Cordex™ CXCM4
System Controller
CXCM4
> Modular, hot swappable controller for use with 3.1kW, 3.6kW and 4kW
rectifier platforms
> Internet ready and remotely accessible for complete system monitoring
and control
> Integrated SNMP functionality for cost effective multiple site monitoring
> Advanced battery monitoring and power save features for OpEx savings
and reduced carbon footprint
> Highly configurable platform with user definable alarms and data logging
provides maximum flexibility with a common platform
Cordex CXC controllers bring advanced monitoring technology to the Cordex series of rectifiers. The CXCM4 is a modular
system controller option for the 4RU 24V-3.1kW, 48V-3.6kW and 48V-4kW rectifier shelf systems.
The CXCM4 controller includes a PDA-style touch screen GUI for simple and convenient local setup. A built-in web server
provides alternate setup via local or remote IP access using a standard Windows Internet Explorer browser.
The integrated logging feature allows the capture of data from multiple inputs for AC/DC voltages, load/battery current,
and cell voltage/temperature. Common applications of the CXCM4 logging include power system details, thermal performance
of outdoor enclosures, battery cell specifics, or mains variations captured by an AC voltage watchdog. The CXCM4 I/O
feature set can be easily expanded with the addition of CXC smart peripherals such as battery cell monitoring, shunt
multiplexing, and alarm relay expansion.
Cordex CXCM4 modular controllers ensure effortless operation of the Cordex rectifier family. Time consuming, complicated
set up and monitoring of DC power systems are now a thing of the past.
Your Power Solutions Partner
Cordex™ CXCM4 System Controller
Part Number: 018-574-20
Features >Log files
Daily statistics:...................Min., max. and average on analog input
>User Interface channels with date and time stamp
GUI:....................................LCD touch screen display for local access Battery current, rectifier current and
Embedded web based GUI accessed via AC mains voltage for last 90 days
ethernet or modem using Internet Explorer Event log:...........................All events such as alarms, power on, change
(IE6 and above) of state on digital inputs or other events
Display:..............................Full graphic LCD, 160x160 pixels, with Battery log:.........................Battery health history on last 20 discharges
backlight and contrast adjustment with time of discharge and battery capacity
Audio:.................................Built-in speaker for audible alarm Data logging:......................Up to 16 user configurable logs of all system
Indicators:..........................System OK (green LED) signals including smart peripherals
Minor alarm (yellow LED)
Major alarm (red LED) Electrical
>Rectifier features
• Single point adjustment Input voltage:..................... 17 to 65Vdc
• Auto load share Current:..............................<100mA @ 48Vdc
• Power save <200mA @ 24Vdc
• Power on delay start
Mechanical
>Battery features
• Temperature compensation Dimensions:
• Manual, auto, and periodic equalize mm:..................................177H x 87W x 257D
• Battery current terminate equalize in:.....................................7.0H x 3.4W x 10.1D
• Battery over temp equalize shutoff Mounting:...........................Modular controller for 3.1kW, 3.6kW and
• Dynamic charge current control 4kW shelves
• Battery runtime and capacity indication Weight:...............................1.8kg (3.9lb)
• Battery low capacity warning
• Auto or manual battery test mode Environmental
>System features Temperature:......................-40 to 65°C (-40 to 149°F)
• CAN bus interface to Cordex rectifiers and smart peripheral modules Humidity:............................0 to 95% RH non-condensing
• Password protection
• Virtual rectifier, battery & shunt addition current Related Components
• User configurable alarms
• User configurable signals 036-202-20:........................External I/O terminal block connector kit
• Languages for English, Chinese & 3rd language option
• Downloadable software & firmware upgrades Agency Compliance
>Communications Safety:................................UL/CSA C22.2 No 60950-1
Alarm relays:......................Potential free Form C contacts IEC/EN 60950-1
SNMP:................................SNMP v2.5 via ethernet CE marked
Requires SNMP management software EMC:..................................ETSI 300 386
(e.g., HP openview, SNMPc) Emissions:..........................CFR47 (FCC) part 15 Class B
Email:.................................SMTP via ethernet or modem ICES-03 Class B
EN55022 (CISPR 22) Class B
>Communication ports C-Tick (Australia)
CAN:...................................Interface to Cordex series rectifiers and Immunity:............................EN 61000-4-2,-3,-4,-5,-6
optional smart peripheral modules
Ethernet:.............................10/100 Base T with half/full duplex (front)
Serial:.................................RS-232 (front)
>System I/O
Alarm relays:......................8
Voltage inputs:...................1 +1 internal
BiV inputs:..........................2
Temp inputs:.......................2
Current inputs:...................4
Digital inputs:.....................4
Alpha Technologies Ltd. For more information visit www.alpha.ca
Canada: Burnaby, British Columbia Tel: 604 436 5900 Fax: 604 436 1233 #048-725-10 Rev C (02/2012)
United States: Bellingham, Washington Tel: 360 647 2360 Fax: 360 671 4936
Alpha Technologies reserves the right to make changes to the products and information contained in this document without notice. member of The Group™
Copyright © 2010 Alpha Technologies. All Rights Reserved. Alpha® is a registered trademark of Alpha Technologies.
member of The Alpha Group™ is a trademark of Alpha Technologies.