1.
The contents of this document will be updated irregularly for product version upgrade or other
reasons. Unless otherwise specified, this document only works as guide. All statements,
information and suggestions in this document do not constitute any guarantee.
2. This product can only be installed, commissioned, operated and maintained by technicians who
have carefully read and fully understood the user manual.
3. This product must only be connected with PV modules of protection class II (in accordance with
IEC 61730, application class A). PV modules with a high capacitance to ground must only be used
if their capacity does not exceed 1μF.Do not connect any sources of energy other than PV
modules to the product.
4. When exposed to sunlight, the PV modules generate dangerous high DC voltage which is present
in the DC cable conductors and live components. Touching live DC cable conductors and live
components can result in lethal injuries due to electric shock.
5. All components must remain within their permitted operating ranges at all times.
6. The product complies with Electromagnetic compatibility 2014/30/EU, Low Voltage Directive
2014/35/EU and Radio Equipment Directive 2014/53/EU.
1. Ensure that the inverter is installed out of the reach of children.
2. To ensure best operating status and prolonged service life, the
ambient temperature of the location should be ≤40°C.
3. To avoid direct sunlight, rain, snow, pooling of water on the inverter, it is
suggested to mount the inverter in places which are shaded during the majority of
the day or to install an external cover that provides shade for the inverter.
Do not place a cover directly on top of the inverter.
4. The mounting condition must be suitable for the weight and size of the inverter. The inverter is suitable
to be mounted on a solid wall that is vertical or tilted backwards (Max. 15°). It is not recommended to
install the inverter on walls made of plasterboards or similar materials. The inverter may emit noise
during operation.
5. To ensure adequate heat dissipation, the recommended clearances between the
inverter and other objects is shown in the image to the right:
1
2. Remove the plastic AC/COM cover from the inverter, pass the cable through the waterproof connector on
the AC/COM cover in the wall-mounting accessories package, and retain the appropriate sealing ring
according to the wire diameter, lock the cable terminals onto the inverter-side wiring terminals respectively
1. Use a Φ12mm bit to drill 3 holes at a depth of about 70mm according to the location of the wall (L1/L2/L3/N/PE,M8/M5), install the AC insulation sheets onto the wiring terminals (as shown in Step 4 of the
mounting bracket. (Figure A) figure below), then lock the AC/COM cover with screws (M4x10), and finally tighten the waterproof
2. Insert three wall plugs into the wall and fix the wall mounting bracket to the wall by inserting three connector. (Torque M4:1.6Nm; M5:5Nm; M8:12Nm; M63:SW65,10Nm)
M8 Screws (SW13). (Figure B)
3. Hang the inverter to the wall mounting bracket. (Figure C)
4. Secure the inverter to the wall mounting bracket on both sides using two M4 screws.
Screwdrivertype:PH2, torque:1.6Nm. (Figure D)
3. If required, you can connect a second protective conductor as equipotential bonding.
Object Description
M5×12 screw Screwdriver type: PH2, torque: 2.5Nm
OT terminal lug Customer provided, type: M5
Grounding cable Copper conductor cross-section: 16-25mm2
Figure A Figure B
◆ Make sure PV modules have good insulation against ground.
◆ On the coldest day based on statistical records, the Max. open-circuit voltage of the PV modules must
not exceed the Max. input voltage of the inverter.
◆ Check the polarity of DC cables.
◆ Ensure that DC switch has been disconnected.
Figure C Figure D ◆ Do not disconnect DC connectors under load.
1. Please refer to “DC Connector Installation Guide”.
2. Before DC connection, insert the DC plug connectors with
◆ All electrical installations must be done in accordance with all local and national rules.
sealing plugs into DC input connectors of the inverter to
◆ Make sure that all DC switches and AC circuit breakers have been disconnected before establishing
ensure protection degree.
electrical connection. Otherwise, the high voltage within the inverter may lead to electrical shock.
◆ In accordance with safety regulations, the inverter need be grounded firmly. When poor ground
◆ connection (PE) occurs, the inverter will report PE grounding error. Please check and ensure that
◆ the inverter is grounded firmly or contact Solplanet service.
1. AC cable requirements are as follows. Strip the cable as shown in the figure, and crimp the copper wire to
the appropriate OT terminal (provided by the customer). ◆ Separate communication cables from power cables and serious interference sources.
◆ The communication cables must be CAT-5E or higher-level shield cables. Pin assignment complies with
Object Description Value
EIA/TIA 568B standard. For outdoor use, the communication cables must be UV-resistant. The total
A External diameter 20-42mm
length of communication cable cannot exceed 1000m.
B Copper conductor cross-section 16-50mm2
◆ If only one communication cable is connected, insert a sealing plug into the unused hole of sealing
C Stripping length of the insulated conductors Matching terminal
◆ ring of the cable gland.
D Stripping length of the cable outer sheath 130mm
◆ Before connecting communication cables, ensure the protective film or communication plate attached
The external diameter of the OT terminal shall be less than 22mm. to the
The PE conductor must be 5 mm longer than the L and N conductors.
◆ communication opening on the inverter is sealed tightly.
Please use a copper - aluminum terminal when aluminum cable is selected.
2 3
1. COM1: WiFi / 4G (optional) 4. COM2: RS485 (Multi-machine communication)
1) Refer to the following Settings
◆ Only applicable to the company's products, can’t be connected to other USB devices.
◆ The connection refers to “GPRS/ WiFi-stick User Manual”.
2. COM2: RS485 (Type 1)
1) RS485 cable pin assignment as below.
◆ Check that the inverter is grounded reliably.
◆ Check that the ventilation condition surrounding the inverter is good.
◆ Check that the grid voltage at the point of connection of the inverter is within the permitted range.
◆ Check that the sealing plugs in DC connectors and the communication cable gland are sealed tightly.
◆ Check that grid connection regulations and other parameter settings meet safety requirements.
1. Switch on AC circuit breaker between the inverter and the grid.
2) Disassemble the AC/COM cover and unscrew the waterproof connector, and then guide the cable through the 2. Switch on DC switch.
connector and insert it into the corresponding terminal. Assemble the AC/COM cover with M4 screws and screw 3. Please refer to the AiProfessional/Aiswei App manual for commissioning of the inverter via Wifi.
the waterproof connector. (Screw torque: M4:1.6Nm; M25:SW33,7.5 Nm) 4. When there is sufficient DC power and the grid conditions are met, the inverter will start to
operate automatically.
Within the scope of the EU directives:
- Electromagnetic compatibility 2014/30/EU
(L 96/79-106 March 29, 2014)(EMC)
- Low voltage directive 2014/35/EU (L 96/357-374 March 29, 2014)(LVD)
- Radio equipment directive 2014/53/EU (L 153/62-106 May 22, 2014)(RED)
3. COM2: RS485 (Type 2) AISWEI Technology Co., Ltd. confirms herewith that the inverters mentioned in this document
1) The cable pin assignment as below, others refer to the above type 1. are in compliance with the fundamental requirements and other relevant provisions of the above
mentioned directives.
The entire EU Declaration of Conformity can be found at www.aiswei-tech.com.
4 5
If you have any technical problems with our products, please contact our service.
Provide the following information to assist in providing you with the necessary assistance:
- Inverter device type
- Inverter serial number
- Type and number of connected PV modules
- Error code
- Mounting location
- Warranty card
EMEA
Service email: [email protected]
APAC
Service email: [email protected]
LATAM
Service email: [email protected]
Aiswei Greater China
Service email:
[email protected] Hotline: +86 400 801 9996
Taiwan
Service email: [email protected]
Hotline: +886 809089212
https://solplanet.net/contact-us/