VGB-R 455e Cooling Water Guidline
VGB-R 455e Cooling Water Guidline
VGB-R 455e
Publisher
VGB PowerTech e.V.
Publishing house
VGB PowerTech Service GmbH
Verlag technisch-wissenschaftlicher Schriften
P.O. box 10 39 32, 45039 Essen, Germany
Phone: +49 201 8128-200
Fax: +49 201 8128-329
E-mail: [email protected]
www.vgb.org
© All rights reserved.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
Preface
The present Guideline supersedes VGB Cooling Water Guideline VGB-R 455 P, the
first edition of which appeared in October 1990. The present edition has been re-
structured, updated and expanded. The information given is based on the experi-
ence gained in the VGB Working Panel "Chemistry of Water Treatment" from the
operation of main, service and other cooling systems. The editor is unable to accept
any responsibility for the accuracy of the content. The users are themselves respon-
sible for observing any patent and other intellectual property rights that might apply.
Our special thanks go to these gentlemen and to all the other members of the
Working Panel who played an active part in the revision of this Guideline.
The editor invites users to submit supplementary information and suggestions for
improvement for incorporation into future editions of the guideline
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
Contents Page
1 Introduction .......................................................................................... 7
2 Cooling procedures.............................................................................. 7
2.1 Once-through cooling with or without outfall cooling............................ 8
2.2 Recirculation cooling in an open circuit ............................................... 9
2.3 Recirculation cooling in a closed circuit ............................................... 12
2.3.1 Recirculation cooling with a surface condenser................................... 12
2.3.2 Recirculation cooling with direct-contact condenser............................ 14
2.4 Recirculation cooling with hybrid cooling tower ................................... 15
3 Cooling water conditioning and treatment............................................ 16
3.1 Once-through cooling systems ............................................................ 16
3.1.1 Water quality........................................................................................ 17
3.1.2 Mechanical cleaning ............................................................................ 17
3.1.3 Treatment with microbiocides .............................................................. 17
3.1.4 Process engineering aspects............................................................... 18
3.2 Open-circuit recirculation cooling systems .......................................... 19
3.2.1 Water quality........................................................................................ 19
3.2.2 Treatment of make-up water................................................................ 19
3.2.3 Conditioning of the circulating water .................................................... 21
3.2.3.1 Hardness stabilisers ............................................................................ 21
3.2.3.2 Dispergents.......................................................................................... 22
3.2.3.3 Corrosion inhibitors .............................................................................. 22
3.2.3.4 Microbiocides ....................................................................................... 24
3.2.4 Process engineering aspects............................................................... 25
3.3 Closed-circuit recirculation cooling systems ........................................ 28
3.3.1 Water quality........................................................................................ 28
3.3.2 Conditioning of the circulating water .................................................... 29
3.3.2.1 Conditioning of generator cooling systems.......................................... 29
3.3.2.2 Conditioning of cooling systems for motors and refrigerating units ..... 29
3.3.3 Process engineering aspects............................................................... 30
4 Materials .............................................................................................. 30
4.1 Materials and cooling water quality...................................................... 31
4.2 Materials and design............................................................................ 34
4.3 Materials and mode of operation ......................................................... 35
5 Monitoring by analysis ......................................................................... 37
5.1 Monitoring by chemical analysis .......................................................... 37
5.1.1 Significance of cooling water analysis parameters .............................. 40
5.2 Microbiological analysis ....................................................................... 44
5.2.1 Investigations ....................................................................................... 44
5.3 Monitoring for corrosion ....................................................................... 45
5.3.1 Investigations ....................................................................................... 45
6 References .......................................................................................... 46
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
1 Introduction
This guideline deals with the cooling procedures and technologies commonly used in
power generation plants. It dedicates particular attention to the inter-action between
the cooling water and the components of a cooling system - heat exchangers, piping,
valves, pumps, and possibly cooling towers - under the conditions of the respective
cooling procedure. Condensation in air as a method for cooling turbine steam is not
part of the scope of this guideline.
The pertinent statutory codes and regulations must be observed in all actions taken
to improve the operation of cooling systems, especially with respect to the treatment
and conditioning of cooling water and, as necessary, the discharging of spent water
and effluent.
The conditions applying to discharge into waterbodies are described in the appendi-
ces to the German Waste Water Ordinance dated 31st March 1997. The Waste
Water Ordinance and its appendices replace the General Framework Administrative
Procedure on Minimum Requirements for the Discharge of Effluents into Water-
bodies. The minimum requirements established e.g. in Appendix 31 (Water
Conditioning, Cooling Systems, Steam Generation) of the 31st July 1996 edition of
the General Framework Administrative Procedure continue to apply until such time
as minimum requirements for effluent according to the Waste Water Ordinance have
been defined. These minimum requirements apply unless the local licensing
authority prescribes other standards on special grounds.
2 Cooling procedures
In a power plant, the turbine condenser is the main heat sink with the greatest cool-
ing water demand. Cooling water systems for cooling turbine condensers can in
principle be operated according to three methods which differ in terms of the extent
to which the cooling capacity of the water is utilised and what happens to the heat
removed:
- once-through cooling with or without outfall cooling
- recirculation cooling in an open circuit and
- recirculation cooling in a closed circuit.
Besides the turbine condenser, there are other components in the power plant that
have to be supplied with cooling water. Problems in the form of corrosion or deposits
have occasionally been encountered when such cooling loads are supplied with
freshwater direct from the waterbody or with conditioned cooling tower make-up
water [1]. The state of the art is to combine such secondary cooling loads into closed
circuits operated with demineralized water as initial fill and make-up water. The heat
to be removed from such closed systems is generally passed to the condenser
cooling system via a heat exchanger. The heat exchanger used is subject to the
same criteria as the turbine condenser.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
return pump
C B A
condenser
supply
receiving
A = coarse sreen waterbody
B = fine screen
C = strainer
The waste heat input into the receiving waterbody can be reduced by operating the
once-through cooling system with outfall cooling, i.e. the heated cooling water will be
re-cooled in a spray cooling tower before it is discharged into the waterbody. At the
same time, the intensive mass transfer between the water and the air enriches the
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
oxygen content in the air, which is a desirable side effect because there is frequently
an oxygen deficit in surface waters. Some slight evaporation and spray losses occur
as the water passes through the outfall cooling tower.
Once-through cooling systems operated with an outfall cooling tower normally by-
pass the cooling tower as long as the water level and the temperature of the receiv-
ing waterbody permit the entire waste heat to be discharged. Outfall cooling has to
be taken on line if the temperature of the receiving waterbody approaches the al-
lowable limit or if the authorities call for oxygen enrichment of the cooling water.
Intermittent operation of an outfall cooling tower makes the cooling tower internals
particularly prone to clogging due to deposits. For this reason, special attention must
be paid to the suspended solids in the cooling water (see Section 3.1.2).
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
evaporation
turbine
cooling tower
make-up water
return
condenser
supply
pump
blowdown
The make-up water requirement (MU), evaporation and spray losses (E), blowdown
(BD) and the concentration factor (C) are correlated with each other according to the
following functions:
MU
MU = E + BD C = BD
E·C E
MU = C - 1 BD = C - 1
Evaporation, which depends on many climatic factors and the technical design of the
cooling tower, can be approximated by means of the following formula:
E = f · U · ∆T
in which
-1
f = so-called "climate factor" in K ,
3
U = circulating water mass flow in the circuit in m /h,
∆T = temperature difference between supply and return lines in K.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
60
Zusatzwasser Z
make-up water MU Abflut A BD
blowdown Ve rd unstung VE
evaporation
50
40
[m³/h]
30
20
10
0
1 2 3 4 5 6 7 8 9 10
Eindickung
concentration E C
factor
The make-up water input point into the circuit depends largely on the treatment
procedure used and the properties of the make-up water (see Section 3.2.4). To
prevent wide fluctuations in the concentrations of the substances contained in the
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
turbine
return
condenser
supply
pump
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
turbine
return
condenser
supply
pump
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
evaporation
turbine
cooling tower
make-up water
return
condenser
supply
pump
blowdown
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
The types of water that can be used for once-through cooling contain undissolved
and dissolved substances in widely different quantities. The undissolved substances
include coarse dirt such as flotsam, tree trunks, branches, leaves, grass, etc. and
suspended solids such as sand, clay, dead macro- and micro-organisms. The
substances dissolved in the water comprise mainly salts of the alkaline metals
sodium and potassium and of the alkaline earth metals calcium and magnesium.
Also the gases oxygen, nitrogen and carbon dioxide and in lesser amounts heavy
metal salts, organic substances such as detergent and cleaning agent residues, and
ammonium salts. Coastal seawater, especially, may also contain hydrogen sulphide.
Both the undissolved and the dissolved substances may vary widely depending on
the time of year, the temperature, the water level in the waterbody, various effluent
discharges, and the tides in the case of seawater and brackish water. The maximum
concentrations of the water contents should be taken into account in the planning for
the plant.
Suspended substances that get past the fine screen are separated out by travelling
screens. Instead of these screening devices, which form part of the intake structure,
filter vessels may be used immediately upstream of the heat exchangers. These
have proven particularly effective against seaweed and heavy mollusc growth. All
screening facilities are equipped with backwash systems which come into action at a
pre-determined differential pressure. These facilities also have a safety feature to
protect them against excessive differential pressure; if this safety feature trips,
contaminated water may enter the cooling systems. To prevent corrosion damage to
the heat exchanger tubes, the cooling systems must be cleaned by hand after each
such ingress.
Especially when seawater or brackish water is used for cooling, an explosion of the
macro-organism and micro-organism population can lead to critical operating
conditions. For instance, macro-organisms may block the passage of tube cleaning
balls, and micro-organisms may impair heat transfer in the heat exchanger tubes by
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
forming a biofilm on the tube surface. Also, organisms can cause corrosion damage
to copper-based alloys and stainless steels.
To prevent these adverse effects, microbiocides are added to the cooling water. The
most commonly used microbiocides are chlorine gas, chlorine bleach and chlorine
dioxide. Their effect is based on the formation of hypochloric acid in the aqueous
medium. In cooling waters with a higher pH (>8.5) the less effective hypochlorite ion
-
(OCl ) is formed. Oxidizable substances in the cooling water, such as organic
compounds. sulphides, ammonia, etc. likewise react with the microbiocide, so this
must be taken into account in the determination of the dosage required. Intermittent
injection is most effective, but continuous dosing is also possible.
If continuous dosing is used, a free chlorine content of 0.1 mg/l in brackish water or
about 0.25 mg/l in seawater is generally sufficient for adequate protection of the
cooling system. Mollusc larvae can be destroyed by continuous chlorination with
0.5 mg/l Cl2 or by intermittent chlorination with 2 to 3 mg/l for one hour at a time at
intervals of four to six hours. If mollusc growth is present, higher chlorine
concentrations of around 10 mg/l will be needed and must be maintained for several
days [12].
To prevent deposits and formation of biofilm, the heat exchanger tubes should be
continuously cleaned by means of travelling balls; the balls must be monitored for
wear and replaced in good time. If a clinging deposit has formed on the inside of the
tubes, it may be necessary to operate the tube cleaning system with abrasive balls
for a time.
The microbiocide is as a rule added at the intake structure, and the dosing points
should be arranged to ensure a uniform distribution. The microbiocide concentration
must be monitored.
From case to case, ferrous sulphate may be added to promote the formation of a
protective surface layer on copper-based alloys. Useful information for process
engineering is given in the literature [13], [14] and [15].
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
Of importance in this context are the substances contained in the water that, as a
result of concentration build-up and rising temperatures, can exceed their solubility
point and form insoluble substances. These include the alkaline earth carbonates
and phosphates and, more rarely, the alkaline earth sulphates and silicates.
Ammonium, phosphates and nitrates contribute to the nutrient supply for biological
growth.
Since the water is re-cycled within the open circuit, much less raw water is required
than for once-through cooling. In large recirculation cooling systems, however,
considerable amounts of water are still needed to make up for the evaporation and
blowdown losses. This makes it impossible to completely eliminate all the
substances contained in the raw water that could cause trouble in the cooling
system. Treatment must be limited to eliminating or at least reducing the substances
with the greatest interference potential, first and foremost the mechanical
contaminations and the hardness hydrogen carbonates that are inclined to form lime
deposits [22], [23], [24].
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
Course mechanical cleaning of surface water from rivers and lakes is the same as
for once-through cooling (see Section 3.1.2).
Before the raw water goes on for further treatment or use, it is usually subjected to
fine cleaning by filtration through sand or gravel or by flocculation followed by
sedimentation. These procedures significantly reduce the residual suspended solids
content. Well water and bank-filtered water do not require coarse mechanical
cleaning but must be aerated or percolated if they contain major amounts of carbon
dioxide, iron or manganese. In these processes, the carbon dioxide is expelled and
the oxygen content raised. At the same time, iron and manganese are oxidated into
practically water-insoluble oxide hydrates that can be separated out in downstream
filters. The removal of iron and especially manganese is as a rule microbiologically
enhanced by specially adapted bacteria at the filter surface.
As already mentioned, the chemical treatment of raw water for use as cooling tower
make-up water in large-scale systems is usually limited to decarbonation, which is
generally performed with acid or lime, but in special cases also in weakly acidic
cation exchangers. Decarbonation by means of dosing of the water with acid, usually
sulphuric acid, involves replacing the hydrogen carbonates that are of interest here
by sulphates:
Hydrogen carbonates lend the circulating water a certain buffer capacity against
influences that would tend to reduce the pH and that come about for example due to
induction and washing out of acid gases in the cooling tower or as a consequence of
biological processes. Moreover, the hydrogen carbonates of calcium and
magnesium are involved in the formation of corrosion-inhibiting layers on steel
surfaces. Thus, regardless of the procedure used, decarbonation should be
performed only to the extent required to leave a residual content of between 0.5 and
1 mmol/l hardness hydrogen carbonate, corresponding to 1 to 2 mmol/l hydrogen
carbonate, in the circulating water. This also applies to subsequent correction of the
pH value or the hardness hydrogen carbonate by dosing the circulating water with
acid. Excessive decarbonation enhances the corrosion risk for low-alloyed steel and
also for copper alloys [25], and beyond the limit recommended here it increases the
probability of calcium carbonate precipitation at the heat exchange surfaces. If
hardness stabilisers are added, higher values may be tolerable.
[26] identifies features of decarbonation procedures and conditions for their use
under which one procedure or another may be more suitable for a given application.
Among the selection criteria, the question of how to dispose of the effluent and solid
residues is going to become increasingly important [27], [28].
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
3.2.3 Conditioning of the circulating water [12], [29], [30], [31], [32], [33], [34],
[35], [36], [37], [38], [39]
In the large cooling systems of modern power plants, whose supply and return lines
are protected or, given the composition of the water, are not susceptible to corrosion
attack, and equipped with condensers made of stainless steels or titanium, use of
corrosion inhibitors is not necessary.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
formulas in high doses (all organic treatment (AOT) (see Section 3.2.3.3)) are also
capable of stabilising much higher hardness former contents: up to hydrogen
-
carbonate contents of c(HCO3 ) = 10 mmol/l at calcium contents of up to
2+
c(½ Ca ) = 28 mmol/l. It is very difficult to establish a general rule here, as all the
chemical parameters of the water have to be taken into account.
3.2.3.2 Dispergents
Dispergents prevent the solids contained in the circulating water from coagulating
and settling, so as to keep them in suspension. Most dispergents are synthetic low-
to medium-molecular polymers, such as polyacrylates, co-polymers of acrylic acid
and methacrylic acid or of acrylic acid and acrylic acid methyl ester, with molar
masses between 1,000 and 20,000 g/mol. Adsorption of the dispergents on the solid
particles imparts a like electric charge to these, to that they repel each other and
remain in suspension. Anionic polymers are preferably used. (The mechanism of
dispersion - influence on the zeta potential - and of hardness stabilisation via the
threshold effect - steric hindrance of agglomeration due to surface occupation - are
theoretical borderline cases that make it very difficult to distinguish between
hardness stabilisation and dispersion in phenomenological terms.) Dispergents may
synergetically intensify the action of hardness stabilisers, corrosion inhibitors and
microbiocides and are thus present in nearly all combination products. They are of
particular importance in combination with corrosion inhibitors, as they keep the
surfaces to be inhibited free from deposits. If continuously added, preferably in
combination products, the application concentration of dispergents is normally less
than 10 mg/l in the circulating water. If discontinuously added, the dose is 100 to
200 mg/l.
Inhibitors build up more or less solid protective layers or actively stop the corrosion
process by intervening in the chemical reaction.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
O2 + 2 H2O + 4e ↔ 4 OH
- -
is controlled by the pH value. On the other hand, the higher the pH value, the greater
becomes the danger of deposits especially of calcium carbonate and calcium
phosphate or slightly soluble zinc salts, so that neutral and alkaline conditioning is
always performed in combination with hardness stabilisers and/or dispergents. In the
acid and neutral modes, ortho-, polyphosphates and/or zinc salts are used as
inhibitors against corrosion of iron. Orthophosphates are attributed a primarily anodic
action (3 Fe + 2 PO4 → Fe3(PO4)2↓), zinc salts a cathodic action (Zn + 2 OH-
2+ 3- 2+
The all organic treatment mode (AOT), which is counted as an alkaline mode,
promises highly reliable protective layers in many waters, as the addition of special
phosphonates and/or polymers allows a very stable and yet thin ferrous/ferric
protective layer to build up [22], [23].
The acid mode with relatively high doses of corrosion inhibitors and acids is now less
frequently used. The neutral mode features moderate dosage rates by comparison.
The alkaline mode calls for significantly higher additive doses but does not require
the addition of acids for pH control. The alkaline mode manages with little or no
phosphor compounds but contains considerable quantities of dispergents.
Corrosion attacks on copper materials are to be feared mainly if the copper oxide
protective layer is deficient or if its primary build-up has been disturbed. Higher pH
values tend to reduce corrosion. On the other hand, complexants, ammonium
compounds or ozone [41] enhance corrosion. If a copper inhibitor has to be used,
this is usually added in the form of organic triazoles (most commonly tolyltriazole
TTA). In this case, attention must be paid to the manner and amount of dosing
required to obtain long-term protection. The inhibitors work best if a metallic clean
surface has been established beforehand.
In cases of copper corrosion, a special watch must be kept on deposits, under which
microbiologically-induced corrosion (MIC) may be present.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
3.2.3.4 Microbiocides
Some microbiocides effect the permeability of the cell walls, thus intervening in the
life processes of the organisms. By reducing the permeability of the cells, surface-
active agents impair the intake of nutrients and the excretion of waste products;
cationic surface-active microbiocides react with negatively charged ions bonded to
the cell walls, while anionic surface-active microbiocides first reduce the permeability
of the cell and then proceed to dissolve the cell membrane. Organic sulphur
compounds inhibit the metabolic reactions between enzymes and substrate.
Oxidising microbiocides destroy the protein groups and prevent normal enzyme
activity, so that the cell dies.
For ecological reasons, the oxidising agents are predominantly used in open-circuit
cooling systems, chlorine and bromine- and chlorine-releasing compounds and,
more recently, ozone being most commonly used [43], [44], [45]. Chlorine and
chlorine-releasing products are increasing coming in for criticism because they give
rise to chloro-organic compounds. Trials are currently in progress on the use of
hydrogen peroxide, also in combination with other additives [46].
The amount of microbiocide required depends essentially on the contact time, the
pH value and the water temperature, but it may also be subject to an upper limit. For
example, a threshold of 2 mg/l of free chlorine should not be exceeded, as there is
otherwise a danger of corrosion to stainless steels and copper alloys. The
effectiveness of chlorination declines as the pH value rises, as at pH values above
8.5 there are practically only hypochlorite ions present.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
Large power plant cooling towers should be designed and operated with allowance
for the influences identified above, so that it is not necessary to use microbiocides
on a regular basis.
The structural design of a cooling system and its components and the conditions
under which it operates play an essential role in coping with the specific problems of
open-circuit recirculation cooling systems. Disturbances in cooling operations can be
avoided not only by resorting to chemical intervention but also by process
engineering measures and possibly by the choice of suitable materials (see Section
4). Options for ensuring trouble-free operation by means of chemical agents are
treatment of the make-up water (see e.g. [48]) and conditioning of the circulating
water. Process engineering measures focus primarily on keeping the tube surfaces
clean by means of continuously or intermittently operating tube cleaning systems
and on removing suspended contaminations from the circulating water by filtering a
bypass flow - up to 5 % of the hourly recirculation rate - generally by means of gravel
filters. Cooling water filters upstream of the turbine condenser have proved useful for
preventing tubes from becoming blocked by fragments from the cooling system or
foreign bodies from the cooling tower region. If conditioning agents are added,
attention must be paid to repercussions on the inhibition and stabilization
mechanisms and to adsorption at the filter surfaces.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
Table 1: Options to be used depending on the solids content of the cooling water.
Preconditions
- solids content mg/l <5 < 15 < 15
- flow velocity m/s > 0.5 > 1.5 > 1.5
alternative measures
- continuous tube not necessary, since recommended necessary
cleaning solids content low,
not possible at flow
velocities < 1.5m/s*
- bypass flow filtration not necessary, since recommended necessary
solids content low, (not necessary if
continuous tube
cleaning and
dispergents are
used)
- use of dispergents recommended recommended recommended
(not necessary if
continuous tube
cleaning and bypass
flow filtration are
used)
*) if the tube cleaning system is modified, flow velocities < 1.5 m/s are also possible
The nature of the make-up water treatment should be taken into account in the
choice of location for feeding the make-up water into the cooling circuit; it may also
be necessary to take special measures on the materials side.
− Use of mechanically cleaned water only as a rule places no restrictions on the
choice of feed-in point.
− Make-up water decarbonated by means of lime can be introduced directly into
the cooling tower basin. Problems may be experienced if the water has
previously been used in the heat exchangers of secondary cooling loads. An
elevated corrosion risk, especially to low-alloyed steels, as a result of calcium
carbonate precipitation due to delayed reactions in the heat exchangers has
been observed [49]. This can be prevented by adding acid to the water that has
been decarbonated with lime; on the other hand, this releases carbon dioxide,
which causes corrosion of unprotected carbon steel and copper-based alloys. If a
corrosion inhibitor is used to condition the circulating water, it may be
advantageous to add the conditioning agent already to the make-up water.
− Water decarbonated by injecting mineral acid or decarbonated in weakly acidic
cation exchangers likewise contains free carbon dioxide and should be passed
via a degasifier or into the circulating water on the way back to the cooling tower.
Components coming into contact with such make-up water must be made of
acid-proof materials or be provided with a protective coating. The same applies in
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
cases where the make-up water has been decarbonated by means of the
flocculation/precipitation method. In this process, the concentration of hardness
hydrogen carbonate can drop so far below 1 mmol/l that no protective layer forms
on steel surfaces and the buffer capacity of the make-up water and circulating
water is lost. Pitting corrosion may then occur in copper materials.
The conditioning agent feed-in points should be chosen to ensure rapid and
complete mixing with the circulating water. As a rule, this will be the case if the
conditioning agent is introduced upstream of the cooling water pumps.
The introduction of conditioning agents, which has nowadays been optimised and
requires only very low quantities, calls for the observance of certain process
engineering conditions:
− Adequate but not excessively high flow velocities so that enough conditioning
agent can always be introduced but on the other hand there is no danger of the
formation of the protective layer being impeded by erosion. For reasons
explained earlier, it goes without saying that the agent may not perform properly
in stagnant water during outages or in dead-end lines. A flow velocity range of
between 0.5 and 3 m/s should be assured at all timed.
− The material temperature on the cooling water side of the heat exchanger should
be adequately below boiling temperature, as boiling processes interfere with the
inhibition and stabilization mechanisms. In this context, it should also be
remembered that the boiling temperature drops with falling pressure.
To protect the heat exchanger tubing from clogging due to coarse dirt entrained into
the recirculation system via the cooling tower or fragments from the cooling tower
internals, it has proven expedient to provide screens at the suction side of the
turbine condenser cooling water pumps.
The correct choice of design and backfits, of process engineering solutions and of
conditioning for recirculation cooling systems is essential to trouble-free and cost-
optimised operation.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
As a rule, demineralized water is used for the initial fill and as make-up water.
However, a condensate that has been cleaned in an ion exchanger or the
condensate from a turbine condenser is also suitable for use. The quality of the
circulating water may deteriorate due to foreign substances present as
contaminations in the cooling system or that penetrate the system from the outside,
e.g. gases from the atmosphere or electrolytes from saline leakage water from the
re-cooling system. As a result, elevated corrosion rates may be experienced
especially on non-alloyed steel surfaces and can lead to a rise in the solids content.
Corrosion products and other solids deposited on the heat exchanger tubing impair
heat transfer. The cooling performance of the heat exchangers may also be
adversely affected in the event of an oil leak into the cooling circuit [50], which may
promote microbiological growth and thus trigger microbiologically-induced corrosion
(MIC).
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
Parameters Recommendation
Conductivity at 25 °C µS/cm < 30
Conductivity at 25 °C downstream of strongly µS/cm <5
acidic sampling cation exchangers
pH value at 25 °C >7
Oxygen mg/l < 0.020
Oil mg/l <1
Conditioning is not necessary if the conductivity and pH value are in line with the
recommendations in T a b l e 2 . In large, highly ramified cooling systems with various
material combinations, the circulating water must be conditioned to prevent
corrosion. Commonly used conditioning agents are ammonia and soda lye. In
cooling systems that form part of a water/steam cycle, the same conditioning agent
as in the water/steam cycle should be used. It is common practice to use alkaline
conditioning agents to establish pH values between 9.0 and 9.5. If cooling elements
made of aluminium are used, only lower pH values of not more than 8 are
admissible.
The special requirements of cooling systems for water-cooled generators with high
power ratings make stringent demands on the quality of the circulating water. The
crucial parameter is the direct conductivity, with an allowable maximum limit of
1.5 µS/cm at 25 °C. The pH value and oxygen content are significant factors
determining the corrosion rates of the copper used as the conductor material.
Dissolved copper (pH value < 7.0) can cause electrical bridging due to galvanic
deposition in the rotor winding insulation and can thus reduce the dielectric
resistance of the rotor. If cupric oxide is precipitated out of the super-saturated
condition in turbulence zones, it can impede or block the cooling water flow at the
stator windings. Plant-specific operating modes have been developed in practice to
avoid copper and cupric oxide deposits [51].
The water used as the circulating cooling water for these systems normally contains
some salts (drinking water quality). Conditioning is performed using combination
products containing corrosion inhibitors and, if necessary, anti-freeze compounds.
Water analyses must be performed at regular intervals to check the efficacy of the
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
If the electrolyte or solids content in the circulating water rises, the following counter-
measures may have to be taken:
− on-line blowdown of the system (particularly effective for removing solids, as
these are kept in suspension; but high water consumption)
− partial drain-off and replacement with make-up water (expedient for reducing the
electrolyte content)
− mechanical bypass flow filtration
− re-conditioning of a part flow through ion exchangers
4 Materials
Cooling water circuits are complex systems in which heat exchangers can be
exposed to diverse conditions and have to satisfy different requirements. There can
be no such thing as the ideal material that meets all these requirements. For this
reason, the choice of materials for the components of a cooling system will as a rule
boil down to a compromise. Normally there will be a some freedom of discretion that
allows a choice to be made between various materials or material systems.
In these decisions, the effects of the corrosion behaviour of the heat exchanger tube
materials in the secondary-side system may be of crucial importance (e.g. it may be
necessary to avoid the use of copper in the water/steam cycle).
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
Natural cooling waters contain varying amounts of salts and suspended solids and
as a rule display a neutral to slightly alkaline reaction.
Ta b l e 3 shows such a classification and recommends materials for the tubes, tube
sheets and water boxes of heat exchangers (condensers) and cooling water piping
for each of the water categories. Where the table gives several options, (A) is the
preferred option, (B) and (C) may be considered as alternatives in that order (with
different reservations as regards corrosion resistance). The chloride values in
Table 3 serve by way of example only as a rough guide for the choice of materials,
which must in any case take into account the actual water chemistry and process
engineering conditions at the specific location.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
Tube material
Of the three groups of tube materials - copper alloys, stainless steels and titanium
[16], [17], [52] - use of the copper alloys for the tubing of heat exchangers in large
cooling systems is on the decline world-wide, due to the well-known risk of damage
(erosion corrosion, stress corrosion cracking, corrosion due to ammonia) [53], [54],
[55], [56], [57], [58]. Austenitic chromium/nickel steels (stainless steels) [59] and, for
brackish water and seawater cooling, titanium are today’s first choice. However, it
must be remembered that, unlike the copper alloys, these materials do not have a
bactericide effect and are thus are more susceptible to fouling by organic material
(biofouling).
Tube sheets
The choice of material for the tube sheets is largely governed by the material used
for the tubes, as otherwise compatibility problems may be encountered at the tube-
to-tube-sheet joints. There are basically four standard combinations of tube-to-tube-
sheet joints:
− any tube material and steel tube sheets coated with epoxy resin or other resin
systems,
− copper-alloy tubes and brass or bronze tube sheets
− copper-alloy or stainless steel tubes and tube sheets plated with stainless steel
− titanium tubes and titanium-plated tube sheets
The water boxes, which are usually made of steel, are usually provided with a thin
(0.5 to 1 mm) coating or lining of the same materials as for the tube sheets to make
them suitable for use in low-salt-content cooling waters.
The material for the cooling water piping must also be matched to the water quality.
Unprotected pipes of non-alloyed steel are adequately corrosion-resistant in cooling
waters of category I (Table 3). Low-alloyed steel can even be used in waters of
category II in particularly benign conditions, i.e. if the hydrogen carbonate content
and neutral salts content of the water is in line with DIN 50930 and continuous
throughflow is present [49]. Dip-galvanized steel pipes may also be used for small-
diameter lines [60]. Otherwise, stainless steels or sturdy plastics, e.g. polypropylene,
are suitable for small-diameter lines in waters of categories II to VI; in larger-
diameter lines (as of about >200 mm), the pipes must be made of concrete or of
steel or cast iron with
− cement mortar lining
− plastic mortar lining
− plastic-enhanced cement mortar lining
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
Concrete parts
Care must be taken in the overall design of the cooling system and the structural
design of the components to ensure that the inherent resistance of the materials
selected on the basis of the cooling water quality is not impaired by overlying ef-
fects. The causes of problems in cooling systems - despite careful selection of the
material - can be traced to failure to observe certain simple rules:
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
The operating conditions to which the components of a cooling system are exposed
are also an important consideration in the choice of materials, especially for the heat
exchangers. The necessary inspection and maintenance activities must be defined
for the specific materials and site. They depend primarily on the cooling water flow
velocity, the thermal load on the tubes, and the frequency and duration of the
anticipated downtimes.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
The cooling water flow velocity is an important parameter with respect to flow-in-
duced corrosion. Determining the cooling water flow velocity by calculation alone
involves some uncertainties. The actual flow velocities should be known and, if
necessary, verified by measurement. Empirical experience shows that tubes made of
copper and copper alloys are already susceptible to erosion corrosion if the flow
velocities given in Table 4 are exceeded. This can cause an inadmissible material
depletion of > 0.05 mm/a. The attack is even stronger if the cooling water contains
erosive components such as sand (e.g. as of grain size > 0.5 mm, concentration
> 5 mg/l), or if it is super-saturated with air (two-phase flow) [66]. Under such severe
conditions, only flow velocities are allowable that lie about 20 % below the values
valid for water with a low suspended-solids content, unless mechanical or chemical
precautions - such as cathodic protection, coating, sleeving of tube inlet ends, or
dosing with ferrous sulphate - are taken to eliminate the erosion corrosion hazard.
These restrictions do not apply to austenitic chromium/nickel steels and titanium.
Unlike copper alloys, these exhibit excellent resistance to erosion corrosion even at
high flow velocities of around 5 m/s. On the other hand, the danger of corrosion
attack beneath mineral or organic deposits is particularly high in the case of
stainless steels. Because of the possibility of crevice corrosion, use of continuous-
action tube cleaning systems, usually with polishing balls, is necessary if tube mate-
rials from this group with effective sums W < 35 % [% Cr + (3.3x% Mo); German
material codes 1.4401, 1.4439] are used in connection with cooling waters with an
elevated salts or suspended solids content. This applies in particular if calcite crys-
tals can grow out of super-saturated cooling water.
Table 4. Design data for maximum cooling water flow velocities (in m/s).
Material Material No. Cooling water with low Cooling water with sand
suspended-solids or suspended solids
content content
1)
DIN EN 12451, edition 1999-10; Copper and Copper Alloys – Seamless, round tubes for heat
exchangers
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
By contrast, corrosion beneath deposits on titanium surfaces has never been ob-
served to date, so that this material is ideally suitable for heat exchangers operated
with water with a high suspended solids content. The greater susceptibility of non-
copper materials to biofouling may call for occasional or regular cleaning using
special cleaning balls, e.g. with plastic granulate or corundum coating or filled with
powdered pumice, instead of sponge-rubber balls in the tube cleaning system [58].
The temperature can influence both corrosion and deposition processes. Corrosion
processes accelerate with rising temperature; a temperature rise of 10 K nearly
doubles the corrosion rate. The crucial factor here is the actual wall temperature,
which may be widely different from the average temperature, e.g. as a result of local
differences in the thickness of deposits. Since rising temperatures also promote the
formation of crystals, the temperature influence on corrosion is particularly strong at
locations susceptible to crystal formation, Higher temperatures also promote the
growth of micro-organisms, provided there is an adequate supply of nutrients. These
processes can be controlled by use of hardness stabilisers or microbiocides and by
cleaning heat exchanger tubes to remove mineral and organic deposits, as
explained earlier.
Downtimes can have an adverse effect on the corrosion behaviour of the materials,
but there are precautions that can be taken to mitigate these effects. Heat exchang-
ers, and especially condensers, should have mineral and microbiological deposits
removed as far as possible by continuous operation of the tube cleaning system
before they are shut down for an extended period of time, and if they are to remain
filled the circulating water, which may have built up an elevated salts concentration,
should be replaced by demineralized water. Condensers are normally drained when
not in service. In this case there is a corrosion hazard from remaining water pockets
- for example in sagging tubes - in which the salts and suspended solids can
concentrate due to evaporation and eventual dry-out. Except in condensers with
titanium tubing, which do not require such precautions, condensers should be
flushed with demineralized water immediately after draining (and mechanically
cleaned if they are to remain shut down for an extended period) and dried with hot or
dry air. It is advisable to leave the water boxes open for the duration of the outage
[16], [17].
5 Monitoring by analysis
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
The samples for the customary cooling water analyses are best taken at the dis-
charge side of the cooling water pumps. For a sample to be representative, the
system must have been in undisturbed continuous operation for at least two hours.
Other sampling locations may need to be chosen for special-purpose analyses. For
example, to check on the metering of chemicals, the samples must be taken down-
stream of the feed-in point; for monitoring material depletion or the condition of the
protective layer on condenser tubes, cooling water samples must be taken down-
stream of the condenser.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
Table 5. Minimum scope of analyses for monitoring the circulating water in open-circuit
recirculation cooling systems.
Recommended frequency of
Basic parameters
measurement
Temperatures
(upstream and downstream of loads) cont.
pH value cont./(d)
Ca + Mg w/(req.)
- 2-
Further parameters, such as Cl , SO4 , P and N compounds, Cu, Fe, Na (K), COD
(DOC), undissolved substances, colony count, concentration of dosed chemicals
should be monitored according to criteria defined for the specific system and site.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
Table 6. Minimum scope of analyses for monitoring the circulating water in closed-circuit
recirculation cooling systems.
Recommended frequency of
Basic parameters
measurement
Conductivity
as auxiliary para-
direct measurement req.
meters instead of
measurement downstream of strongly req.
pH measurement
acidic sampling cation exchanger
Oxygen req.
Fe / Cu req.
req. ⇒ as required
Temperature
Electrical conductivity
Nonspecific global parameter for the electrolyte content in the cooling water.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
pH value
A measure of the hydrogen ion and hydroxide ion concentration; an important pa-
rameter for measuring corrosion attack.
Hardness
A measure of the overall concentration of alkaline earth ions, in most waters identical
with the calcium and magnesium ion content.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
Chloride
Sulphate
A significant parameter for the corrosion behaviour of concrete materials [14] which,
for this reason, must not exceed certain concentrations.
This must be borne in mind if sulphuric acid is used to decarbonate the water.
Phosphor compounds
Nitrogen compounds
A generic term for various species, such as ammonia, nitrate, nitrite and organic
nitrogen compounds; elevated ammonia, nitrate and nitrite contents in the cooling
water are an indication of microbiological processes as a result of which corrosion
can occur.
Copper
An indication of ongoing corrosion and for the behaviour of the protective layers on
heat exchanger tubing made of copper-based alloys.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
Total iron
Sodium, potassium
Parameters that are of no importance to operation of the cooling system but knowl-
edge of which makes it possible to close the ion balance and to demonstrate the
plausibility of a cooling water analysis.
Oxygen
COD (TOC)
Nonspecific global parameter for the chemical oxygen demand of the cooling water.
In open-circuit recirculation cooling systems, the COD (or the DOC/TOC content)
makes it possible to draw conclusions as to the presence of (oxidisible) organic
contents in the cooling water.
Undissolved substances
The high adsorption of chlorine and chlorine bleach into the undissolved substances
may cause chlorine depletion if these substances are used for biocide treatment.
Chemical agents
The service concentration of conditioning agents should be controlled via the input
flow. It may, however, also be necessary to measure the content of the effective
agents in the circulating water directly. Direct or indirect measurement of the input
chemicals may make it possible to reduce the amount of chemicals used.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
If a tube cleaning system is installed in the cooling system, attention must be paid to
ensuring that it is fully operational in order to avoid biological deposits in the heat
exchanger tubes (impaired heat transfer, higher corrosion rate). If necessary, tube
cleaning balls with abrasive coatings (corundum, granulate) must be used in times of
high biological activity to remove deposits on the tube walls.
5.2.1 Investigations
The frequency of investigations will depend on the microbiological activity and the
type of cooling water.
Use of test heat exchangers in cooling systems gives an overview of the biofouling
hazard. However, these measurements provide reliable results only over long
periods.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
Parameter Method
5.3.1 Investigations
Material specimens can be integrated into the cooling system for assessment of the
corrosion potential.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
scaling, fouling and biofouling. These results indicate trends and have to be nor-
malised by long-term testing.
6 References
[1] Behrsing, V., Grimm, W., and Wittrowsky, G.: Investigation on the Treatment of Lime-
decarbonized Cooling Tower Make-up Water for Use as Secondary Cooling Water.
VGB PowerTech 68 (1985) No. 2, pp 147-150.
[2] Martin, P.: Some Thoughts on Co-ordinating the Operating Characteristics of Turbine
and Condensator. VGB PowerTech 68 (1988), No. 6, pp. 540-545.
[3] DIN 1947, edition 1989-05
Thermal performance acceptance testing of water cooling towers (VDI Code of
practise).
[4] Buss, E., and Engel. L.: Aspekte moderner Kühlwasserpflege. Erdöl und Kohle -
Erdgas - Petrochemie vereinigt mit Brennstoffchemie 30 (1977), No. 7, pp. 322-328.
[5] Trage, B., and Hintzen, F.J.: Design and Construction of Plants with Indirect Dry
Cooling Systems. VGB PowerTech 69 (1989), No. 2, pp. 164-170
[6] Ham, A.J.: The Conservation of Water as a Power Plant Resource. VGB PowerTech 69
(1989), No. 1, pp. 15-21
[7] DIN EN 45510-6-3, edition: 1998-06
Guide for procurement of power station equipment - Part 6-3:
Turbine auxiliaries; condensator plant; German version of EN 45510-6-3: 1998.
[8] Alt, W., and Mäule, R.: Hybrid Cooling Towers in an Economic Comparison with Wet
and Dry Cooling Towers. VGB PowerTech 67 (1987), No. 8, pp. 689-694.
[9] Enger, R., Blanck, D., and Schwickert, M.: Hybridkühltürme als Teil einer Kühl-
wasserversorgung. VGB Conference "Kühltürme 1991", (TB 602) Lecture 3, parts 1-3.
[10] Münch, S., and Fichtner, H.: The Hybrid Cooling Tower for the 2x60-MW West Co-
generation Plant of Stadtwerke Frankfurt am Main. VGB PowerTech 71 (1991), No. 6,
pp. 501-505.
[11] Cossmann, R., and Vodicka, V.: Hybridkühltürm für einen 1300 MW-Block.
Brennst. - Wärme - Kraft 36 (1984), No. 7-8, pp. 310-313.
[12] Kühlwasser, 4th revised and extended edition, 1994, by H.-D. Held, revised by H. G.
Schnell. Vulkan-Verlag Dr. W. Classen, Essen
[13] Effertz, P.-H., and Fichte, W.: Kühlwasserseitiger Schutz von Kondensator- and Kühler-
berohrung durch Eisensulfatdosierung. Der Maschinenschaden 49 (1976), No. 4, pp.
163-172.
[14] Effertz, P.-H., and Fichte, W.: Iron Sulphate Dosing in Cooling Systems; Fundamentals
and Application. VGB PowerTech 57 (1977), No. 2, pp. 116-120.
[15] Stubbe, J., and Briquet, J.: Assessment of FeSO4 Dosing of a Heat Exchanger. VGB
PowerTech 69 (1989), No. 7, pp. 631-634.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
[16] VGB Guideline "Tubes for Condensers and Other Heat Exchangers (Part A Copper
Alloys)" (VGB-R 106 L e). VGB-KRAFTWERKSTECHNIK GMBH, Essen.
[17] VGB Guideline " Tubes for Condensers and Other Heat Exchangers (Part B Stainless
Steels)" (VGB-R 113 L e). VGB-KRAFTWERKSTECHNIK GmbH, Essen.
[18] Gümpel, P., Kreikenbohm, R., and Neumann, K.: Betrachtungen über mikrobiell
induzierte Korrosionsvorgänge und deren biologischen Hintergrund. Mat.-wiss. U.
Werkstofftech. 27 (1996), pp. 122-128.
[19] Becker, H. A., and Armon, Th.: Microbiological corrosion in cooling water systems.
Chem. Processing (1995), pp. 60 to 65.
[20] DIN 4030-1, edition: 1991-06
Assessment of water, soil and gases for their aggressiveness to concrete; principles
and limiting values.
[21] Czolkoss, W., Fichte,W., and Schleithoff, K.: Deckschichtstrukturen auf Kondensator-
rohroberflächen. Der Maschinenschaden 64 (1991), No. 5, pp. 194-201.
[22] Kretzer, R., and Schluck, K.: Experience with the Combination of Process Steps for
the Treatment of Cooling Tower Make-up Water. VGB PowerTech 57 (1977), No. 1,
pp. 36-47.
[23] von Hagel, G., Berlenbach, N., and Klegraf, F.: A New Procedure for Treatment of
Cooling Tower Make-up Water by Means of Slow Decarbonization. VGB PowerTech 57
(1977), No. 1, pp. 47-51.
[24] Schub, P., and Seifert, K.-G.: Experience with a System for Cooling Tower Make-up
Water Treatment. VGB PowerTech 63 (1983), No. 3, pp. 221-222.
[25] Resch, G.: A Study on the Control of Corrosion in Cooling Systems while Dispensing
with Chemical Conditioning. VGB PowerTech 68 (1988), No. 6, pp. 564-568.
[26] VGB Instruction Sheet VGB-M 403 G "Treatment of Operating Water and Cooling
Tower Make-up Water by Decarbonization or Flocculation and Decarbonization“. VGB-
KRAFTWERKSTECHNIK GMBH, Essen.
[27] VGB Instruction Sheet VGB-M 408 G "Waste Water and Solid Residues from Water
Treatment Plants and Systems in Contact with Water and Steam in Thermal Power
Plants". VGB-KRAFTWERKSTECHNIK GMBH, Essen.
[28] Eickelpasch, N., Lasch, M., and Brunnhuber, L.: Agricultural Utilisation of Lime
Residues from Cooling Tower Make-up Water Treatment. VGB PowerTech 69 (1989),
No. 6, pp. 528-530.
[29] Resch, G., and Burgmann, F.: Experiments with Organic Phosphorus Compounds for
Cooling Water Treatment. VGB PowerTech 56 (1976), No. 3, pp. 157-160.
[30] Wehle, V.: Ecological Aspects of the Application of Phosphorus Acids for Cooling
Water Treatment. VGB PowerTech 56 (1976), No. 3, pp. 160-164.
[31] Angenend, F.J., and Schulte-Wieschen, U.: A Contribution to the Determination of
Polycarbonic Acids in Cooling Waters and Waste Waters of Power Plants. VGB
PowerTech 59 (1979), No. 12, pp. 904-906.
[32] Horn, W., Buss, E., and Probst, W.: New Aspects of Cooling Water Maintenaince
in View of the Influence and Control of System Pollution. VGB PowerTech 60 (1980),
No. 2, pp. 130-135.
[33] Buss, E., Freedman, A.J., and Probst, W.: New Conditioning Programmes for
Corrosion Protection in Recirculating Cooling Systems Using Lime-softened Make-up
Water. VGB PowerTech 62 (1982), No. 2, pp. 108-111.
[34] Wutte, G., and Lexy, H.: Cooling Water Treatment with Special Consideration to
Minimum Requirements for Waste Water from Cooling Systems. VGB PowerTech 65
(1985), No. 1, pp. 69-71.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
[35] Bohnsack, G.: Modern Cooling Water Treatment. On the Mechanism of Film Inhibition
of Steel Corrosion. VGB PowerTech 66 (1986), No. 1, pp. 47-52.
[36] Shannon, J.E., and Lexy, H.: Cooling Water Treatment Under the Influence of High
Concentration Ratio and Recycling of Blowdown. VGB PowerTech 67 (1987), No. 9,
pp. 897-901.
[37] Marshall, A., and Germann, R.: Environmentally Acceptable Cooling Water Treatment.
VGB PowerTech 67 (1987), No. 10, pp. 969-973.
[38] Aprosi, G., Bidard, F., Nepveu, C., Roofthooft, R., and Duvivier, L.: Neue Konzepte
beim Betrieb von Umlauf-Kühlsystemen mit Kühltürmen. VGB Conference "Chemistry
in Power Plants 1987" (TB 423), pp. 133-143.
[39] Bohnsack, G., and Greiner, G.: Consequences of § 7a Water Resources Act for the
Operation of Circulating Cooling System with Regard to Power Plant Chemistry. VGB
PowerTech 65 (1985), No. 1, pp. 71-75.
[40] Steber, J., and Hater, W.: Ökologische Beurteilung von Kühlwasserbehandlungsmitteln.
VGB Conference "Chemistry in Power Plants 1997" (TB 433), lecture P 12,
size 9 pages.
[41] Yang, B., Johnson, D. A., and Shim, S. H.: Effect of Ozone on Corrosion of Metals
Used in Cooling Towers. Corrosion 49 (1993), No. 6, pp. 499 to 513.
[42] Germann, R., and Marshall, A.: Behandlung von Kühlsystemen mit Mikrobioziden -
Möglichkeiten und Grenzen. VGB Conference "Chemistry in Power Plants 1990"
(TB 426), pp. 27-35.
[43] Wasel-Nielen, J., and Baresel, M.: The Treatment of Cooling Water with Ozone at
Hoechst AG in Comparison with Other Microbiocidal Processes. VGB PowerTech 77
(1997), No. 2, pp. 124-128.
[44] Olkis, A., Kleinstück, R., Noks, E., and Johnson, D. A.: Kühlwasserbehandlung mit
Ozon im Kraftwerk EZH-RoCa3 Rotterdam - Praxiserfahrungen mit einem "All Organic"-
Programm. VGB Conference "Chemistry in Power Plants 1998" (TB 434), lecture P 15,
size 12 pages.
[45] Schmittecker, B.M., Henke, K.-P., and Bergmann, R.: Kühlwasserbehandlung mit
Ozon. Betriebserfahrungen aus dem Großkraftwerk. VGB KraftwerksTechnik 79 (1999),
No. 4, pp. 82-87.
[46] Gömöri, J., and Braun, D.: Verfahren zur Kontrolle der Mikrobiologie im Kühlturm-
wasserkreislauf des KKW-Gösgen mit einem Produkt auf Basis H2O2-Silber. VGB
Conference "Chemistry in Power Plants 1997" (TB 433), lecture P 13, size 14 pages.
[47] Bauer, R., and Reichel, P.: Construction and Working Procedure of an Efficient
Chlorination Plant for Cooling Cycles with Large Volumes. VGB PowerTech 61 (1981),
No. 3, pp. 222-224.
[48] Krabbe, H.-J., Pietsch, M., and Werner, H.-P.: Cooling Tower Make-up Water
Treatment Plants with Respect to the Chemical and Biological Approach. VGB
PowerTech 73 (1993), No. 7, pp. 543-545.
[49] DIN 50930-2, edition: 1993-02
Corrosion of metals; corrosion of metallic materials under corrosion load by water
inside of tubes, tanks and apparatus; evaluation of the corrosion likelihood of unalloyed
and low-alloy iron materials.
[50] Peters, Th., Borchardt, H.-P., Bohlinger, W., Fichte, W., and Rullik, W.: Entfernung von
Ölverschmutzungen aus geschlossenen, weitverzweigten Zwischenkühl-wasserkreis-
läufen bei laufendem Betrieb. VGB Conference "Chemistry in Power Plants 1997"
(TB 433), lecture R 5, size 12 pages.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
[51] Svoboda, R., Sandmann, H., Seipp, H.G., and Liehr, C.: Water Chemistry in Generator
Water Cooling Systems. VGB-EPRI Conference "Interaction of Non-Iron-Based
Materials with Water and Steam", Piacenza / Italy 1996, size 15 pages.
[52] VGB Guideline " Tubes for Condensers and Other Heat Exchangers (Part C Titanium)"
(VGB-R 114 L). VGB-KRAFTWERKSTECHNIK GmbH, Essen
[53] Effertz, P.-H., Fichte, W., and Forchhammer, P.: Kühlwasserseitige Korrosion an
Kondensatoren und Kühlern in Kraftwerken. VGB KraftwerksTechnik 54 (1974), No. 2,
pp. 82-93.
[54] Resch, G., and Zinke, K.: Investigations Relating to the Effect of the pH-Value on the
Corrosion of Brass. VGB PowerTech 60 (1980), No. 1, pp. 61-63.
[55] Angenend, F.J.: Corrosion of Condenser Tubes Resulting from a Disturbance in the
Composition of Protective Coatings. VGB PowerTech 61 (1981), No. 7, pp. 487-494.
[56] Glaze, F.: Improved Condenser Efficiency and Enhanced Tube Life through Condenser
Monitoring. VGB PowerTech 64 (1984), No. 5, pp. 382-388.
[57] Beurich, H., and Henke, K.-P.: Admiralty Brass Condenser Tubing – Origin of Cooling
Water Problems? VGB PowerTech 69 (1989), No. 1, pp. 91-95.
[58] Schleithoff, K., and Schmitz, F.: Stainless Steel and Titanium Condenser Tubes;
Operating Experience and Measures for Refurbishment and Life Extension. VGB
PowerTech 69 (1989), No. 1, pp. 7-15.
[59] Seipp, H.-G., Deimling, H.-J., and Müller, R.: Testing of the Corrosion Characteristics of
Corrosion-resistant Heat Exchanger Tubes for Installation in Power Stations and
Operating Experience. VGB PowerTech 65 (1985), No. 5, pp. 480-488.
[60] DIN 50930-3, edition: 1993-02
Corrosion of metals; corrosion of metallic materials under corrosion load by water
inside of tubes, tanks and apparatus; evaluation of the corrosion likelihood of hot dip
iron materials.
[61] Freier, R.K., Herms, R., and Kallenbach, R.: Experience with Coatings in Plants in
Contact with Water. VGB PowerTech 56 (1976), No. 2, pp. 98-102.
[62] DIN 4030-1, edition: 1991-06
Assessment of water, soil and gases for their aggressiveness to concrete; principles
and limiting values.
[63] DIN 4030-2, edition: 1991-06
Assessment of water, soil and gases for their aggressiveness to concrete; collection
and examination of water and soil samples.
[64] DIN 1045, edition: 1988-07
Structural use of concrete; design and construction.
[65] DIN 1164-1, edition: 1994-10
Cement - Part 1: Composition, specifications.
[66] Effertz, P.-H., and Forchhammer, P.: Parameterstudie zum Erosions-Korrosions-
Verhalten von Werkstoffen für Wärmeaustauscherrohre unter dem Einfluß von
chemischen und mechanischen Größen bei Staustrahlbedingungen. Der Maschinen-
schaden 62 (1989), No. 2, pp. 68-80.
[67] Flemming, H.-C.: Ökonomisch-technischer Überblick. Werkstoffe und Korrosion 45
(1994), pp. 5-9.
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020
Corporate License/Unternehmenslizenz
----------
∙ VGB PowerTech DIGITAL ∙ © 2016, Essen, Germany ∙ CORPORATE LICENSE | Ordinary Members | INTERNAL USE ONLY ∙
Licensee/Lizenznehmer: JAVNO PODJETJE ENERGETIKA LJUBLJANA p.o. - 22.09.2020