QDT Instruction Book
QDT Instruction Book
Instruction book
Atlas Copco
Compressed air filters
Instruction book
Original instructions
Copyright notice
Any unauthorized use or copying of the contents or any part thereof is prohibited.
This applies in particular to trademarks, model denominations, part numbers and drawings.
This instruction book is valid for CE as well as non-CE labelled machines. It meets the
requirements for instructions specified by the applicable European directives as identified
in the Declaration of Conformity.
2010 - 03
No. 2920 7090 71
Replaces No. 2920 7090 70
www.atlascopco.com
Instruction book
Table of contents
1 Safety...............................................................................................................................4
2 General............................................................................................................................6
3 Installation.......................................................................................................................7
3.5 OPTIONS........................................................................................................................................10
4 Standards......................................................................................................................13
5.1 SERVICE.........................................................................................................................................15
5.2 PROCEDURE....................................................................................................................................15
6 Technical data...............................................................................................................17
2 2920 7090 71
Instruction book
2920 7090 71 3
Instruction book
1 Safety
Explanation
Warning
Important note
All responsibility for any damage or injury resulting from neglecting these precautions, or
non-observance of the normal caution and care required for installation, operation,
maintenance and repair, even if not expressly stated, will be disclaimed by the
manufacturer.
General precautions
1. The operator must employ safe working practices and observe all related work safety requirements and
regulations.
If any of the following statements does not comply with the applicable legislation, the stricter of the two
shall apply.
2. Installation, operation, maintenance and repair must only be performed by authorised, trained, specialised
personnel.
3. The compressor is not considered capable of producing breathing air. The filter does not remove methane,
carbon monoxide and some other toxic gases and fumes.
4. Before any maintenance, stop the compressor. In addition, the power isolating switch must be opened and
locked and the system depressurized.
5. Never play with compressed air. Do not apply the air to your skin or direct an air stream at people. Never
use the air to clean dirt from your clothes. When using the air to clean equipment, do so with extreme
caution and wear eye protection.
6. Never operate unit at pressures below or in excess of its limit ratings.
7. No external force may be exerted on the air outlet /inlet. The connection pipes must be free of strain.
4 2920 7090 71
Instruction book
3. Before starting maintenance or repair, a warning sign bearing a legend such as "work in progress; do not
start" shall be attached to the starting equipment.
4. Always wear safety glasses during maintenance or repair work.
5. Use only the correct tools for maintenance and repair work.
6. Use only genuine parts.
7. All maintenance work shall only be undertaken when the filter has cooled down.
8. Before removing any pressurized component, effectively isolate the machine from all sources of pressure
and relieve the entire system of pressure.
9. The aspirated air must be free of flammable fumes and particles that can lead to internal fire or explosion.
10. Never operate the machine when there is a possibility of taking in flammable or toxic fumes vapours or
particles.
11. The filter shall only be lifted with adequate equipment in conformity with local safety rules and can only
be moved when not in use.
12. The electrical connections shall correspond to the local codes. The units shall be grounded and protected
against short circuits by fuses.
2920 7090 71 5
Instruction book
2 General
QDT filters
QDT filters are designed for the removal of oil vapours and odours from compressed air.
The air flows through the activated carbon which is contained in the QDT filter element and which adsorbs
oil vapours and odours. The QDT has to be preceded by a DD and PD filter.
QDT filters adsorb all oil and most of the volatile compounds in the air.
Some volatile organic substances are more difficult to remove. As an example, this filter does not remove
methane, carbon monoxide, carbon dioxide and some other toxic gases and fumes. Therefore air from the
QDT can not directly be used for breathing purposes.
Factors that influence the performance of activated carbon in air:
• Type of compound to be removed:
In general compounds with a high molecular weight, lower vapour pressure/higher boiling point and high
refractive index are better adsorbed.
• Concentration:
The higher the concentration, the higher the carbon consumption which results in a lower lifetime.
• Temperature:
The lower the temperature, the better the adsorption capacity.
• Pressure:
The higher the pressure, the better the adsorption capacity.
• Humidity:
The lower the humidity, the better the adsorption capacity.
This filter does not remove methane, carbon monoxide, carbon dioxide or other toxic gases
and fumes.
6 2920 7090 71
Instruction book
3 Installation
2920 7090 71 7
Instruction book
The filter (6) must be installed on a level floor suitable for taking the weight of the filter. There must be a free
space above the filter of 800 mm for service.
8 2920 7090 71
Instruction book
To connect the filter with the air net it is necessary to place a valve (2) at the inlet and the outlet. This valve
must be placed as close as possible to the filters to make it easily reachable for service personnel.
Make sure that the air delivered to the filter does not exceed the limitations mentioned in this instruction book,
such as reduced oil content and a lowered dew point. Both parameters have a big impact on the lifetime and
performance of the activated carbon tower.
When the compressor (1) does not have an internal dryer, a separate dryer should be included in the setup.
Before the QDT filter install two inlet filters: a type DD filter (4) for general purpose filtration (particle removal
down to 1 μm with a maximum oil carry-over of 0.1 ppm ) and a high efficiency PD filter (5) for a particle
removal down to 0.01 μm with a maximum oil carry-over of 0.01 ppm. At the outlet, a high efficiency PDp
filter (7) is placed for the removal of particles down to 0.01 μm.
A drain tube must be installed on both inlet filters. The drain pipes (3) to the drain collector must not dip into
the water.
The preferred and recommended installation sequence is a compressor with internal dryer (1) - filters (4,5,6,7)
- air receiver (8). The compressor intake has to be located in an area where there is minimal contamination
from internal combustion engine exhaust or other sources of organic vapours. Check that the correct start-up
procedure is followed. This procedure is described in detail in this instruction book (chapter 5.2).
Consult Atlas Copco customer centre for more information.
DD/PD filter
To protect the activated carbon element, the QDT filter must always be preceded by a DD and PD filter. The
filter should be mounted as close as possible to the point of use of the air.
2920 7090 71 9
Instruction book
DDp/PDp filter
The QDT contains activated carbon which could create dust. Depending of the required purity of the air the
QDT filter must be followed by a DDp or PDp dust filter.
3.5 Options
Oil indicator
An oil indicator is available as an option to control the purity of the air. The oil indicator is a calibrated
measuring instrument, used to detect aerosol-mist levels of oil entrainment that may be present in compressed
air systems. Sensitivity of the indicator is limited only by the total number of hours it is allowed to remain on
the air supply system. The indicator is sensitive enough to measure a concentration of oil entrainment as low
as 0.01 ppm. This sensor will indicate when the cartridge is saturated and has to be replaced. The oil indicator
has a maximum pressure of 8.75 bar (127 psi).
10 2920 7090 71
Instruction book
0.02 units/hr or below 0.002., the measured rate should be divided or multiplied by any factor which will
bring it into the range of the chart. This number should then be used to determine the oil concentration (ppm).
This concentration must then be multiplied by the same factor used previously to determine the actual oil
concentration.
Example:
The Rate of Colour Travel after a QDT filter at 5.6 bar (80 psig [560 kPa]) is found to be 0.5 units/4000 hrs
= 0.000125.
Multiply this rate by 100 (0.000125 x100 = 0.0125 units/hr) to bring it into the range of the conversion chart.
Locate this new rate on the chart, showing a concentration of 0.18 ppm.
Divide this concentration by the previous factor (0.18 : 100 = 0.0018 ppm) to obtain the actual oil concentration
in the air being tested.
Note:
• Multiply ppm by 0.12 to obtain oz/100000 scf
• Multiply ppm by 1.2 to obtain mg/m3
Simplified estimation at 7 bar:
Measure the time needed for 1 unit colour travel Concentration in ppm = 10/Time of one unit of colour travel
2920 7090 71 11
Instruction book
Fit the mounting brackets with bolts, washers and nuts to a solid frame within easy reach, leaving sufficient
space at the top for maintenance and service.
12 2920 7090 71
Instruction book
4 Standards
The ISO 8573-1 (ed . 2010) norm only concerns compressed air for general use and does
not deal with, or is not applicable to, e.g. breathing air.
ISO maximum number of particles per m3 pressure total oil concentration (aerosol,
Class dewpoint °C liquid and vapour) mg/m3
0.1 - 0.5 μm 0.5 - 1.0 μm 1.0 - 5.0 μm
0 as specified by the equipment user or supplier and more stringent than class 1
1 20000 400 10 -70 <0.01
2 4000000 6000 100 -40 <0.1
3 not specified 90000 1000 -20 <1
4 not specified not specified 10000 3 <5
5 not specified not specified 100000 7 -
6 mass concentration: 1 - 5 mg/m3 10 -
Downstream the QDT the total oil concentration will be <0.003 mg/m3 (class 1 for total oil concentration).
For food grade air an ISO class of minimal 2.2.1 is needed.
The QDT reduces the total oil content down to class 1. When followed by a PDp dust filter, the dust
concentration will also be according this regulation.
A desiccant dryer will be needed to reduce the dew point down to -40 °C.
2920 7090 71 13
Instruction book
14 2920 7090 71
Instruction book
5.1 Service
Change the QDT filter element yearly or every 4000 hours, whichever comes first. Its
pressure drop will not increase during its useful life. Nevertheless, the adsorption element
must be changed earlier at the first signs of oil vapour and odour.
When the filter has to process air with a temperature higher than the reference temperature, the filter’s lifetime
will reduce considerably. It is then advisable to oversize the filter.
The air flow of the filter is from the top to the bottom of the filter. Due to the composition of the activated
carbon element, the bag must be placed with the knot at the top of the bag.
If an oil indicator is mounted, the purity of the air is measured. When the indicator shows a fast increase of
oil content in the air, the QDT filter element and the indicator tube have to be replaced.
5.2 Procedure
A small amount of acid-free vaseline may be applied to screw threads and o-rings to facilitate the assembly
1. Isolate the filters from the air net.
2. Depressurize the QDT filter by means of the DD or PD filter drains.
3. Uncouple the pipe at the inlet with the flange.
4. Unscrew the head.
5. Remove the spring and the perforated plate.
6. Remove the filter bag.
2920 7090 71 15
Instruction book
16 2920 7090 71
Instruction book
6 Technical data
2920 7090 71 17
Instruction book
Ambient temperature. higher ambient temperatures could contain more oil vapours and need a higher
correction.
Some environmental aspects could cause a higher amount of oil or volatile organic compounds in the air due
to processes with organic solvents/oils nearby. Contact Atlas Copco when higher concentrations can be
expected.
Add both concentrations together and determine the oil correction factor in the table below: (Oil area + oil
compressor)
total oil (mg/m3) correction factor total oil (mg/m3) correction factor
0.13 0.6 0.8 1.9
0.2 0.7 0.9 2.1
0.3 0.9 1 2.3
0.4 1.1 1.2 2.7
0.5 1.3 1.4 3.1
0.6 1.5 2 4.3
0.7 1.7 2.5 5.3
18 2920 7090 71
Instruction book
This correction is than again corrected for the pressure in the system. To calculate the total correction, the oil
correction factor is multiplied with the pressure correction.
Pressure 1 2 3 4 5 6 7 8
(bar)
Factor 5.00 2.00 1.75 1.30 1.20 1.00 1.00 1.00
Pressure 9 10 11 12 13 14 15 16
(bar)
Factor 1.00 0.95 0.95 0.90 0.95 0.80 0.75 0.75
Examples
Example 1:
The QDT filter is placed downstream an oil lubricated compressor installed in a warehouse where the
temperature is kept at 20 °C.
The compressed air temperature before the QDT filter is 35 °C.
The filter is operated at 7 bar and 44 l/s (= compressed air flow)
Maximum total oil content: 0.1+0.25 mg/m3 -> oil correction factor for 0.35=1
and the pressure correction factor: at 7 bar = 1
Total correction is 1x1=1, thus for 44 l/s an QDT 45 is recommended
Example 2:
The QDT filter is placed after an oil lubricated compressor which is situated in a room where the temperature
is 25°C, due to processes.
The compressed air temperature before the QDT filter is 40°C.
The filter is operated at 5bar and 60 l/s
Maximum total oil content: 0.15+0.4 mg/m3 = 0.55 mg/m3 -> oil correction factor =1.4
Pressure correction factor: at 5 bar = 1.2
Total correction is 1.4 x 1.2 = 1.68, thus for 60 l/s the total calculation would give a value 101.
Possible options are QDT 95 and 125.
Selecting an oversized QDT 125, the filter would give the best guarantee for a lifetime of 4000 hours and the
lowest pressure drop.
It is advised to never underrate the filter. By selecting an undersized QDT 95, the element has to be replaced
before 4000 hours and the pressure drop could also exceed its limitations.
2920 7090 71 19
In order to be First in Mind-First in Choice® for all your quality
compressed air needs, Atlas Copco delivers the products and
services that help to increase your business’ efficiency and
profitability.
Atlas Copco's pursuit of innovation never ceases, driven by our
need for reliability and efficiency. Always working with you, we are
committed to providing you the customized quality air solution that
is the driving force behind your business.
www.atlascopco.com