab time

MINT application:
− If the Sys start/stop command is activated in dead bus condition, all sets that should start according
to load reserve are started in GCB closed mode if it is enabled by GCBClosedStart.
− New BO: SUS excitation is added. This BO became active/unactive according to the following
schema:
In the schema the ‘input’ MinNGRSUSful (Minimum Number of Gensets Ready for SUS Fulfilled) is
used. This ‘input’ became active when the sum of nominals of engines with active BO:ReadyToExcite
exceeds the setpoint value: #Pwr management:MinRunPower 1. This condition is evaluated via
CAN2 line.

BO:AnyGCBclosed

AND
BO:GCBfeedback

OR SET
BO:ReadyToExcite
RS BO:SUS excitation
MinNGRSUSful AND
function
OR
ExciteTimeout
RESET

Fuel Solenoid

Single applications:
− GCB closed start: Before any attempt for start, the controller starting to the dead bus closes its GCB
and starts the engine. If MCB is closed at that time (SPtM in parallel to mains); standard start is
performed.

Ap
om s.r.
C

o.

ComAp, spol. s r.o. Tel.: +420 246 012 111


Kundratka 2359/17 ISO 9001 Certified Fax: +420 266 316 647
180 00 Praha 8 E-mail: [email protected]
t

alit
Qu

en

Czech Republic y M a n a ge m Internet: http://www.comap.cz


New Features of IS-NT-SUS 1.3.1 - page 10 of 12

New setpoints
GCBClosedStart [ENABLED/DISABLED]
Enables and disables start with GCB closed.

Excite window [%]


Determines speed limits for activation of binary output ReadyToExcite and successful start with GCB
closed. Given as percentage of nominal speed.
The algorithm of Excite window evaluation and ReadyToExcite output activation:
After engine fires, the Starting RPM setpoint is reached, the Idle time setpoint is count down. After the Idle
time is finished, the Excite window setpoint is evaluated. If the RPM is in the Excite window for 1s (fixed
delay) the BO:ReadyToExcite is activated – see the above drawings.

Step: 0.1 %
Range: 0.0 – 100.0 %

Excite timeout [s]


If the gen-set doesn’t reach required speed within this delay from reaching Engine params:Starting RPM
+ Engine params:Idle time, the GCB is opened and standard start is performed.
Step: 0.1 s
Range: 0.0 – 6000.0 s

TimeToLoad [OFF / 1 - 600s]


Describes behavior in case the genset has active BO:ReadyToExcite signal but the sum of nominals of
engines with active BO:ReadyToExcite is lower than Process control: MinRunPower1;
When option OFF is chosen, the engine stays running, but is not loaded.
If some value from range 1 – 600s is chosen, the timer counts down this interval and then the genset is
loaded, generating Wrn: TimeToLoad. This occasion is written to the History.
Step: 1 s
Range: 0 – 600 s

StopExcSource [INTERNAL/EXTERNAL]
This setpoint defines the source of the BI:StopExcitation.
If INTERNAL is chosen, the BI:StopExcitation is controlled internally, according to the following
description:
When the GCBClosedStart is Enabled, the StopExcitation input is activated simultaneously with the start
of genset, which should start and run deexcitated. When the BO:SUS excitation is activated, the
BI:StopExcitation is deactivated. The BI:StopExcitation is deactivated at latest with the ExciteTimeout
expiration, regardless the state of BO:SUS excitation.
If EXTERNAL is chosen, the BI StopExcitation is controlled externally (e.g. from PLC) and this input must
be configured as a physical input to the controller.

New binary inputs


StopExcitation
Binary input undermines start with closed GCB. Blocks electric generator protections.

Ap
om s.r.
C

o.

ComAp, spol. s r.o. Tel.: +420 246 012 111


Kundratka 2359/17 ISO 9001 Certified Fax: +420 266 316 647
180 00 Praha 8 E-mail: [email protected]
t

alit
Qu

en

Czech Republic y M a n a ge m Internet: http://www.comap.cz


New Features of IS-NT-SUS 1.3.1 - page 11 of 12

New binary outputs


ReadyToExcite
Closes if RPM is in Excite window for 1 second.

AnyGCBclosed
In MINT application only. Closes, if any GCB from the site is closed. This information is evaluated via
CAN2 line, no additional wiring is necessary

Recommended wiring

LOAD
MCB MGCB GCB1
3x
G1 AVR Ka
SUS excitation

IG-AVRi TRANS
3xUG
3xUB

SUS excitation
3xIG
SUS excitation
Out
AVRi AVRi
BO:
ReadyToExcite IG-AVRi
PLC IS-NT
BI: SG SPEED
CAN2 GOVERNOR
EXCITATION START/STOP
SYS START/STOP

GCB2
SUS excitation
G2 AVR Ka

IG-AVRi TRANS
3xUG
3xUB

3xIG

SUS excitation
SUS excitation
Out
AVRi AVRi
STOP BO:
ReadyToExcite IG-AVRi
EXCITATION IS-NT
BI: SG SPEED
CAN2 GOVERNOR
EXCITATION START/STOP
START/
STOP
SYS START/STOP

Hint:
The blue colour depicts the possibility, when the StopExcSource setpoint is adjusted as EXTERNAL.

MCB and MGCB are controlled by external device, providing activation and deactivation contacts
Start/Stop and Stop Excitation (optional).

Ap
om s.r.
C

o.

ComAp, spol. s r.o. Tel.: +420 246 012 111


Kundratka 2359/17 ISO 9001 Certified Fax: +420 266 316 647
180 00 Praha 8 E-mail: [email protected]
t

alit
Qu

en

Czech Republic y M a n a ge m Internet: http://www.comap.cz


New Features of IS-NT-SUS 1.3.1 - page 12 of 12

GCB closed start: If the engine speed is in the required window from the nominal speed (setpoint
ProcessControl:Excite window) for 1s (fixed delay), then the binary output ReadyToExcite closes. If the
set does not reach the required speed within the given timeout Process control:Excite timeout from
reaching the starting speed +Idle time, the GCB is opened, StopExcitation input must be deactivated and
standard start is performed.

Setpoint MinRunPower1 indicates the initial power request,

If is MinRunPower1< sum all gen-sets on the bus, which are into required window of speed (are
ReadyToExcite), then this condition is met and these gen-sets (with active ReadyToExcite) are excited –
and the rest of gen-sets are rejected (their GCBs are opened and are synchronised by standard way later)

If MinRunPower1> sum of all „ReadyToExcite“ gen-sets and TimeToLoad=0 , then after time
(ExciteTimeout + TimeToLoad) the gen-sets are never excited, and run deexcited.

MinRunPower1 < Nominal power of any gen-set


if any set is earlier in RPM window, then this one is excited, the second one is refused (GCB is opened).
(if second gen-set is into required window of speed in 200ms after first, then both gen-sets are excited)

If Setpoint MinRunPower1=0 , then condition is always met.


In this case gen-sets are started with GCB closed (if GCBClosedStart=Enabled), but immediately after
start all GCBs are opened and all gen-sets continue to start by standard way. First gen-set, which is
ready, is connect to the load (GCB is closed to the dead bus)

Attention: Only gen-set with highest priority are started (we recommended to set the same priority of all
gen-sets).