Certificate of compliance

Applicant: UPOWER ELECTRIC CO., LTD


4F-A Block, No.62, Yinhe Road, Longgang District, Shenzhen, Guangdong
China

Product: Hybrid inverter

Model: UHome-3K0L
UHome-3K6L
UHome-4K0L
UHome-4K6L
UHome-5K0L
UHome-6K0L
UHome-8K0L

Inverter for single-phase parallel connection to the public grid. The network monitoring and disconnection device is an integral
part of the above-mentioned model.
Applied rules and standards:
EN 50549-1:2019
Requirements for parallel connection of installations with distribution networks - Part 1: Connection to an LV distribution network -
Production of installations up to and including Type B
4.4 Normal operating range
4.5 Immunity to disturbances
4.6 Active response to frequency deviation
4.7 Power response to voltage variations and voltage changes
4.8 EMC and power quality
4.9 Interface protection
4.10 Connection and starting to generate electrical power
4.11 Ceasing and reduction of active power on set point
4.13 Requirements regarding single fault tolerance of interface protection system and interface switch
DIN VDE V 0124-100:2020 (5.5.2.1 Functional safety of network and system protection)
Grid integration of generator plants - Low-voltage - Test requirements for generator units to be connected to and operated in
parallel with low-voltage distribution networks
Commission Regulation (EU) 2016/631 of 14 April 2016
Establishing a network code on requirements for grid connection of generators (NC RFG).
Type approval for generation units to use in Type A and Type B plants.
At the time of issue of this certificate, the safety concept of an aforementioned representative product corresponds to the valid
safety specifications for the specified use in accordance with regulations.
Report number: CIZC-ESH-P22120590 Certification Program: NSOP-0032-DEU-ZE-V01
Certificate number: U23-0790 Date of issue: 2023-09-12

Certification body

Alf Assenkamp

Certification body Bureau Veritas Consumer Products Services Germany GmbH accreditation to DIN EN ISO/IEC 17065
Testing laboratory accredited according to DIN EN ISO/IEC 17025
A partial representation of the certificate requires the written approval of Bureau Veritas Consumer Products Services Germany GmbH
Annex to the EN 50549-1 certificate of compliance No. U23-0790

Appendix

Extract from test report according to EN 50549-1 No.CIZC-ESH-P22120590

Type Approval and declaration of compliance with the requirements of EN 50549-1 and Commission Regulation (EU)
2016/631 of 14 April 2016
Manufacturer / applicant UPOWER ELECTRIC CO., LTD
4F-A Block, No.62, Yinhe Road, Longgang District, Shenzhen, Guangdong,
China

Micro-generator Type Hybrid inverter


UHome-3K0L UHome-3K6L UHome-4K0L UHome-4K6L
MPP DC voltage range [V] 80-500
Max. input DC voltage [V] 550
Max. input DC current [A] 14/14
Output AC voltage [V] 230 50/60Hz
Max AC current [A] 14,3 16,0 19,1 20,0
Apparent power [VA] 3300 3680 4400 4600

UHome-5K0L UHome-6K0L UHome-8K0L --


MPP DC voltage range [V] 80-500 --
Max. input DC voltage [V] 550 --
Max. input DC current [A] 14/14 14/28 --
Output AC voltage [V] 230 50/60Hz --
Max AC current [A] 21,7 28,7 38,3 --
Apparent power [VA] 5000 6600 8800 --

Firmware version DSP: V1.05.07, ARM: V1.04.15

Description of the structure of the power generation unit:


The power generation unit is equipped with a PV/DC and line-side EMC filter. The power generation unit has no galvanic isolation
between DC input and AC output. Output switch-off is performed with single-fault tolerance based on the inverter bridge and two
series-connected relays in each line and neutral. This enables a safe disconnection of the power generation unit from the network
in case of error.