COMAP IG-AVRI IG-AVRi
COMAP IG-AVRI IG-AVRi
18 IG-AVRi
4.18.1 Description
Automatic voltage Regulator interface is used for volt / PF control adjustment with galvanic separate input –
output.
Every time refer to corresponding AVR manual before interface connecting. Use no droop AVR.
IG-AVRi-TRANS (AC power supply for AVRi) has to be supplied from gen-set voltage.
AVRi output can be connected as symmetrical: OUT1-OUT2 or unsymmetrical OUT1-GND or OUT2-GND.
Potentiometer on the AVRi defines maximal OUT1, OUT2 voltage range.
Use symmetrical (OUT1,OUT2) AVRi output to connect the AVRi to AVR auxiliary voltage input.
Use unsymmetrical output if an external AVR potentiometer has to be replaced with AVRi.
AVRi output voltage should change generator voltage typically in range ±10 % of Nominal voltage.
For more details please refer to Application guide – chapter AVR interface examples.
IG-AVRi TRANS/LV is power supply unit for IG-AVRi, it is not included in package with IG-AVRi.
4.18.2 Dimensions
4.18.3 Connectors
OUT1
GND Output terminals for alternator AVR
output OUT2
AC1
Power supply from IG-AVRi TRANS/LV
AC2
AVRi+
input Input signals from the controller
AVRi-
Output level Set output voltage bias
4.18.4 Wiring
Storage temperature - 40 °C to + 80 °C
Operating temperature - 30 °C to + 70 °C
Heat radiation 6W
Storage temperature - 40 °C to + 80 °C
Operating temperature - 30 °C to + 70 °C
Heat radiation 6W
4.19.1 Description
Hardware Key for Load Sharing and Power Management.
Dongle enables multiple controller cooperation (via CAN bus) for:
Digital Load Sharing
Digital VAr Sharing
Optimizing number of running engines: Power management; kW, kVA or % load based
Valid for these SW:
IGS-GSC - standard - all versions
IGS-NT - standard - all versions
IGS-NT-GeCon-Marine - version 3.0 and higher
IGS-NT-GeCon-Land-based - version 3.0 and higher
IG-NT-400Hz - all versions
IGS-NT-Async - all versions
IGS-NT-SUS 1.3 and higher