ASIMON360 Tips & Tricks:IO-Link
Replacing a
defective device
Possibilities of replacing a defective device
1
1.1 This Quick Start Guide describes how to replace 1.2 If the Safety Monitor is part of a Safe Link
the following devices from the ASi circuit: connection, teaching Safe Link is required (section 4).
●
Defective safety slaves (section 2) The steps have to de done at the gateway which has
● Defective standard slaves (section 2) been defined as the group manager.
●
Defective slaves with a chip card (section 2)
●
Defective Safety Basic Monitors (section 2)
●
Defective safety monitors (section 3).
Replacement of a defective slave
2
2.1 Note that the new slave must have the same 2.2 Push the "Service" button on the master for 3 2.3 Connect the new slave to the ASi circuit. Note 2.4 For replacing a standard slave without safe in-
profile and address as the defective slave. If the seconds. A message indicating that the new slave that the contacts on the slave must be closed. and outputs, remove the defective slave from the
master is from Bihl+Wiedemann, a slave with can be connected will appear on the master's Afterwards press the "Service" button for 3 ASi circuit and connect the new slave. No further
address 0 can be used to replace the defective one. display. seconds again. The new slave is now ready for actions are required.
The proper address will be then given by the use. The procedure is the same for slaves that are
master. Remove the defective slave from the ASi connected to a Safety Basic Monitor, but in this
circuit. case the "Set" button has to be pressed.
2.5 To replace a defective slave that contains a chip 2.6 Take the chip card out of the defective device 2.7 Connect the new slave to the ASi circuit. 2.8 All slaves that contain a chip card, as well as
card, separate it from the ASi circuit. and insert it into the new device. Safety Basic Monitors, can be exchanged in the
same way.
Replacement of a defective safety monitor
3
3.1 Disconnect the defective safety monitor from 3.2 Take the chip card out of the defective master 3.3 Connect the new monitor to the ASi network 3.4 Follow the steps on display to copy the
the power supply and the ASi network. and insert it into the replacement device. and to the power supply. information from the chip card into the master.
3.5 If asked in which direction the copying shall be 3.6 Type the release code of the configuration. 3.7 Confirm with "OK". Afterwards the safety 3.8 The replacement is now completed. The new
started, select "Chipcard->Master". Confirm the release code. monitor will be started. safety monitor is ready for use. But if the master is
part of a Safe Link connection it is necessary to
teach in Safe Link at the group manager. (section 4)
Teaching in Safe Link after replacing a safety monitor
4
4.1 The teach-in of Safe Link has to be done at the 4.2 Go to “Safety” and select “Safe Link”. 4.3 Indicate the number of replaced nodes and click 4.4 The new safety monitor is ready for use.
group manager of the Safe Link connection. Press on "Teach in" to start. Click "OK" once complete.
the "OK" button to open the display menu.
Important Note!! Bihl+Wiedemann GmbH
5 This document is intended solely as an aid for the users of safety monitored equipment.
Flosswoerthstr. 41
It does not relieve the user of responsibility for proper testing. Please refer to the safety 68199 Mannheim
instructions in the user manual. Germany