Signalling in Railways
Signalling in Railways
SIGNAL ENGINEERING
MANUAL
VOLUME 2
JULY 2020
भारत सरकार
GOVERNMENT OF INDIA
रे ल मं ालय
MINISTRY OF RAILWAYS
भारतीय रे ल
सगनल इंजी नयर नयमावल
भाग – 2
INDIAN RAILWAYS
SIGNAL ENGINEERING MANUAL
VOLUME 2
MOHAN
cedffd46, postalCode=500017, street=IRISET TARNAKA ROAD, ou=S AND T,
JULY 2020
o=I R I S E T, cn=CHALAMALASETTY MOHAN
Date: 2020.07.11 15:15:42 +05'30'
Digitally Signed
Director / IRISET
Signal Engineering Manual Issue History
Chapter Section /
Chapter Name Page No.
No. Annexure
14 LC Gates
Section 1 LC general 22
Section 2 Installation of LC gates 27
Section 3 Maintenance of LC gates 30
Annexures
Annexure 14/1 Safety measures to be provided at Level Crossings 33
Annexure 14/2 Maintenance schedule of Level Crossing & Sliding Boom 36
15 Cables
Section 1 General 38
Section 2 Installation of Cables 41
Section 3 Cables and Cables Laying in RE Area 43
Section 4 Insulation Testing 44
Section 5 Maintenance of Cables 45
Annexures
Annexure 15/1 Maintenance schedule of Cables 47
Annexure 15/2 Maintenance schedule of Earth Leakage Detector (ELD) 52
Annexures
Annexure 23/1 Maintenance Schedule of Train Protection & Warning 293
System (TPWS)
Annexure 23/2 Maintenance Schedule of Train Collision Avoidance 294
System (TCAS)
Annexure 23/3 Maintenance Schedule of Auxillary Warning System 296
(AWS)
Annexure 23/4 Maintenance Schedule of Centralized Traffic Control 297
(CTC)
Annexure 23/5 Communication Based Train Control (CBTC) 299
CHAPTER - 13 : DATALOGGERS AND PREDICTIVE
MAINTENANCE SYSTEMS
Section 1: Dataloggers
13.1.1.0 Purpose: Remote monitoring of indoor equipments
(b) To aid the maintenance staff by providing health data at central location.
(f) Wherever Potential free contacts are available for any signalling equipment like
SPD, fire detection system, etc the same can also be monitored through Data
logger.
(g)Fire detection system alarms, Relay room door opening, SPDs health indication
potential free contacts etc.
(a)The Data Logger system shall perform the following 4 functions; (i) Monitoring
the equipment and data (ii) remote monitoring at central place (iii) generation of
alarms (iv) Generation of sms
(c) The system shall chronologically monitor and record the status of various field
functions like track circuits, points & signals through their indoor repeater relays,
operator’s push buttons/switches (digital Inputs) and level of various analog
signals like DC and AC supply voltages.
(d) It shall be capable of receiving both Digital Inputs & Analog Inputs at regular
intervals by scanning them for change of state/Values
(f) The system shall be suitable for working on non-electrified, AC electrified areas
(i) The monitoring of signalling installation may also be done at LC gates, auto
signal goomties and IB Signal Huts using Remote terminal unit which shall be
connected to Datalogger system through suitable communication media.
(a) For monitoring digital inputs, potential free contacts shall be used. Analog
signals shall be connected directly to Datalogger which in turn will convert to digital
data for further processing.
(b) The data logger shall have built in Real Time Clock for time stamping the
receipt of a particular information.
(c) Synchronisation with IRNSS Clock or any Satellite Based approved clock is
required for clock synchronisation with the network
(d) Existing telecom services shall be used to send alerts to required staff.
(a) Data Logger shall be capable of working with different transmission media like
underground telecom cable, microwave (Digital or Analog) & OFC. The modem
can be either in-built or external. The external modem will be housed within the
data logger cabinet.
(b) It shall be possible for networking and remote monitoring of several data
loggers from the central location. All features like on-line Simulation, Off-line
simulation, failure management, exception logics and Synchronization should be
feasible from the central location.
(iii) Axle Counters - Track Sensing Device - Voltage, Current, and Vibration at
the Rail end, EM field, Moisture / Humidity. The maintenance data as made
available by the MSDAC/ SSDAC should also be acquired by the system.
(iv) Signals -Voltage, Current, vibration, humidity, wind in the signal unit/
location box
(v) SPDs - EM Fields, Health of each of them using digital inputs from it,
(vi) IPS - Indoor Potential fee contacts, Diagnostic data given in soft form
(viii) Relays - Same as being done with present system of Data Loggers
(xi) Signal & Power Cables : Current and Voltage sensors, Earth Leakage
sensors, Seismic/ OFC based Acoustic for preventing damage to cables
etc.
b) The remote Analog signals shall be scaled to a suitable limit using signal
conditioner before converting to digital signal. Each analog input shall be
isolated (at least 2KV isolation voltage) from the system and one another.
While tapping analog input, it shall not load the analog channel/ field gear
by more than 5ma. DC & AC analog currents shall be measured with
suitable calibrated sensors which provide galvanic isolation to the source
being monitored.
c) Collect: The Main unit of RMPMS must have MQTT (Message Queuing
Telemetry Transport) protocol installed to stream in data over cloud
e) Cleanse and filter – Tools to define functions may be used and triggered
when IoT Analytics detects missing data, so that it can run code to
estimate and fill gaps. It can also define max/min filters and percentile
thresholds to remove outliers in streaming data. Shall be implemented to
discard data arising due to train movement or any other hardware
malfunction.
g) Store - Time-Series Data Store - IoT Analytics may stores the device data
in an optimized time-series data store for faster retrieval and analysis. It
can also manage access permissions, implement data retention policies
and export data to external access points. Store - Processed and Raw
Data - IoT Analytics may store the processed data and also automatically
stores the raw ingested data so that it can be processed at a later time.
h) Analyze to Run Ad-Hoc SQL Queries - IoT Analytics may provide a SQL
query engine so that can run adhoc queries and get results quickly. For
example, might run a quick query to find the number of fail prone gears for
each station.
i. Time-Series Analysis - IoT Analytics may supports time-series
analysis so that can analyze the performance of devices over time
and understand how and where they are being used, continuously
monitor device data to predict maintenance issues, and monitor
sensors to predict and react to environmental conditions.
ii. Hosted Notebooks for Sophisticated Analytics and Machine
Learning - IoT Analytics may include support for hosted notebooks
like Jupyter Notebooks etc for statistical analysis and machine
learning. The service may includes a set of notebook templates that
contain authored machine learning models and visualizations to
help you get started with IoT use cases related to device failure
profiling, forecasting events such as low remaining life that might
signal the maintainer to replace the gear, or segmenting devices by
rest remaining life levels or gear health.
IOT shall support SNPM or OPC-UA via HTTPS/ SOAP. The following shall be
the media between various devices.
a) For communication from IoT device (in station yard near point, signals and
other equipments) to Gateway at station
(i) Wireless media on LoRA (or Zigbee or any open source technology) in
free band of wireless spectrum.
(ii) WLAN
b) For communication from outdoor type IoT devices (for field gears like
signal, point, track circuits, etc) to Gateway at station, the wireless
connectivity is mandatory along with optional Fiber connectivity (Type LC
connector).
c) For communication from indoor type IoT device (for IPS, Axle counter
evaluator, Data logger, etc) to Gateway at station – RJ45 (copper) and/or
LC port (Fiber) shall be provided.
13.3.12.1 The AI/ ML algorithms should be as per ISO/IEC JTC 1/SC 42 standards. The
system shall provide predictive maintenance and optimization with the help of
advanced analytics, Machine Learning and Data visualization. Prediction of
Equipment / Asset Failure, SMS alerts to the concerned SSE’s mobile number
and ticketing application for event failure attending. Application should be
backed by intelligent health monitoring algorithms for gears using machine
learning algorithms to predict the equipment failure or errors. It is expected that
accuracy of predictive alerts should be better than defined levels after one year.
(a) Machine Learning algorithm should be able to suggest and predict defects,
device failure and remaining useful life (RUL). Alert generation in case of
variation in parameter readings based on Threshold set.
(b) It is desirable that Cloud and AI shall be based on open source platforms
and AI algorithms developed shall have IPR of Indian Railways. There shall
be no propriety of industry partners on the intellectual property so emerged
(c) The AI techniques shall have two versions, one edge device/local server
version and second cloud based. During initial development of system, the
supervised machine learning will be required and slowly it will switch to
unsupervised machine learning using Artificial Intelligence.
(e) Local Server Based Analytics: Following types of analysis may be made
available
(i) Generate alerts about device failure and remaining useful life (RUL).
Alert generation in case of variation in parameter readings based on
Threshold set. Using advanced analytics algorithms and machine
learning techniques the system should be able to suggest and predict
defects with specified accuracy, improving upon it with passage of time
as per learning tools within time period as specified in RDSO
specification.
Note :- This Chapter has under mentioned Annexures for further study
3 Point bobbing RDSO The time difference of (NWKR/RWKR) (UP to DN to UP) is in M 59 NWKR Point
between 500 msec. to 2 sec which should be taken as 1 Bobbing
count and for satisfying the fault logic 2 to 3 counts should
happen within 10 sec. At that time TPR is UP
4 Point Failure RDSO 1. If NWKR, RWKR both are down for more than time interval M C (120 59 Point Failure
then it is point failure. Sec)
2. In case of siemens-WKR1 is Down for more than the
given time interval
5 Sluggish Operation of RDSO 1. In case of siemens --- The time difference between WKR1 M 51 NWKR Point
Point Down to Up is in between the set time interval. Sluggish
2. Other than siemens --- time interval of NWKR down to Operation
RWKR up OR RWKR down to NWKR up is more than set
time.
6 Track Circuit Failure RDSO T1,T2,T3 are sequential tracks, M C (120 51 TPR Track
a) When T2 is DN. Sec) Circuit Failure
b) T1 and T3 UP.
c) The time difference between T1 UP and T2 DN is more
Page 10 of 301
Datalogger Fault Logics – An Example Annexure 13/1
Moment Confir Example of Fault
Fault name Ref: Fault Information
ary med message
than 5 sec
d) The time difference between T3 UP and T2 DN is more
than 5 sec.
e) T2 is not bobbing and is DN for more than 10 sec
7 Fusing of Signal lamp RDSO When 110 v supply to signals has not failed (i.e. analog M C (120 S1 HHG Fusing
voltage value is used in fault logic) Sec) of Signal lamp
a) Yellow (three aspect):- After HR picks UP and DR is
DOWN, if HECR is not picked UP within 10 seconds. HR is
triggering signal
b) Green (three aspect):- After HR and DR pickup if DECR
has not picked UP within 10 seconds.HR and DR is
triggering signal.
c) Red:- After HR/DR is DN, if RECR has not picked UP
within 10 seconds .HR/DR is triggering signal
d) Yellow/green (two aspect):- After HR/DR picks UP, if
HECR/DECR has not picked UP within 10
seconds.HR/DR is triggering signal.
8 Signal Blanking RDSO When 110 v supply to signals has not failed and all ECRs are M C (120 S1 Signal
down ( i.e. analog voltage value is used in fault logic) Sec) Blanking
9 Signal Flying back to RDSO When RECR is up continuously for more than 2 seconds - in M C (120 S1 Signal Flying
danger that condition if UCR/LR/U(R)S is up and HR/GR2 is down Sec) back to Danger
and signal replacement track(TPR) is up and EGGNR down,
then it is Signal Flying back to danger.
10 Timer setting more RDSO The TIME difference between JSLR UP and NJPR UP is M S1 Timer setting
greater by more than 10% (more than 132 seconds for 120 More
seconds timer) of the prescribed time
Page 11 of 301
Datalogger Fault Logics – An Example Annexure 13/1
Moment Confir Example of Fault
Fault name Ref: Fault Information
ary med message
11 Button stuck up Button relay is up for more than specified time 20 sec C 101 WNR Button
Relay Stuck Up
12 Point Loose packing RDSO In Between two sequential TPRs Down to Up (To ensure it is C 59 Point Loose
train movement) if the status of NWKR or RWKR Changes Packing
more than 2 times and status of EWNR not changed
(Point emergency operation not done) then it is Loose
Packing.
13 Signal bobbing without If HR/DR is up and HECR/DECR changes its status from Up M S1 HECR Signal
design problem (i.e signal to Dn to Up is in between 500 msec to 2 Secs and Bobbing without
control relay not dropped) HECR/DECR is not operated along with HR/DR then it is Sig Design Problem
Not Applicable Bobbing without design problem. ECR is
triggering sig Not Applicable
14 Signal bobbing with If HR/DR is up, HECR/DECR changes its staus from Up to M S1 HECR Signal
design problem (i.e signal Dn to Up is in between 500m sec to 2 Secs and Bobbing with
control relay dropped) HECR/DECR is operated along with HR/DR then it is Sig Design Problem
Not Applicable Bobbing with design problem.ECR is
triggering sig Not Applicable
17 Fuse blown off (additional RDSO Additional hardware to be used to detect Fuse Failure C
hardware to be used to
detect fuse failure)
Page 12 of 301
Datalogger Fault Logics – An Example Annexure 13/1
Moment Confir Example of Fault
Fault name Ref: Fault Information
ary med message
18 ELD detected low RDSO Potential free contact of ELD C Earth Leakage
insulation of supply appeared in 110V
(potential free contact of AC Supply, Earth
ELD to be wired as input Leakage
to data logger) disappeared in
110V AC Supply
19 Route not set when RDSO GNR, UNR are Up, EGGNR is dn then after given time C Route Failure
operation is valid giving interval if HR is in down then check the Route.
the sequence of relay
operations
(1.Possible in case of
panels where
button/switch relays pick
up with operation of
button/switch even-though
the operating conditions
are not favourable
2.Sequence of relays shall
be provided by railways
3.Not possible for switch
type non route setting
type panels)
20 Point Burst RDSO If the train arrives on the track2 proving the sequence of M C (120 101 Point Burst
track1 DN and ahead track to point zone track is down, the Sec)
point setting in the unfavourable position and then the
NWKR/RWKR both are DN for 2min.
21 Clearing of signal without RDSO At the time of HR/DR/ HECR/DECR up, signal lock relays i.e C S1 Signal
Route Locking all G(R)LR's/G(R)R/ASR/ALSR in the possible Routes from Cleared without
Page 13 of 301
Datalogger Fault Logics – An Example Annexure 13/1
Moment Confir Example of Fault
Fault name Ref: Fault Information
ary med message
signal are in down state then it is Failure. Route Locking
22 Timer setting Less RDSO The TIME difference between JSLR UP and NJPR UP is C S1 Timer setting
less by more than 10% (less than 108 seconds for 120 Less
seconds timer) of the prescribed time
23 Check for Passing of RDSO a) When track 2 is DN after track 1 is DN and RECR is UP C S1 Check for
danger signal b) The time difference between T2 DN and T3 UP is more Passing of
than 5 sec Danger Signal
c) The time difference between T2 DN and RECR UP is
more than 5 sec
d) T2 is not bobbing and is DN for more than 1.2 sec
SPAD CASES
Page 14 of 301
Datalogger Fault Logics – An Example Annexure 13/1
Moment Confir Example of Fault
Fault name Ref: Fault Information
ary med message
4. Two opposite signals (ex. starter and opposite shunt from
siding) with one track circuit in between and no approach
track circuit for shunt signal -- in starter signal SPAD logic
use shunt GNR/UNR not operated condition or Conflicting
HR Down
24 Route released without RDSO a) ASR UP / G(N)LR Up and C S1 Route
sequential route relays in b) Concerned route TSSLR DN or TPZR DN or TLSR DN or released without
route picking up TRSR DN or UYRs Down or U(R)Ss Up sequential route
c) Emergency route cancellation, NJPR DN, AJTR3 /JR Dn relays in route
picking up
25 Signal assuming green RDSO At the time of DR/DECR is picked up, RWKR in the C S1 Signal
with points in the route corresponding Route are picked up then it is Fault. assuming Green
reverse with 31 Point
Reverse
26 Home/Main line starter RDSO When DR/DECR Of Home/Main Line starter Signal is up and C S1 Home Signal
signal assuming green if the Advance Starter RECR is up the it is Fault assuming Green
with adv starter danger with S2 Adv
Starter Danger
27 Advance starter off HR/DR UP and concerned Line clear relay DN C S2 Advance
without Line Clear starter Off without
Line Clear
28 Over speeding RDSO T1,T2 and T3 are track circuits in M Over Speeding at
sequence. Length of T2 is fed in the 1TPR On Main
logic option line/Loop line
a) Counter starts when T2 goes DN with T1 already DN
b) Counter stops when T3 goes DN with T2 already DN
c) Time interval between (a) and (b) is less than length of T2
divided by maximum permissible speed by more than 10%
29 Failure to set point against RDSO After complete arrival of the train,if the point is not set against C Rear end Point
Page 15 of 301
Datalogger Fault Logics – An Example Annexure 13/1
Moment Confir Example of Fault
Fault name Ref: Fault Information
ary med message
occupied line the line on which the train is received within a pre determined not set against
time.On Double line rear end points and on single line both 01T Occupied
front and rear end points are to be line from S1-S4
consideredNote:1.Implementation of this logic on big yards is
not possible as the options are too many.2. There can be a
case where it is not possible to set the point as all lines are
occupied
30 Relay room opening RDSO If Relay Room Door Relay is Down then it is Relay room C Relay Room Door
(75,76) opened Opened, Closed
Page 16 of 301
Datalogger Fault Logics – An Example Annexure 13/1
Moment Confir Example of Fault
Fault name Ref: Fault Information
ary med message
signal is cleared late compared to set time
37 Premature Operation of RDSO If LCPR Dn before DR/DECR Dn and SR is Up. C Premature
Double line block to TOL Operation of
Block Instrument
38 Late Closure of LC Gate RDSO Possible in case the design of circuit is such that route gets M Late Closing of
locked after operation of the signal before gate closing and LC-131 Gate in
the signal clears as soon as the gate is closed the Route S1-S3
Page 17 of 301
Datalogger Fault Logics – An Example Annexure 13/1
Moment Confir Example of Fault
Fault name Ref: Fault Information
ary med message
43 EMERGENCY SIGNAL If GNR(Input1) is Up & EGGNR(input2) is Up then it is OM S1 Emergency
CANCELLATION Emergency Signal Cancellation. GNR, EGGNR are Signal
triggerings Cancellation
44 POINT REPEATED In Between WNR(input1) Up to Up, if NWKR(input2), OM 13 NWKR Point
OPERATION RWKR(input3) are not Up then it is Point Repeated Repeated
Operation. WNR is triggering (or) In between NCR/RCR up Operation
to Down if Point(NWKR/RWKR) is not set then it is Point
repeated operation, NCR/RCR (Down) triggering
45 PANEL FAILURE DUE All RECR's(Confilcting signals) are down then it is Panel MM Panel Failure Due
TO AC POWER FAILURE failure due to AC Power Failure. All are triggering inputs to AC Power
Failure
46 PANEL FAILURE DUE All ASR's(Conflicting signals) are down then it is Panel failure MM Panel Failure Due
TO DC POWER FAILURE due to DC Power Failure. All are triggering inputs to DC Power
Failure
47 Shunting with permission When RECR(input1) is Up and TPR1(input2), TPR2(input3) MM S1 Shunting with
are Down, TPR3(input4) is Up and time difference between Permission
TPR2 Down (triggering) and TPR3 Up is more than time
T1,and the time difference between TPR2 Down and RECR
Up is more than the given time interval T1, TPR2 is
continuously Down for T2.,SHKR Down status considered in
extra variable.
48 SPAD at adv str without When RECR(input1) is Up and TPR1(input2), TPR2(input3) SC S1 SPAD at adv
shunt permission are Down, TPR3(input4) is Up and time difference between str without shunt
TPR2 Down (triggering) and TPR3 Up is more than time permission
T1,and the time difference between TPR2 Down and RECR
Up is more than the given time interval T1, TPR2 is
continuously Down for T2.,SHKR Up status considered in
extra variable
49 IPS Failure RDSO DC-DC Converter, Inverter-1,2,3....,SMPS, CALL S& T, 50% MC (120s IPS Failure
Page 18 of 301
Datalogger Fault Logics – An Example Annexure 13/1
Moment Confir Example of Fault
Fault name Ref: Fault Information
ary med message
DOD, MAINS FAIL, FRFC FAIL ec)
50 IPS Restored RDSO DC-DC Converter, Inverter-1,2,3....,SMPS, CALL S& T, 50% MM (120s IPS Restored
DOD, MAINS FAIL, FRFC FAIL ec)
51 TFR Relay Stuckup IF TFR IS PICKED UP THEN IT IS TFR RELAY STUCKUP MM
52 Wrong operation If Buttons (GNR,UNR) are pressed in wrong combination MM S1-S2 Wrong
Then it is WRONG OPERATION. both are triggering signals Operation
53 Route not Released RDSO At the time of Point zone track(input1) Up, if Platform MM S1-S2 Route not
track(input2) Down, Before Point zone track(input3) Up and Released
after time interval if G(R)LR(input4) is Up then Check the
following. Backlock tracks are in Up state and G(R)LR is Up.
If any of above relays are not in required state then it is Fault.
Point zone track is triggering
Page 19 of 301
Maintenance Schedule of Datalogger Annexure : 13/2
Schedule Code : DL1
Periodicity : Signal Technician : Monthly
Sectional JE/SSE : Quarterly
Incharge SSE : Half Yearly
S.No. Check the following
1. Data logger free from rust, dirt & all the connectors & PCBs (Cards) in the main
Euro rack inserted properly & all screws of cards tightened.
2. All cable terminations (Analog, digital input) are tightened & properly connected.
4. FAS (Fault Analysis System) free from dust & ensure proper connectivity with data
logger.
5. Check LED position of both side of modems.
a) CD, CTS-LED should continue glow & -In normal condition.
b) TD & RD LED should blink (flickering)- In normal condition . i.e. data is
getting transferred. If LED status is different then reset modem by pressing
reset button or supply switching.
c) If LED status is different then reset modem by pressing reset button or
supply switching.
6. Reading of all cells of data logger battery bank voltage when charger is in on
position. Switch off charger & Data logger load takes on battery bank about 30
minutes then measure all cells voltage.
7. Measure all analog & Digital supply input voltage in Datalogger with true RMS
meter then compare all this voltage with FAS (Computer) voltage reading. The
variation of both reading is under +/- 5% for accuracy.
8. Measure working voltage of data logger unit. It should be in permissible limit as
given below.
a) Between 11.4 V to 12.6 V if Datalogger model was 90/98.
b) Between 22.8 V to 25.2 V if Datalogger model was 99/01 and 99/06.
Schedule Code : DL2
Periodicity : Sectional JE/SSE : Half Yearly,
Incharge SSE : Yearly
1. Measure the communication channel (OFC) loss with Telecom staff & it should not
be more than 25 dB between two modems of data logger.
2. Ensure that latest NMDL software (i.e. software used for network management in
Datalogger) & test room yard layout, fault updated in FAS (Computer) at site & all
NMDL utility programs (Reports, Simulation, track off etc.) running smoothly.
3. Check Induced voltages:
a) Voltage between the communication cable conductor and earth shall not be
more than 5V AC.
b) Voltage between the two conductors of communication cable shall not be
more than 1V AC.
Schedule Code : DL3
Page 20 of 301
Maintenance Schedule of Datalogger Annexure : 13/2
Periodicity : Sectional JE/SSE : Yearly,
Incharge SSE : Yearly
1. Measure the earthing resistance & it should be less than 1 ohm.
2. Check & ensure that data Logger validation register is kept at each station and
details of potential free contacts of digital & analog inputs must be tallied with
NMDL at DLMC office.
Schedule Code : DL4 (only for SSE/DLMC)
Periodicity : Incharge SSE : Yearly
1. Checking of all type of exceptions reports (As per RDSO) generated by data
logger & analysis of the reports for reliability of Data logger.
2. To check & ensure that temperature of relay room & Datalogger is shown in
NMDL.
3. Ensure that DL-1 & DL-2 shall be followed for FEP, CMU & Server unit at DLMC
office.
Page 21 of 301
CHAPTER 14 : LC GATES
Section-1 : LC General
14.1.1.0 Gate Signals : This chapter shall be read in conjunction with chapter III and
Chapter XVI of General Rules.
14.1.2.0 A Gate Stop Signal shall be fixed at an adequate distance from the gate, this
adequate distance not being less than the value stipulated in Para. 14.1.4.1
and 14.1.4.2.
14.1.3.0 The Gate Stop Signal shall be provided with ' G ' marker except where
prohibited under special instructions.
The ' G ' marker shall consist of letter ' G ' in black on yellow circular disc. The
instructions in Chapter 20, section 1 shall apply to signals protecting level
crossing gates in automatic block territory.
14.1.4.1 On sections provided with two aspect Signaling, a Stop Signal at 400 metres
from the gate shall be provided. Where the section is otherwise provided with
separate Warner signal, such a signal shall be provided at a distance of not
less than 1.2 km. from the Gate Stop Signal.
14.1.4.2 On Sections provided with multiple aspect signalling, a Stop Signal at not less
than 180 meters (120 m in case of automatic signalling Or suburban sections)
from the gate and a Distant/Inner Distant signal shall be provided at not less
than 1 km in rear of the Stop Signal shall be provided.
14.1.5.0 Interlocked Level crossing gates inside station limits or in the vicinity :-
(a) The Outer Signal shall be located at a minimum distance of 400 meters
from the gate
(b) Where the Outer Signal cannot be so located and the Outer Signal falls in
between Home Signal and Gate, a separate Gate signal may be located at a
distance of 400 meter in rear of the gate
(c) Where there is adequate visibility of the Outer Signal (1.2 km if sectional
speed is 100 kmph above and 0.8 km if sectional speed is less than 100
kmph) the Gate Signal shall work independent of the Outer Signal
(d) Where the visibility of Outer Signal is not adequate, the Outer Signal shall
be shifted and combined with the Gate Signal where feasible or inter-slotting
arrangement shall be provided between the Outer Signal and the Gate Signal.
14.1.5.2 On sections provided with Multiple Aspect Signaling when the interlocked
Chapter – 14 : LC GATES
Page 22 of 301
gates are situated between distant and Home Signal:
(a) The Gate Signal shall be located at not less than 180 meter (120 mts in
case of automatic signalling or Suburban sections) in rear of the gate.
(b) The Distant Signal shall be located at not less than one kilometer in rear of
the Gate Signal which shall function as Gate Distant as well and where the
sectional speed is more than 110 kmph, another Distant signal shall be located
at not less than 2 km in rear of the gate signal in second distant territory.
14.1.6.1 Level Crossing gates in automatic sections shall be worked by lifting barrier
gates operated mechanically or electrically and shall be interlocked with
signals. The gates shall be both approach locked and back-locked by track
circuits/Axle Counters. They shall also be provided with audible warning on
both sides of the road, actuated by approaching trains. In addition, road-
warning lights shall be provided on both sides of the road, which will be lit
when there is any train on the approach or whenever the gate is not in the
open condition.
14.1.6.2 (a) The approach locking shall be effective from the moment the train occupies
the track circuit in rear of the signal, which assumes clear aspect when the
Gate Signal is taken 'OFF' and the back locking shall be effective until the train
clears the level crossing. The audible warning (For Road Users) shall stop as
soon as gate is closed and locked but the Red warning light (for road users,
where provided) shall be displayed till the gates are re-opened for traffic.
(b) Approach locking should be effective from a distance not less than braking
distance required for maximum permissible speed on that section.
14.1.6.3 The audible and visual train approach annunciation shall be such that the
Gateman gets adequate warning time, which shall be a minimum of 60
seconds for the train with maximum permissible speed, for closing the level
crossing gates before the train approaches within the sighting distance of the
relevant gate signals.
14.1.7.0 Approach Locking & Back Locking at other than Automatic/ Suburban
sections
14.1.7.1 Approach locking should be effective from a distance not less than the
Maximum Emergency braking distance of the trains running on the section at
the maximum permissible speed on the ruling gradient.
Where there are no track circuits in the rear of the Gate stop signal or the
total length of such track circuits in rear of the Gate stop signal is less than the
braking distance, then Dead approach locking of 60 seconds shall be provided
14.1.7.2 Back locking of LC gate: If Gate is located beyond stipulated distances (i.e if
a gate situated of more than 180 m in Multiple Aspect Signalling and 400 m in
Chapter – 14 : LC GATES
Page 23 of 301
Two Aspect Signalling in advance of the controlling Gate Signal), and
continuous Back lock Track Ciruits/Axle Counters are not provided , then an
arrangement for back locking of Gate to keep it in closed condition till Passage
of train, proved either through two sequential track circuits /Axle counters or
through a time delay of 30 seconds in automatic sections/suburban area and
60 seconds in other sections (Time reckoned from Replacing Gate signal to
most Restrictive aspect, after passage of train) or any other approved means
shall be provided
(a) Special class... for roads having TVU greater than 50,000
(b) A Class... for roads having TVU between 50,000 and 30,000 or Line
capacity utilisation 80% (on single line section) and number of road vehicle
more than 1000.
(c) B Class - B1, B2 having TVUs between 30000 and 20000 and road vehicle
greater than 750
(d) C Class All other Level crossings for road not covered in above classes
Note :- Please refer to IRPWM & other Engg. Dept`s notifications on latest
norms.
14.1.9.1 NON- INTERLOCKED GATES : These gates may be in the form of lifting
barriers or swing /movable gates of approved design . These gates are
installed and maintained by engineering department. Communication
equipments of approved type are provided at such manned gates by S&T
department.
Chapter – 14 : LC GATES
Page 24 of 301
14.1.9.3 ENGINEERING GATES : Gates beyond the outermost stop signals are called
Engineering gates and are manned and operated by Engineering staff. These
gates may be non- interlocked or interlocked with signals
14.1.9.4 TRAFFIC GATES : Gates located between the outermost stop signals are
called Traffic Gates and are manned and operated by Traffic staff. These gates
shall be interlocked with station signals.
14.1.12.0 The working instruction in the form of Gate Working Rules, including the gate
working diagram at Interlocked Engineering Level Crossing gates equipped
with gate signals, shall be provided at the gate lodge. A copy of the working
instruction shall also be kept at the controlling station and shall form Appendix
of the Station working rules (Appendix A) of the station controlling the Level
Crossing gate. These instructions shall be provided in English and Local
language.
14.1.14.0 Safety measures for different classes of level crossings such as interlocking
with signals, provision of telephone communication and approach warning
arrangement shall be as per Annexure-14/1
14.1.15.1 Norms as notified from time to time by Rly Bd shall be followed for Interlocking
of Gates and Essentials of Interlocking given in chapter 7 shall be followed.
14.1.15.2 Where interlocked level crossings within station limits are operated from a
place other than the place of operation of the signal protecting the gate,
arrangements of interlocking should be such that the last operation before
taking off the signal should be the closing of the gate and the first operation
after the train has cleared the level crossing and the signal has been put back
to 'ON' position, should be the opening of the gate by the Gateman
14.1.15.3 Approach locking and back-locking shall be provided on the control lever of the
interlocked level crossings situated on sections provided with automatic
signalling. The approach locking shall be effective from the moment the train
occupies the track circuit provided at braking distance in rear of the gate signal
and the back-locking shall be effective until the train clears the level crossing.
Chapter – 14 : LC GATES
Page 25 of 301
14.1.16.0 Communication between the Gate-lodge and the Station Master's Office/
cabin man
14.1.16.2 The communication of Gateman should be directly with local ASM and also
with CTC where ever provided.
14.1.18.2 Emergency Sliding Booms shall be provided at all interlocked gates to work
trains on signals in case of failure of lifting barrier. In case of Sliding Boom,
normal aspect of signals as per interlocking may be provided during use of
Sliding Boom Barrier with following arrangements.
14.1.18.3 Fixing of Emergency Sliding Boom shall be outside lifting barrier to ensure
safety of road users & trains. Painting scheme of sliding boom shall be same
as lifting barrier.
14.1.18.4 Sliding Boom should be directly locked by ‘E’ type lock or by any suitable
means.
14.1.18.5 Stop indicator Board (Retro reflective type) shall also be provided on
Emergency Sliding Booms. Also road signal if provided shall display ON
aspect to avoid confusion to road traffic.
14.1.18.6 E-type locks of same ward (matching with working lifting barrier) should not be
used in sliding boom type.
14.1.18.7 When level crossing gate has failed in closed condition: An Emergency
key shall be provided at the gate lodge at all interlocked gates and shall be
kept in "EKT sealed box with pad lock", to enable Gate man to open the gate
and allow road traffic in case of failure of lifting barrier to open. EKT contact
shall be proved in Data logger/RTU and SMS alert to be sent to concern
staff/officer.
14.1.18.8 Counter should be provided for logging gate man extraction of emergency key
to open LC gate.
Chapter – 14 : LC GATES
Page 26 of 301
14.1.18.9 Record of use of emergency key shall be maintained in a register with reason.
14.1.18.10 Emergency key IN and OUT contact must be proved in relevant interlocking
circuit so that; Signal shall be taken off only when Emergency key is proved
"IN" and signal Taken OFF must be put to Most Restrictive aspect if
emergency key is taken OUT from EKT.
14.1.18.11 There shall be a facility provided for Gateman to put back Gate Signal to
danger in case of emergency
14.2.19.1 At stations, it is desirable that level crossings should not be located at fouling
reception, stabling lines and signal overlaps. Berthing track and signal
overlaps. As far as possible, level crossings should be provided at a place,
which gives an uninterrupted view not only to drivers of approaching trains but
also to the road users.
14.2.19.2 Lifting barrier of approved design and drawing shall be installed.
14.2.19.3 Interlocking arrangement at the interlocked gate shall be as per approved plan
and wiring diagram.
14.2.19.4 The minimum distance of lifting barrier from the centre line of nearest track
shall be minimum 3.5 m.
14.2.19.6 Lifting barrier shall have two booms, one each on either side of the track. The
boom of the barrier shall extend across the full width of the road. It shall be
installed perpendicular to the road. In case of wider roads provided with road
divider, provision of two half barriers, each set operated diagonally by a
separate winch in mechanical lifting barrier or operating panel in electric lifting
barrier may be provided. Pedestals should be outside the road.
14.2.19.7 The boom of the barrier shall extend across the full width of the road. It shall
be installed perpendicular to the road
14.2.19.8 The boom rest (stop post) shall be in alignment with the boom. The open
position of the lifting barrier shall be within 80 to 90 deg. from the horizontal
and the closed position shall be within 0 to 10 deg. from the horizontal. Road
user signal shall be provided to indicate whether the gate is closed or open.
14.2.19.9 When the gate is closed to road traffic, clearance between the road surface
level and the boom shall be 0.8 to 1 metre. The road surface level shall be
maintained as per concerned para of IRPWM.
14.2.19.10 The open position of the lifting barrier are specified at para. Above For Electric
Chapter – 14 : LC GATES
Page 27 of 301
Lifting Barrier it should be as specified in the relevant specification.
14.2.19.11 Lifting barrier shall be so installed that it shall be possible to stop or reverse its
movement at any point during operation without damage.
14.2.19.12 At the centre of the boom, the lifting barrier shall be provided with a 600mm dia
red disc having red reflector/ luminous strip facing the road traffic.
14.2.19.13 The boom shall be either painted with 300mm bands of alternate black and
yellow colour or provided with approved type of retro-reflective strips.
Fluorescent or any other approved type of paint shall be used yellow color
14.2.19.19 A gate Working diagram shall be provided at the place of operation for all
interlocked engineering level crossing gates. At all interlocked LC gate having
independent operations of signals, indication panel shall be provided.
14.2.19.20 All relays, batteries, etc. for operation of gate and gate signals shall be housed
in signalling gooty/ masonary structure.
14.2.19.21 Equipment for communication of approved type shall be fixed inside gate lodge
on a wooden or on any other approved type shelf/box at appropriate height
from ground level as space available. The wiring for communication equipment
shall properly secured by adopting best practices.
14.2.19.22 Rumble strip, speed breakers and warning signs to road user shall be provided
by Engineering department as per extant instruction.
14.2.20.1 Power supply for level crossing shall be made available from both UP and DN
AT supply in accordance with para 20713.2 (iii) of ACTM Vol. II (Part I) in
addition to local supply.
Chapter – 14 : LC GATES
Page 28 of 301
14.2.20.2 For interlocking a level crossing in RE area neutral section shall be relocated
wherever minimum distance between gate signals and neutral section is not
available as per para 16.4 and 16.5 of AC Traction Manual (Volume II, Part II)
14.2.21.1 A separate fracture segment shall connect the boom with the mechanism near
the pivot. Fracture segment mounting shall be of such a design that it can be
transported, replaced easily and quickly and in case of a mighty hit shall allow
for the break of the segment without endangering the mechanism itself.
14.2.21.2 Winch for the operation of the lifting barrier shall be located at a place
(including cabin) not exceeding 150 metres from the gate and having clear
visibility of the road.
14.2.21.3 It shall be ensured that while closing the gate, warning bell rings and lamp
bracket also gets turned to give required indication to road users. Alternatively
standard audio and visual signals for road users as required for electric lifting
barriers shall be provided.
14.2.21.4 It shall be ensured that the roller fitted to the rope drum enters the trunnion
bracket and activates the boom for closure/opening.
14.2.21.5 It shall be ensured that Boom locking is effective and it is not possible to lift the
boom by more than 10 degree from closed position.
14.2.21.6 The wire rope shall not be overlap at the winch and rope drums.
14.2.21.7 The guy rod shall be given sufficient tension for smooth operation of the boom.
14.2.21.8 Oil holes, grease nipples, etc. shall be provided with spring loaded covers.
14.2.21.9 It shall be possible to extract the key from the winch only when the gate is fully
closed.
14.2.21.10 At mechanical interlocked gates, interlocking shall be achieved through 'E' type
locks or by approved means.
14.2.22.1 Where reliable power supply is available at any interlocked level crossing
gates (of special class, A, B1, B2 class & C class) in any section , electrically
operated lifting barrier of approved design shall be provided
14.2.22.2 The boom shall be approved type. The metallic type boom shall be segmented
for easy transport, installation and replacement.
14.2.22.3 Operation of the lifting barrier may be provided from a gate control panel or by
Chapter – 14 : LC GATES
Page 29 of 301
any other approved equipment.
14.2.22.6 The boom must be so balanced that in case of failure of power supply, the
barrier shall remain in the position last assumed.
14.2.22.8 Road user signal shall be provided to indicate whether the gate is closed or
open. While closing/opening the Electric lifting barrier, a hooter shall sound
and road user signal shall exhibit flashing red. In closed condition of ELB, the
hooter shall stop and road user signal shall display steady red. In open
condition of ELB, the road user signal shall display steady yellow.
14.2.22.9 At least two types of operations should be provided i.e. Power operation and
Manual Cranking operation. Hand Generator operation type may also be
provided if feasible.
14.3.23.2 Gears, rope drums and wire rope shall be doused with soft grease.
14.3.23.3 Cleaning of rodding and wire transmission should be done properly. Cleaning
of all pipes and ducts to prevent obstruction by accumulation of dirt shall be
ensured.
14.3.23.4 All bolts and nuts shall be tightened and split pins shall be split properly.
14.3.23.6 It shall be ensured that both the booms are parallel in open condition.
14.3.23.10 It shall be ensured that 'E' type lock which locks the winch should also lock
winch handle in closed position of barrier.
14.3.23.11 All gate locking apparatus must be examined regularly and working parts kept
oiled. Gate locks must be kept in good working order.
Chapter – 14 : LC GATES
Page 30 of 301
14.3.23.12 Proper working of audio/visual warning shall be ensured.
14.3.24.1 Machines must be kept in good condition, free from rust, dust and dirt.
14.3.24.2 The bearing surface and moving parts of the electric lifting barrier shall be
lubricated properly
14.3.24.3 Contacts must be kept clean and in proper adjustment. If contact surfaces are
pitted, they must be replaced.
14.3.24.4 (a) Commutator must be clean, smooth and have a bright appearance.
(b) Brushes must be kept clean and properly bedded on the commutator.
Brushes should have proper pressure and should be free in brush holders.
14.3.24.5 Friction clutch must be so adjusted that the same should get de-clutched when
the boom is raised or lowered fully and the power supply is not cut off.
14.3.24.6 The shock absorber at the boom rest (stop post) must be kept properly
adjusted.
14.3.24.7 The time of operation of electric lifting barrier shall not exceed stipulated time.
Measured value of current should not exceed rated values.
14.3.24.8 The satisfactory functioning of the lifting barrier by a hand crank shall be
checked
14.3.24.9 All gate locking apparatus must be examined regularly and working parts kept
oiled. Gate locks must be kept in good working order
14.3.28.0 Communication of approved type, provided between Level Crossing gates and
the adjoining stations shall be checked in regard to their satisfactory
functioning.
14.3.29.0 Heavy repairs, renewals or alterations to gate interlocking must not be carried
out until Jr. Engineer/Sr. Section Engineer (Signal) concerned has arranged for
the protection of the road traffic by the concerned department and the work
Chapter – 14 : LC GATES
Page 31 of 301
shall be carried out under proper disconnection.
14.3.30.0 Sr. Section Engineer(Signal) shall maintain a register indicating details of each
class of level crossing gate in regard to its location, number, type of gate
provided, provision of communication, interlocking arrangement, provision of
approach warning and flash lights etc., pertaining to his section. A statement in
regard to the above should be submitted on first January and first July every
year, to the Sr. Divisional Signal and Telecommunication Engineer/Divisional
Signal and Telecommunication Engineer.
Chapter – 14 : LC GATES
Page 32 of 301
SAFETY MEASURES TO BE PROVIDED AT LEVEL CROSSINGS : Annexure 14/1
Spl.
A Class B1 Claass B2 Class C Class (Manned) Other Stipulations
Class
TVU-> >50000 >30000 and >25000 and >20000 >3000 Cat I & >2500 Cat II
<50000 <30000 and
<25000
a) Within Should be Should be Should be Should be Should be Interlocked with To minimize the Mean Waiting Time for road
Station Interlocked Interlocked Interlocked Interlocked Station Signals in Suburban users, the arrangement of Interlocking should be
Limits with Station with Station with Station with section, in Automatic Block such that the last operation before taking ‘OFF’
Signals Signals Signals Station signalling. In Non-Suburban of Signal should be the closing of the Gate and
Signals section, all traffic gates should the first operation after the train has cleared the
be interlocked with station signal Level Crossing and the Signal is put back to
or if it has to be interlocked for ‘ON’ position, should be opening of the Gate by
any other reason. the Gateman.
b) Outside Should be Should be Should be Should be Should be Interlocked with Gate i) In case of Level Crossing protected by signal,
Station Interlocked Interlocked Interlocked Interlocked Signals, in Automatic Block where the sighting of the signal by an engine
Limits with Gate with Gate with Gate with Gate Signalling sections. driver is in adequate and the Gate signal is not
pre – warned through other means (Distant
Signals Signals Signals Signals
Signal / Independent Warner Signal / Repeater
Signal etc.), a Warning Board should be placed
at not less than the emergency braking
distance in the rear of the Gate Stop Signal.
The board should be vertical 2000 mm by 450
mm with alternate black and yellow strips 125
mm width painted on it at an angle of 45
degree. The top of the board should be 4 M
above rail level. The board need not be lit at
night but should as for as possible be provided
with scotchlite or other effective light reflectors
or retro- reflective tape.
Page 33 of 301
ii) Where level crossing is situated outside station
limits but in close proximity thereof, the clear
distance between the level crossing and an
outer signal should not be less than the full
train length.
Note: All manned level crossing gates both within and outside station limits falling on suburban sections and Automatic Block Signalling section shall be
interlocked irrespective of the classification / TVUs of the gates
>50000 >30000 and > 25000 and > 20000 and >3000 Cat I and >2500 Cat II
<50000 < 30000 < 25000
c) Normal Shall be normally kept open to Road Traffic If Interlocked, shall be normally
Position kept open to Road Traffic
of Gate
2. Telephonic or any other approved type Communication from the Gate Lodge.
Within or Telephone or any other approved type be provided with ASM’s office with all Manned Level In Block Sections having large number of
outside Crossing Gates. Level Crossing Gates, the connections
Station should be uniformly distributed between the
Limits Block Stations.
Within or Provision of Warning bell or hooter operated by Approach Train at Interlocked LC Gates in suburban section and non-suburban sections be
Outside provided on sections having Automatic Signalling. (Ref. RB’s letter No. 2011/SIG/WP/LC/IR/1 dated 20.02.2013)
Station
Limits
a) Within or Electrically Electrically Electrically Electrically Electrically Operated Lifting In Non-Suburban Section, Electrically
Outside Operated Operated Operated Operated barrier in Sub-urban Section. Operated Lifting barrier be provided, where
Station Lifting barrier Lifting Lifting barrier Lifting Power supply is Reliable.
Limits barrier barrier
Page 34 of 301
5. Approach Locking.
Provision of Warning Bell or Hooter may be provided at all interlocked LC gates for road users which will sound during closing of gate.
Page 35 of 301
Maintenance Schedule of LC Gate & Sliding Boom : Annexure 14/2
Maintenance Schedule of Power Operated Lifting Barrier
Page 36 of 301
Maintenance Schedule of LC Gate & Sliding Boom : Annexure 14/2
Maintenance Schedule of Power Operated Lifting Barrier
to make position once gate is closed and panel push button is pressed.
8. All cable terminations are tight and properly connected.
Schedule Code : LC3
Periodicity : Signal Technician :Quarterly,
Sectional JE/SSE : Half yearly,
Incharge SSE : Yearly
1. Measure the time of operation, working voltage of ELB and operating current.
These records shall be kept in record book. Also ensure all parameter under
permissible limit.
2. The input voltage/Current range of ELB are
For barriers without hand generator
Type Rated Normal (Max.) operating Maximum rated current for
voltage Current/barrier for boom each barrier for boom length
length up to 9.76m up to 9.76m (=10m.)
(=10m.)
AC 110V 2.5 Amps 4.0 Amps
DC 24 V 4 .0 Amps 7.0 Amps
DC 110 V 1.0 Amps 1.8 Amps
b. For barriers with hand generator –
Type Rated Normal (Max.) operating Maximum rated current for
voltage Current/barrier for boom each barrier for boom length
length up to up to 9.76m(=10m.)
9.76m(=10m.)
DC 24 V 3 .0Amps 5.0Amps
DC 110 V 0.7Amps 1.2Amps
3. Checking of NX switch / Crank handle.
4. Balancing of weight & booms
5. Tightening of Screws of ebonite cams of contacts.
Schedule Code : LC4
Periodicity : Incharge SSE : Yearly
1. Proper functioning and interlocking of Sliding Boom.
2. Approach/dead approach locking.
3. Boom is perpendicular to road.
4. Check the resistance of all Limit switch/Circuit controller.
5. Clearance of boom from road (0.8-1m).
6. Boom opening (85-90 degree).
7. Yellow reflector strips on all booms on both sides.
Schedule Code : LC5
Periodicity : Incharge SSE : Yearly
1. Annual testing of tail cable insulation & motor insulation with 100V megger.
Page 37 of 301
CHAPTER 15: CABLES
Section 1: General
15.1.1.0 Railway signalling circuits should normally be carried on cables. For new
works, signalling circuits shall only be carried on cables. In the 25 KV AC
electrified areas, overhead lines shall not be used.
15.1.2.0 Cables used for carrying signalling circuits shall conform to relevant
approved specification. The conductors used shall be of annealed copper
and of approved size.
15.1.3.0 For detailed guidelines, refer Guidelines on signaling cable laying issued
by research, Design & standards organization (document no.
RDSO/SI/G/2010)
15.1.3.1 While planning for cabling on a route, the number of conductors required,
depending upon the circuits should be first determined. Recommended
core sizes as per specifications shall be used.
15.1.3.3 Where a number of cables have been laid along a route, the circuits shall
be so distributed that cables can be disconnected for maintenance
purpose with the least possible dislocation to traffic. Line wise and, if
necessary; function wise cable shall be provided. Auxiliary signals shall
be taken in different cables.
15.1.3.4 After deciding the size and the number of conductors in the different
types of cables to be used on a route, a foot survey along the track
should be done to determine the best route for the cable.
15.1.3.5 The route so planned, shall be shown clearly on a cable route plan
showing the actual alignment of track, giving offsets from permanent way
or permanent structures. The diagram should indicate the various road
and track crossings, crossing with power cables, water and sewage
mains and other points of importance. It is preferable to chart the route on
a route plan on which the existing routes of power cables, etc. are shown.
In case Horizontal Directional Drilling method is used, depth should be
such that to avoid damage to existing cables. Changes if any should be
incorporated in the chart/plan.
Chapter 15 : Cables
Page 38 of 301
15.1.3.7 As far as possible low lying areas, platform copings, drainages, hutments,
rocky terrains, points and crossings, shall be avoided. Proximity to
Electrical Sub Stns / Switching stns shall be avoided.
15.1.3.8 Separate cables of suitable size shall be laid for point operation. It is
desirable to have separate detection for each end of the point.
15.1.4.0 Signalling cables for outdoor circuits should not normally be laid above
ground. In exceptional cases where it becomes unavoidable, the following
precautions should be taken.
(a) The cable should be suspended in wooden cleats, from cable
hangers or in any other approved manner so that no mechanical
damage occurs to the cable even under exposed condition.
(b) The cable supports shall be so spaced as to avoid sag.
(c) In station yards, cable shall be laid in ducts suitably protected.
(d) Indoor signalling cable should normally be laid on ladders,
channels or in any other approved manner. The cables should be
neatly tied/laced.
Note: In AC electrified areas cables shall be laid underground only. For
laying cables in RE area, instructions as laid down in section 3 of this
Chapter shall also be followed.
15.1.5.0 Cables may be laid underground, either in the trench, in ducts, in cement
troughs, in pipes or in any other approved manner.
15.1.6.3 The ducts shall be of such design as to prevent water collecting in the
duct.
15.1.6.4 When cables are laid in rocky area, it is desirable to protect them with
split RCC ducts of suitable design.
15.1.6.5 Where it is necessary to take the cable between the tracks, it shall be
carried in trunking/Duct/pipe kept sufficiently below the ballast level.
15.1.6.6 In block section horizontal directional drilling method may also be used
based on site conditions for the laying of Quad and OFC cables across
the track at sufficient depth to avoid damage due to future work of
doubling etc.
15.1.7.0 Where several cables of different categories have to be laid in the same
trench, they shall be placed as far as possible in the following order
starting from the main track side, so that in the event of failures, the
maintenance staff may easily recognise the damaged cables.
(a) Telecommunication cable
(b) Signalling cable
(c) Power cable
Chapter 15 : Cables
Page 39 of 301
15.1.7.1 At RRI & important Jn. stations, all the main cables shall be laid in
Concrete Ducts from end to end. At other stations, it is recommended to
adopt this scheme between Home signals on either side, to minimise
cable damages due to digging activities by other depts.
15.1.7.2 Where it is not feasible to provide concrete ducts, half Cut DWC-HDPE
pipes of approved type shall be used for Protection of cables.
15.1.7.3 Where it is not feasible to achieve required depth due to rocky soil/other
obstructions, Concreting to be done for protection.
15.1.7.4 Bottom of Trench shall be filled with available River sand or any other soft
material.
15.1.7.5 Each cable shall be distinguished by a identity RFID tags (made of lead
or any other non perishable material) at about 50m spacing with its
numbering embossed to facilitate locating in case of failure. Cable
Termination Drgs. shall show details of cable numbers at each
termination.
15.1.7.6 PCSTEs may issue further detailed procedures for Cable laying.
15.1.8.0 Cables belonging to other department must not be laid in the same trench
along with Signal & Telecommunication cables. A distance of
approximately 10 cm must be maintained between cables of other
department and signalling cables. The signalling cables must be
separated from power cables by a row of bricks or any other suitable
means between them. To avoid nonstandard practice during laying
approval from Sr.DSTE / Dy.CSTE must be taken.
15.1.9.1 Cable drums shall not be stacked on flat side. Suitable stoppers shall be
placed for stability.
15.1.9.2 Cable drums shall have access for lifting and moving.
15.1.9.3 When rolling the cable drum either for unloading or transportation, the
drum shall always be rotated in the direction of the ‘arrow’ which is
marked on the drum.
15.1.9.4 The drums shall not be rolled over objects that could cause damage to
the protective battens of the cable.
15.1.9.5 When unloading is carried out from the vehicle, the drum shall not be
dropped on the ground directly to avoid damage due to impact. Fork lifter
or ramp shall be used.
15.1.9.6 During all stages of storage, it is essential that the ends of the cable are
effectively sealed by end cap or in any other approved manner to avoid
water entry into the cable.
15.1.9.7 It is desirable that cable drums are stored in covered shed to protect
against direct exposure to sun.
Chapter 15 : Cables
Page 40 of 301
Section 2 : Installation of Cables
15.2.10.0 PAYING OUT AND TESTING OF CABLE
15.2.10.1 For paying out cables, the cable drums shall be mounted on cable
wheels. It should be ensured that no kink is formed while paying out the
cable.
15.2.10.2 The drum on the wheel shall be brought to one end of the trench, the end
of the cable freed and the cable shall be laid along the trench.
15.2.10.3 A party of labourers shall move along the trench carrying cable at suitable
intervals so that cable is not damaged due to dragging along the ground
or bent unduly.
15.2.10.4 Before the cable is laid in the trench, a visual inspection of cable shall be
made to see that there is no damage to the cable. It shall be tested for
insulation and continuity of the cores. Thereafter the cable shall be laid
into the trench. Record of Measurements (insulation and loop resistance)
to be maintained.
Note: - It is recommended that at Test Check spots, Video recording of
Trench showing Depth, Nearby Fixed Structures & cable route be done
where ever feasible & such Digital Data shall be preserved in Divisional
Office with appropriate Labelling.
15.2.10.5 In cases where the wheels are not available, the drum shall be mounted
on an axle at one end of the trench and cable paid out and carried by
labourers.
15.2.10.6 In no case, shall the drum be rolled off on to the road for laying the cable
and the cable dragged on the ground for laying purposes.
15.2.10.7 Whenever mechanized equipment is used, the work shall be carried out
by a trained operator under the supervision of SSE/JE(Signal), in charge
of the work.
15.2.10.8 In case of Tunnel, provision of cable duct should form part of the Tunnel
design.
15.2.10.10 Where the cable drum is in damaged condition the cable may be placed
on a horizontal revolving platform and the cable paid out in the same
manner as given in paras above.
15.2.10.11 Paying out of cable should be done by rotating the cable drum and not by
pulling the cable with excessive force.
15.2.11.1 Cables shall be laid generally as per instructions given in this chapter.
However, special precautions to be taken in the station yards etc where a
Chapter 15 : Cables
Page 41 of 301
number of other utilities may be existing, may be detailed in a joint
circular issued by the Civil Engineering, Signalling and Electrical
Department(where applicable) of the Railway.
15.2.12.0 The Main cable laid parallel to the track shall be such that top of the cable
is not less than 0.8 m from ground level. While those laid across the track
shall not be less than 1.0 metre below the rail flanges. However, in case
of rocky soil, the depth may be reduced but protection measures by
means of Concreting / Ducting /Pipe shall be provided. Tail cable shall be
laid such that top of the cable at a depth of not less than 0.5 m. In theft
prone areas the cables may be laid at a depth of 1.2 m with anchoring at
every 10 m.
15.2.13.0 The width of manually made cable trenches should commensurate with
number of cables. The minimum width shall be kept as 0.3 metres. The
bottom of the cable trench should be levelled and got rid of any sharp
materials. In the soft ground, the cable should be laid at the bottom of the
trench previously levelled. In the rocky ground, the cable should be laid
on a layer of sand or sifted earth of 0.05 meter thickness previously
deposited at the bottom of the trench. In both the above cases, the cable
should be covered with a layer of sand or sifted earth of 0.10 meter
thickness and thereafter a protective cover of trough or a layer of bricks
or split DWC pipe of approved design should be placed.
15.2.14.1 When a cable has to cross the track, is should be ensured that-
(b) The cable does not cross the track under points and crossings
15.2.14.2 Wherever practical, the cable may be taken underground across the drain
bed at a suitable depth for crossing small culverts with low flood level,
horizontal directional drilling method may be used where ever feasible.
Chapter 15 : Cables
Page 42 of 301
15.2.16.5 While laying the cables in accordance with the above instructions, the
following instructions should be adhered to for the safety of the track.
(a) Outside the station section, the cables should generally be laid at
not less than 5.5m from the centre of the nearest track.
(b) Within the station section, the trenches shall preferably be dug at a
distance of not less than 3m from the centre of the track, width of
the trench being outside the 3m distance.
(d) Cable is to be laid parallel to the track in the block section with
minimum deviations and on one side of the track.
15.2.17.0 It is desirable that the excavation of the trenches is not done in long
lengths and does not remain uncovered for long period. It is preferable
that cables are laid and refilling done on the same day.
15.2.18.0 Back filling of the trenches should be done properly. The soil excavated
shall be put back on the trench, rammed and consolidated.
15.2.19.0 During excavation, the soil of the trenches should not be thrown on the
ballast. The soil should be thrown by the side of the trenches away from
the track.
15.2.20.0 In places where cables to be laid within 1 metre from sleeper end, digging
beyond 0.50 meter shall be done in the presence of an official from
Engineering Department, and the laying of the cable and refilling of trench
should be done with least delay.
15.2.22.0 The work shall be supervised at site personally by an official of the Signal
and Telecommunication Department not below the rank of a JE/SSE
(Signal).
15.3.23.4 The screened cable, if used, shall be PVC insulated, armored and to an
approved specification IRS S-35.
Chapter 15 : Cables
Page 43 of 301
15.3.23.5 The cable shall be so laid that it is not less than one meter from the
nearest edge of the mast supporting the catenary or any other live
conductor, provided the depth of the cable does not exceed 0.5 meters.
When the cable is laid at a depth greater than 0.5 meters, a minimum
distance of 3 meters between the cable and the nearest edge of the
O.H.E structure shall be maintained. If it is difficult to maintain these
distances, the cable shall be laid in concrete / heavy duty HDPE/Ducts or
any other approved means for a distance of 3 meters on either side of the
Mast. When so laid, the distance between the cable and the mast may be
reduced to 0.5 meters. These precautions are necessary to avoid
damage to the cable in the event of the failure of an overhead insulator.
15.3.23.6 In the vicinity of traction sub stations and feeding posts, the cable shall be
at least one metre away from any metallic part of the O.H.E and other
equipment at the sub station, which is fixed on the ground, and at least
one metre away from the sub station earthing. In addition, the cable shall
be laid in concrete or heavy-duty HDPE/DWC pipes/ Split RCC pipes or
other approved means for a length of 300 meters on either side of the
feeding point. As far as possible, the cable shall be laid on the side of the
track opposite to the feeding post.
15.3.23.7 In the vicinity of the switching stations, the cable shall be laid at least one
metre away from any metallic body of the station, which is fixed in the
ground, and at least 5 meters away from the station Earthing. The
distance of 5 meters can be reduced to one metre provided the cables
are laid in concrete pipes/ heavy-duty HDPE-DWC pipes /ducts or any
other approved means.
15.3.23.8 Where an independent Earth is provided for an OHE structure, i.e. where
the mast is connected to a separate Earth instead of being connected to
the rail, the cables shall be laid at least one metre away from the Earth.
15.3.23.9 Where there are O.H.E structures along the cable route, the cable
trenches shall as far as possible, be dug not less than 5.5 meters away
from the centre of the nearest Track.
15.4.24.1 The insulation resistance tests should be made when conductors, cables
and insulated parts are clean and dry.
15.4.24.2 A 500 V insulation tester should be used for insulation testing. The fact
that the cable has capacitance means that it has to be discharged before
a measurement of the insulation resistance can be made. The insulation
resistance should therefore be recorded after the test voltage has been
applied for one minute or so when the insulation tester shows a steady
reading.
15.4.24.3 Any metallic sheath or metal work of any rack or apparatus case should
be bonded to earth during test.
Chapter 15 : Cables
Page 44 of 301
15.4.24.4 Disconnect all cores of a cable at both ends. The disconnection may be
made through links of ARA /Modular terminals, if provided.
15.4.24.5 Connect one terminal of the insulation tester to the conductor under test
and other terminal to all the other conductors being bunched together and
connected to earth.
15.4.24.6 Similarly test remaining conductors of the cable one by one as in above
Paras
15.4.24.7 Insulation Resistance so measured should not be less than 5 mega ohms
per kilometer at buried temperature, if the insulation resistance is found to
be lower than 5 mega ohms, the cause should be investigated and
immediate steps taken to repair or replace it.
15.4.24.8 Insulation Resistance tests should be made in such a manner that safe
operation of trains is not affected. It should be ensured that no unsafe
conditions are set up by the application of test equipment.
15.4.24.9 All conductors in signalling cables must be tested for their insulation
before commissioning
15.5.25.1 All conductors in signalling cables must be tested for their insulation in
dry weather once in three years provided cables are monitored through
ELD else annually preferably before monsoon as per instructions
specified in section 4. Reading shall be recorded as per the format
mentioned in Annexure ‘15’. Tail cables should be tested for insulation
once a year. A comparison of the test results between successive tests
carried on a cable under similar conditions will give an indication of the
trend towards deterioration of the insulating material over a period of
time. If a sudden fall in insulation is observed, the cause should be
investigated and immediate steps taken up to repair or replace the cable.
Note :- For Maintenance Schedules of Cables , please refer to Annexure
15/1
Chapter 15 : Cables
Page 45 of 301
15.5.25.2 In addition to the regular testing of cables in dry weather, random tests in
wet weather may also be carried out, where considered necessary, to
localise any sudden deterioration in insulation of cables.
15.5.26.0 Earth Leakage Detector (ELD) : The use of this device is desirable in all
electrical signalling installations, such as Route Relay Interlocking, Panel
Interlocking, Centralized traffic control and EI.
Note :- For Maintenance Schedules of ELD, please refer to Annexure
15/2
15.5.27.0 All cables termination devices, pillar boxes, cable heads and glands shall
be kept clean and dry. These parts shall be frequently inspected and any
tendency for moisture or water leak shall be immediately attended to.
15.5.29.0 The protective works provided for the cables at places like track
crossings, culverts, bridges etc shall be regularly inspected by the
maintenance staff, special attention being paid to these protective works
soon after the monsoon.
Chapter 15 : Cables
Page 46 of 301
Annexure : 15/1
Schedule Code : C1
Periodicity : Signal Technician : Monthly, Sectional JE/SSE: Quarterly, Incharge
SSE : Half yearly
S.No. Check the following :
1. All termination at CTR, Location Box, Junction Box and relay room should be
checked for sulphation. Entries of cables in relay room, cable pit, location box
etc. to be checked and should be sealed properly
2. Check for possible rat bite, vulnerability to bush fire / likely damage due to
ongoing works nearby.
3. Visual check of connections, cable armour earthing arrangement in location
boxes.
Schedule Code : C2
Periodicity : Signal Technician : Quarterly, Sectional JE/SSE: Half yearly, Incharge SSE
: yearly
1. Visual check of protective arrangement provided at track crossing, culverts,
bridges, construction site and cable route marker in complete section. Special
attention should be paid to these protective works soon after the monsoon
2. Checking of exposed cable in earth, bridges, duct, Platform, pipe etc. Exposed
cable shall be buried or protected by concreting. Ends of the pipe must be
concreted.
3. Condition of cable pipe to be checked. Cables pipe on bridges to be fastened
properly, bracket to be tightened & fixed. Entries of cables in pipes should be
sealed properly.
Schedule Code : C3
Periodicity : Sectional JE/SSE: Yearly, Incharge SSE : Yearly
1. Verification of cable route plan and ensuring availability of cable route markers.
All missing/damaged cable markers shall be identified and provided Yearly.
Schedule Code : C4
Periodicity : As given in following pages
1. Periodical Meggering of main and tail cables to be done. Periodicity and
procedure described in Annexure B. The results of the insulation resistance
tests should be recorded in performa given in Annexure A.
Page 47 of 301
Annexure 15/1 (Contd.)
1. थानसेतक
6. न कयाहुआ/ न कयाहुआ
Location From....................to....
Type unscreened/screened
2. कोड 1. पीवीसी/रबड़/काग़ज़ वसंवाह
Cores.......................... Insulation PVC/Rubber/Paper
3. आकर 2. सं थापनक तार ख
Size......................... Date of Installation Commisioning
1. ेड 9. नमाताकानाम
Grade 250/440/650/1100V.... Name of Manufacturer
2. ल बाई
Length................................
वा समवाह तरोधओ सम
Insulation Resistance in M.Ohms
प र णक तार ख,
मह नेऔरवष
Date, Month & Year
वसंवाह मू
कोडनं. पदनाम वसंवाह मू य वसंवाह मू य वसंवाह मू य य
Core No. Designation Insulation Value Insulation Value Insulation Value Insulation
Value
1
2
3
4
5
6
7
8
9
10
11
12
अ यिु तयाँ Remarks:
ह ता र Signature:
पदनाम Designation
NOTE: Each conductor shall be meggered with respect to Earth and all other conductors.
Page 48 of 301
Annexure 15/1 (Contd.)
GENERAL
1.1 These instructions apply only to cables used for Railway Signalling and do not cover open line
wires and internal wiring
1.2 Insulation Resistance tests should be made in such a manner that safe operation of trains is not
affected. It should be ensured that no unsafe conditions are set up by the application of test
equipment.
1.3 All conductors in signalling cables must be tested for their insulation at the time of
commissioning and thereafter in dry weather every year preferably during the same part of the
year.
1.4 The insulation resistance tests should be made when conductors, cables and insulated parts are
clean and dry.
1.5 In addition to regular testing of the cables in dry weather, random tests in wet weather may also
be carried out where considered necessary.
1.6 The conductors of the cables possess appreciable electrostatic capacity and may accumulate
electrostatic charge. The cable conductors should be shorted or earthed to completely
discharge any accumulated charge (i) before connecting the insulation tester while commencing
the test (ii) before the insulation tester is disconnected when the test is completed. This is in the
interest of safety of personnel and protection of equipment.
1.7 A 500V insulation tester should be used for insulation testing. The fact that the cable has
capacitance means that it has to be discharged before a measurement of the insulation
resistance can be made. The insulation resistance should therefore be recorded after the test
voltage has been applied for one minute or so when the indicator of the insulation tester shows
a steady reading. (Insulation of all quad cables shall be tested with 100V megger.)
1.8 Any metallic sheath or metal work of any rack or apparatus case should be bonded to earth
during test.
PROCEDURE
1.1 Disconnect all cores of a cable at both ends. The disconnection may be made through links of
ARA terminals, if provided.
1.2 Connect one terminal of the insulation tester to the conductor under test and other terminal to all
the other conductors being bunched together and connected to earth.
1.3 Similarly test remaining conductors of the cable one by one as in 2.2
1.4 Insulation Resistance so measured should not be less than 5 mega ohms per kilometer at buried
temperature. If the insulation resistance is found to be lower than 5 mega ohms, the cause
should be investigated and immediate steps taken to repair or replace the cable to prevent any
malfunctioning of the equipment and circuits.
Page 49 of 301
1.5 The results of the insulation resistance tests should be recorded in approved proforma. A
comparison of test results between successive tests carried out on a cable under similar
conditions will give an indication of the trend towards deterioration of the insulation resistance of
the cable. If sudden fall in the insulation resistance is observed the cause should be
investigated and immediate steps taken to repair or replace the cable.
2) TAIL CABLE
a) For Signal and Track tail cable:
ii) After major work in a yard, all cables should be meggered and cycle at (i) above, will be
restarted.
iii) Spare conductors will be tested every year.
B. Where technology like ELD’s is NOT provided, cable meggering schedule is as under-
1) MAIN CABLE
i) First measurement of insulation of the cable should be carried out after laying of the cable and
after first monsoon for all the conductors.
ii) Thereafter periodical testing of all the conductors including spare conductors should be carried
out every year.
Page 50 of 301
2) TAIL CABLE
i) First measurement of insulation of the cable should be carried out after laying of the cable and
after first monsoon for all the conductors.
ii) Thereafter testing of all the conductors including spare conductors should be carried out every
year for signal and track circuit tail cable.
iii) Testing of all the conductors including spare conductors should be carried out every six
months for Point tail cable.
Page 51 of 301
Annexure : 15/2
TABLE - 1
NOTE: Above values are only indicative. Based on cable health and experience above settings may be
adjusted as per site conditions.
TABLE - 2
DATE :-
STATION: -
Leakage
S.no Channel no Supply monitored resistance in Remarks
Kilo ohm
1 Channel -1 24 V EXT EAST
2 Channel -2 24 V EXT WEST
3 Channel -3 24 V INT
4 Channel -4 110 V DC (point)
5 Channel -5 110 V Ac (Sig ) EAST
6 Channel -6 110 V Ac (Sig ) WEST
7 Channel -7 110 v AC ( Track) EAST
110 v AC ( Track )
8 Channel -8
WEST
9 Channel -9 24 V Axle counter
12 V BLOCK
10 Channel -10
INSTRUMENT
NOTE: Whenever any ELD Fault message is received by ESM/JE/SSE or Fault is informed by Datalogger
control the same shall be attended immediately.
Page 53 of 301
CHAPTER - 16 : POWER SUPPLY SYSTEMS FOR
SIGNALLING INSTALLATIONS
Section 1 - Power Supply General
16.1.1.0 Power supply for different types of signalling installations
shall be in accordance with policy approved by the Principal
Chief Signal and Telecommunication Engineer of the
Railway, if Standard Power supply scheme from Rly
Bd/RDSO is unsuitable for a specific application.
16.1.1.3 Power supply system shall be such that fixed stop signals
for approaching train do not become blank when main power
supply source fails.
16.2.2.7 The supply from the power supply control panel as provided
by Electrical Deptt. shall be taken to various S&T locations
by S&T Deptt.
16.2.2.8 The supply from the power supply control panel shall be
extended through separate MCBs to cabins, LC gates,
telecom installations etc. If these are falling within one km of
power supply control panel. For locations which are at one
km or beyond, a separate set of ATs and power supply
control panel shall be provided.
16.2.3.4 For all new installations even in Non RE area, Power supply
arrangements shall be designed suitable to RE.
16.3.4.3 230V power supply which is selected from the auto / manual
change-over panel shall be distributed to various power
equipments such as IPS, transformer-rectifier sets, battery
chargers, transformers etc. through a Distribution Panel.
Proper capacity HRC fuses / MCBs, lightening and surge
protection devices shall be provided for protection of the
equipment against overload and lightning / surges.
16.4.5.2 Battery chargers for axle counters shall have in-built filters to
maintain ripple content below specified value.
16.4.5.10 Battery Chargers shall not directly feed the line circuit of
Block Instruments.
16.5.6.3 The batteries shall be so installed that they are away from
direct rays of sun and any heat radiating equipment.
16.6.7.5 Battery leads shall be colour coded (Red for positive , Black
for negative and green for Earth terminal) and cut to correct
length. They shall be crimped / soldered to appropriate
terminal.
16.7.8.5 The connection between the battery and the DG Set shall be
through sufficiently thick wire to avoid drop in voltage.
16.8.9.2 The battery room and location boxes shall be kept well
ventilated, free from water, oil or dust. Surroundings and
batteries shall be kept clean.
16.8.9.8 Each cell shall be tested periodically and its cleaning and
charging arranged so that its voltage and specific gravity are
within specified limits. Test results and dates of cleaning and
charging adjustments shall be recorded on the format
enclosed as Annexure-16/3. A separate card shall be
maintained for each battery set. The voltage of individual cell
shall not fall below 1.85 volts.
16.9.10.4 The wiring shall be checked to ensure that wires are in good
condition and connections are properly tightened.
16.10.11.5 Leakage of fuel oil, lubricating oil and radiator water shall be
effectively checked.
16.10.11.6 Radiator fan shaft shall be grease lubricated and worn out
shafts replaced. Radiator hose and fuel oil hose shall be
checked for leakage and replaced in time.
I. Maintenance of Integrated Power Supply System with Battery bank by Signal Technician :
II. Inspection of Integrated Power Supply System with Battery bank by Supervisors:
Page 63 of 301
Signal Technician shall comply (I) 1 to 15 every fortnight regularly.
Supervisors during their inspections shall ensure compliance of (I) 1 to 15 by the Signal Technician, (II) 1 to 11
and also record the readings as per Annexure-15A.
3. Any abnormalities found during inspection or otherwise, it shall be brought to the notice of next higher level
irrespective of schedule.
Tools required:
1. Digital multi-meter.
2. Clamp on ammeter.
3. Digital earth meter.
4. Standard ESM tool kit.
5. Rubber gloves.
Signature
Name
Designation
Date
Page 64 of 301
Annexure-16/2
IPS with Battery Bank Readings
Specific Gravity of LMLA cell 1180-1220 VRLA cell : Specific Gravity N/A
Voltage of LMLA cell 1.85 - 2.25V VRLA cell Voltage: 1.85 – 2.27V
Cell Specific
No.1 Gravity
Voltage
Cell Specific
No.2 Gravity
Voltage
Cell Specific
No.3 Gravity
Voltage
Contd Specific
.... Gravity
Voltage
Cell Specific
No.55 Gravity
Voltage
Total Battery
Voltage:
Battery charging
current:
Load current:
SPARE CELLS:
Cell Specific
No.1 Gravity
Voltage
Cell Specific
No2 Gravity
Voltage
Cell Specific
No.3 Gravity
Voltage
Contd..
Signature with
Designation.
Page 65 of 301
AC Input Voltage :
AC Input Current :
SMR 1: Voltage/Current :
SMR 2: Contd......
Inverter 1: Input / Output Voltage :
Inverter 1 Load Current :
Inverter 2: Input / Output Voltage :
Inverter 2 Load Current :
CVT/AVR (Signals) 1 Input / Output Voltage :
CVT/AVR (Signals) 1 Load Current :
CVT/AVR (Signals) 2 Input / Output Voltage :
CVT/AVR (Signals) 2 Load Current :
CVT/AVR (Track) 1 Input / Output Voltage :
CVT/AVR (Track) 1 Load Current :
CVT/AVR (Track) 1 Input / Output Voltage :
CVT/AVR (Track) 1 Load Current :
110V DC for Points :
Signature
Name
Designation
Date
Page 66 of 301
Annexure-16/3
MAINTENANCE INSTRUCTIONS FOR CONVERTIONAL POWER EQUIPMENT
Railway : Division : Station :
I. Maintenance of Conventional Power Equipment (Stabilizer, Charger & Inverter) with Battery bank by Signal
Technician :
Item Works to be carried out Remarks
No. (Yes or No)
1 Cleaned all Power Equipment including Stabilizer, Charger & Inverter and all their modules etc., and found
satisfactory.
2 Checked visually working of all Power Equipment including Stabilizer, Charger & Inverter, their measuring
meters and found satisfactory.
3 Checked physically input and output terminations and cables on all Power Equipment & Power rack (if
applicable) and found satisfactory.
4 Checked AC mains input supply to the Stabilizer, AC output from Stabilizer and found within specified range
as per the Stabilizer manual. If any abnormality, suitable action taken and informed Supervisor.
5 Checked AC mains input supply to the Charger, DC output from Charger and found within specified range as
per the Charger manual. If any abnormality, suitable action taken and informed Supervisor.
6 Checked DC input supply to the Inverter, AC output from Inverter and found within specified range as per
the Inverter manual. If any abnormality, suitable action taken and informed Supervisor.
7 Ensured continuity of earth lead wires from earth pit to all Power Equipment.
8 Cleaned all Battery terminals and ensured proper inter-connections and found satisfactory.
9 Applied petroleum jelly / Vaseline on the battery terminals, as required.
10 Checked for any leakage of electrolyte / deformation of cells and found satisfactory. If any abnormality,
suitable action taken and informed Supervisor.
11 Measured voltage, specific gravity of individual cell, total voltage, charging/load current and recorded the
readings as per Annexure-16A. Topped up distilled water wherever required. If any abnormality,
suitable action taken and informed Supervisor.
12 Observed exhaust fan in both Charger Equipment room and battery room are working satisfactorily. If any
abnormality/non-availability, informed Supervisor.
13 After completion of maintenance, ensured that doors / cabinet covers of all Power Equipment are closed
and locked properly.
14 Plugged all unnecessary openings to avoid Dust/water/rodent entry.
15 Ensured that all connections from all Power Equipment (Stabilizer, Charger, Inverter & Battery) to
Datalogger are proper and found satisfactory.
II. Inspection of Conventional Power Equipment (Stabilizer, Charger & Inverter) with Battery bank by
Supervisors:
Item Works to be carried out Remarks
No. (Yes or No)
1 Measured voltage, specific gravity of individual cell, total voltage, charging / load current and recorded the
readings as per Annexure-16A. Topped up distilled water wherever required. If any abnormality, suitable
action taken and informed Section Officer.
2 Checked Auto load sharing by Rectifier modules of charger (if applicable) and found satisfactory.
3 Checked Auto load sharing by Inverter modules of Inverter (if applicable) and found satisfactory.
4 Checked connection of all fuses, MCBs, SPDs (all types), intactness (observed indication) and found
satisfactory. If any abnormality, suitable action taken and informed Section Officer.
5 Ensured that proper maintenance by AMC Engineer is being done as per the schedule and conditions of
contract, if applicable.
6 Ensured the working condition of spare modules of all the Power Equipment and spare cells, if applicable.
7 Ensured continuity of earth lead wires from earth pit to all Power Equipment.
8 During Quarterly Inspection by SSE In-charge: Measured Earth value using clamp on earth meter. Earth
resistance shall be ≤ 1 Ω. Recorded the measured value of earth resistance. If it is beyond limit, suitable
action taken and informed Section Officer.
9 During Quarterly Inspection by SSE In-charge: Ensured the capacity of the battery bank by discharging up to
50% of the rated capacity and charged the bank again to 100%. If any abnormality, suitable action taken and
informed Section Officer.
10 During Quarterly Inspection by SSE In-charge: Ensured that all connections from all Power Equipment
(Stabilizer, Charger, Inverter & Battery) to Datalogger are proper and found satisfactory. Measured voltages
at Equipment room are tallying with voltages shown by Datalogger. If any abnormality, suitable action taken
and informed Section Officer.
Page 67 of 301
Signal Technician shall comply (I) 1 to 15 every fortnight regularly.
Supervisors during their inspections shall ensure compliance of (I) 1 to 15 by the Signal Technician, (II) 1 to 9 and
also record the readings as per Annexure-16A.
3. Any abnormalities found during inspection or otherwise, it shall be brought to the notice of next higher level
Irrespective of schedule.
Tools required:
1. Digital multi-meter.
2. Clamp on ammeter.
3. Digital earth meter.
4. Standard ESM tool kit.
5. Rubber gloves.
Signature
Name
Designation
Date
Page 68 of 301
Annexure-16/4
Conventional Power Equipment (Stabilizer, Charger & Inverter) with Battery bank Readings
Cell Specific
No.1 Gravity
Voltage
Cell Specific
No.2 Gravity
Voltage
Cell Specific
No.3 Gravity
Voltage
Contd Specific
.... Gravity
Voltage
Cell Specific
No.55 Gravity
Voltage
Total Battery
Voltage:
Battery charging
current:
Load current:
SPARE CELLS
(if applicable) :
Cell Specific
No.1 Gravity
Voltage
Cell Specific
No.2 Gravity
Voltage
Cell Specific
No.3 Gravity
Voltage
Signature with
Designation.
Page 69 of 301
AC Input Voltage to Stabilizer :
AC Output Voltage from Stabilizer :
AC Input Voltage to Charger:
AC Input Current at Charger :
Rectifier 1: Voltage / Current :
Rectifier 2: Contd......
Inverter 1: Input / Output Voltage :
Inverter 1: Load Current :
Inverter 2: Input / Output Voltage :
Inverter 2: Load Current :
CVT/AVR (Signals) 1 Input / Output Voltage :
CVT/AVR (Signals) 1 Load Current :
CVT/AVR (Signals) 2 Input / Output Voltage :
CVT/AVR (Signals) 2 Load Current :
CVT/AVR (Track) 1 Input / Output Voltage :
CVT/AVR (Track) 1 Load Current :
CVT/AVR (Track) 2 Input / Output Voltage :
CVT/AVR (Track) 2 Load Current :
110V DC for Points :
Signature
Name
Designation
Date
Page 70 of 301
Annexure-16/5
Page 71 of 301
Annexure-16/6
Page 72 of 301
Annexure-16/7
Page 73 of 301
Annexure-16/8
Page 74 of 301
Annexure-16/9
Page 75 of 301
Annexure-16/10
Page 76 of 301
Annexure-16/11
Page 77 of 301
Annexure-16/12
Whenever required 60-60 V/5A Dc-Dc converter modules may be used instead of 24-
32V/5A depending upon Relay type.
Page 78 of 301
CHAPTER-17 : TRAIN DETECTION
TRACK CIRCUITS & AXLE COUNTERS
Section 1: Track Circuits
17.1.1.0 Types of Track circuits
17.1.1.1 A closed type track circuit shall be provided to prove the clearance of rail
track.
17.1.1.2 Double rail track circuits shall be provided on non-RE areas. In RE areas,
Single Rail track circuit for D.C track circuit and Double Rail track circuit for
AFTC shall be used.
17.1.5.1 Glued Joints or Insulation Joints of approved type shall be provided for
defining boundary of track circuit. In all future works of track circuiting, glued
insulated joints should be provided. Glued joint should be tested before
insertion.
Note:- Where ever Insulation Joint is mentioned, it applies to glued
insulated joint also.
17.1.5.2 Where staggering cannot be avoided the distance between staggered joints
shall not exceed the minimum wheel base of the vehicles.
17.1.5.3 Rail ends of glued/insulated joints shall be square and true. All rough edges
and burrs shall be removed from bolt holes. Battered ends shall be put right
and the gap between the rails should be equal to the thickness of the end
post.
17.1.5.4 Fish bolts at the joints must be kept tight and the sleepers well packed in
the vicinity of the joints.
Page 79 of 301
17.1.5.6 Ballast shall be kept clean throughout the track-circuited section and care
should be taken to see that the ballast is kept clear off the rails and rail
fastenings. The clearance from the foot of the rail should not be less than
50mm. Well screened ballast right up to the formation level shall be
provided.
17.1.5.7 Rail ends shall be kept free from brake-dust, dirt, sand, rust, other foreign
materials etc. All rough edges and burrs at rail ends must be removed.
17.1.5.8 To avoid crushing of end posts of insulated rail joints due to creep, at least
one rail length on either side of insulated joint should be provided with anti
creep devices.
17.1.5.9 Rail screws should preferably be used in place of dog spikes at insulated
joints.
17.1.5.11 Where short welded rail panels are used, SWR shall not butt against
insulated joint. Two rail lengths of 13 meters/12 meters shall be interposed
to isolate short welded rail from insulated joint. This standard length of rails
shall be anchored effectively to arrest movement in either direction.
17.1.5.12 In case of turnouts and crossings, insulated stretchers, insulated gauge tie
plates and insulated crossing plates shall be provided as per approved
drawings.
17.1.5.13 GFN liners shall be provided in the track circuited area using concrete
sleepers
17.1.5.14 Track circuited area shall be free of vegetation only insulated trolleys shall
be used.
17.1.5.15 Provision of zigzag wielding on the top of rail to be done where rusty rails at
siding/ Emergency crossover are there
17.2.6.1 Track relays shall be located at the entry end of the track circuits wherever
possible.
17.2.6.2 Where track relays cannot be located in the cabin/Relay Room, they shall
Page 80 of 301
be housed in locations of an approved type.
17.2.6.4 Connections between the track relays and track repeating relays shall be
made in accordance with the approved wiring diagram and must invariably
incorporate both cross protection and double cutting arrangements.
17.2.6.5 The feed and relay ends shall be connected by separate and individual
cables.
17.2.6.6 Relay End and Feed End of the track circuit should be located at the
boundaries of the track circuit.
17.2.8.1 Jumper connections shall normally be so made that the whole of track
circuit is in series excluding traction return rail. When the rails of a track
circuit are in parallel, care shall be taken that the jumper connections are
effective.
17.2.8.3 All connections to the track shall be of sufficient length and allow for rail
creep. Connections shall be firmly fitted to the web of the rail.
17.2.8.4 For short jumpers, galvanized iron wires and for long jumpers cables, may
be used. Where galvanized iron jumper is used, duplicate jumpers shall be
run. The cross section of galvanised iron wire shall not be less than 8 SWG.
Where cables are used, the size shall not be smaller than 7/0.750 mm.
17.2.9.0 Lead Wires: The lead wires used for connecting the feed set to the feed
end boot leg/track lead JB and the track relay to the relay end boot leg/track
lead JB shall preferably be of copper conductor having a minimum cross
section of 2.5 sq.mm.
17.2.9.1 The Feed as well as Relay Ends +ve & -ve leads shall be connected by
using individual 2x2.5 sq.mm cable, duly paralleled at each end.
17.2.10.1 Bond wires/Rope wires shall be of an approved type. Duplicate wires shall
Page 81 of 301
be installed close to the fish plate, it is desirable to use bond wire clips for
securing the bond wire.
17.2.10.2 Bond holes shall be drilled with a twist drill and the bonds driven-in
immediately. The wires may be fixed by using channel pins in the holes or
by brazing/welding.
17.2.10.3 The resistance of rail and bonding per 1000 m of track shall not exceed 0.5
ohm for track circuits longer than 700 m. A rail and bond resistance upto 1.5
ohm per 1000 m of track may be allowed for length of track circuit less than
700 m.
17.2.10.4 The rail bonding and connections to the relay and feed set shall be made
according to approved drawings.
17.2.10.5 The lugs of impedance bond connections shall be firmly fixed by pressing
rivets into the web of the rail with a bond press.
17.2.11.1 For track circuited points or lines in a station, track circuit termination shall
be provided sufficiently before the Fouling Mark so as to avoid infringement
to the standard dimension by any portion of the vehicle. The distance
between track circuit termination and Fouling Mark shall not be less than
3.0 m.
17.2.12.1 Where cut section track circuits are installed, the track relays concerned,
when de-energized, shall open the track feed and shunt the track circuit.
17.2.13.1 All components of insulated joint shall be of approved type and shall
conform to RDSO drawings. The components shall be installed using
correct sizes and combinations.
17.2.13.2 Insulated rail joints shall, as far as possible, not be provided on the outer
rail in curves. Insulated rail joints are not required for AFTC except point
zone.
17.2.13.3 Before an insulated joint is installed, it shall be ensured that permanent way
requirements stipulated in para no. 17.1.5.0 are complied with. The
installation of glued rail joints shall be done by Civil Engineering
Department. The installation of Nylon insulated rail joints shall be done in
accordance with RDSO's booklet No.STS/E/IRJ/lMI - Installation and
Maintenance Instructions for Nylon insulated rail joint. Particular attention
shall be paid to the following: -
(a) Hammer driving offish-bolt shall be avoided, as this will damage nylon
bushes, If the rail hole and the fishplate holes are in their proper position
Chapter 17 : Train Detection Track Circuits & Axle Counters
Page 82 of 301
and alignment, the fish bolt can be easily inserted by hand pressure.
(b) If an end-post projects above the rail table at the rail ends, it shall be
trimmed and brought to the level of the rail table, especially when
inserted between the worn-out rails, before first wheel of a train passes
over it.
(c) The distance of 13 m. between the insulated Block Joint or Detection
Point and the starter Signal can be reduced from 13 m to 3 m for
Signaled movements. The insulated Rail Block Joint or Device of Axle
Counter or Joint Less Track Circuit shall be so fixed that their boundary
shall be within zero to 3 m in advance of the starter signal.
(d) In the case of point track circuits, the insulation joint shall not be in the
stock rail joint but in the rail joint ahead of it wherever feasible.
17.2.13.4 Only 'J' type clip shall be used in glued joint portion of track. The "J" clips
shall be prominently painted in "YELLOW" colour, by P way staff.
17.2.14.0 Track Indicators: At track circuited stations where track indicators are
provided, the following arrangements shall be made:
(a) Normally the track indicators would show no light when the line is
unoccupied. When action is initiated to set the route for taking off a
signal and the concerned route is set, the track indicator light for the
route shows Yellow/White, if unoccupied. However, if any portion of the
track circuited area is occupied, a "RED" indication is shown on the
panel diagram, irrespective of the route being set or not.
(b) The track indicators would show white/yellow light when the track is
cleared after the intended movement is completed till the route signal
button or switch is restored to normal unless the panel interlocking/
route relay interlocking is provided with Automatic Route Release
facility in which case the indication would be lit until the sub
route/sectional route/ route is released.
In future installations, only plug in type track relays (9 ohm) shall be used,
Page 83 of 301
both in Non-RE & RE areas.
17.2.15.3 Q series track relay must be used in conjunction with Q series slow to pick
up relay as a repeater relay.
17.2.15.6 Maximum length of track circuits :- Maximum length of track circuit under
different track parameter conditions shall not exceed the limits as given in
the following table. Maximum length of track circuit under different track
parameter conditions shall not exceed the limits as given in the table below
Min. Max.
Section Ballast TSR length of
S. RE/ Type of Track Relay
Sleeper (Yard/ Resistance in Track
No. Non-RE to be used
Block) in Ohm per Ohms Circuit
Km in metre
QT 9 ohms AC
3 RE PSC Block 4 0.5 450
immune
4 RE PSC Yard 2 0.5 450 -do-
(a) Approved type of secondary cells shall be used for feeding track
circuits,
(b) Secondary cell(s) shall be used along with battery charger/solar panel
of adequate capacity.
Page 84 of 301
17.2.16.0 Audio Frequency Track Circuits(AFTC)
17.2.16.1 The use of audio frequency permits the physical limits of an individual track
circuit to be defined by tuned short circuits between the rail rather than the
insulation in the rails themselves. These types of track circuit have distinct
advantage of not requiring IRJs (Except Point Zones) and offers
considerable saving in IRJs and impedance bond, especially on tracks
subjected to high speed, high axle load traffic or where there is an intensive
service.
(b) Built in time delay, therefore a slow to pick up QSPA1 Relay as TPR
is not required.
(d) It is an Audio Frequency track circuit, but can also be used with
Insulated Rail Joint.
17.2.16.3 Only approved type modulated Audio Frequency track circuit shall be used.
17.2.16.4 Track circuit shall not be configured in single rail mode operation.
17.2.16.5 Audio Frequency Track Circuit may be operated as local fed or in a remote
fed mode.
(a) Installation of track circuit shall strictly follow the instructions given
for that type of track circuit.
(b) Tuning area shall be devoid of check rails, level crossing, insulated
bond and each fish-plated joint shall be bonded with jumpers of
adequate thickness.
Page 85 of 301
(d) A frequency assignment scheme for the track circuit shall be decided
in advance and it shall be strictly followed.
(e) Terminal junction on insulation joint to track circuits with the same
frequency is prohibited, however, frequencies not belonging to same
pair can be used.
(f) Cable cores of same cable shall not be used for connecting
transmitter & receiver of a track circuit.
(g) When wiring and installing track circuit, circuit pairing should be
observed in the line cables. Each transmission or reception shall use
conductors from one same pair. Circuit pairing results in cable
transmission parameters being changed and may induce significant
cross talk levels in adjacent circuits.
(l) In case of failure of track circuit attempt shall not be made to pick up
the track circuit by adjusting the gain of receiver of TC without
investigating the cause of drift in the receiver voltage.
(m)Impedance bond within track circuit shall be tuned with the correct
resonating capacitor across the auxiliary coil and this tuning shall
match with the frequency of track circuit.
(n) Maximum length of track circuit depends upon various factors like
ballast resistance, frequency adopted, track layout (whether any
level crossing or bridge falls within track circuited area) and vendor
of AFTC, and it cannot be laid down in absolute terms. Broadly its
length is limited to 700 metres in end fed mode.
Page 86 of 301
17.3.17.1 Track circuit on AC electrified section may use IRJs (Insulated Rail Joints)
or ESJs (electrical separation joint) and may be configured as single rail or
double rail track circuit. Track circuit which use electric separation joint shall
be configured only as double rail track circuit.
(a) With single rail track circuits, one of the rails is reserved for the
traction return current. This rail is referred to as the uninsulated rail.
Any connection from the O.H.E. mast or other structure shall be
made only to the un-insulated rail. Similarly, connections for the
return current at feeding points as well as from booster transformers
and return conductors shall be made only to the uninsulated rail.
(b) As far as practicable, the rail adjacent to the O.H.E Mast shall be
utilised as the un-insulated rail. However, this may not always be
possible, particularly in yards where there are a large number of
points and crossings or where the O.H.E masts are not always on
the same side or where track circuits are staggered.
(c) In single rail track circuits, in the event of a break in the uninsulated
rail, very heavy current will flow through the track relay as well as the
equipment at the feed point. To avoid this the uninsulated rails of the
adjacent tracks shall be cross-bonded at intervals of not more than
100 Mts. In case the track circuit is less than 100 Mts. the cross
bonding shall be provided on the uninsulated rail at either end of the
track circuit (ref Drg no 22.16).
(d) In the case of adjacent track circuits, the return rail shall be
staggered.
(a) In double rail track circuits, since both rails are used for traction
return current, impedance bonds shall be provided at the IRJs.
(c) Connections at the feeding points and from booster transformers and
return conductors shall be made to the center points of impedance
bonds.
Page 87 of 301
17.3.17.4 DC Track Circuit in RE area (Single Rail)
(a) This track circuit can only be configured to work as single rail track
circuit.
(e) The length of track circuit can be extended upto 450 meters when
QTA 2 plug-in relay is used.
(f) Restriction on the track circuit length due to use of concrete sleeper
can be relaxed upto 450 meters by PCSTE of Railway (if adequate
ballast resistance can be consistently obtained)
Page 88 of 301
length of track circuit of 750 meters using one additional 'B' type
choke at the relay end, under minimum ballast resistance of 2
ohms/km. Operation of track circuit with this type of relay will require
four cells delivering 8.8V. QBAT relays shall be used in conjunction
with QSPA1 relays conforming to BRS 933A.
(i) Before installation of single rail D.C track circuits in A.C Electrified
areas, measurements of stray D.C currents shall be taken in
accordance with the instructions in ‘17/7’. The total stray current as
measured, shall not exceed:
(i) 10 milli-amperes, if length of track circuit is less than 100 meters
(ii) 100 milli-amperes, if length of track circuit is 100 meters and
above
If measured value of current exceeds the specified limit as above,
other type of track circuit suitable to work in A.C. traction area shall
be used.
(j) To protect the equipment from the effects of the rail voltage, a choke
coil of approved type shall be provided in series with the feed
resistance.
(a) Only approved type modulated Audio frequency Track Circuit shall
be used.
(b) Audio frequency track circuit shall be configured only as double rail
track circuit and like any double rail track circuit it requires both rails
to be balanced with respect to earth and with respect to current flow
in each rail.
Page 89 of 301
approved type.
(d) Leads between impedance bonds across IRJ on the same track shall
be capable of carrying the traction current. It shall be PVC sheathed
cables, terminated by compression lugs of an approved type and
bolted to the impedance bond termination.
(e) The design and installation of impedance bonds should take into
account the requirements for mechanised track maintenance and
should not be a hazard for men walking along the track.
(b) It is, however, important to recognize that the operation of track circuit
is dependent upon the integrity of traction return bonding. It is
therefore important that attentions are given to the testing during
installation and also during maintenance of traction return bonding.
Page 90 of 301
430V under traction short circuit conditions.
(ii) To ensure that protective equipment operates satisfactorily,
(iii) To minimize damage to installations due to traction short circuit,
(iv) To maintain correct operation of track circuits.
(ii) The signal department will then indicate on these plans the
proposed position of insulated joints, impedance bonds, signal
structures and track circuit bonding and in single rail track
circuited areas, will identify the track circuit rail by marking with a
thickened line. In double rail track circuited areas S&T
department shall specifically indicate the provision of earth wire
for structure earthing.
(i) The track circuit rail must be series bonded in order to ensure
that defective bonding cannot cause a wrong side failure of the
track circuit. Accordingly, the bonding arrangement of the track
circuit rail must ensure that the conductive path between the
track circuit feed connection and the relay or receiver end
connection is interrupted in the event of a disconnection.
(iii) In single rail track circuits, in the event of a break in the un-
insulated rail, very heavy current will flow through the track relay
as well as the equipment at the feed point. To avoid this, the un-
insulated rails of the adjacent tracks shall be cross-bonded at
intervals of not more than 100 meters. In case the track circuit is
less than 100 meters, the cross bonding shall be provided on the
uninsulated rail at either end of the track circuit.
Page 91 of 301
return current. The un-insulated rail shall be connected to each
of the traction masts by a structure bond, which shall be riveted
at both ends. The arrangement for Double Line and Single Line
Sections is as illustrated in Drawing given below.
(v) Typical bonding examples with single rail track circuits are
shown in figure.
(ii) Rail bonds and Cross-bonds: Where rail bonds and cross
bonds are required for traction return purposes they shall be
installed by and remain the responsibility of the electrical
department.
(iv) In addition, the two rails of the non-track circuited track outside
any track circuit or in between two track circuits shall be bonded
together immediately after the block joints.
(v) Detailed instructions for bonding of track are given in the A.C
Traction Manual.
(a) There is always a good connection between power feed and track,
relay and track and also between adjoining rails, through jumpers
and rail bonds.
(b) The ballast resistance always remains high and does not fall below
prescribed minimum values.
Page 92 of 301
(d) The insulating joints are of high resistance.
(e) The surface of rail is clean and is free of dust, sand and foreign
materials.
(a) Pick up and drop away values shall be maintained within the limits
specified by the manufacturer.
(vi) Electroplating
(c) The relay that is in any way defective should be changed at once and
sent to shops together with a brief report stating the nature of the
defects. On no account should any attempt be made by the line staff to
rectify the relay.
Page 93 of 301
17.4.19.0 Insulated Rail Joints
Insulated rail joints shall be maintained in accordance with the instructions
given in Booklet No. STS/E/IRJ/IMI "Installation and Maintenance
Instructions for Nylon Insulated Rail Joint" issued by the RDSO/Lucknow,
with particular attention being paid to the following :
(a) Before opening an insulated rail joint, the components required for
replacement, conforming to the rail-section, shall be kept ready by
the side of the track.
(d) Fish bolts shall be kept tight. Nuts shall be tightened several times
during the first two weeks after installation/replacement, until all
components of an insulated rail joint are firmly set.
(e) A metal flow is seen often at the rail-table at the joints. Such metal
flow of metal forms a lip and creates sharp burrs at the rail ends.
Projections formed at the rail ends shall be chiseled without
damaging the end post so that these do not bridge the rail expansion
gap and cause a short circuit.
(f) Brake-block dust, which may accumulate on the head and sides of
the end post and top surfaces of the fish-plates, shall be brushed off
frequently so that the possibility of electrical conductivity being
established between the rail ends is eliminated.
(g) Opening & fixing of fish plates of Nylon insulation joint for
installation/replacement of joint shall not be done by S&T staff as it is
the responsibility of Engineering Department.
(h) Special type pandrol clips ('J' type) shall be provided at Nylon
insulation joints/ glued joint to avoid touching of pandrol clip with the
fish plate.
17.4.20.0 A faulty insulated joint may be detected by taking the voltage readings
across the track relay terminals and noting if this reading changes when the
adjacent track circuit feed is shunted or disconnected. Any change in the
voltage reading will indicate a faulty insulated joint.
Page 94 of 301
to see that they are in sound condition. All defective insulation shall be
changed.
(b) Bonds shall be painted with aluminum paint, where bond corrosions
are excessive.
17.4.24.0 Ballast
Minimum ballast resistance per km. of track should not be less than 2 ohm
per km. in station yard and 4 ohms per km. in the block section.
17.4.25.0 Drainage
(a) Special attention shall be paid during the rains to track drainage.
Defects, if any, shall be reported to the SSE/JE(P-Way).
Page 95 of 301
17.4.27.0 Train Shunt
(a) A train shunt test shall be taken every quarter and every time the
track circuit is adjusted or any alteration is made.
(b) Shunt test shall be taken not only at relay end but also at other
parallel portions of the track, such as, turnouts and crossovers.
(a) Track circuit test record Card No.S&T/TC-1, Annexure ‘17/1’ for DC
track circuits, shall be maintained for each track circuit. For other
types of track circuits, suitable record card may be framed by the
Principal Chief Signal and Telecommunication Engineer. Readings
shall be recorded every six months. Suitable remedial action shall be
taken when abnormal readings are noticed at any time.
(c) The test card shall be kept up-to-date in accordance with the
instructions given on the cards.
17.5.31.0 Axle counter consists of track device (axle detector) mounted on the rails,
trackside electronic equipment provided near the track and connected with
track device & evaluator. Evaluator monitors the counts of track device (s)
to give clear/occupied indication. Evaluator/track side electronic
equipment (Field Unit) may be kept in relay room or site.
17.5.32.0 Digital Axle counters of approved type may be used in lieu of track circuits
to prove the clearance of a portion of track.
Page 96 of 301
17.5.33.0 Axle counters may also be provided in lieu of conventional track circuits for
block working, viz. Intermediate Block Signalling, Automatic Signalling,
Block Working controlled by track circuits, etc.
17.5.34.0 Digital Axle Counter (DAC) shall be preferred on girder bridges in Lieu of
conventional track circuits
17.5.35.0 Axle counters of approved type shall be used for following application-
(a) Splitting of block section by introducing IBS
(b) Proving clearance of block section
(c) Track circuiting of flood prone suburban section
(d) Track circuiting of station section having poor drainage
(e) Automatic block signaling
(f) Track having problem of rust
(g) Tunnels and bridges as per site requirement
(b) The track detection unit shall be fixed minimum 4 meter away from
the nearest rail joint.
(c) The distance between the 2 axle detectors of different axle counting
circuits shall be at least 2 metres or as specified in OEMs manual so
as to avoid mutual interference.
Chapter 17 : Train Detection Track Circuits & Axle Counters
Page 97 of 301
(d) To protect track fittings against damage from hanging parts of
moving trains, protectors shall be mounted on both sides of the fitting
on single line and one side on double line. Protectors shall be placed
in the sleeper space next to the track fittings.
(f) The incoming cables from axle detectors and evaluator may first be
terminated on a cable distribution board to provide facility for testing
(i) The copper cable will be quad cable as per IRS: TC: 30-2005
(0.9 mm dia) or quad cable as per RDSO/SPN/TC/72/2007 (1.4
mm dia) or PIJF Telecom Cable as per IRS: TC 41/97 (0.9 mm
dia.).
Optical fibre cable may also be used for communication with
suitable interfaces.
(k) The power to evaluator is fed from a power supply like dc-dc
converter of approved type with adequate battery back up . Each
evaluator shall be provided with a separate dc-dc converter for better
availability. The input power supply will have a maximum ripple of
Page 98 of 301
50mV peak to peak/10 mV rms.
(l) All lead connections to and from battery and dc-dc converter shall
have adequate current capacity to ensure that the voltage drop does
not exceed 0.2 V. These connections at terminals shall be secured
properly and should preferably be made through lugs to give firm
contact.
17.6.38.0 Axle Counter Resetting: Whenever axle counters are used for block
working, for control of reception signals, etc., reset arrangement of
approved type may be provided so that whenever the axle counter shows
fault condition, the same can be reset to normal by the Assistant Station
Master in charge after ensuring that the monitored portion is clear of
obstruction.
17.6.39.0 Each and every operation of the reset button shall be counted on a non
resettable type counter and shall be properly recorded in the Train Signal
register indicating the movement before and after the operation of the reset
button.
17.6.40.0 The procedure/records to verify the vacancy of the track before resetting
shall be checked during inspection by the SSE/JE in charge of Signalling
and Supervisory staff of Traffic Departments and the staff should be
properly educated during the various courses at the Zonal Training Schools.
17.6.41.0 Before resetting axle counters provided in station section etc. the following
further safeguards shall be followed.
(a) Once the axle counter has failed and is showing fault condition, the
SM should verify that line on which train is to be received is
physically clear of any obstruction and then operate the reset
arrangement of that track section. The first train after the reset
operation shall be either received on calling-on signal or piloted as
per the extant rules after verification of the clearance of the reception
line.
(b) The reset box shall be operated by a key which shall be kept locked
in a separate box secured in the SMs office . Whenever it becomes
necessary to reset, the resetting shall be co-operative and done
jointly by the ASM along with SM and in case SM is not available this
resetting shall be done jointly by ASM with Switchman or by ASM
with other traffic staff. Physical verification of failed section shall be
done through Line verification box which shall be installed near the
section to be verified.
Page 99 of 301
(c) Each and every operation of the reset button shall be recorded in the
Train Signal Register by the ASM and during inspection of the
station, the Signal and Traffic inspecting officials shall specifically
check up the procedures being followed in respect of the above
resetting device and ensure that laid down procedure for resetting is
being followed. This procedure of ensuring that the monitored portion
is free of any vehicle before resetting is done, shall be clearly laid
down in the Station Working Rules.
17.6.42.0 Where axle counters are used for block working, viz, Intermediate block
signaling, Block signalling, automatic signalling etc, the following
precautions shall be observed :-
(a) Once the axle counter has failed and the concerned signal cannot be
taken off, the dispatching station shall verify the clearance of the block
section by exchange of Private Number with the station In advance.
After ensuring that the block sections is clear, the axle counter shall be
reset by co-operative effort between the ASM of the dispatching and
the receiving stations using preparatory reset. The circuitry shall be
such as to obviate the possibility of the resetting by the dispatching/
receiving station independently. The procedure shall be clearly laid
down in the Station Working Rules.
(b) Each and every operation of the reset button shall be recorded in the
Train Signal Register by both the stations and during inspection of the
stations the Signal and Traffic Inspecting officials shall specifically
check up the procedures being followed in respect of the above reset
buttons and ensure that the exchange of private number in this regard
is being maintained properly.
17.6.43.0 In case of double rail mounted track devices there shall be no differential
creep between the two rails of the track to the extent as to alter their inter
distance beyond the permissible tolerance, it is, therefore, necessary that 4
rail lengths on either side shall be well anchored.
17.6.45.0 Anchoring of track on either side of the rails where track devices of axle
counters are fixed, shall be closely watched by the Permanent Way staff to
ensure that there is no differential creep.
17.6.46.0 Tie Tamper shall not be used for 4 sleepers on either side of the track
devices. Incidentally they should be manually maintained.
17.6.47.0 Replacement of components axle counters shall be done with utmost care
and as per technical manuals of OEMs related to this subject. As a general
rule, any maintenance activities in track device area, like, ballast packing &
rail changing etc., that require disconnection of track devices and
Chapter 17 : Train Detection Track Circuits & Axle Counters
…………….Railway
Relay End
Station …………………………….
Schedule Code : T1
Periodicity : Signal Technician : Fortnightly,
Sectional JE/SSE:, Monthly (on A,B & C routes)
Quarterly (on D & E route),
Incharge SSE : Half yearly
S.No. Check the following :
1. Cleaning of track lead junction boxes, track feed battery chargers, regulating
resistance, Secondary cells & all terminals.
2. Checking & replacement of defective Feed end, relay end lead wires, jumper
cables & their terminations & securing them firmly.
3. Checking & replacement of defective/ corrosive track bonds, Continuity bonds,
channel pins etc.
4. Visual check and cleaning of insulated block joints/glued joints.
5. Condition of insulation sleeve on OHE bond beneath rails to be ensured. It may
be ensured that it is not displaced or worn out. Check that no Z /transverse
bond, continuity bond and structural bond is loose.
6. Check level & Specific gravity of electrolyte in all the LMLA cells & top-up
distilled water if required, clean the terminals and connections shall be coated
with pure Vaseline or petroleum jelly to prevent corrosion. Grease shall not be
used.
7. Measure and record Specific gravity (1180-1220) & voltage (1.8 to 2.2V) of each
& every cell by switching off charger, charger voltage and charging current, feed
end/relay end voltage and currents, regulating resistance value & voltage across
it, voltage across Choke and ensure all are in the acceptable ranges. Take
suitable remedial action for values beyond acceptable range.
8. Checking of TF charger failure alarms.
Schedule Code : T2
Periodicity : Sectional JE/SSE : Quarterly (it will be done by
ESM in the presence of JE/SSE),
Incharge SSE : Half yearly
1. Interchange coil terminals R1 & R2 on Track Relays.
2. Checking train shunt resistance at relay, feed end and other parallel portions of
track circuit.
3. Testing of block joints/Glued joints/Point stretcher bar insulations and detecting
faulty joints by using fault injection method / taking the voltage readings across
track relay terminals and note if these reading changes when adjacent track
circuit feed is shorted or disconnected.
Schedule Code : T3
Periodicity : Incharge SSE : Half yearly
1. Checking that excitation with respect to rated pick up voltage, of DC track
circuits is not more than 250% for shelf type relays, 300% for QTA2 and 235%
for QBAT relays.
2. Tail cables testing with 500 V Megger.
3. Coating by insulating varnish/epoxy over GJ/IBJ.
4. Replacement of insulations of all Block joints, insulations of Gauge tie plate,
Stretcher bar and point rodding etc, on main line.
Schedule Code : T4
Periodicity : Incharge SSE : Half yearly
Sectional JE/SSE
IC SSE to carry out every alternate inspection)
Joint check with JE/SSE (P-way) of track circuited portion for
Page 105 of 301
1. The condition of rail and insulation at the rail joints, tightness of fish plate bolts,
packing of sleepers in the vicinity of IBJ/GJ, ballast & sleepers, abnormal
collection of brake dust, rusting of the rail, drainage and position of P-way
fittings likely to cause short circuits like spike, pendrol clips and bearing plates.
2. Condition of ballast, 50 mm ballast clearance from bottom of the rail flange and
availability of anti-creep, ‘J’ clips at GJ/ IBJ, minimum 97% GFN Liners and
Pads for track circuits with PSC sleepers.
3. Joint check with traction supervisors for availability of cross bonds / jumpers
and good condition for return rail in single rail track circuits in AC electrified
territory and rail bonds effectiveness.
4. As per IRPWM, advance correction slip No.128 dated 05.03.2012, SSE/
JE/P.Way and SSE/ JE/S&T should jointly inspect insulated Steel Sleepers,
every six months for checking the effectiveness of insulation in track circuited
areas. SSE/ JE/S&T should coordinate this.
Schedule Code : T5
Periodicity : Incharge SSE : Yearly
1. Conducting visual inspection of track relays for arcing, pitting of contacts, dust
on contacts, rusting/fungus of components, presence of Ants, cracks or
breakages in components, correctness of label and presence of seal.
2. Replacement of insulations of all Block joints, insulations of Gauge tie plate,
Stretcher bar and point rodding etc., on loop lines.
NOTE: (1) In the month of Scheduled Inspection at SSE In-charge level, Scheduled
Inspection by Section SSE/JE may not be required, since it is repetitive. However,
Section SSE/JE will associate during Scheduled Inspection of SSE In-charge.
(2) Date of inspection of SSE In-charge/Sectional SSE/JE and maintenance by Signal
Technician shall be staggered since maintenance will take more time.
(3) Any abnormalities found & unable to attend during maintenance/inspection or
otherwise, same shall be brought to the notice of higher level irrespective of
Maintenance/Inspection schedule.
Schedule Code : T1
Periodicity : Signal Technician : Fortnightly
Sectional JE/SSE : Monthly
Incharge SSE : Quarterly
S.No. Check the following :
1. Cleaning junction boxes tuning Units.
2. Outside track led wires, impedance bonds, bond wires and clips/Lug, cable
connections.
3. All nuts and bolts of tuning unit terminals (AFTC)/Transformer terminals (AC
Track ckt) and rail connection and ensure that these are fully tight. Also,
Packing in and around TU is proper.
4. Firmness, corroded/insulation condition of Track leads connections, replace
track lead wire if insulation worn out or connections corroded & properly
securing them. Replacing corroded AFTC bonds/Z-jumper (For AFTC only).
5. That there is no cavity/butting at centre post of Glued joint, voltage across all
the insulations of glued joint to be measured, if found zero/ near to zero
(generally it should be half of track voltage across rail) then plan it for
replacement .
6. Condition of insulation sleeve on OHE bond beneath rails to be ensured. It may
be ensured that it is not displaced or worn out. Check that no Z/transverse
bond, continuity bond and structural bond is loose.
7. That all cable entry point or any opening of TU/TLJB junction box is sealed.
8. That centre tap connection of S-bond is protected by insulating tape.-For AFTC
only.
9. That Continuity jumpers are duplicate and not rusty.
Schedule Code : T2
Periodicity : Sectional JE/SSE : Quarterly (it will be done by
ESM in presence of JE/SSE),
Incharge SSE : Half yearly
1. Checking the lightning arrestor and its connection.-For AFTC only.
2. For AFTC- Measurement, testing AFTC parameters and compare with last
reading. Take necessary action if not found within range/deviation with respect
to last reading (Voltages & current, AFTC Power Supply, TX Voltages, RX
current and gain etc. as per Annex (AFTC) attached.
3. For AC Track ckt- Measurement of AC track circuit control voltage over AC
track circuit relay (130-200% of rated PU value of TR) and phase angle
between control voltage and local voltage(should not be less than 67 degree).
4. Coating by insulating varnish / epoxy over GJ / IBJ.
5. AFTC gain setting kept in the dynamic range / as prescribed for different AFTC.
Schedule Code : T3
Periodicity : Sectional JE/SSE : Half yearly,
Incharge SSE : Yearly
1. Testing of cable from K Board with 500v megger.
2. TSR also be tested whenever track circuit adjusted or AFTC gain setting
changed.
Schedule Code : T4
Periodicity : Sectional JE/SSE : Half yearly,
Incharge SSE : Yearly
Page 107 of 301
1. Joint check with JE/SSE (P-way) of track circuited portion for The condition of
rail and insulation at the rail joints, tightness of fish plate bolts, packing of
sleepers in the vicinity of IBJ/GJ, ballast & sleepers, abnormal collection of
brake dust, rusting of the rail, drainage and position of P- way fittings likely to
cause short circuits like spike, pendrol clips and bearing plates, Bridge
insulation on girder bridges installed / maintained by P.Way, mud ballast
accumulation near LC, Points, Trolley paths and other areas.
2. As per IRPWM, Advance correction slip No. 128 dated 05.03.2012,
SSE/JE/P.Way and SSE/JE/S&T should jointly inspect insulated Steel
Sleepers, every six months for checking the effectiveness of insulation in track
circuited areas. SSE/JE/S&T should coordinate this.
3. Condition of ballast, 50 mm ballast clearance from bottom of the rail flange and
availability of anti-creep, ‘J’ clips at GJ/ IBJ, minimum 97% GFN Liners and
Pads for track circuits with PSC sleepers.
4. Test Glued joint insulation with 100V Source (megger), it should not be less
than 25M Ω in dry condition & not less than 3 K Ω in wet condition.
NOTE: Sectional JE/SSE & In charge SSE to carry out every alternate inspection.
Annexure (AFTC)
Siemens AFTC Parameters (To be recorded through FSVM)
Test
equipment
Sr. Module Socket Permitted
Description measuring Remarks
range
No. No. No. range
Amplifier 9 V to 12
Input V AC
1 B40/B41 1&2 20V AC
(Transmitter
output
12 V Supply 11 V to 13
2 B33 I-8 & II-8 20 V DC
voltage V DC
Amplifier 60 V to 90
3 B42 Output 3.1 & 4.1 200 V AC V AC
30 V to To track
(before cable
4 B40/B42 Filter Card 3&4 200 V AC 100 V AC
stabilizing
resistor)
Rx I CH I > 6.5 V AC With track
5 B33 Input I-5 & II-8 20V AC to < 20 V clear
AC
> 6.5V AC
Rx I CH II With track
6 B33 II-5 & II-8 20V AC to < 20
Input VAC clear
Rx I CH I With track
7 B33 I-5 & II-8 20V AC < 5 V AC
Input occupied
Rx I CH II With track
8 B33 II-5 & II-8 20V AC < 5 V AC
Input occupied
Rx I CH I 12 V to 15
9 B33 I-6 & II-8 20V DC
Output V DC
ALSTOM AFTC
ABB AFTC
390 1
195 2
134 3
98 4
78 5
65 6
56 7
50 8
45 9
39 10
35.4 11
32.4 12
30 13
For gain of 13 the track circuit will operate from 15 mA to 60 mA. This is the
dynamic range of the track circuit.
NOTE: 1) Verification of parameter as per latest TAN issued by RDSO/ Head Quarters if
any.
2) Check the functioning of Event logger card. Data shall be analysed by attaching the
same with any laptop/PC.
Annexure (AFTC)
Siemens AFTC Parameters (To be recorded through FSVM)
Test
equipment
Sr. Module Socket Permitted
Description measuring Remarks
range
No. No. No. range
Amplifier 9 V to 12
Input V AC
1 B40/B41 1&2 20V AC
(Transmitter
output
12 V Supply 11 V to 13
2 B33 I-8 & II-8 20 V DC
voltage V DC
3 B42 Amplifier 3.1 & 4.1 200 V AC 60 V to 90
Page 114 of 301
Output V AC
30 V to To track
(before cable
4 B40/B42 Filter Card 3&4 200 V AC 100 V AC
stabilizing
resistor)
Rx I CH I > 6.5 V AC With track
5 B33 Input I-5 & II-8 20V AC to < 20 V clear
AC
> 6.5V AC
Rx I CH II With track
6 B33 II-5 & II-8 20V AC to < 20
Input VAC clear
Rx I CH I With track
7 B33 I-5 & II-8 20V AC < 5 V AC
Input occupied
Rx I CH II With track
8 B33 II-5 & II-8 20V AC < 5 V AC
Input occupied
Rx I CH I 12 V to 15
9 B33 I-6 & II-8 20V DC
Output V DC
Rx I CH II 12 V to 15
10 B33 II-6 & II-8 20V DC
Output V DC
Demodulator 1.3 V to 2
11 B33 I-7 & II-8 20/2 V AC
Input CH I V AC
Demodulator 1.3 V to 2
12 B33 I-7 & II-8 20/2 V AC
Input CH II V AC
Relay 16.5 ± 1 V
13 B39/34 I-11 & I-12 20 V DC
Voltage CH I DC
Relay II-11 & 16.5 ± 1 V
14 B39/34 20 V DC
Voltage CH II II-12 DC
Power Power supply 11 V to 13
15 12V/0V 20 V DC
supply unit V DC
Power Power supply 4.5 V to
16 5V/0V 20 V DC
supply unit 5.5V DC
17 B33 Receiver I input E1E2 20V AC 0.3-2V AC
ALSTOM AFTC
390 1
195 2
134 3
98 4
78 5
65 6
56 7
50 8
45 9
39 10
35.4 11
For gain of 13 the track circuit will operate from 15 mA to 60 mA. This is the
dynamic range of the track circuit.
US&S AFTC
ANNEXURE (MSDAC)
ELDYNE MSDAC
s) Signature
SIEMENS MSDAC
Outdoor parameters
Transmitter frequency of
FS 43KHz 42.8 KHz to 43.2 KHz
double wheel detector
FRAUSCHER MSDAC
Indoor Equipment:-
Outdoor Equipment:-
*The maximum loop resistance of the cable from the GAK to the backplane ABP is 250
ohm.
Reset
Input Reset Signature
CEU Panel
Input Voltage Voltage Panel of
Sl. No. Date Temp Earth resistance (Ω) Earth Contact Physical EMI Filter CT Rack Wires Termi Remarks
(At CT Rack) (At SM Physical Maintainer
status nations in
Room) status Official
SM Room
M
m
t
c
o
n
a
st
oi
di
pl
bl
H
D
P
S
B
e
o
no
d
a
L
o
o
h
s
Nc
ks
-
Cr
t
t
21.6- 21.6- 21.6-
21.6-28.8V OK/ NOT OK/ NOT OK/ NOT OK/ NOT
Range 28.8V 28.8V 28.8V -40 to 85 °C < 1Ω < 1Ω OK/ NOT OK OK/ NOT OK
DC OK OK OK OK
DC DC DC
1.0 Before installing a D.C. Track Circuit in areas, which are to be A.C. Electrified, stray
Direct Current tests shall be carried out so as to ensure that D.C. Track Relays shall not
operate with the stray currents.
3.0 If there are already existing track circuits in the area, these shall be disconnected to
safeguard against false readings being recorded in case of leakage of Block Joints.
4.0 The length of the track required being track circuited should be insulated by means of
Block Joints on either end of the rails. The rail joints in the track-circuited length may or may
not be bonded for purpose of these tests.
5.0 electing a suitable earth, which shall not exceed 5 ohms in resistance, test shall be
carried out.
6.0 A suitable type of milli-volt meter and milli-ammeter shall be used for recording voltages.
7.0 These stray current and rail earth voltage measurements shall be recorded in
accordance with the diagram for measurements indicated below: -
Note:- For measurement of stray current set up the circuit as shown above and measure the
current simultaneously.
Note :- Where 9 ohms, 4 ohms or 2.25 ohms relays are used, use 9 ohms, 4 ohms or 2.25
ohms resistance and measure the voltage once at 'X' and next at ' XV.
9.0 Where stray current/voltages are observed, the length of the Direct Current track circuit
shall be cut down so as not to exceed the following limits for each length of Track Circuit: -
a) The Rail-Earth voltage as measured across 9 ohms, 4 ohms, or 2.25 ohms shall not
exceed 0.1 volt.
b) The total stray current as measured shall not exceed 100 mA. Where all track circuits to
be installed on the line are less than 100 metre long, the highest acceptable figure of stray
current is 10 mA.
18.1.1.1 All block instruments shall be of robust construction and approved type only.
18.1.1.2 On sections where A.C. voltages are induced due to power line parallelism,
suitable block instruments with appropriate protective measures shall be
provided as per Section
18.1.3.0 Prevention of irregular operations - There shall not be any opening giving
access to the interior of the instrument through which it is possible to operate
the mechanism by any irregular means.
18.1.4.0 Locking and sealing facilities - Facilities shall be provided for locking and
sealing the instruments. The doors of the instruments giving access to the
internal mechanism shall be provided with a double lock, the key of one of
which shall be in the custody of the Station Master on Duty and the key of
the other will be with the technician signal in charge of the maintenance of
Block Instruments. It shall not be possible to open the door of the Block
Instruments without the co-operation of both the agencies.
Note: It is desirable to monitor Block door opening through Data logger
where ever feasible.
18.1.8.0 “An isolated power supply (battery in standalone mode or DC-DC Converter
with isolated output) shall be used for line circuit for each block instrument.
This power supply shall only feed the block instrument and not any other
circuits. The power supply housing shall be locked and sealed if provided in
(a) When the instruments are normal and there is no train in the block
section, "Line Closed" at both the stations.
(b) When Line Clear for a train to leave the Block station in rear has been
given, "Train Coming From" at the receiving station.
(c) When Line Clear for a train to leave a Block station has been received
from the Block station ahead, "Train Going To" at the sending station.
18.1.12.0 Operation:
18.1.12.1 "Train Going To" and "Train Coming From" - The instruments shall be such
that the co-operation of the Station Master at the other end of the section
shall be necessary. Even with the co-operation of the Station Master at the
other end, the Station Master has to go through one or more definite moving
operations on the instrument in addition to working of bell plunger.-
(a) before he can grant Line Clear to the Station Master at the other end of
the section to release a token, or
18.1.12.2 "Line Closed" - Both the instruments shall be restored to normal before a
further operation of setting the instrument to "Train Going To"/"Train Coming
From" can be carried out. It shall not be possible for the instruments at either
end of the section to be restored to normal without the co-operative features
indicated in Para 18.1.12.1
18.1.13.0 Operation of "Line Clear" receiving and granting mechanism - It shall
not be possible for the mechanism which permits a "Line Clear" to be
received and that which permits a "Line Clear" to be granted to be in
operation at the same time.
18.1.14.0 The instruments that is set to "Train Going To" for initiating a train movement
shall be the first one to be restored to "Line Closed" on complete arrival of
the train at the receiving station.
18.1.15.0 Extraction of token.—It shall be possible to extract one token only when the
instrument has been set to "Train Going To". It shall not be possible to
Chapter - 18: Block Instruments, BPAC & IBS working
18.1.16.0 Token instruments shall be so installed that a token of one block section
cannot be placed in the instrument of an adjacent section and preferably
such that if the token is over-carried, it cannot be placed in an instrument at
the next station.
18.1.17.0 The tokens of each section shall be engraved with the code name of the
stations at both ends of the block section and with a serial number.
18.1.19.1 "Train Going To" and "Train Coming From ": The instrument shall be such
that even with the co-operation of the Station Master at the other end of the
section, the Station Master has to go through one or more definite moving
operations on the instrument in addition to the working of bell plunger.
18.1.19.1 (a) before he sets his instrument to " Train Coming From ".
18.1.19.1 (b) before he sets his instrument to " Train Going To ".
18.1.19.2 "Train On Line" Means shall be provided to ensure that the instruments are
set to "Train On Line" automatically by the entry of the train into the block
section and maintained in that position until the train has cleared the block
section. This indication shall be in addition to the "Train Going To" or "Train
Coming From" indications of the handle.
18.1.19.3 "Line Closed" Both the instruments shall be restored to normal before a
further operation of setting the instrument to "Train Going To"/"Train Coming
From" can be carried out. It shall not be possible for the instruments at either
end of the section to be restored to normal without the cooperative features
enumerated in Para 18.1.19.1.
18.1.20.1 "Train Going To" and "Train Coming From": The co-operation of the Station
Master at the other end of the section may be dispensed with. The
instrument shall be such that a button in addition to the bell button shall be
operated for "Train Going To" position.
18.1.20.2 "Train On Line": Means shall be provided to ensure that the instruments are
set to" Train On Line " automatically by the entry of the train into the block
section and maintained in that position until the train has cleared the block
section. This indication shall be in addition to the "Train Going To" or "Train
Chapter - 18: Block Instruments, BPAC & IBS working
18.1.20.3 Line Closed.— Both the instruments shall be restored to normal before a
further operation of setting the instrument to "Train Going To"/"Train Coming
From" can be carried out. The instrument shall be such that a button in
addition to the bell button shall be operated by the receiving station for
setting both the instruments to the "Line Closed" condition. This feature can
be dispensed with where an automatic device of closing the Block section is
provided.
18.1.21.4 Operation of "Line Clear" receiving and granting mechanism — It shall not be
possible for the mechanism which permits a "Line Clear" to be received and
that which permits a "Line Clear" to be granted to be in operation at the same
time.
(i) when the train enters the block section at the sending station;
(ii) when the train has passed the Home Signal at the receiving station.
(b) Shunting key suitably interlocked with the Block instrument for use as an
authority for shunting behind the Last Stop Signal and upto the opposing
First Stop Signal.
18.1.23.0 Indicators for Up and Down Lines :- The Instruments shall be provided
with Visual indicators separately for Up and Down Lines to show the
following three conditions :-
(a) Line Closed
(b) Line Clear
(c) Train On Line.
18.1.25.0 Operation before granting or receiving Line Clear :- The instrument shall
be such that the Station Master has to go through one or more definite
moving operations on the instrument besides working the bell or plunger
before he can grant Line Clear.
18.1.26.0 Audible Indicator :- Where required, the instruments may be provided with
audible indicators
(a) to warn the receiving station when the train has passed the Home Signal,
and
(b) to warn the sending station when the train has passed the Last Stop
Signal.
18.1.28.0 The requirements indicated in paragraphs 18.1.23.0 and 18.1.26.0 will apply
to these instruments. In addition, the following shall be provided in these
instruments :-
(a) Automatic "Train On Line" :- Means to ensure the instruments are set to
"Train On Line" position automatically by the entry of the train into the block
section and maintained in that position until the train has passed the Home
Signal at the receiving station and the instrument set to " Line Closed "
condition.
(b) Audible Indicator :- Audible Indicator to warn the receiving station when
the train enters the block section at the sending station.
(c) Shunting Keys :- Two Shunting keys, one for each line, suitably
interlocked with the block instruments for use as an authority for shunting in
the block section.
18.1.29.0 Use of track circuits for proving block section to be clear - On sections
where use of track circuits for proving the block section to be clear is to be
introduced, the following equipment shall be provided :-
(a) Track circuits or axle counters extending from the Last Stop Signal of the
block station at one end of the block section to the other end of the block
section
(b) An indicator in each block station to show whether the block section is
occupied or not.
(c) A control to ensure that the Last Stop Signal of the block station in rear is
automatically replaced to ' ON ' by the passage of a train and maintained in
that position until the train has cleared the block section
(d) A control to ensure that the First Stop Signal is automatically replaced to
' ON ' by the passage of the train
(e) On single line, a control to ensure that the opposing Last Stop Signals of
the Block section cannot be taken ' OFF ' at one and the same time.
18.2.30.2 If any other block instrument is to be used, prior approval of Railway Board
shall be obtained.
18.2.30.3 Block instruments may use special PVC insulated quads in the aluminum-
sheathed cable/4 or 6 quad jelly filled telecommunication cable or other
suitable communication means, like OFC and radio, for their working.
18.2.30.4 When quad cable is used for the working of block instruments, Block
Telephone and Block Bell circuits shall be worked through a transformer
utilizing the two pairs of block quad. The Block circuits shall be worked on
the phantom pair or by other suitable means.
18.2.30.6 The Block Bell shall be worked through Block Bell equipment of approved
type.
18.2.30.7 Separate line battery or DC-DC converter shall be used for each block
instrument. This battery shall feed only the block instruments and not any
other circuit.
Note:- Two different earths shall be provided separately for SPD and Block.
18.2.30.8 When OFC, Radio or other communication means are used for block
working, Universal fail-safe block interface (UFSBI) of approved design shall
be used. UFSBI shall be installed in relay/panel room and which may not be
always close to the place where block instruments are installed. In case the
distance between UFSBI and block instrument is more than 500 metres,
block filter and block bell and telephone shall be inserted in cable pairs
connecting them.
(a) Where earth return is used, the rest contact of the instrument shall be
substituted by the contacts of a slow release relay. The arrangement shall be
Chapter - 18: Block Instruments, BPAC & IBS working
(b) Whenever stray DC is present in the earth, metallic return is provided for
block circuit. Metallic return should be used with a modified filter circuit
eliminating the condenser. The chokes and surge arrestors shall be retained
and shunt resistors shall be provided across the Galvo (150 ohms) and
Polarised Relay (77 ohms). The resistors shall be of substantial rating so that
they do not get open circuited. The circuit details are illustrated in drawing
No. 18 D3. In this case, slow to release relay is not required.
(a) IRS type Block Instrument with Block filter shall be used for Double Line
section electrified with 25 kV AC. The circuit details are illustrated in Drawing
No. 18 D4.
(b) The voltage of the Battery shall be sufficient to ensure not less than 18-
ma and not more than 25-mA current through the polarized relay. Needle coil
resistance shall be modified to obtain this level of current
18.3.31.2 The Table or other fixture on which instruments are placed must be
substantial and the Instruments are securely fixed there on.
18.3.31.3 Turn-table arrangement may be provided for fixing the Token and Handle
type instruments to enable easier maintenance but the plate on which the
instrument turns shall be securely fixed to the table.
18.3.33.5 Specification of Wires:- All wires or cables shall be in accordance with the
Indian Railway Standard Specification or other approved specification.
18.3.33.6 Lightning Dischargers shall not be located in the Block Instrument but
installed separately and shall be the demarcating point for test purposes.
18.3.35.1 It shall be ensured that induced voltage due to power line parallelism does
not exceed 150V and the short circuit fault current does not exceed 430V as
prescribed by CCITT.
18.3.35.2 If the induced voltage goes beyond these limits, overhead block circuit shall
be transferred to an underground telecom PET quad cable/OFC/Radio, so as
to bring the induced voltage within the permissible limits.
18.3.35.3 Since the immunity of PR relay is only up to 10V, block filters shall be used in
all block instruments using this relay where this limit is exceeded.
18.3.35.4 Block filters shall be used with Handle type Block instruments using
frequency coded signal.
18.3.35.5 Use of single line push button token less block instruments is permitted in
sections where length of parallelism does not exceed 1.5 Km, so as to
ensure that the DC coding used in these block instruments is not distorted.
18.3.36.0 Earth
18.3.36.2 The length of the Earth wire shall be as short as possible and cross section
of the wire not smaller than the size of the line wire and in any case shall not
be smaller than 4mm dia. The earth wire shall not have a sharp bend or
spiral. Earth wire should be adequately protected from mechanical injury and
be efficiently connected to the earth. All connections to the earth shall be well
soldered.
18.4.39.0 Block Instruments must be mounted level (spirit level may be used) so that
tokens will not get into any particular race in case of ball token instrument
and the token will not tilt in case of tablet token instrument.
18.4.40.0 Tests to be conducted after installation and before commissioning :-
18.4.41.1 Check that correct polarities are connected to the instruments at both the
ends.
18.4.42.2 Check that all mechanical parts are free to move without undue friction and
that there is no jamming of moving parts.
18.4.43.3 Check that the commutator does not change unless the token gets into the
races in the case of Ball Token instruments and slides down the rail beyond
the tablet receiver in the case of Tablet Token instrument.
18.4.44.4 Check that the insulation of electrical components and internal wiring of the
block instrument is proper and free from leakage from the instrument
body/earth.
Note- RDSO Booklet STS/E/BTI/IMI may be referred to for detailed
instructions regarding installation & testing.
18.5.47.0 All the external connections to the block instrument shall be removed and
insulation resistance measured between individual insulated circuits and
Earth. The minimum value between each individual insulated circuit and
Earth shall not be less than 10 mega ohms.
18.5.50.0 Check that the Last Stop Signal at the sending station cannot be taken 'OFF'
until the receiving station instrument is set to "Train Coming From" condition
and the sending station instrument is set to "Train Going To" condition.
18.5.51.0 Check that the Line Clear can be granted only when reception signals and
the Last Stop Signal are proved at 'ON'.
18.5.52.0 Check that the Last Stop Signal is replaced to 'ON' by the entry of a train into
the block section and the same is maintained in the 'ON' position until the
train has cleared the block section and the instruments are brought back to
the 'Line Closed' condition and fresh "Line Clear" is obtained.
18.5.53.0 Check that the opposing Last Stop Signals of the block section cannot be
taken "OFF" at one and the same time.
18.5.54.0 Check that the circuit for proving the arrival of a train is directional.
18.5.55.0 Check that the shunting key can be taken out only when the instruments are
in "Line Closed" condition or "Train Going To" condition.
18.6.57.0 Block release shall be by the operation of two track circuits sequentially.
18.6.59.0 Check that the commutator handle is locked first before the "Train On Line"
indication appears on the indicator when the handle is turned from "Line
Chapter - 18: Block Instruments, BPAC & IBS working
18.6.60.0 Check that the Block Clearance Relay picks up only after the commutator is
turned to "Train On Line" position.
18.6.61.0 Check that the Last Stop Signal cannot be taken 'OFF' when the commutator
is in other than "Line Clear" position.
18.6.62.0 Check that the Last Stop Signal is automatically replaced to 'ON' when the
train enters the block section and continues to remain in the 'ON' position
until the train has arrived at the receiving station and a fresh "Line Clear' is
obtained.
18.6.63.0 Check that when the commutator is turned from "Line Closed" position to
"Train On Line" position, the commutator is free for return to Line Closed'
position.
18.7.65.1 Tokens, which are cracked or deformed or have worn to a size smaller than
the normal size or are damaged in any other way and are liable to jam in an
instrument and cause a failure shall be removed, broken up and returned to
Stores. Advice of tokens that have been removed shall be given to all
concerned.
18.7.65.2 Token so removed shall be replaced with another token of the same number
and all concerned advised.
18.7.67.0 Particulars of lost tokens on Card No. S&T/TL, as per Annexure – 18/2 shall
be conspicuously exhibited near the relevant instrument for the information of
the Operating Staff,
18.7.68.0 If a lost token is not found for six months, it shall be replaced with a token of
next higher number in continuation of the series in use on the section. The
lost token, if found subsequently, shall be broken and returned to stores.
18.7.69.1 Technicians shall, whenever necessary, transfer tokens from the instrument
in which they have accumulated to the instrument at the other end of the
section. Each Technicians in charge of single line token instruments shall be
provided with a "Token Balance Book" consisting of Form No. S&T/TB, as
per Annexure – 18/3, serially numbered. Each book before issue shall be
endorsed by Senior Section Engineer(Signal) as under :-
18.7.69.2 Technicians shall fill up portions 'A' and 'B' of Token Balance Book form and
take the signatures of –
i. The Station Master of the Station from where tokens have been extracted
to verify that token numbers as mentioned were extracted from the
instrument with his permission;
ii. The receiving Station Master to verify that token numbers mentioned in the
book have been correctly deposited in the relevant instrument.
18.7.69.3 An entry in the "Train Signal Register" shall be made to this effect.
18.7.70.0 Token pouches shall be kept in proper repair by the Traffic Department and
damaged pouches shall not be allowed to be used.
18.8.73.1 Locks : - Electrical or Mechanical Locks are in a condition that they are not
liable to be forced.
18.8.73.2 Indicators :- Indicators operate fully and return to the normal position
correctly when released.
18.8.73.3 Contacts :- All contacts are clean and free from pitting, if surfaces are pitted,
they shall be cleaned with chamois leather and refurbished.
18.8.73.4 All springs are in good condition and kept properly adjusted.
18.8.73.5 Relay armatures :- Relay armatures are free and return to their normal
position when no current is flowing.
18.8.73.6 Track Circuits : - Instructions as laid down in Chapter 17 are adhered to.
18.18.73.7 External Wiring : - All wiring is in good condition and free from joints. Joints,
wherever necessary, are properly soldered and insulated.
18.8.73.8 Terminal Screws : - All terminal screws, lock nuts and locking screws are
kept tight and split pins opened.
18.8.73.9 Batteries :- All batteries are kept clean, terminals tight and free from dirt or
corrosion and maintained in accordance with instructions in Chapter 16.
18.8.73.10 Lightning protector :- Lightning and power protective devices and earth
connections are effective and in good condition.
18.8.73.11 Block instrument telephone :- Block instrument telephone, its flexible cord
and the condenser or other means provided for isolating the telephone from
the Block instrument circuit are in good condition. The isolation is such that
there is no direct path for the current to flow from one circuit to the other.
18.8.73.12 Receiver diaphragms are not buckled and are at the correct distance from
the pole pieces.
18.8.76.0 Block earths shall be tested for resistance at intervals of not more than 12
months by the Section Engineer(Signal) or Senior Section Engineer(Signal)
in accordance with Annexure – 18/4. Where the resistance exceeds 10
ohms, action shall be taken to reduce the resistance by providing additional
earths in parallel.
18.8.77.0 In A.C. electrified areas, two different Earth shall be provided for Discharger
and Block Earth.
18.8.78.0 The four Terminal Condenser used in filter shall be connected in such a way
that the DC circuit is completed through the plate or foil of the condensers. It
shall be ensured that any break in the foil or Earth connection, which might
affect the efficiency of the filter, puts the circuit Itself out of use.
18.9.80.0 Token indicator shall be checked to see if it is free to move. The pin shall be
oiled once a fortnight with axle oil medium grade to IS: 1628. Effectiveness of
'No token' lock shall be checked. It shall not be possible to take handle to
Train Going To' position when token indicator shows Red.
18.9.81.0 Care shall be taken to see that "Train Going To" and "Train Coming From"
locks rocker arm is free to move about its fulcrum pin. The locks shall be
about 1mm above the rack; if not, the locks shall be changed. The edge of
the lock shall be square.
18.9.82.0 It shall be ensured that all parts of the instrument, which undergo wear and
tear are replaced at the time of overhauling.
18.9.83.0 The locking Pawl shall be checked to ensure that it is correctly shaped,
Chapter - 18: Block Instruments, BPAC & IBS working
18.9.84.0 Care shall be taken to see that in the case of Tablet instrument, the tablet
holding arm release lever is working satisfactorily and the tablet can be
released only after full rotation and release of the instrument handle in the
Train Going To" position.
18.9.85.0 It shall be checked that the notches in the rack are correctly shaped and
square.
Note : RDSO Booklet No. STS/E/BTl/IMI may be referred to for detailed
instructions regarding maintenance of Token instruments.
18.9.86.0 Single Line Token less Instruments – Push Button Type : The tests
enumerated in paragraphs 18.5.50.0 to 18.5.55.0 shall be carried out during
routine maintenance.
18.9.87.0 Double line Block Instruments – SGE type: Locking assembly shall be
replaced during each overhauling irrespective of its condition. It shall also be
ensured that all parts of the instrument which undergo wear and tear are
replaced at the time of overhauling as per approved instructions.
18.9.89.0 Degraded working for BPAC: Whenever Axle Counter system connected
to Block Instruments fail and such failure is likely to continue longer than one
day(due to any reason viz Landslide / Severe cable damage etc), the Block
working shall be given in degraded mode of working (where technically
feasible) by isolating axle counter interface and verification of last vehicle
shall be done by Operating staff duly following provisions of GR 4.17.
Note :- Such a degraded arrangement shall be provided with a counter
whose counting shall be registered in the Train Signal Register with reasons
thereof. This shall also be monitored through Data logger.
18.11.90.1 Various parameters of axle counter track equipment and UFSBI shall be
maintained within permissible values as per the instructions issued from time
to time and as per the OEM manuals.
18.12.91.1 Various parameters as per the instructions issued from time to time shall be
maintained within permissible values as per the OEM manuals.
18.12.91.2 It shall be ensured that various signal levels at the prescribed points of
electronic equipment are within permissible limits.
18.13.92.1 IBS is an arrangement made for increasing the section capacity by splitting
of a relatively long block section into two portions namely rear section and
advance section by installing an IBS at the point of bifurcation of that running
line with respect to the nominated direction of the traffic.
18.13.92.2 The rear section i.e. "station controlled intermediate block section" starts
from LSS of the rear station and ends at IBS including 400 m block overlap in
that direction
18.13.92.3 Advance section i.e. "block controlled Intermediate Block section ”starts from
IBS and ends at home signal of advance station including block overlap in
that direction
18.13.92.4 Track sections both in Rear section i.e. "station controlled intermediate block
section" & Advance sections i.e. ‘block controlled Intermediate Block section”
are monitored either by axle counter or By Track circuit.
18.13.92.5 Train entry into rear section i.e. "station controlled intermediate block
section" is controlled by LSS of rear station in that direction.
18.13.92.6 Train entry into advance section i.e. ‘block controlled Intermediate Block
section” is controlled by IBS in that direction.
18.13.92.7 A Signal Post Telephone (SPT) or any approved type communication shall
be provided at the IBS post for communication with the station in the rear
18.13.92.8 IBS system needs distant and inner distant signal where applicable for pre
warning of IBS.
18.13.92.9 IBS works like Class C station & IB Distant signals are to be provided to
match with the section signaling.
18.13.92.12 Provision must be there to indicate a train passed IBS at danger/ blank.
18.13.92.13 IBS system needs panel with various indications and push buttons at each
block station pertaining to direction of traffic.
18.13.92.14 The IBS shall be so located that the running time of the rear section will be
equal to the running time of the advance section in such a way that optimum
headway can be maintained between the trains at maximum possible speed.
However, the gradient at the approach of the IBS and the existence of
neutral section, visibility of signals etc; are also to be considered for locating
the IBS. If required, up & down IBS may be staggered to suit the local
condition.
18.13.92.16 Resetting Operations: There are two types of resetting operations which
requires co-operation of the other end Station Master.
(a) When a train passes IBS at danger/blank
(b) When axle counter fails
18.13.92.17 IBS system will permit only one train in the entire block section, when a train
passes IBS at danger or axle counter is not clear even after the passage of
the train beyond the axle counter section.
18.13.93.1 IBS should be interlocked with Double line block instrument/Block Panel
(BPAC USING UFSBI/SSBPAC)
18.13.93.2 IBS shall not be taken off for Train unless line clear has been obtained from
Block Station in advance.
18.13.94.1 Provision shall be there to establish the direction of traffic for IBS in single
line.
(a) First direction of traffic shall be established and then line clear shall be
obtained from the Block station in advance as per the established direction of
traffic.
(b) Only after establishing the direction of traffic the train movement in the
station controlled intermediate block section shall be permitted
(c) IBS shall not be taken Off unless the line clear has been obtained from
Block Station in advance and direction of traffic is established.
18.13.94.2 IBS should be interlocked with the single line block instruments/Block Panel
(BPAC USING UFSBI/SSBPAC) for IBS system in single line
Note : This Chapter has under mentioned Annexures for further study
BLOCK SECTION……………………….
Serial No…………………………………………….
…………………… Railway
Name of Maintainer………………………
Portion A Portion B
Tokens taken from ……………………… Tokens taken from ………………………
(Name of Station) (Name of Station)
each token taken
Serial Number of
Serial Number of
Station Master
Station Master
Tokens taken
Tokens taken
Date & Time
Signature of
Signature of
Signature of
Total No. of
Total No. of
each token
Maintainer
Maintainer
brought
brought
away
away
1 2 3 4 5 6 7 8 9 10
(2) To test an Earth, iron bars shall be driven about 6 m from the Earth to be tested and 5 m
from each other as shown in the diagram below.
The bars shall be used as temporary Earths and driven in the ground for 1 m, 0.25m at a
time, then worked backwards and forwards so as to leave a space for watering. Salt
water shll be used to ensure that the bars make a good connection with the Earth.
Should salt be not available a weak solution of salamoniac in water may be used.
In the diagram, E-1 represents the Earth under test, E-2 and E-3 represent temporary
earths.
The resistance in ohms, between the respective Earths shall be tested with the
Wheatstone Bridge or G.P.O. Detector or Megger Earth Tester.
E1
6M 6M
E2 E3
6M
19.1.2.0 While using metal tools like screwdrivers, nose pliers, cutting pliers, etc.
near the working apparatus, care shall be taken to avoid short circuiting and
consequent blowing out of the fuse.
19.1.3.0 All staff shall possess adequate number of appropriate insulated tools like
rubber gloves, pliers, screw drivers, etc. A rubber floor mat may be used for
standing while attending to circuits carrying more than 110-Volt except in
outdoor locations.
19.1.4.2 Care shall be exercised to avoid dropping of particles of solder and clippings
of wire on adjacent terminals and apparatus.
19.1.4.3 In addition to soldering irons of adequate wattage ( 65-125 W), for the type
of work done, the following shall be at hand:
(c) A mica sheet of adequate size or a suitable stand for soldering iron
19.1.4.4 Electrical soldering irons shall be switched off when not in use over
extended periods.
19.1.4.5 While making a soldering joint, the surface shall be thoroughly cleaned,
fluxed and tinned
19.1.4.6 Use of too much solder shall be avoided to prevent lumpy connection.
19.1.4.7 Soldering iron shall not be held on the wire connection for too long to avoid
damage to insulation.
19.1.4.8 Imperfect joints are the result of any one of the following causes, which
should be avoided,
(b) Soldering iron held on the connection for insufficient length of time
19.1.4.9 A newly soldered connection shall not be disturbed till the solder has
thoroughly cooled.
19.1.4.10 Railway to conduct the periodical training on proper practices for soldering,
in-house or through outside agencies.
19.1.5.1 While terminating wires, care shall be taken to bend the wires in clockwise
direction.
19.1.5.2 Wire strippers shall be used for the purpose of stripping off the wire
insulation. Cutting pliers shall not be used for the purpose.
19.1.5.4 Not more than two wires shall be terminated on one terminal.
19.1.5.5 Multi-strand wires shall be terminated on terminal lugs and covered with
insulation sleeves.
19.1.5.7 Crimping tools of appropriate design should be used and whenever lugs are
crimped, proper soldering should also be ensured.
Colour Light Signals shall be multi unit approved type and with LED lamps
of approved type.
19.2.9.1 Colour Light Signals may be mounted on a rigid ground post or a signal
gantry clear of standard dimensions.
19.2.9.3 Signal posts shall be kept plumb and packed with suitable material
19.2.9.4 Suitable packing may be used to close the excess gap from post to signal
unit, surface base to post. The cable entry at the signal unit should be
provided with wooden plug around the cable to close excess gap to prevent
rodent entry.
19.2.10.0 Alignment :- Each signal unit shall be aligned correctly for better visibility.
19.2.12.0 Cables :-
Cables shall be used from the point of operation to the location box/signal
unit and/ or location box to the signal unit. Cable shall be protected suitably
at the entry points of location box and signal post.
19.2.13.0 Gaskets and Sealing :- All openings shall be gasketted and cable/wire
entrance shall be sealed to make the enclosure water tight, dust-proof and
vermin-proof,
19.3.16.1 The JE/SSE (P.Way) has made all the provisions at the Points as detailed in
Chapter 12
19.3.16.4 The top of sleepers which are to support the point machine are at level and
that surrounding ballast is well tamped to prevent sinking during the
passage of train.
19.3.16.6 Proper drainage shall be provided to avoid water logging near point area.
19.3.17.0 Wiring :- Wiring from the point of operation to the location box/apparatus
case nearest to the machine shall be in cable. The cable shall be of
appropriate size to keep the voltage drop minimum. The connection
between location box/apparatus case and point machine shall be through
underground cable adequately protected below track and near point
machine, through Gl/Flexible hose pipe or equivalent. It shall be tested for
insulation and continuity before bringing into operation.
19.3.17.1 The excess gap around cable entry to the machine shall be plugged to avoid
rodent entry/water ingress.
Electric Point Machine shall be provided with suitable gaskets and wire
entrances shall be sealed to make them water tight and dust proof. All the
extra openings shall be closed as far as possible.
19.3.19.0 Locking :- Electric Point Machine covers shall be locked. The cover
provided for insertion of crank handle shall also be locked with separate key
providing access only for crank handle and crank handle key.
The machine shall be hand cranked to the end of the stroke to close the
tongue rail. Insert 1.6 mm test piece between stock rail and switch rail at
150 mm from toe of the switch and operate the point. Ensure detector
contacts just make. A test gauge of 3.25 mm shall be inserted between the
switch rail and stock rail at a distance of 150 mm from the toe of the switch.
The detector connection of the closed switch shall be adjusted till the
appropriate detector contacts are just broken. The same shall be repeated
at the other end of the stroke. All the relevant nuts shall be tightened.
Note:- Where lock slide is provided in the machine, during switch detector
adjustment the test shall first be done with fictitious locking. After completing
the above test, same test be repeated with machine properly locked.
19.3.25.0 Obstruction Test:- The point driving rod and the lock connections of the
machine must be so adjusted that with 5 mm thick test piece obstruction
placed between the switch and the stock rail at 150 mm from the toe of the
switch:-
(a) the point cannot be locked,
(b) the point detector contacts should not assume the position indicating
point closure &
(c) Friction clutch should slip.
19.4.27.0 Electric point machine with clamp lock type of machine. (Components of
Thick web switches as per RDSO Drg. No. RDSO/S-3454 for 60 Kg rail and
RDSO/S-3455 for 52 Kg rail).
19.4.28.0 Thick web switch has wider crossing angle and wider switch opening of 160
mm (as against of 115 mm of ordinary cross over)
19.4.30.0 A Clamp Lock clamps the closed switch with the stock rail to ensue firm grip
with stock Rail.
19.4.31.0 For the working of clamp lock, the throw bar of points machine is provided
with a total of 220 mm stroke (60 mm for unlocking of closed switch rail and
movement of open switch towards stock rail, 100 mm for the throwing of both
switch rails simultaneously there by open switch rail gets closed and next 60
mm for the locking of closed switch rail and open switch moves 60 mm there
by total opening become 160 mm of point)
19.4.32.0 Thick web point (TWS) is compulsory for speeds above 140 kmph
19.4.33.0 Due to complementary tapers in switch and stock rail, the switch rail toe fits
underside the stock and therefore the wheel of the train engages the switch
rail well after 6" from toe. Therefore, damage and wear and tear of the switch
is prevented
19.4.34.0 Provides direct locking between tongue rail and stock rail in closed and open
position
19.4.35.0 No stretcher bar is used and switches can move independent of each other
19.4.36.0 A spring setting device (SSD) is provided at junction of Rail head (JOH), in
lieu of stretcher bars, to assist in proper setting of switch upto junction of Rail
head (JOH), which is placed between sleeper number 13 and 14. SSD also
maintains point gauge. SSD installation and maintenance is responsibility of
Engg Dept
19.4.37.1 Bring the toe 32 mm in advance of centre line of sleeper No.3 and the
distance between sleeper No.3 and 4 to 745 mm , where point machine to
be installed (From centre line to centre line)
19.4.37.2 Ensure that insulated gauge tie plate is provided on sleeper No. 3. Ensure
distance between point machine center to nearest stock rail inner edge is
1140 mm
19.4.37.4 Provide spring setting device of “approved design” at junction of rail head
(JOH).
19.4.37.5 Maintain gap at junction of rail head (JOH) not less than 57 mm for every
flange way
(i) For marking holes in stock rails mark centreline on the web of stock rail
at the height of 76 mm from bottom of stock rail up to the length of 550
mm from toe.
(ii) Mark centre punch to the length of 450 mm for I st hole and 530 mm
for II nd hole from the edge of the tongue rail toe.
(iii) Ensure that there is a gap of 80 mm between both the holes (Centre
line to Centre line of the holes) as shown in figure given below.
(iv) Drill two holes of 22 mm dia in the web of both stock rails for fixing
stock rail brackets.
(i) For marking in tongue rails, mark centre line on web of the tongue rail
at the height of 55 mm from bottom of tongue rail up to the length of 500
mm.
(ii) Mark centre punch to the length of 428 mm for first hole and 498 mm
for second hole from toe.
(iii) Ensure that there is a gap of 70 mm between both holes (Centre line
to centre line of the holes).
(iv)Drill two holes of 22 mm dia in the web of the tongue rail for fixing
switch rail bracket.
(a) First make the centre line in the flange of both tongue rails up to 350 mm
length from toe.
(b) Mark punch up to the length of 148 mm for first hole and 328 mm for
second hole from toe in LH tongue rail.
(c) Mark centre punch up to the length of 200 mm for first hole and 272 mm
for second hole from the toe in the RH tongue rail.
(a) First make the centre line in the flange of both tongue rails up to 350 mm
length from toe.
(b) Mark punch up to the length of 200 mm for first hole and 272 mm for
second hole from toe in LH tongue rail.
(c) Mark centre punch up to the length of 148 mm for first hole and 328 mm
for second hole from the toe in the RH tongue rail.
19.4.40.1 Lock and detector rods are to be assembled at site by inserting drop lug in
the threaded portion of the rods. The drop lugs can be suitably turned to suit
LH/RH mounting.
19.4.40.2 Put tapered washer on the foot of the switch rail such that the thicker portion
of the washer is towards the edge of the rail.
19.4.40.3 Now connect jaw of the detector/lock rods with the foot of the tongue rail and
drop lug with the detector/lock slide of the point machine.
19.4.41.0 Adjustment:
19.4.41.1 Lubricate all the moving parts the clamp lock assembly
19.4.41.2 Put grease on the bronze brush in the lock arm assembly
19.4.41.3 Put grease on the notches of the lock slide and fishtail portion of the lock
arm.
19.4.41.4 Loosen the nuts of stock rail bracket so that it can be move freely in its
oblong holes and takes its own portion.
19.4.41.5 Operate the machine with crank handle and adjust the lock and detector
slides usually (Near end first)
19.4.41.7 For proper locking on both sides additional numbers of packing shims have
been provided between switch rail and tongue rail bracket.
19.4.41.8 Required no of shims will be put outside the tongue rail bracket to facilitate
locking on either side.
19.4.41.9 Six numbers of packing shims are provided with each clamp point assembly.
19.4.42.1 The detector slides, lock slides and drive rod must be so adjusted with 5 mm
thick test piece placed between the switch and gauge face of stock rail at 150
Chapter 19: Installation, Testing , Commissioning & Maintenance Of Of Signalling Equipments
19.4.42.3 The point cannot get locked either by clamp lock or by locking segment inside
the point machine.
19.4.42.4 Lock segment does not enter into the notches of locking slides
19.4.42.6 The slipping current is not exceeding twice of the normal working current.
19.4.43.1 Point machine: Check that point machine is insulated from ground
connection.
19.4.43.3 Clamp lock assembly. Check that it is insulated from both the rails.
19.5.45.1 These shall not be newly installed normally (except in few Installations like
LC Gates) and the existing one to be replaced in phased manner. Railways
still having these equipments may please refer the earlier version of SEM
Part-II , September 2001.
19.6.46.4 Track relays shall always be of metal to carbon contact type & normally be of
plug in type, unless otherwise specially permitted.
19.6.46.6 In electrified area, the following relays shall be used:- 9 ohm DC neutral, AC
immunized, 9 ohm DC biased, AC immunized.
19.6.46.7 Double element motor type relay, operating on 83 & one third Hz in AC
traction area and 50 Hz in DC traction area shall be used. Vane type relays
may continue in use till replacement.
19.6.46.8 Relays for track circuit provided with coded, pulsed, electronic (audio
frequency or high frequency track circuit), shall be of an approved type of
track/line relay or as recommended by manufacturer.
19.6.46.9 Where magnetic latch relays are used, the circuit shall be so designed so as
to prevent undue dropping of the relay due to back emf generated by other
relays
19.6.46.10 Wiring of 'Q' type relays shall be done through flexible multi strand wire
preferably and contacts to be paralleled as feasible.
19.6.47.0 Mercury wet contact type relay shall be used for flasher circuits, alternatively,
a solid state flasher may be used. If solid state flasher is used, flashing
indication on operating panel should be provided for indicating healthy
condition of flasher.
19.6.51.0 Flashing of Relay Contacts : If the Period of Storage is more than 3 Years ,
then Relay Contacts shall be Flashed to remove any accumulated Dust ,
before they are transported to Site for Installation
19.6.53.0 Where Relays cannot be located in the Cabin, they shall be housed in
location of approved type which are properly secured.
19.6.54.0 In 'Q' style relay the code pins configurations for plug in relay shall not be
changed by drilling additional holes on plug board to avoid fixing of a wrong
relay which may lead to unsafe condition. In Siemen's K-50 relays, the Code
pins position on base plate should not be changed and to be retained as fixed
by the manufacturer.
19.6.55.0 All relay clips shall be checked for proper locking in the base when plugged
in. Extreme care shall be exercised while removing the clips from the jacks of
the plug-in type relay.
19.6.56.0 In all installations, a relay index board shall be provided for locating relays
easily.
19.6.57.0 Relays involving external circuits shall have cross protection and double
cutting. Signal control relays shall preferably be provided with double cutting.
19.6.58.0 A contact chart shall be prepared duly showing the contacts used circuit-
wise with reference and spare contacts available, wire count for each contact
and relay position in the rack.
19.6.59.1 In case of metal to carbon contact type relays, sealing shall be done at
Manufacturer's premises before dispatch and if the seals have to be broken
due to any defect noticed, resealing must be done at the workshops.
19.6.59.2 In case of metal to metal contact type relays, sealing of the cover shall be
done by not below the rank of the Junior Engineer at site. Whenever seals
have to be broken at site for maintenance purposes, the same shall be done
by an official not below the rank of Junior Engineer.
19.6.59.3 Line Relays shall be energized at the rated voltage specified in the
specification.
Cleaning shall be done regularly from outside so that dust is not deposited on
the relays.
19.6.62.0 Cleaning shall be done regularly so that dust is not deposited on the relay.
There is no loose connection on the terminals, plug in relays is fitted tightly &
the sealing is intact. Metal contacts are not blackened due to arcing. There is
no pitting of carbon contacts. No foreign materials are inside the relay. There
is no rusting or sulphation on the parts. Relays are not due for P.O.H.
19.6.63.0 (a) Pickup and drop away values shall be maintained within the limits
specified by the manufacturer. Relays shall not be tilted or turned over to
close the contacts.Track relays shall be inspected visually every two years by
the JE/SSE and the following visual checks conducted :
(i) Movement of armature and contact carriage;
(ii) Wiping of contacts;
(iii) Arcing of contacts, if any;
(iv) Pitting or charring of contacts;
(v) Dust on contacts;
(vi) Electroplating
(vii) Corrosion, rusting of components;
(viii) Cracks or breakage in components;
(ix) Presence of fungus, if any;
(x) Charring of cover near contacts (for plug-in relays)
(xi) Correctness of label;
(xii) Presence of seal.
(b) The relay that is in any way defective should be changed at once and sent
to shops together with a brief report stating the nature of the defects. On no
account should any attempt be made by the line staff to rectify the relay. The
connection of DC track relay shall be quarterly interchanged to prevent
permanent magnetisation.
19.6.64.1 All relays used in vital circuits shall be visually inspected each time during
inspection.
19.6.65.0 JE/SSE/Section Engineer shall visually inspect the relays. During visual
inspection, relay shall be taken out of service if any of the defects are noticed
in respect of :-
(a) Movement of armature and contact carriage;
(b) Wiping of contacts;
(c ) Arcing of contacts;
Chapter 19: Installation, Testing , Commissioning & Maintenance Of Of Signalling Equipments
All metal to carbon contact miniature plug-in type relays other than track
relays should not be overhauled. these relays should not be used after
completion of the codal life of 25 to 30 years or after their falure. Plug in type
track relays have to be replaced on completion of 12 years or earlier if
warranted by the actual condition of the relay and/or its usage.
Section 7 : Fuses
19.7.67.1 Fuses shall be of an approved type. Normally non-deteriorating type, PPTC
fuses, 'G' type, alarm or cartridge type fuses shall be used. When fuse is not
provided with fuse blown off indication, additional indication circuit may be
provided.
19.7.67.2 At the time of commissioning of any signalling installation, the normal load
current of every circuit shall be measured and recorded. These recorded
values shall be checked with the theoretically obtained values. Fuse of
correct capacity which should be not less than 2.5 times the rated current,
shall be provided.
19.7.67.3 When there is a case of fuse blowing off, the concerned circuit current shall
be measured and compared with the original recorded value. If there is a
variation, action shall be taken to locate and remove the defect before a new
fuse is inserted.
19.9.71.0 Suitable proforma should be devised for recording the tests of electrical
equipment before testing of the installation is taken up to ensure availability
of records of the tests and their analysis.
19.9.73.1 It shall be checked that the work has been carried out in accordance with the
approved plans and that equipment is of proper type and is in good condition.
19.9.73.2 The following aspects shall be checked during the physical inspection:
(a) The signals, location boxes and other out-door equipment are as per
approved plans and are in good condition. Arrangements for proper
ventilation, where provided, are not choked.
(b) Each location contains all the apparatus required as per approved plans,
the apparatus is of approved type and that the power supply equipment,
batteries, fuses, etc., are installed according to the approved plan and
specification.
(e) Each wire is tagged or marked where feasible so that it can be identified
at each end and the nomenclature on the tag corresponds to that on the
wiring diagram. The tags or other sleeves of identification shall be of
insulating material.
(f) The number of wires terminated on each terminal or relay terminal boards
or other devices are counted and tallied with the number of wires shown in
the wiring diagrams.
(g) All connections on terminals and binding posts are properly secured,
(h) The lightning arrestors are properly connected and earthed as per plan
(i) Detailed specifications & instructions for inspection and testing of different
types of equipment as applicable to them should be available.
(j) All other equipment such as lever frames, cable sheaths, signal screens,
location huts, etc., in A.C. electrified areas are properly earthed as per
requirements contained in Chapter 22.
19.9.74.1 Wiring shall be checked to ensure that it has been carried out as per
approved wiring diagram. Point to point testing shall be carried out before
plugging in the relays. Wires shall be tested one by one for continuity and
insulation.
19.9.74.2 Prior to conducting continuity and insulation test, contact occupancy test
must be carried out for each relay as per the contact analysis available. The
number of contacts allotted must tally.
19.9.74.3 During the course of continuity testing, wire count test shall also be done
simultaneously to verify the number of wires actually available on each
contact.
19.9.74.4 All cables shall be tested in accordance with the instructions given in Chapter
15
19.9.75.1 It shall be checked that each individual circuit is actually controlled by the
proper contacts of the relays or other devices as per wiring diagram.
19.9.75.2 Where feed to a particular device is controlled through two or more paths in
parallel, the check of each path must be carried out separately.
19.9.75.4 Once the indoor wiring works are completed before conducting the system
testing, simulation test shall be conducted. This will ensure the correctness of
indoor system, complete. System testing shall be carried out after all the field
functions are connected to the relay room.
19.9.77.1 After the tests mentioned in previous paras have been carried out, the
electrical installation shall be subject to the detailed operational/system tests.
19.9.77.2 These tests shall be planned carefully. Requisite number of staff considered
essential for carrying out such tests shall be selected and deputed to
concerned locations. They should be equipped with requisite tools, meters,
portable telephones and/or walkie talkie sets so that they are in contact with
the official in charge of testing and other testing parties and take such action
as directed.
19.9.77.3 These tests shall be carried out against approved Selection Table/Control
Table/Route Chart and Signalling Plan.
19.9.77.4 Complete tests shall be carried out against approved Selection Table/Control
Table/Route Chart. Checks against signalling plans for main signal routes
and a few spot checks of the remaining routes shall also be carried out.
19.9.77.5 Following guide lines are laid down for carrying out system tests:-
Each route shall be set up individually. After ensuring that the signal for
this particular route has been cleared, each track circuit controlling the
approach locking shall be de-energised in turn. The signal shall be put
back to 'ON'. Efforts shall be made to alter the route under test and to set
up conflicting route. It shall be checked that it is not possible to cancel
the route set up and/or to set up a conflicting route and/or to individually
operate any point in the route under test. This locking shall be effective till
the set route is cancelled and the time release circuit has operated
Chapter 19: Installation, Testing , Commissioning & Maintenance Of Of Signalling Equipments
(i) Tests shall be carried out to ensure that once a signal is cleared for a
particular route, position of none of the points in the route can be
changed when track circuit immediately in advance of the signal is de-
energised.
(iii) Where sectional route release is not provided tests shall be made to
ensure that the entire route remains locked when any of the track circuits
beyond the signal up to the track circuit controlling the last point is de-
energised.
(iv) In cases where the route is controlled by single track circuit the route
shall be released after prescribed time delay to be effective after the
concerned track circuit has been occupied and cleared by the train.
(i) Each point shall be set to reverse position by operating the controlling
lever/switch/buttons. After the point has been fully reversed, each track
circuit controlling the point shall be individually shunted in turn and
operation of points to normal position shall be attempted. It shall not be
possible to operate the point under these conditions. These tests shall be
repeated with the point set in normal position, attempt being made to
operate it to the reverse position.
(ii) With the obstruction in the points, the point shall be operated from
normal to reverse and reverse to normal and it shall be checked that the
over-load relay where provided gets energised and the feed to the motor
is cut off immediately. Where over load relay is not provided, the feed to
the motor shall be cut off after the lapse of a prescribed time.
(iii) The out of correspondence test shall be carried out by opening cut
out contact of one end of point machine and the point lever/knob/button
operated. The other end of the point may operate but the point indication
relay shall not energise.
(i) The point shall be operated from normal to reverse and reverse to
normal and the position of point detection relay as well as the indication
of the point in the cabin/panel shall be checked for correspondence with
the position of the points at site. It shall also be checked that with the
obstruction in the point, the detection relay is de-energised and both
normal and reverse point indication in the cabin/panel are extinguished
in case of electromechanical signal and flash in case of PI/RRI
installations.
(ii) The operation of the detection relay to the correct position as well as
its de-energisation should be checked by making and breaking the
relevant point detector contacts at site.
(i) It shall be checked that when the crank handle is removed from its
normal position in Electric Key Transmitter/other approved Relay
interlocking arrangement, the signals reading over the concerned
route/zone cannot be taken 'OFF' nor the points could be operated from
the cabin/ panel. It shall also be checked that when the signal reading
over the concerned route/zone is taken 'OFF', the crank handle cannot
be released from its normal position in Electric Key Transmitter/other
approved Relay interlocking arrangement.
Indication when
Indication when
shunting is not
shunting is permitted in
permitted in the
the direction to which it
Type direction to which it
refers
refers
Day Night Day Night
Indication Indication Indication Indication
Black disc
Disc with a Yellow Edge of
No light
Type yellow cross cross light disc
painted on it
Light Yellow cross Yellow
No light No light
Type light cross light
(a) Point Locking Operate point No. 2 to reverse position and clear the signal
route No. 2WBI by operating signal switch/button. Operate point knob 2 to
normal. The point should remain locked. Restore the point knob to reverse.
De-energise 2RWKR. Signal 2WBI shall go to 'ON'. Restore the signal
switch/button to normal. When point No. 2 is free, shunt the track 2T. Turn
the point knob 2 from reverse to normal. The point should remain locked.
Again take 'OFF' signal for route No. 2WBI. Shunt the approach Track
A2WT. Normalize the signal switch/button. Try to alter the route. Route
Chapter 19: Installation, Testing , Commissioning & Maintenance Of Of Signalling Equipments
Clear the signal route 2WBI after setting the route. Try to clear the signal
4EB by operating the relevant switch/button. Signal 4EB should remain in
'ON' position and signal 2W should continue to display 'OFF' aspect.
Similar tests shall be carried out for signal 2E also.
(i) Clear the signal route 2WBI again. Shunt the track 2WT. Signal should
go to 'ON'. Remove the shunt, the signal should not re-clear. Normalize
route and re-clear again. Shunt A2ET and other controlling track circuits
one by one. Signal should go to 'ON' in all cases. Remove the shunt.
Normalize the route.
(ii) Where track circuits provided with redundancy, its proper working
shall be thoroughly tested for redundancy and effectiveness in the
signalling circuits.
(i) Clear the signal 2W for route 2 WBI again. Shunt the track 2WT. The
signal should go to 'ON'. Normalize the signal switch. The route should
be held. Shunt and clear all the back locking tracks as per selection table
in sequence. The route shall be released by sequential proving of tracks
as per the provisions of para 4.3.3 of Relay interlocking specification IRS:
S 36-87.
(ii) Clear the signal route 2WBI again and de-energize the L-xing gate
control relay. The signal should go to 'ON'. Re-energize the relay, the
signal should assume 'OFF' aspect.
(a) No signal taken 'OFF' for a train movement is thrown to 'ON' in the
face of the train.
(c) No point and isolation in a route set for a train movement is disturbed.
19.10.80.1 All the tests indicated in this chapter shall be conducted at the time of new
installation or making any alteration to the existing installations.
19.10.81.1 Polycarbonate Lenses of LED lamp shall be kept clean. A dry soft cloth free
from lint and abrasives shall be used for cleaning.
19.10.81.2 Housing shall be kept clean and opening in inclement or stormy weather
avoided. The condition of the gasket shall be checked to ensure that rain
water does not have access to the interior of lamp unit.
19.10.82.0 Replacement
19.10.82.2 The LED lamps shall be replaced as per prescribed codal life.
19.10.82.3 New lamp shall be pre-tested as per approved instructions before putting into
use.
19.10.83.0 The following checks shall be made periodically
19.10.83.1 The LED lamps bulb shall be seated fixed and fastened properly.
19.10.83.3 All adjusting nuts are properly tightened. Maintenance checks to be done as
per Annexure 19/1
19.10.85.0 Cleanliness :- Machines shall be kept in good condition free from rust, dust
and dirt.
19.10.86.0 Lubrication :- All gearing and bearing shall be properly lubricated according
to manufacturer's instructions.
19.10.87.1 Commutator shall be kept clean, smooth and have bright appearance.
Commutator may be cleaned with chamois leather. Under no circumstances,
shall emery paper be used.
19.10.87.2 Brushes shall be kept clean and properly bedded on the commutator.
Brushes shall have proper pressure and shall be free in brush holders.
19.10.88.0 All cables connections on terminal, motor terminal etc. shall be checked for
intactness.
19.10.89.0 All tail cables shall be checked for their insulation as per periodicity given in
Annexure 15/1.
19.10.91.0 Rain water drainage arrangements shall be checked especially prior to and
during rainy season.
19.10.92.1 Fixing nuts and screws of newly installed point machine often tend to get
loose. Care shall be taken to attend to them and readjust where required. To
prevent this, check nut with spring washer shall be provided
19.10.92.2 All moving parts including locking Dogs and notches slides, etc. shall be
checked for chamfering or undue wear. Where badly worn-out, the relevant
parts shall be promptly replaced.
19.10.93.0 Tests
19.10.93.1 Obstruction Test :-The point driving rod and the lock connections of the
machine must be so adjusted that with 5 mm thick test piece obstruction
placed between the switch and the stock rail at 150 mm from the toe of the
switch:-
(b) the point detector contacts should not assume the position indicating
point closure
19.10.93.2 The Technician shall check whether the current required to operate the
machine in either direction is the same (approximately). The reason for
unbalance, if any, shall be investigated and eliminated.
19.10.93.3 Test the spring in each switch and ensure sufficient spring. It shall not be too
excessive to cause excessive wear on machine part, neither it shall too less
to hold the switch against the stock rail. In either of the case, the point drive
rod shall be adjusted.
19.10.93.5 Friction clutch where provided shall slip at a value prescribed by the
Manufacturer
19.10.93.6 Badly worn-out pins shall be replaced; the holes shall be reamed out and
fitted with a oversized pin. Split pins where provided shall be properly split
out.
Chapter 19: Installation, Testing , Commissioning & Maintenance Of Of Signalling Equipments
19.10.93.8 Cable and wire insulation and continuity tests shall be done
19.10.94.0 It shall be ensured that during obstruction in the point, the feed to point is
automatically disconnected or friction clutch is tripped on overload described
by manufacturer and reconnects only when a fresh operation is done.
Where sequential operation of point machine is done, the maximum time
before disconnection may not exceed to 3.5 times the normal operating time
of one machine.
19.10.94.0 Each JE/SSE in charge of electrical apparatus shall test the operating values
of the machine and adjustments of the machine by obstruction test every
month. The Sectional in charge of the section shall carry out these tests once
in three months.
These shall not be used in new installations and the existing one to be
replaced in phased manner. Railways still having these equipments may refer
to earlier version of SEM Part-II, September 2001.
Maintenance schedules as shown in Annexure 19/3 shall be followed till their
replacement
These shall not be used in new installations and the existing one to be
replaced in phased manner. Railways still having these equipments may refer
to earlier version of SEM Part-II, September 2001.
These shall not be used in new installations and the existing one to be
replaced in phased manner. Railways still having these equipments may refer
to earlier version of SEM Part-II, September 2001.
19.10.98.0 Maintenance of Electric Key Transmitters , Fuse & Fuse Alarm Systems
(a) Points
(ii) Ensure that all nuts and bolts are tight and split pins are opened
properly.
(iii) Lubricate at the following moving parts of the clamp lock fortnightly.
(vii) Ensure that the rodding and other connections are tight.
(viii) Check that the point area is well ballast, packed and free from
vegetation.
(ix) Check that water does not stagnate in the vicinity of points.
(i) Ensure that wire connections of the machine are tight and laced
properly.
(ii) Ensure that the locking segment enters freely into the notches on the
lock slides and with a little pressure in the notch of drive rod.
(iv) Check all parts for any crack or breakage etc. and replace
immediately if any defect is found.
(v) Ensure smooth working of the gears without any cracking noise.
(vi) The slipping of friction clutch during obstruction shall be ensured and
slipping current shall not exceed twice the normal working current.
(vii) Ensure that the carbon brushes are exerting sufficient pressure on
commutator. Clean the commutator properly by using chamoise leather.
(viii) Ensure that all moving parts are free from dust and are well
lubricated.
(x) Ensure that the roller rolls freely on the periphery of the control and lift
Chapter 19: Installation, Testing , Commissioning & Maintenance Of Of Signalling Equipments
(xi) Check that the contact pressure of control and detection contact is
adequate.
(xiii) After every six months or as per instructions issued by the railway
pour lubricating oil, SAE-30/SHELL 100, through inlet in to the oil
reservoir for lubricating gearbox of the motor.
At stations having dense traffic and high speeds, the Railways may prescribe
more frequent inspections, if considered necessary.
(a) Lightning and surge protection shall be provided to protect from following
undesirable effects:
(b) Thermal effect: Excessive energy in lightning discharge may cause fire.
(d) Electrical effect: Due to increase in ground potential, surge current may
damage electronic equipment
(f) Effects on Humans: Electrocution burns or even loss of life and may lead
to cardiac arrest.
(a) S&T equipment shall be protected as per National Building Code 2016
(NBC 2016) and IEC 62305. S&T equipment, including those given below,
are to be grounded and protected from lightning surges. Code of Practices,
Technical Advisory Notes, Guidelines issued by RDSO on the subject shall
be taken into consideration.
(b) Equipotential bonding to be provided for all the equipment for effective
lightning and surge protection in Signal Equipment Room as per RDSO TAN
STS/E/TAN/3006 or latest TAN
(c) External Lightning Protection and Class I, II, III, IV devices are to be
provided at
(a) Earths will be of two types (i) functional (ii) protective. The earth return
used for block instruments is a functional earth which is used to conduct the
current through earth during normal operation/function of equipment. While
the earth for dissipating surges is a protective earth which comes in contact
to equipment's supply line through Surge Protection Devices while
conducting during surges so as to protect the equipment.
(d) The maximum earth resistance shall be specified as per OEM & RDSO
recommendations.
(a) Earthing of cables, equipment, buildings and structures is done for one or
(e) To provide a direct connection with earth for surge protection devices,
lighting protectors, etc.
(f) A separate functional earth of approved type shall be provided for each
block instrument for DC line circuits. The earth shall be as per RDSO
Specifications and Guidelines. Earth resistance upto 10 ohm is permissible.
(g) These earth pits shall then be inter linked using approved arrangements.
(i) Earth required for return conductor facility shall be provided separately.
(b) The lever frame and other metallic frames of the cabin shall be connected
together to a separate earthing.
(f) Block circuits working on earth return through the respective Block filters
(h) In case of signals falling within 2 meters from the electrified track, the
protection screen shall be connected to an earth.
(i) There shall not be any possibility of simultaneous human contact with
metallic bodies connected to different earths, where it is not possible to
provide suitable spacing or partition between various metallic objects referred
Chapter 19: Installation, Testing , Commissioning & Maintenance Of Of Signalling Equipments
(e) To provide a direct connection with earth for discharge tubes/ surge
arrestors, lighting protectors, etc.
(a) It is not necessary to earth the sheath and armouring of screened cables
or armouring of unscreened cables when they are used as a tail cables
except in special cases where the length of the tail cable exceeds normal
prescribed limits.
(b) Block circuits working on earth return through the respective Block filters
and the surge arrestors provided in block ckts
(c) In case of signals falling within 2 meters from the electrified track a 25 KV
live conductor, the protection screen shall be connected to an earth
(e) There shall not be any possibility of simultaneous human contact with
metallic bodies connected to different earths, where it is not possible to
provide suitable spacing or partition between various metallic objects referred
to above, they shall be connected to a common earth
(b) To the extent possible, perimeter earth shall be provided around the
Electronic Interlocking room
(c) Earth value shall be less than one ohms and shall be measured annually
(d) Earth wire from Surge protection device to main earth terminal inside the
room should be as straight and short as possible to provide a low impedance
path for discharge of surge energies.
(f) All earth wires shall be as straight as possible and shall never be coiled.
All Earth wires should be of adequate current carrying capacity and should
never be less than 4 Square mm copper cross section.
Earthing of approved type shall be provided for each block instruments and
other signalling equipment at a station. Dedicated earthing arrangement to be
provided for earth return circuits individually if any.
19.12.109.0 The resistance of earth for signalling circuits shall not exceed 10 ohm or as
prescribed by OEM / RDSO. If the resistance is more than the required value,
steps to reduce the earth resistance shall be taken. If it is still not possible to
reduce the value below the required value, even with the adoption of these
methods, additional earths may be provided in parallel.
19.12.110.0 Where more than one earth is used, the distance between earthing pipes
shall be as per approved design.
19.12.111.1 Earth wires shall be protected against mechanical damage and possibility of
corrosion particularly at the point of connection of earth electrode.
19.12.111.2 The earthing lead shall be mild steel flat of size 35mm x 6mm or copper wire
of 29 sq. mm cross sectional area (19 strands of 1.4 mm dia) or as per the
approved earthing practice for various equipments as per OEM
guidelines/RDSO instructions for the same. In case the conductor is buried
underground, It shall be protected from corrosion by an application of suitable
anti-corrosive paint or bitumen or varnish. The length of the cable so treated
shall extend half a metre beyond the buried length.
19.12.111.3 The earthing lead shall be soldered or crimped on a lug, which shall be bolted
to the earth electrode or preferably exothermically welded. The nut & bolt to
be painted with anti corrosive paint.
The site for earthing shall be chosen in the following order of preference :-
c) Clay and loam mixed with varying proportions of sand, gravel and stone;
and
19.12.113.0 A site which is naturally well drained shall be chosen. A water logged
situation, however, is not essential unless the soil be sand or gravel.
Perennial wells may also be used as sites for earth electrodes with
advantage where the bottom of the earth is rocky.
19.12.114.0 Electrodes shall preferably be situated in a soil which has a fine texture and
which is packed by watering and ramming as tightly as possible. Where
practicable, the soil shall be sifted and all lumps broken up and stones
removed in the immediate vicinity of the electrodes.
19.12.115.0 Where soil conductivity is poor, the chemical treatment may be resorted to
improve the same. Common salt together with charcoal in alternate layers is
generally used for this purpose and the addition of less than one part by
weight of salt to 200 parts of soil mass may reduce the resistivity by 80% but
there is little advantage in increasing the salt content above 3%. Calcium
chloride and sodium carbonate are also beneficial.
19.12.116.0 Use should be made where possible of natural salts in soil produced by
bacteriological action on decaying plants. The resistivity of the soil on which
plants are growing will be less than that of a similar soil in the absence of
plants.
19.12.117.0 As far as possible, the earthing arrangement shall be located in the natural
soil. The made-up soil which has not consolidated or is likely to be eroded by
weather, shall be avoided.
19.12.118.0 The minimum clearance of equipment earths from system earths provided by
the Electrical Department either of the Railways or of the other
Administrations shall be 20 metres.
19.12.119.0 Ashphalt or concrete cover of about 50mm thickness around the Earth for a
radius of 1 metre to retain the soil moisture is desirable.
19.12.121.0 Earth Resistance of an 'earth' is the sum of three separate resistances, viz.,
(a) the resistance of the conductor joining the earth electrode to the
installation;
(b) The contact resistance between the surface of the earth electrode and the
(c) Normally the first two resistances are negligibly small compared with the
third; so, the resistance of an 'earth' is primarily determined by the nature of
the soil and not by the electrode itself.
19.12.122.0 The material used for a standard electrode system should be corrosion
resistant. Under ordinary soil conditions, use of galvanized iron or mild steel
electrode is recommended. In cases where soil corrosion is likely to be
excessive, it is preferable to use either copper or copper clad electrode. The
electrodes shall be free from paint, enamel or grease.
19.12.122.1 Earth tester normally used for measurement of earth resistivity comprises of
the current source and meters in a single instrument and directly read the
resistance value.
When using a megger as shown below, the resistivity may be evaluated from
equation P = 2
2πSR
Where,
P = resistivity of soil on ohm meters
S = distance between successive electrodes in meters
R = megger readings in ohms
19.12.122.2 (a) Test Procedure :- At the selected test site, four electrodes are driven into
the earth along a straight line in a chosen direction at equal intervals' S'.
(b) The depth of the electrodes in the ground shall be of the order of 10 to 15
cm. The megger is placed on a steady and approximately level base, the link
between terminals P1 and C1 opened and the four electrodes connected to
the instrument terminals as shown in the fig. An approximate range on the
instrument is then selected to obtain clear readings, avoiding the two ends of
the scale, as far as possible. The readings are taken while turning the crank
at about 135 rev/min (in case of Magneto Generator Type) or pressing
concerned button in some Other Type of Meggers. Pl see equipment
Manufacturers manual and follow as stated there in
(d) Method of finding out the resistance of an Earth - Refer annexure 18/4
All Earth connections shall be carefully examined and kept intact and joints
soldered. The wire between each earth and the connected equipment shall
be electrically isolated. The exothermic welding termination on maintenance
free earth rod shall be checked and cleaned.
19.12.125.0 Block earths and their connections shall be examined at intervals of not more
than one month by the Section Engineer/Signal and at intervals of three
months by the Senior Section Engineer /Signal.
19.12.126.0 Block earths shall be tested for resistance at intervals of not more than 12
months by the Section Engineer/Signal or Senior Section Engineer/Signal in
accordance with Annexure -. Where the resistance exceeds 10 ohms, action
shall be taken to reduce the resistance by providing additional earths in
parallel.
19.12.127.0 If routine testing indicates that existing earth electrode system is not
satisfactory, a new earth electrode system (or part of a system to supplement
the existing system) shall be provided
Maintenance Schedules as given in Annexure 19/6 shall be followed
Note :- This Chapter has under mentioned Annexures for further study
Schedule Code : S1
1. Cleaning of LED lighting unit & current regulator/integrated LED, all terminations,
housing, signal units & around signal post.
2. Measurement of input voltage & current with clamp type ammeter at input
terminals of current regulator/LED signal for all signal aspects and V/I reading
shall be within specified range as below:
(a) Main signal Voltage: 82.5 to137.5V and Current: 112 to 154 mA.
(b) Calling on/A/AG Marker Voltage: 88to132V and current: 120 to 165mA.
(c) Route signal Voltage: 88 to 132V and Current: 23.75 to 26.25mA per
LED.
(d) Shunt signal Voltage: 88 to 132V and Current: 52.25 to
57.75mAperLED.
3. Checking of tightness of all adjusting screws of LED signal unit as well as
Current regulator/ integrated LED.
4. Ensure condition of signal post is satisfactory.
10. Ensure the cable terminations in location box should be cleaned for removing
oxidation, rusting &tightened properly.
11 Visual check of insulations of cables, PVC wires, proper termination without
criss cross, condition of rubber gasket arrangement.
1. Check infringement of Signal & all its fitting with respect to schedule of
dimensions jointly with SSE/P.WAY(infringement to be removed, if found).
2. Test Route ECR- ensure that route ECR should be dropped if any 3 nos. of
LEDs in the given route supply is cut for all the routes.
3. Test Shunt ECR- ensure that shunt ECR should be dropped if any one of
Shunt LED does not lit.
4. Set jumper setting in current regulator as per ECR used & measure current
with AC clamp meter. The range of current shall be within the limit as per ECR
used.
5. Implantation distance from center line of nearest track along with an arrow
indicating towards nearest track should be painted on signal post in following
colours
a) Black on white background for normal implantation.
Note:- Whenever engineering Machine work is carried out, signal implantation shall be
measured prior/after to commencement/completion of work.
Schedule Code : P3
Periodicity : Signal Technician : …..
Sectional JE/SSE: Quarterly (Sectional JE/SSE & I/C SSE to carry out alternate
inspections)
Incharge SSE : Quarterly (Sectional JE/SSE & I/C SSE to carry out alternate
inspection)
Note:- Whenever any wire, cable, gears etc. are opened and disconnected, care
should be taken for proper reconnection of wires, cables, gears etc. and must be
followed by correspondence test with panel before giving reconnection
Schedule Code : K1
Periodicity : Signal Technician : Monthly,
Sectional JE/SSE:, quarterly,
Incharge SSE : Half-yearly
S.No. Check the following :
1. Clean and ensure dust free.
2. Visually check the condition of PVC wires is good and intact.
3. Checking the effectiveness of locking, sealing, indication and Buzzer.
4. Voltage across KLCR shall be measured.
a) Permitted Range for 24V DC Relay 19.2 to 28.8 V DC.
b) Permitted Range for 60V DC Relay 48 to 72 V DC.
2. Check and ensure that relays are in good condition & no dry soldering.
Note:- (i) During periodic schedule of SSE in-charge inspection, section SSE/JE
inspection not required since inspections are repetitive in nature.
(ii) Ensure that independent Power supply is connected to KLCR.
Schedule Code : F1
Periodicity : Signal Technician : Monthly
Sectional JE/SSE:, Quarterly
Incharge SSE : Half-yearly
S.No. Check the following :
1. Visually check the fuses and indication LED on fuse block provided to ensure
intactness.
2. Visual inspection of fuse blown off indications & their replacement with proper
fuses, if blown off.
3. In the Fuse Monitoring Panel (FMP), if fuse blown off indication is
available/audio alarm bells, check for fuse/LED/Buzzer and replace them, if
defective.
4. PPTC Fuses
Ensure that the main fuse and PPTC are in working condition by checking
individually (without disturbing the working circuit). If not replace the defective
component.
Fuse Auto Changeover System
1. Visually check the Fuse monitoring changeover system, fuses and its
indications.
2. Physically check the functioning of fuse monitoring panel. If any main fuse is
removed/blown-off, the audio alarm with indication appears on Fuse
monitoring panel.
Schedule Code : F2
Periodicity : Signal Technician : …..,
Sectional JE/SSE:, ….,
Incharge SSE : yearly
Check that all fuses provided are of ND type/’D’ type/’G’ type, PPTC or
1. approved type and of correct rating as per requirement.
2. Ensure proper tightness of all terminals and fuses.
3. Ensure that the Main fuse and Stand-by fuse are in working condition by
checking individually (without disturbing the working circuit). If not replace the
defective component.
4. Check that fuse capacity as per specification for the maximum load current.
NOTE: (i) While commissioning or any alteration, it has to be ensured that Fuses are
provided in one limb of the circuits
(ii) Checking that fuse capacity is not > 2.5 times the load. Measure circuit current
when fuse is blown off & investigating the cause if current is found more than initial
value
Schedule Code : E1
Periodicity : Signal Technician : Monthly
Sectional JE/SSE:, Quarterly
Incharge SSE: Half-yearly
S.No. Check the following :
Checking that –
1. All earth connections of block earth, Axle counter, MUX and other equipment
earth are intact.
2. Earth wire lead is not corroded and is well protected.
3. Nut connecting earth wires to electrode are not corroded.
4. SPD (B & C type at 230 V entry stage) indications are OK.
5. Connections to SPD are intact.
Schedule Code :E2
Periodicity : Signal Technician : …..
Sectional JE/SSE:, Half-yearly
Incharge SSE: Yearly
Check that –
1. SPD(C type at the output side of DC supply) indications are OK. Before
onset of monsoon and after every lightning it has to be verified.
2. Connections to SPD are intact.
Schedule Code :E3
Periodicity : Signal Technician : …..
Sectional JE/SSE:, ……
Incharge SSE: Yearly
Check that –
1. Proper rating and type of SPD used.
2. Available potential free contacts are wired.
3. Separate earth exists for each block.
4. Different earthing conductors are insulated from each other.
5. Measuring the value of earth resistance of the earthing provided for signaling
circuit, improving earth resistance if found more than beyond specified limit
of installed equipment , take steps to reduce it further
6. Keeping records of the earth resistance measurement and painting its value
on earth enclosures /nearest wall.
Note:- There should not be any other earth or system earth of electrical, placed less than 20
meters away from the equipment earth
20.1.5.2 Track circuits/Axle Counter shall also be provided on all passenger running
lines as well as other reception lines between passenger lines including
their connections to the main lines at all stations on the Automatic Section
including stations at either end of the section. There shall be no dead
section between the track circuits/Track sections of the station and the
Chapter - 20: Automatic Block Signalling
20.1.5.3 The design of the axle counters between two adjacent stations, shall be
such that, individual track sections in each direction shall have resetting
facility from dispatching end station master in case of failure of equipment,
with co-operation of receiving end station master for verification of last
vehicle.
20.1.5.6 Track indicator for Automatic Signalling —An indicator shall be provided at
either end station to indicate whether the block section is occupied or not.
Display of each aspect of Automatic signal & Track status shall also be
provided wherever technically feasible, on Visual Display units wherever
Electronic Interlocking is existing or being provided
20.1.6.0 Markers:
20.1.6.1 Each Automatic Stop Signal shall be identified by its number and provided
with a Marker consisting of a white disc with letter ‘A’ in black.
20.1.6.2 A Semi-Automatic Stop Signal shall be provided with a Marker which shall
show a white illuminated letter ‘A’ against a black background when the
signal works as an Automatic Stop Signal.
20.1.7.1 Automatic Signalling shall not be provided on sections with heavy and
continuous falling gradients steeper than 1 in 80 unless the brake power of
trains on the section is adequate to enable the trains being stopped at each
of the Automatic Stop Signal
20.2.8.2 All fail-safe circuits shall work on continuously energized principle such that
any open circuit in wiring, relay contacts, etc. or loss of power supplies
shall not cause an unsafe condition.
20.2.9.2 All fail-safe circuits shall work on continuously energized principle such that
any open circuit in wiring, relay contacts, etc. or loss of power supplies
shall not cause an unsafe condition.
20.2.9.3 An automatic signal shall require all tracks to be clear up to the next signal
in advance and also for an adequate distance beyond it before it can
display 'OFF' aspect. In case of single line , favourable direction of traffic to
be established
20.2.9.4 Integrated LED signal lamps or any Latest Lamps as approved by RDSO
shall be used.
20.2.9.5 All external circuits shall be provided with double cutting arrangements.
20.2.9.6 The lamps of the signal shall be so wired that if the lamp of the aspect
displayed fails, the signal shall immediately assume the next restrictive
aspect.
20.2.9.7 (a) The circuit for illuminated 'A' marker of a Semi Automatic Signal shall be
such that the 'A' marker lights up only when the signal is working as an
automatic signal.
(b) The circuit for illuminated 'AG' marker where provided shall be such that
the 'AG' marker lights up only when the conditions for 'A' Marker to light up
are satisfied except for the level crossing gate which may either be open to
20.3.12.3 The following shall be tested by the SSE (Signal) at-least once in a year.
20.3.12.3 (a) Track Circuit control on signal and aspect control by signals in
advance;
20.3.12.3 (b) Automatic Cutting-in of the next restrictive aspect when the LED
aspect of the main signal fails ;
20.3.12.3 (c) Interlocking equipments and circuits for level crossings and points;
20.3.12.3 (d) The circuits that establish the direction of traffic in Single Line and
prevent clearing of conflicting signals on sections provided with
Chapter - 20: Automatic Block Signalling
20.3.14.1 Adequate precautions should be taken after every track renewal work to
ensure proper working of track circuits / Axle counters.
20.3.15.2 Provisions contained in Chapter 17 shall be adhered to.
20.3.15.0 Power Supply: - Provisions contained in Chapter 16 shall be adhered to.
20.3.16.0 Installation Guidelines of Volume 2 shall be followed
20.4.19.0 The mid section Modified automatic signal shall be painted with alternate
blue and white strips in between.
20.4.20.0 During abnormal conditions like fog, bad weather impairing visibility, the
midsection modified semi-automatic stop signal may be worked by
extinguishing 'A'/‘AG’ marker in the manner prescribed under special
instructions and this action shall also ensure that the 'A'/‘AG’ marker of the
Advanced Starter Signal of the station in rear and Home signal of the
station in advance shall also be extinguished. This facility should be also
be available in CTC
20.4.21.0 The relevant indications whether the signal is in normal automatic mode or
modified semi automatic mode shall be available to the station masters at
both the ends.
(b) Non-route setting type i.e. Route is set with individual operation of
points.
21.1.1.2 The equipment used in the system shall, as far as practicable, comply with
the requirements of IRS, IS, BRS and BS specifications and drawings.
21.1.1.3 For areas having 25KV AC traction, all equipments and circuitry shall comply
with the requirements of Chapter 22 on "Requirements of signalling in AC
electrified areas".
21.1.1.4 The signalling and interlocking arrangements for the yard shall be in
accordance with the approved signalling plans, selection/control tables,
detailed wiring diagram including control panel diagram, relay contact
analysis and relay rack arrangements.
21.1.2.1 The display of the layout on the front of the panel referred to as the
illuminated diagram shall be well proportioned. Where additional facilities are
likely to be provided, domino type panel shall, preferably, be used. The
areas covered by each track circuit shall be clearly distinguished by use of
different colours.
21.1.2.3 The operating members, namely route switches/buttons, point switches etc.,
referred to in the following clauses shall normally be provided on the
illuminated diagram itself in Geographical order. A separate illuminated
diagram for indication and a separate 'console' containing all the operating
members may also be provided.
21.1.2.4 The route setting shall be on the basis of "Entrance Exit" principle for
installations of Route Setting type.
Chapter - 21 : Relay & Electronic Interlocking
21.1.2.6 In route setting system, each route shall be controlled either by means of
two push buttons-one at the entrance and the other at the exit of the route
Note :- In some Zonal Railways this is achieved by means of one switch at
the entrance and one push button at the exit of the route. The entrance
switch button may be of three position type or two position type as required.
In future installations this arrangement is not recommended.
21.1.2.7 In non route setting type installations, after setting of the route by individual
operation of points is completed, signal can be cleared by an individual push
button in conjunction with a group button or by an individual switch
controlling each signal or a common switch for conflicting signals which are
not required at the same time, or one push button at the entrance and other
at the exit end.
21.1.2.9 Where a route has more than one overlap, it shall be possible to select and
set the desired overlap beyond the exit signal of the route.
21.1.2.10 Where the route has alternate approach routes, it shall be possible to select
and set the desired route with desired overlap.
21.1.2.11 The switches/buttons shall have distinctive colours so that they can be
readily distinguished, such as running signal red, shunt signal yellow, calling
on signal red with white dot & exit button white. The alternate overlap white
with black dot, alternate route Grey, point black, slot green, crank handle
blue and point group button black with red dot etc.
21.1.2.12 The control panel shall be provided with suitable covers with locking and
sealing facility which shall be easily removable to facilitate access to the
internal wiring etc.
(e) Arrangement to adjust the supply voltage for panel indication circuit to
control the intensity of illumination with the help of button/switches
provided on the panel, if necessary.
(f) When SM's key is taken out, it shall not be possible to change the last
operated position of any signalling apparatus from control panel.
However, facility shall be provided to put back the signal to 'ON' position
without altering the route. It shall preferably be ensured that no
command gets executed automatically on reinsertion of SM's key.
21.1.2.14 An indication panel giving position of the yard and important indications
required for maintenance staff shall be provided inside the relay room in
major yards.
21.1.3.0 The control panel shall be provided with the following indications :
(a) Route indication lamps shall be provided to indicate setting and locking
of the route. Indication that route is set and locked shall be given by a
set of white lights (not less than two) on each track section. When any
route is not set, route indicator lamps shall be extinguished.
(b) The complete route over which the movement is to take place shall be lit
with a row of white lights when the route is correctly set and locked.
(a) Indication that a stop signal is at 'ON' shall be given by a red light and a
permissive signal is at 'ON' shall be given by a yellow light on the
corresponding signal symbols on the panel.
(iii) Failure of double yellow, both green and red* flash; &
(c) Signal indication for the 'ON' aspect of a shunt signal on the same post
as the running signal is not required. In the case of shunt signal on
independent post, the 'ON' indication shall be given by a white light
strip or two miniature white lights in a horizontal position on the
corresponding shunt signal symbol on the panel.
(d) Signal indication for 'OFF' aspect of a shunt signal shall be given by a
slanting white light strip or two miniature slanting white lights. Such
indication of a shunt signal located on the same post as a running
signal shall be given below the running signal indication.
(e) A white light for 'A'/'AG' marker indication should be lit up on the panel
below the symbol of the signal when set for automatic working.
(f) Indication that "Calling on" signal is 'OFF' shall be given by a white light
below the running signal indication of corresponding signal symbol.
(g) Repeat indication shall be provided by a white strip light which should
be lit when repeater of the signal has displayed 'OFF' aspect. This
indication should be provided by a white strip over the running signal
(a) Indication that the track circuit is occupied shall be given by a row of
red lights (not less than two) on the each track circuit portion.
(b) When the track is not occupied, the red lights shall be extinguished.
(a) Approach track circuits where provided, for all directions shall be
indicated on illuminated diagram. In continuous track circuit territory, the
approach track circuits will cover all the track circuits in rear of the first
stop signal up to the next signal in rear or up to the track circuit specified
in the table of control for approach locking. An approach track circuit
controlling calling on signal shall be indicated separately with a distinct
mark.
(c) Where required, failure of a signal lamp/route lamp shall light a red lamp
on the panel and give an audible warning for the same. Such indication
may cover group of signals. A common audible warning can also be
provided for a group of signals. It shall be possible to silence the audible
warning by pressing a push button. Such cancellation of audible warning
shall not apply to subsequent failures for which the push button must be
pressed again.
(d) A suitable and distinct indication shall be provided on the control panel
distinguishing between locked and free condition of crank handle.
(e) The respective signal lock indication (white light) shall start flashing
when an emergency route cancellation is initiated, in an approach
Chapter - 21 : Relay & Electronic Interlocking
(f) If push buttons are used on control panel, a buzzer to indicate that push
button/push buttons has/have been left pressed may be provided.
(g) Suitable indications for slots, gate control etc. shall be provided.
(h) The panel indication lamps shall be operated by not more than 24V
miniature type bulbs or light emitting diodes.
(i) Return wires from indication lamps and relays shall be suitably
bifurcated so that excessive current does not damage them. Any break
in return wire shall not fail the indication/relay or give a wrong indication
or pick-up a wrong relay.
(j) When an approved electronic flasher relay other than Mercury type is
provided, a flashing white indication shall be provided at appropriate
corner of the operating panel to indicate to the operator the satisfactory
working of electronic flasher relay.
(a) Before designing the detailed circuits, route and point control tables
showing approach locking, back locking, overlap release, isolation,
interlocking, dependence of signal aspect, grouping of crank handles
and the condition for release of crank handles, route release, gate
release etc. shall be drawn up and approved by the competent
authority. Provisions of GR & SR shall be observed.
(b) Signal circuits shall be so designed that the signal shall not change to
a lesser restrictive aspect than intended one and route shall not be
released because of fluctuations in power supply voltage or when the
supply resume following its failure.
(f) Where relays other than 24V, 1000 ohm relay with metal to carbon
contacts are used, the circuits shall be so designed that not more
(g) The proving of back contacts of metal to metal relays should be done
in the circuitry,
21.1.4.2 Route setting and interlocking circuits for installations provided with route
setting system.The route setting and clearance of signal shall be with the
following conditions:
(c) Operate the points in the route including overlap and isolation, if any,
to desired position.
(d) The crank handle for all the motor operated points and keys for all the
key-locked points in the route, overlap and isolation are locked and
their control is not released.
(e) Interlocked level crossing gates are closed and locked against the
road traffic in the route including overlap, if any.
(f) The complete route including overlap and isolation, if any, is correctly
set and electrically locked.
(g) The track circuits in the route up to the next signal/dead end and its
overlap, if any, are clear.
21.1.4.3 Route setting and interlocking circuits for installations provided with "route
setting by individual operation of point" system.
The route setting and clearance of signal shall be with the following
conditions:
(a) The points in the selected route and if required in overlap and
isolation are operated to required position by individual operation of
switches or push buttons in conjunction with group push button.
(iii) The points including hand operated points in the route including
overlap and isolation if any, are set, locked and detected.
(iv) The crank handle for all the motor operated points and keys for
all the key-locked points in the route, overlap and isolation are
locked and their control is not released.
(v) All interlocked level crossing gates are closed and locked
against the road traffic in the route and overlap, if any.
(vii) The track circuits in the route up to the next signal/dead end and
its overlap if any, are clear.
Note:- i) For clearing calling on signals, proving of track circuits in the route
and overlap is not required. Calling on signal shall detect all the
points including interlocked level crossings in the route, which the
main signal above it detects.
ii) For clearing of shunt signals the proving of berthing track circuits,
points & LC gates in overlap are not needed. This applies to both the
systems having route or non route setting facilities.
21.1.4.4 The interlocking between conflicting routes shall be achieved through route
interlocking electric circuits.
21.1.4.5 Approach locking or dead approach locking shall be provided for all manual
stop signals. Approach locking shall be continuously effective from the
predetermined point on approach of the signal.
21.1.4.6 Controls on level crossings, ground frames, cabins, sidings etc., shall be
suitably interlocked.
21.1.4.7 A white indication for block control on the last stop signal should be provided
on control panel, where -
(a) Section ahead is worked on Absolute Block System and control panel
21.1.5.1 Complete route release including overlap shall be effective only after the
signal governing the route is put back to 'ON' and corresponding route
switch/button has been operated to normalize the route. Automatic route
release by the passage of train and complete release of route through
sequential route release shall be provided.
21.1.5.2 Where a route has got number of route sections, the circuit shall be so
designed that the route section does not release only by picking up of the
concerned track relay. Same is released only after the next track circuit is
also dropped and picked up, except in case when the last track is a berthing
track. In cases where the route is controlled by single track circuit, the route
release shall be controlled after predetermined time delay.
21.1.5.3 The route release circuit shall be so designed that it will release only when
at least two track circuits drop and pick-up in sequence.
21.1.5.4 In installations provided with route setting system, sectional route release
shall be provided where required. In such cases sub-route section already
released shall permit setting up of other routes, if interlocking otherwise
permits.
21.1.5.5 In case of installations provided with non route setting system, sectional
route release may be provided where considered necessary. The complete
route release shall be effective only after the signal governing the route is
put back to 'ON' and corresponding route switch/push button has been
operated to normalize the route. However, where sequence proving relays
are provided to prove the authorized passage of a train, automatic route
release shall be provided.
21.1.5.6 It shall be possible to release a route in emergency after suitable time delay,
with the approach track occupied, provided the train has not passed the
signal during the time interval.
21.1.5.8 When the route is released by the passage of train, the overlap points shall
be released only after the lapse of two minutes of occupation of berthing
track as well as clearance of last point track circuit of the route. However, in
major yard this timing of route release can be reduced upto 60 seconds with
the approval of PCSTE. On cancellation, the overlap points may be
Chapter - 21 : Relay & Electronic Interlocking
21.1.6.2 Circuits shall be so designed that the failure of any part of a circuit affecting
the control of the signal shall cause the signal to display a more restrictive
aspect than the intended aspect.
21.1.6.3 The circuit shall be so designed that in case of failure of a signal lamp, the
lamp of more restrictive is lit automatically and in case of failure of red lamp
it shall not be possible to clear the signal in rear.
21.1.6.4 Fouling protection, approach locking, indication locking, route locking, siding
control key locking, crank handle locking and track locking shall be
incorporated in the relevant control circuits.
21.1.6.5 Each aspect light of a signal may be proved where necessary and the
aspect indication shall be provided as per Para 21.1.3.3 (b)
21.1.6.6 Wherever required, necessary control on the level crossing, ground frames,
cabins, siding control key, crank handles etc. shall be provided.
21.1.6.7 The correspondence of the point control relays and point indication relays
may be proved in signal circuits before the signal displays an 'OFF' aspect.
21.1.8.1 The points once set shall remain in the last operated position until these are
operated by different route setting or by individual operation of points.
However, isolation points of catch siding, slip siding may operate
automatically after the passage of train to their isolation position where
sectional route release is provided.
21.1.8.2 Operation of points shall be possible only when the interlocking is free and
relevant point track circuit is clear. Emergency operations, where provided
when point zone track circuit fails, it shall be possible to operate the
concerned point provided interlocking is free by releasing an emergency
control. Each such operation shall be recorded on a counter.
21.1.8.3 Interlocking between points shall be provided only to the minimum extent
necessary.
21.1.8.4 Point control circuits shall be so designed that a cross connection or a short
circuit cannot operate a point or give a false indication of the same.
21.1.8.5 Crossovers shall be operated by separate point machines, one at each end.
The detection of setting and locking of the points at the two ends of a
crossover shall be connected in series.
Crank handle / point NX key provided for manual operation of the points
worked by electric point machine must be interlocked with signals.
21.1.8.7 It must not be possible to release the crank handle/point NX key unless the
signals have been put back to 'ON' position and concerned route is
released. However, if the route remains locked due to what so ever reason,
it shall be possible to release the crank handle/point NX key after a time
delay of 120 seconds from the time the signals have been put back to 'ON'
position.
21.1.8.8 In major yard where number of points are more, these points should be
grouped in different zones maintaining the yard flexibility. The crank
handle/point NX key for each group of point machines should be so
Chapter - 21 : Relay & Electronic Interlocking
21.1.8.9 Siding control key for manual operation of siding points, taking off from
running lines, shall be so interlocked that it may not be possible to clear the
signal leading over to that line when the key is released for operating siding
points for shunting purposes.
21.1.9.1 For purely internal circuits including vital circuits, double cutting or cross
protection may not be provided unless specifically required.
21.1.9.2 All equipments in external circuits shall be suitably protected from cross
connections and rendered immune to false operation by stray
currents/induced voltages.
21.1.10.1 The various type of relays used in relay interlocked systems shall be of
approved type and conform to appropriate specifications as detailed in
Chapter 8 unless otherwise specially permitted.
21.1.10.2 Time element relays of approved type shall be used. Where approved
electronic time element relays are used, these shall be two in number and
their contacts shall be in series in the concerned time release circuits.
21.1.10.3 The relays, including track relays, located in the track side location boxes,
shall be plug-in type.
21.1.10.4 All plug-in relays and relay groups shall be fitted with non-interchangeable
interlocking device to prevent the wrong relays/relay group being
accidentally plugged-in during replacement.
21.1.10.5 Removal or replacement of plug-in relays/relay groups from the relay racks
during operation shall not cause any unsafe conditions in the circuits.
21.1.10.6 As far as possible, all relays shall be housed in the relay room of the
controlling cabin to achieve maximum centralization.
21.1.10.7 Where feasible all relays except track relays, shall have 10% of working
contacts as spare subject to a minimum of one front and one back to
facilitate addition and alteration to the circuits at a later date. Extra space
(minimum 10%) to accommodate repeater relays shall be provided in the
relay rack to cater for future expansion.
21.1.10.9 Sequential proving of front and back contact shall be ensured where metal
to metal contact relays are provided.
21.1.11.0 SIGNALS
21.1.11.3 Route indicators shall be either of the direction type or multi lamp unit type
or of Stencil type conforming to approved design.
21.1.11.4 'A' marker lights for semi-automatic signals shall be of approved type.
21.1.11.5 Roundels, glasses and lenses wherever used in the colour light signals shall
be of approved type.
21.1.11.6 The signal lamps used for different types of signals shall be of approved
type.
21.1.12.2 Means shall be provided to cut off the motor feed in case of obstruction to
the point movement after a predetermined time lag, based on the type of
point machine used.
21.1.12.3 The point operating control circuits shall have track circuit control, overload
protection and cross protection.
21.1.12.4 Hand worked point switches shall be equipped with circuit controllers that
are operated by the switches when closed. Keys controlling such switches
shall be electrically locked by the approach track back locking track circuit so
that it's not possible to work them in the face of an approaching train.
21.1.12.5 The crank handles shall be provided to facilitate operation of points in case
of failure of point machines. For this purpose, if necessary, the points in the
yard may be divided into convenient groups and to distinguish particular
groups, crank handles with different wards shall be used. The crank handles
may be provided in a suitable place near the group of points to which they
refer. The slots in the point machines provided to take the crank handles
would also be suitably made to take only the crank handle applicable to the
group. The crank handles shall, however, normally be locked. It shall be
Chapter - 21 : Relay & Electronic Interlocking
21.1.12.6 In AC traction area, the point machine shall be immune to the effects of
Electro-magnetic induction. These should be installed within the range to
which these are immune to the effects of AC electrification.
21.1.13.1 Provisions of Chapter -17 on Train Detection (Track Circuits & Axle
Counters) shall be generally followed.
21.1.13.3 Axle counters of an approved design can be used in lieu of track circuits.
21.1.13.4 The track circuits shall be so designed and installed that in the case of a
failure of block joints, the adjacent track circuit feed shall not wrongly
energize the next track circuit relay.
21.1.13.5 A DC track circuit shall not be fed directly from AC supply using transformer
and rectifier. A storage battery must be connected with battery charger and
the connection is so made that if battery is disconnected the battery charger
is also disconnected.
21.1.13.7 At stations where points and signals are operated from an Assistant Station
Master's office at a central place, track circuiting of the entire station section
including all lines where direct reception is provided shall be done.
21.1.14.0 CABLES
21.1.14.2 At least two cores of cable shall be provided between two ends of the yard
to cater for telephone communication for maintenance purposes in non RE
areas. Where the yard is extending over a large area, the location boxes
may be grouped and one socket may be provided in one of the location
boxes in the group so that telephone communication is conveniently
available for co-ordination with the cabin during maintenance or rectification
of failures of various ground equipments. Where such groups are situated in
different directions from the cabin, a separate pair of conductors shall be
used for each direction connected to the cabin. In RE area, provision shall
Chapter - 21 : Relay & Electronic Interlocking
21.1.14.3 Earth leakage detectors of approved type may be provided to detect any
leakage to earth in cable conductors.
21.2.15.1 The wiring used in various equipment shall comply with the requirements
laid down in IRS specification No. S 23.
21.2.15.2 All wiring in the cabin and locations shall be done in a neat manner so that
the wiring does not in any way prevent the proper functioning over working
parts and is easily accessible for maintenance.
21.2.15.3 All wiring in the cabin and location shall be terminated on approved type
terminal blocks/tag blocks unless otherwise specially permitted.
21.2.15.5 The internal wiring of relay rack in locations and cabin shall be generally
carried out with plain annealed copper conductors; PVC insulated
unarmoured flame retarding type of 1100V grade unless otherwise specially
permitted. The size of the conductors can be as follows:-
Type Size
(a) Single Core size 1 mm
(b) Multi core each core of size 1 mm
(c) Multi core each core of size 0.6 mm
(d) Flexible insulated wire size 16/0.20 mm
(e) Flexible multi strand wire size 3/0.75 mm
21.2.15.6 Rack to rack wiring shall be generally carried out with multi core cable
having plain annealed copper single core conductor of size 1/0.6 mm or
multi-strand 16/0.2 mm as per approved specification for indoor cables.
(a) All connections to plug-in non-proved type relays flexible wire of 16/0.20
mm shall be used.
(b) All connections to proved typed relays shall be done with 0.6/1 mm
single strand multi core cable.
(c) For all connections from cable terminations to tag blocks and indicators
etc. shall be done with the help of 1 mm single strand wires.
(d) For all connections to circuit breakers, lever locks etc. single strand wire
of 1.5/1.6 sq. mm size shall be used.
21.2.15.8 Relay to Relay wiring on the same rack should be as far as possible direct
without intermediaries like tag block/terminals.
21.2.15.9 Identification Marker for identifying the terminals and tags shall be provided
to each terminal to identify the circuits for which it is used.
21.2.15.10 Relay racks shall have sufficient capacity to take additional equipment to the
extent of 15% of equipment provided to permit additions and alterations.
21.2.15.11 Charts showing the position of relays on relay racks and contact analysis of
relays indicating the spare and used contacts shall be prepared and kept in
the relay room.
21.2.16.1 Cartridge type fuses shall preferably be of N.D. type. Where screw cap
cartridge type fuses are used, these shall be of different colour codes for
different current rating and these shall be non - interchangeable.
21.2.16.2 Fuses shall be so grouped that blowing of a fuse has minimum repercussion
on train operation.
21.2.16.3 The fuses when blown off, shall preferably give a visual indication .
21.2.16.4 Each group of circuits shall be carefully protected by fuses in the cabins and
in location to facilitate easy fault localization.
21.2.16.5 Fuses shall be so arranged that they can be easily replaced without causing
interference or unsafe conditions to other circuits.
21.2.16.7 The terminal block and tag blocks shall be of approved type unless
otherwise specially permitted.
21.2.16.8 The terminal boards provided at the locations and other places shall be
provided with suitable links to facilitate isolation of the two sides of the
circuits which are connected through the terminal links.
21.2.16.9 For vital circuit fuse auto change over system of approved type to be
provided.
21.2.18.1 Air conditioning may be provided for every signalling interlocking (PI/RRI)
installation with more than 100 routes.
21.2.18.2 For other signalling installations, with less than 100 routes, air-conditioning
may be provided for those installations which are
(i) prone to dust (coal dust, stone dust, iron ore etc.) or
(ii) in the vicinity of chemical/fertilizer/ other industrial factories releasing
harmful fumes or
(iii) in areas with extreme temperature with the agreement of PCSTE and
PCEE.
21.2.18.5 (a) 'Automatic Fire Detection and Alarm System' may be provided at all
stations irrespective of number of routes.
(b) Automatic Fire Suppression System' along with “Automatic Fire Detection
And Alarm System “ may be provided at stations with more than 400 routes.
Note:- For Schedule of Maintenance of Fire Alarm System', Please refer to
Annexure – 21/5
21.2.18.5 Note: In case provision of “Automatic fire suppression system” along with
“Automatic Fire Detection And Alarm System” is considered desirable by
Zonal Railways at critical stations and important junction stations even below
400 routes, same may be provided with the approval of competent authority
Chapter - 21 : Relay & Electronic Interlocking
21.2.18.6 Suitable standard earthing shall be provided for all operating panel, power
supply, switch board, transformers, inverters etc.
21.2.18.8 Communication between the SM's panel room, relay room, equipment room
and locations shall be provided.
(a) Electronic Interlocking System shall be approved type and shall conform
to latest approved specification.
(b) Electronic Interlocking System shall have the highest level of safety
integrity as stipulated.
(h) Provisions given in Sections 1,2 are generally applicable for Electronic
Interlocking also.
21.3.20.1 Control Cum Indication Panel (CCIP) & Control Terminal with Video
Display Unit (VDU).
(d) Operation of Signals, Points and other Controls such as Gate, Crank
handle, Siding, Slot etc., shall be carried out through appropriate dropdown
menus or other approved means.
(g) Only non-resettable counters shall be provided while working with CCIP
or VDU.
(h) VDU shall have provision for Signal, point and Line Block Collars
equivalent of CCIP.
(i) Where CCIP and VDU are provided, it shall be possible to switchover the
controls from CCIP to VDU and vice-versa, and where two VDUs are
provided, it shall be possible to switch the controls from on VDU to other
VDU.
(j) Indication that EI system is healthy shall be displayed on the CCIP using
a blinking green LED or blinking green indicator on VDU.
(a) Interface between Control Terminal, Video Display Unit, Control Panel,
Panel Processor and Electronic Interlocking system shall be of approved
type.
(b) Interface of Points, Signals, Track Circuits and Controls such as Crank
Handle, LC Gate, Siding, Slot etc., with Electronic Interlocking System shall
Chapter - 21 : Relay & Electronic Interlocking
(a) Interlocking application logic (site specific data) requirements for the EI
system shall be as per interlocking principles stipulated for Relay
Interlocking and Standard Circuits for Electronic Interlocking.
(b) After powering up of Electronic Interlocking the system shall block all
signals and other operations. After verification of safety functions by
Electronic Interlocking system, this blocking shall be released after a delay
of at least 120 seconds.
21.3.24.1 Configuration
(a) Electronic Interlocking system shall have hot-standby arrangement and
changeover from one system to other systems shall not interrupt status of
signalling.
(b) Version and checksum of the Application logic (station specific logic)
shall be unique for the installation and shall be approved by the authority
competent to approve the circuit diagrams. Corresponding Checksum shall
be recorded and controlled by the same authority
(b) Application logic (site specific logic) shall be verified for safety and
functionality by carrying out exhaustive safety and functionality tests by
officers authorized by PCSTE.
(c) Only approved application logic with specified checksum shall be used in
the EI system and this data and checksum shall be version controlled and
preserved by the Railways.
(a) System testing of EI system shall be carried out at the time of initial
installation and during subsequent modifications in interlocking.
3. Emergency Operations.
2. Correspondence test
(f) FAT is to be done for all major/minor yards for both new
works/modification in existing EI
(h) FAT & SAT should be done by separate officials where ever feasible
(i) SAT should be conducted thoroughly for all new installations. While in
case of yard modification work in existing EI, if there is no change of
checksum w.r.t FAT checksum and integrity of EI application software is
demonstrated, then during SAT complete testing as per complete
selection table need not be done. For such works, the testing plan as per
para (e) above may be prepared which demonstrates that proper care is
taken to ensure that correspondence and testing related to changed
interlocking is covered in the test plan. The testing plan shall be approved
by minimum JAG level officer.
The power supply for fan shall be fed with separate external supply, which
should be completely isolated from Electronic interlocking supply and same
shall be provided with fuse.
(b) To the extent possible, perimeter earth shall be provided around the
Electronic Interlocking room.
(c) Earth value shall be less than one ohm and shall be measured annually
during dry season.
(d) Earth wire from Surge protection device to main earth terminal inside the
room should be as straight and short as possible to provide a low impedance
path for discharge of surge energies.
(f) All earth wires shall be as straight as possible and shall never be coiled.
All Earth wires should be made of copper of adequate current carrying
capacity and should never be less than 4 Sq.mm cross section.
Section 5 : Maintenance of EI
Latest EI station database files (application logic, VDU database, etc) shall be
kept updated in centralized server as specified.
Chapter - 21 : Relay & Electronic Interlocking
1 Relays in General
1.1 Relay Working Principle: A relay is an electromagnetic device, which is used for
closing or opening of an electrical circuit. The relay may be classified as Shelf type
and Plug-In Type. Plug-in-type relays which are plugged in to prewired terminal
boards. It works on electromagnetic principle. Each relay has a base
electromagnet, armature, contact spring, contacts, transparent cover, and handle.
It works on a low current. A non-magnetic residual pin is fixed on the inner face of
armature, in all relay except magnetic latch relays. When current is applied
through the coil, it sets up a magnetic flux through the bar magnet, core, L shape
heelpiece and armature. It`s Specification is B.R. 930A.
2.1 QN1 Style Relay: This is used as internal relay for all control and detection circuit
except in external circuits of AC RE area. It`s specification No-B.R. No:
930A.Though it is immune to 300 Volt AC 50Hz but only in emergencies can be
used in RE area with protection against AC Interface
2.2 QS3 Style Relay: It is sensitive line relay. It works on a low current. It works on
12V DC. It`s Specification is B.R. 930A.
2.3 QB3 relay is biased neutral line Relay: It works on 12v DC and has a contact
configuration of 4F/2B.it is a biased relay. Its Biasing stands good up to 240 Volt
DC. This is confirming to BRS Specification No.930A.
2.4 QNN1 Style Relay: This comprises two neutral line relays whose contacts and
magnets are mounted side by side with a common heel piece on a base. These
two relays operate independently to each other and also have equal number of
front and back contacts. It is based on BR specification 960.
2.6 AC Immunised DC neutral line Relay: The relay design shall be inherently such
that the immunisation is achieved intrinsically without use of any external means.
The relay shall not make any of its front contacts when 1000 V (r. m. s) of 50 Hz
AC is applied at any instant to the terminals of relay coils. The relay shall not break
any of its back contacts when 300 V (r. m. s) of 50 Hz AC is applied at any instant
to the terminals of relay coils. This is confirming to IRS Specification No. S60 –78.
Usage: these relays are used as interface relays in Electronic Interlocking
systems.
2.8 QBA1 Relay: This is a DC biased AC immune neutral line relay. A copper slug is
provided on the core for immunisation and a permanent magnet is provided on the
core for Biasing. It does not operate if 20 times of the rated voltage is applied in
reverse direction. It’s specification is BR Specification No. 932 A.
2.9 QBCA1 Relay: This is similar to QBA1 relay but having two heavy-duty front
contacts. It can carry 30A inductive current at 110 v through its front contact. the
back contact can carry 3A continuous and 2A switching current like any other
relay. Its Specification is BR specification no. 943.Usage: These relays are used as
Point contactor relays.
2.10 QSPA1 relay: Only this relay is permitted to be used as the repeater for
immunised ‘Q’ series track relays (QBAT & QTA2), due to its slow to pickup
character. Provision of a copper slug between the core and the heel piece behind
and a magnetic shunt between the core and the armature at the front contact make
this relay slow to pickup. Features of QSPA1 relay are: (i) Slow to pick up by 540
/600 milli seconds.(ii) Less slow to release by 140 / 200 milli seconds and immune
to AC. This made to BR specification no. 933A.
2.11 QL1 relay: This is a magnetically latched DC line relay. This relay remains in full
operated condition though the feed to the relay is cut off. This relay has two coils
namely operate coil (R( ) and release coil (N( ) and a permanent magnet. This
made to BR specification no. 935A.Usage : these relays are used as latch relays in
block instruments etc.
Track Relays
Track relays shall always be of metal to carbon contact type & normally be of plug
in type, unless otherwise specially permitted. In non electrified area, the following
relays shall be used:- 9 ohm DC non-AC immunized (plug-in type). In electrified
area, the following relays shall be used:-9 ohm DC neutral, AC immunized.9 ohm
DC biased, AC immunized. Double element motor type relay, operating on 83 &
one third Hz in AC traction area and 50 Hz in DC traction area shall be used. Vane
type relays may continue in use till replacement. Relays for track circuit provided
with coded, pulsed, electronic (audio frequency or high frequency track circuit),
shall be of an approved type of track/ line relay or as recommended by
manufacturer.
2.13 QT2: The construction of this relay is similar to that of a Q – Series line relay
except that its contact load is reduced drastically. The relay is more sensitive and
workable on a low voltage.QT2 relay has only one core and 2F – 1B contacts. The
back contact is used for cross protection for TPR circuit. This has a single coil
unlike the shelf type relay, which has two coils with open ends. Usage: it is used as
track relay in Non -RE area.
2.14 QTA2: Copper slug is provided on the core to achieve AC immunity. It's pick up
voltage is 1.4v and pick up current is 140 ma approximately.QTA2 relays are
available in 9 Ohms coil resistance with 2F/1B contact configuration. This relay
requires more D.C. operating power and it take more time to pick up and drop due
to the copper slug. New Installations: This can be used Upto 450 meters track
Circuit Lengths in RE Areas with Choke at both ends. ii. Existing installations :
This can be used Upto 450 meters track Circuit Lengths in RE Areas with Choke at
the Relay end with high traction return current of 1000 Amps and up to 350 meters
track circuit length without choke at the Relay end with low traction return current
of 600 amps. Usage : used as track relay in RE area.
2.15 QBAT: It's pick up voltage is 1.75v and pick up current is 175 ma approximately.
This is achieved by the provision of a biasing permanent magnet on its core along
with its copper slug. It has only one core and 2F – 2B contacts. This can be used
Upto 750 meters track Circuit Lengths in RE Areas. This is made to RDSO
specification. No. 84 / 88. Usage : it is used as track relay in RE area.
2.17 Types & Usage of Timer Relays: These relays are used in the signaling circuits
to release interlocking after certain period of time to ensure safety. Following types
of Time Element Relays are in use (i) DC Thermal type (ii) Siemens Motorised
Clock Work time relay (iii) Motor type (iv) Electronic type
2.18 DC Thermal Type Element Relay (QJ1) : This type of relay employs heat
operated contact associated with an ordinary DC Neutral Relay. It has a heating
element (H( ) and a neutral line relay (R( ) which together energise an external
line relay after a pre –set time delay. One of such type is “QJI” type relay. Features
of this relay are : (i) Rated Voltage 24 V DC or 50 V DC (ii) Heat coil resistance 40
to 42 Ohms (iii) Max. Heating power 15 Watt at rated supply Voltage. The
Maximum numbers of operations should be restricted to 100 / day otherwise
characteristics of the heating element may change. An increase of 10 % in applied
voltage may result in a time decrease of up to 10% .An decrease of 10% in applied
voltage may result in a time decrease of up to 20% .Usage : these relays are used
to count time delay in Signalling Circuits
3.1 K-50 Relays : K-50 relays are available only in group units of different sizes.
Depending upon the unit size, these groups are broadly classified as: (i) Mini
groups (ii) Minor Groups (iii) Major group. The capacities of various groups are
as follows (i) Mini Group: 2 Neutral control relays, 1 Interlocked relay or 1 ECR with
power conversion unit. (ii) Minor Group: 15 Neutral (with one interlocked relay
replacing two neutral relays, one contactor relay replacing four neutral relays, or
one resistor or condenser fixed in place of one neutral relay in some units.(iii)
Major Group (used only in RRI) : Up to 30 relays space with combination of
Neutral and interlocked relays, One contactor relay replacing four neutral relays
space one resistor and condenser fixed in placed of one neutral relay in same
group
3.2 Group relays in Siemens interlocking : (a) 2-Aspect Signal Group (b) 3-Aspect
Signal Group (c) Shunt Signal Group (d) Universal Route Group in PI, RRI (e) Drs
II Point Group for PI (f) Drs Point Group for RRI (g) Point Chain Group for RRI
3.4 Non AC immunised Neutral Relays : These relays are available in 4F/4B, 5F/3B
& 6F/2B contact configurations. The ohmic values of these relays are 1260 ohms
for 4F/4B, 1260 ohms for 5F/3B and 1840 ohms for 6F/2B
3.5 Interlocked Relays : These relays are available in 4F/4B, 5F/3B & 6F/2B contact
configurations. The ohmic values of these relays are 615ohms for all contact
configuration
3.7 AC immunised relay ( Both Top & bottom Relays) : These relays are available
in 5F/3B contact configuration only. The ohmic values of the relay is 1840 ohms
only.
3.11 Universal ECR : These relays are available in 3F/3B contact configuration only.
The ohmic values of the relay is 83.1 ohms only. It is used as lamp proving relay.
3.12 WKR1 : These relays are available in 5F/3B contact configurations. The ohmic
values of these relays are 1840 ohms only. It is a part of Point minor group and
Point Major group. It is used for point detection.
3.13 WKR2: These relays are available in 5F/3B contact configurations. The ohmic
values of these relays are 1840 ohms only. It is a part of Point minor group and
Point Major group. It is used for point detection.
3.14 WJR: These relays are available in 2F/2B contact configurations. The ohmic
values of these relays are 1840 ohms only. It is a part of Point minor group and
Point Major group. It is used to provide 10 sec time duration for point operation.
3.15 WR (Heavy Duty contactor Relay): These relays are available in 2F/2B contact
configurations. The ohmic values of these relays are 60 ohms only. It is a part of
Point minor group and Point Major group. It is used for point motor operation
3.16 Siemens Motorised Clockwork Timer: This relay works on 11 OV A.C. +/- 10%.
It has a time range of 1 to 5 minutes. The time can be adjusted. Its resetting is
automatic. A synchronous motor drives and switches over contacts after the lapse
of preset time. If the enersining circuit is prematurely interrupted, the mechanism
returns to its normal position before actuating the contacts. Usage : These relays
are used to count time delay
(b) Plug-in type Line relays of Neutral/ Polar Biased/ Magnetic latch/ Interlocked
type rated at 24/48/60 V DC shall normally be used. Suitable type of LED Lamp
proving relays (QECX-61) are used for signal LED lamps to meet with parameters
to suit various LED lamps.
Note:- SSE signal shall inform sectional ASTE/DSTE well in advance regarding
installation becoming due for safety integrity test, which is to be done once every 5
years
Schedule Code : R1
Periodicity : Signal Technician : Monthly,
Sectional JE/SSE:, Quarterly ,
Incharge SSE : Half-yearly
S.No. Check the following
1 Checking & cleaning of dust on relays
2
Working of Fans / AC’s & Electrical fittings to be checked.
3
Condition of windows & Main door to be checked.
Schedule Code : R2
Periodicity : Sectional JE/SSE:, Quarterly ,
Incharge SSE : Half-Yearly
1
Plugging of holes to rodent entries in relay room.
2
Checking of Relay room double lock effectiveness
3
Indoor Relay terminal voltages to be measured and recorded.
4
In cable rack far ends functional relay voltages to be measured and recorded.
5
Check for any rain water leakages.
6
Relay room Proximity switch for Relay room door to be checked.
7 Check the condition of Relay holding clip.
Schedule Code : R3
Periodicity : Incharge SSE : Yearly
1
Visual inspection of relays.
2
Accuracy of time delay circuit.
3
Sealing of relays are intact, effective and not tampered.
4
Checking of No label relays. Painting of nomenclature wherever required.
5
Cable Armour earth intactness and proper tinkering to be checked.
6
Proper bunching and lacing of relay wiring.
7 The relay to be checked for defects in respect of – pitting or charring of
contacts, dust accumulation on contacts, corrosion / rusting of components,
crack or breakage in components, presence of fungus and ants inside the
relay casing, charring of cover near contacts in the case of plug-in-type relays,
corrosion of label, absence or tempering of seal, any other abnormal condition.
NOTE: (i) Effectiveness of anti-tilting arrangement on shelf-type relays to be checked
wherever these are existing.
(ii) Overhauling is not more than 10-12 years old for track relays and 15 years for shelf
type line relays.
5. Clean and tighten all wiring inside the Master control unit.
Switch ON the Panel - if any fault -LED indications will appear on panel
6.
display.
7. Check various parameters
9. Output Supply-24 V DC
Sensor Cable Check Loop resistance for open or short circuit, (Fire survival
10.
Circuit Integrity Cable)
11. System Loop Voltage= 24 V DC.
To check Battery charged or not- after disconnection of wire from battery
12.
terminals= 24 V DC
13. Check the Hooter
Note:- Whenever any wire, cable, gears etc. are opened and disconnected, it should be with
proper written tag, care should be taken for proper reconnection of wires, cables.
Typical Bonding and Earthing Connections for Signalling Equipments. Annexure 6
Ref : STS/E/TAN/3006
Section 1: General
22.1.1.1 Objectives:
(b) To ensure that interference from the traction system cannot, under any
circumstances, cause the Signalling system to exhibit false clear
indications, or in any other way imperil the safe operation of trains. This
objective must be achieved even if the traction or Signalling system is in a
faulty or anomalous condition.
(c) To minimise danger to life from electric shock derived from the traction
system.
Note (i) :- Protective wire-mesh screen of approved design and size shall
be provided wherever clearance of more than 2 meter for any part of the
signal from live OHE conductor is not possible to get.
(a) Length of parallelism between the cable conductors and the electrified
track;
(d) Return current through the rails and return conductor where provided;
22.2.2.2 On electrified sections, the masts, insulators, wires and supports obstruct
the visibility of Signals. In addition, the Signals have to be so erected that
they maintain a minimum clearance from the live parts of the O.H.E. The
instructions in this section shall be strictly followed in so far as the
electrical clearance is concerned. These instructions may be taken as a
rough guide in determining the location of signals, which would afford the
best visibility to the Loco Pilots of approaching trains. However, the actual
visibility shall in all cases, be checked by a Signal Sighting Committee and
action to improve the visibility taken on the recommendations of the
Committee.
22.2.2.3 The location of signals and the protection required shall be worked out
from the following signal clearance diagram.
For tangent tracks & tracks with super
Drg. No 22.D1
elevation less than 60 mm.
Broad For curved tracks with super elevation 60
Drg. No 22.D2
Guage mm to 140 mm.
For curved tracks with super elevation
Drg. No 22.D3
140 mm to 185 mm.
For uncompensated O.H.E for straight
Drg. No 22.D4
Metre track.
Guage For uncompensated O.H.E for track on
Drg. No 22.D5
curve.
Chapter - 22 : Requirements Of Signalling In 25 Kv Ac Electrified Area
22.2.2.5 The normal height of the contact wire is 5.60 meters at supports. The
normal height of the catenary at its highest point is 7.05 meters. In tunnels
as well as underneath bridges, where clearances are limited, the contact
wire may be as low as 4.58 meters for Broad Gauge and 4.02 meters for
Metre Gauge and the catenary is also lowered suitably or terminated at
the face of Bridges or Tunnels. The clearance diagrams have, however,
been drawn to suit the extreme positions of the catenary and the contact
wire. In addition, the diagrams make allowances for the stagger as well as
displacement of wires by wind.
(a) If any portion of a signal post or its fittings where signalling staff have
to work, falls within 2 meters of a 25 kV live conductor, or any metal part
electrically connected to this conductor such portion shall as far as
practicable be protected by an iron screen of size 20mm X 60mm (strand
3.25 mm wide and 1.6 mm thick) or any other approved design, solidly
connected to the Signal unit.
(b) If for any reason it is not practicable to provide the protective iron
screening as given in para (b) of Section 2 above, a Caution Board of
approved design shall be provided on the signal post at a height of 3
metres above the rail level, to caution the signal staff.
(c) The SSE/JE (Signal) shall explain these instructions to the staff
working under them and ensure that they are correctly complied with.
22.2.2.7 Drg. Nos. 22 D6 and 22 D7 illustrate the location of signals on the left-
hand side and right hand side of Broad Gauge track and the figures
indicate the minimum heights and distances of Signal from the track to
avoid electrical infringements.
(a) Neutral section shall be located away from stop signals, level crossing.
(b) If neutral section is provided after a stop signal, the distance* between
signal and neutral section shall be such that after stopping, the train shall
be able to pick up enough speed to coast through the neutral section
without any risk of stalling.
Normally, all signals should be located on the left side of the track for
which it refers. In exceptional cases the signals may be located on the
right side. To ensure adequate visibility of signals the OHE masts should
be implanted as per the ACTM. In case it is not possible, offset brackets
may be used for signal units without affecting the schedule of dimensions.
Further the following steps should be taken to achieve adequate visibility.
(b) PCSTEs and PCEEs of the zonal railways shall give dispensation for
reduction in the distance of placing mast in front of the signal from 30m to
10m on straight track after ensuring staggering for proper visibility of
signal as per provisions of ACTM and SEM.
(d) On tangent tracks it is desirable that the signal should be located within
the OHE structure, i.e. the implantation of the signal from the track centre
shall be less than the implantation of the OHE mast from the track centre.
The setting of OHE masts in the vicinity of the colour light signals shall be
as per para 20.5 of Appendix-I of the AC Traction Manual, Vol-II (Part-!I).
Relevant extracts as in Annexure-22/1.
22.3.3.2 No portion of a post or fittings of a colour light signal shall infringe with the
schedule of dimensions from the centre line of the nearest track.
(a) Setting distance of OHE masts shall be in accordance with Drg. No.22
D8
(b) The signal units shall be so fixed that the height of the centre line of
the red signal shall be approximately 3.65 meters above rail level. No part
of Signal without a route indicator shall normally be higher than 5.2 meters
above rail level.
(b) Portal drop arms shall not normally be located at least for a distance of
600m before the signal in track space where signals are located.
(a) Precautions and parameters for location of portal drop arms shall be as
specified under Para 22.3.3.4
(b) For details of drawings, illustrating the above principles for Colour Light
Signals, reference may be made to Drawing No.22 D.
22.3.3.7 Note :- The visibility of the signal shall be checked by day as well as by
night by the Official in charge (Signal) of the section after each phase of
the O.H.E work, i.e. erection of masts, provision of brackets, wiring, etc. If
at any stage the official feels that the visibility is not adequate, he shall
impose suitable speed restrictions and take such steps as are required to
improve the visibility.
22.4.4.1 As a rule, no aerial circuits shall be retained in the electrified zone. The
only exception may arise in the case of Block Circuits coming in from a
non-electrified zone. However, in each such case, it shall be ensured that
the Block Wires are terminated in a suitable lead in cable upto a distance
of 50 meters from the electrified track at right angle to track. In every such
case, the length of parallelism and the distance of Block Wires from the
nearest electrified track shall be checked to ensure that the maximum
induced voltage does not the exceed 60 volts limits prescribed by CCITT.
Paras 505(e), 508(b) and 549(a) of Indian Railway Telecommunication
manual (old) shall be considered for design and precautions.
22.4.4.3 The following electrical signalling equipment are not safe to withstand AC
induced voltage. The coils of this equipment can only be used inside a
cabin or a location box or internal circuits only. The coils of these
equipment shall be worked from a separate battery/DC-DC Converter and
this battery/DC-DC Converter shall not be connected to any external
circuits going outside the cabin/location box
22.4.4.4 All Batteries and the wiring in the equipment, location box or cabin shall be
well insulated from the ground. PVC insulated wires to an approved
specification (IRS-S-76) shall be used for wiring in location boxes and
cabins.
22.4.4.6 When more than one cable is laid between two locations or cabins, it shall
be ensured that as far as possible, all wires pertaining to any individual
circuit are within the same cable
22.4.4.7 Polarized Relays using permanent magnet shall not be used in any
external circuit in 25 KV AC electrified areas as the permanent magnet in
the relay tends to lose its magnetic properties due to continuous
application of induced voltages. Competent authority shall authorise any
exception in specific cases
22.4.4.8 The relays, which release an interlocking, shall be slow acting so that the
interlocking is not released inadvertently by voltage variations of short
duration. Time delay may be of the order of 0.6 to 0.8 seconds.
22.4.4.9 No external circuit shall work in A.C. electrified area without double cutting
(a) The length of any signalling line circuit must be limited to ensure that
the induced voltage from the traction system does not exceed 400 Volts
under normal conditions. If necessary, line circuits must be sectionalized.
Where line circuits leave line side enclosures or buildings in different
directions, this could give rise to a continuous circuit of such length that
the limits of induced voltage above could be exceeded. In such cases a
sectionalized power supply unit should be provided for each direction.
22.6.6.1 Signal feed system shall be of the 110V 50Hz type or any approved type.
22.6.6.2 The distance between the signal control relays and the signal must not
exceed the prescribed limits in electrified zone, measured along the line of
way. This will ensure that the voltage induced in the circuit will be
inadequate to illuminate the lamps, even under the most adverse
circumstances and with one or more earth faults present.
22.6.6.5 It shall be ensured that the power transformer for feeding circuits as per
section 22.6.6.2 shall be different from the transformer feeding longer
circuits.
(a) Point detection and point detection repeat circuits shall use ac-
immunized relay.
(b) The maximum permissible length for various types of commonly used
Point Machines is as under :-
The point rods in A.C electrified areas are subject to a certain amount of
induced voltage. In addition since the rods are in contact with the rails at
some point or other, the rail voltage, which can be quite high in case of
faults, is transmitted through them to the lever frame. Insulators shall,
therefore, be provided on the rodding as per instructions in section ..... for
protecting the Operating & Maintenance Staff from the effects of these
voltages
(b) Each rod shall be provided with an insulator in the lead out as close to
the cabin as possible. While providing this insulator, it shall be ensured
that there is no possibility of a contact between the insulated portion of
one rod and the un-insulated portion of another rod or signal wires, the rail
or O.H.E mast.
(d) If the distance between the two insulators at either end is greater than
300 meters, additional insulators shall be provided on each rod, so that
the distance between two consecutive insulators on the same rod is not
greater than 300 meters
(e) Each Point, Trap indicator and lock bar operated by rodding shall be
electrically isolated from the track.
(f) All insulators in a run shall be provided between the same two sets of
rollers and guides, so that there is no possibility of the insulated portion of
one rod coming into contact with the un-insulated portion of another rod.
(g) The clearance between the insulator and the adjacent rod roller shall
be adequate to permit normal movement of the rod.
(h) When a rod crosses the track, the top of the rod shall not be less than
40mm from the bottom of the rail. When steel or C.I sleepers are used, the
distance between the rod and the sleeper shall also be not less than 40
mm. Similarly, the distance between any O.H.E mast and the point rods
shall not be less than 40 mm.
(j) When the Engineering department provides the point lever or point box,
Engineering department shall provide the insulator on the operating rod.
22.7.7.5 For details of Block working in RE area please refer to Chapter 18.
22.7.7.6 For details of Track Circuits, AFTC in RE area, please refer to Chapter 17.
22.7.7.8 For details of Axle counter working, please refer to Chapter 17.
(c) Induction in all metallic bodies situated near the overhead equipment.
22.8.8.2 Proximity of a Live Conductor :- Any contact direct or indirect, with the
25 KV conductors is dangerous and shall be strictly avoided.
The flow of return current in the rails will give rise to a potential difference:-
(c) between an insulated rail and the non-insulated rail used for the
traction return current;
22.8.8.4 Wherever staff has to work on installations, which are in direct or indirect
Chapter - 22 : Requirements Of Signalling In 25 Kv Ac Electrified Area
(a) They shall as a general rule, wear rubber gloves and use tools with
insulated handles;
(b) When the work to be done is of such a nature that rubber gloves
cannot be used conveniently, special precautions shall be taken by
splitting the circuits into sections or earthing them. In special cases, both
the steps shall be taken simultaneously. If these protective measures
cannot be applied, staff must insulate themselves from the ground by
using rubber mats, etc. ;
(c) The cable conductors pertaining to the block instruments are likely to
develop heavy induced voltages and every time the staff handles the
terminals of Block Circuits, they must rigidly observe the provisions of
paragraphs (c) and (b) above. These cable terminals shall be printed RED
to remind the Maintenance staff of the danger. The Maintenance SSE/JE
(Signal) shall explain the meaning of this painting to the maintenance staff
and ensure that they correctly understand it.
(c) Before cutting the armour or the metal sheath of the cable or the wires
in the cables, an electrical connection of low resistance shall be
established between the two parts of the armour, the Sheathing and wires
that are to be separated by cutting.
22.8.8.8 Staff shall make themselves familiar with the instructions for treatment of
persons suffering from electric shocks. Instruction Boards in English and
in the regional languages describing the methods to be adopted for
treatment of electric shock shall be clearly displayed in all JEs/SSEs
(Signal)' offices.
(b) The staff responsible for the operation of the Signalling equipment of
the section shall immediately check whether the block and other signalling
equipment are working normally. If an abnormal working of any equipment
is noticed, its working shall be immediately suspended and necessary
action under the Rules shall be-taken.
(c) On receipt of this intimation, the staff responsible for the maintenance
of Signalling of the section shall immediately proceed to the site and test
all circuits and allied equipment paying particular attention to the external
signalling gear to ensure that no damage to it has taken place. An
authorised representative of the Signal Department shall submit Certificate
that everything is working all right and send it to his superiors along with a
detailed test report as soon as possible.
(d) Proper competency certificate shall be issued to all S&T staff working
in 25 KV AC RE area by ZTS/S&T training institute.
(b) Besides, any specific works pertaining to specific section, the following
S&T work shall be completed before issue of certificate for 2.2 kV
charging
Note :- This Chapter has under mentioned Annexures for further study
20.5 Masts near signals: The visibility of should be kept in mind while deciding the setting up masts
in their vicinity. The following principles should be observed for deciding the setting of masts near
signals.
(i) Where no approach signal is provided: The minimum settings of mast before should be 3.25,
3.10,3.05,2.90 and 2.75 m for distance upto 80m, beyond and upto 110m, beyond and upto 190m,
beyond and upto 270m and beyond and upto 400m respectively.
(ii) Where approach signal is provided and for signals other than distant signals:
The minimum setting of masts before the signal should be 3.25, 3.10, 3.05, 2.90 and 2.75m for
distance upto 50m, beyond and upto 70m, beyond and upto 115m, beyond and upto 160m and beyond
and upto 240m respectively.
(i) With horizontal route indicator: The minimum setting of masts before the signal should be 3.72,
3.50, 3.25, 3.05, 2.90 and 2.75m for distances upto 60m, beyond and upto 125m, beyond and upto
170m, beyond and upto 215, beyond and upto 250m, beyond and upto 310m respectively.
(ii) With other than horizontal route indicator: The minimum setting of masts before the signal
should be 3.50, 3.25, 3.05, 2.90 and 2.75m for distance upto 70m, beyond and upto 130m, beyond and
upto 170m, beyond and upto 215m and beyond and upto 280m respectively.
Note : 1. See Drg. No. ETI/OHE/G/00112 also. The setting may be reduced in special cases,
conforming to Figs. 6 to 9 of ibid.
Note: 2. Setting distance may be reduced for starter signals of loop lines and yard lines.
a) Signals without route indicators: No OHE mast should, as far as possible be located in the same
lane as the signal for a distance of at least 600m before a signal. Drop arms of portals should also not
normally be located in the lane where signals are located at least for a distance of 600m before the
signal. Where this is not possible, for any reason, the signal should be mounted on an off-set bracket.
In addition, a special study should be made in each such case in respect of three drop arms before the
signal, to see whether the drop arms can be off-set from the center line of the lane in a direction
opposite to the off-set of the signal or alternatively, whether it is possible to shorten the drop arms.
Reduction in the signal's height may also be examined.
b) Signals with route indicators: The principles mentioned under para 20.5.2 (a) should be observed
in these case also.
Note: 1. No. part of a colour light signal without a route indicator should, as far as possible be higher
than 5.2m above rail level. Great care should be exercised in deciding the locations of colour light
signals with route indicators so that the necessary minimum clearances are available between the
signals and live out of run conductors, or pantogaphs way zone.
2. On signal-line sections, signals (colour light as well as semaphore) should, as far as possible be
located on the side of the track opposite to the OHE masts.
20.5.3 For semaphore signals located outside the track : The minimum settings of masts before the
signal should be 3.05,2.90 and 2.75m for the first, second and next three masts respectively.
Note: For details see Drg. No. ETI/OHE/G/00112.
Page 269 of 301
Annexure `22/2`
Maintenance in Electrified areas
a) Every Engineering official working in electrical traction area shall be in possession of a copy of rules
framed for the purpose of the operation of the Traction Power Distributions System pertaining to
Engineering Department and ensure that staff working under him are also acquainted with the rules.
He will ensure that rules pertaining to carrying out engineering works are strictly observed.
b) All electrical equipment, every power line or cable shall be regarded as being 'live' at all times. No
work shall be commenced adjacent to any electrical equipment except on authority issued in writing by
a competent official of the Electrical Department to the effect that the equipment has been made dead
and earthed.
2) Defects in Overhead Equipment:- Defects or break downs in the overhead equipment including
track and structure bonds noticed by the Engineering staff shall be reported immediately to the
Traction Power Controller. When defects in the overhead equipment that are likely to cause damage to
pantographs or trains are noticed, and it is not possible to convey information to Station Masters or
Signal men to enable them to issue caution orders, the line shall be protected by the staff noticing such
defects according to General Rule 3.62.
3) Traction Bonds: - In electrified areas the return current fully or partially flows through the rail. To
ensure a reliable electrical circuit continuity and also to ensure proper earthing in case of leakage of
current, various types of traction bonds as described below are provided at suitable places and
maintained by the Electrical Traction Department: -
a) Longitudinal Rail Bonds: - In the case of D.C. traction system, practically the whole return current
flows through the rail. Therefore, two flexible copper bonds offering minimum resistance to the flow of
current are provided at each rail joint under the fishplates. Two solid lugs at the two ends of the copper
bonds are inserted in holes drilled at the two rail ends between the fish bolt holes and are pressed by
using a bend press to rivet them firmly to the rails. On points and crossings and at junction fishplates
where continuity bonds of the above type cannot be provided due to space constraints, continuity of
return current path is achieved by using mild steel straps or G.I. wire ropes.
Absence of such bonds may cause unsafe working condition and in extreme cases may damage the
rail ends.
b) Cross Bonds (D.C): Cross bonds are provided between adjacent tracks at regular intervals to
reduce resistance of the current to the minimum. Such cross bonds are also known as transverse
bonds.
c) Structure Bonds:- All structures supporting overhead equipment either in AC or D.C. track circuited
areas are connected to the running rails for ensuring good earthing. Failure of insulator or leakage of
current switches off the supply from the sub station so that men coming in contact with supporting
structure etc., do not get electric shock. Removal or tampering of such bonds can, therefore, result in
unsafe conditions. Since the structure are grouted in concrete, they are likely to become charged in
case such bonds are kept disconnected. Similarly, other steel structures such as foot-over bridges,
sheds, etc., in the vicinity of O.H.E lines are also connected to rails through similar structure bonds.
a) Proximity of a Live Conductor: - The risk of direct contact with live O.H.E is ever present while
working in electrified sections such as for painting of steel work of through spans of bridges and
platform cover.
b) Build up of potential due to return current in rails :- The return current in the rails may cause a
potential difference :-
2) The following precautions should, therefore, be taken while working in traction areas: -
a) No work shall be done within a distance of two meters from the live parts of the O.H.E without a'
permit-to-work'.
b) For work adjacent to overhead equipment the Engineering Inspect or shall apply to the proper
authority sufficiently in advance for sanctioning the traffic and power block required. The Traction
Power Controller through Traction Foreman will arrange to isolate and earth the section concerned on
the date and at the time specified in consultation with the Traffic Controller. He shall then issue 'Permit-
to-work' to the Engineering Inspector. On completion of the work the' Perm it-to-work' should be
cancelled and Traction Power Controller advised, who will then arrange to remove the Earth and
restore Power supply.
c) No part of a tree shall be nearer than 4 meters from the nearest live conductor. Any tree or branches
likely to fall on live conductors should be cut or trimmed periodically to maintain this clearance.
Authorized O.H.E staff should do cutting or trimming.
d) No fallen wire or wires should be touched unless power is switched off and the wire or wires suitably
earthed. In case the wires drop at a level crossing, the Gatekeeper shall immediately make
arrangements to stop all road traffic.
e) Work on Station roofs and Signal Gantries: - Staff working on station roofs and signal gantries
and similar structures adjacent to live Overhead Equipment shall not use any measuring tapes, tools
and materials when there is a possibility of their being dropped or carried by wind on to the live
overhead equipment.
f) Earth Work: - For excavation work adjacent to tracks, the following action is taken :-
i) In D.C. traction areas, intimation should be given in writing sufficiently in advance to the concerned
Traction Distribution Officer to enable him to depute the Traction Staff to be present in order to prevent
possible damage in the traction underground feeder cables which are always located near the running
lines.
ii) In AC traction areas, intimation should be given to the concerned officers of the Electrical General
Services and also S&T Department, since all the S&T and Electrical lines are cabled on account of
Electrical Induction.
In all AC and D.C. traction areas, the Traction Department provides cable markers showing location of
cables. In addition, tiles and bricks protect the cables and during excavation, if workmen come across
such tiles or bricks in an arranged manner, they should at once report the matter to the higher officials.
g) The relative alignments of the centerline of the track with respect to the alignment of the contact wire
must be maintained within the specified tolerances. This applies to both horizontal and vertical
clearances. Slewing or lifting of track must not be done outside the agreed maintenance limits unless
the position of the contact wire is altered at the same time. Adjustment of cant has a magnified effect
on the horizontal displacement of the centerline of the track with respect to the alignment of the contact
wire.
Horizontal clearances to structures within the limits laid down in the Schedule of Dimensions must be
maintained. For slewing or alterations to track involving adjustment of contact wire (outside the agreed
maintenance limits) sufficient notice should be given to the traction staff so that that they arrange to
adjust the overhead equipment.
h) Alterations to Track Bonding: - All bonds removed by the staff of the Engineering Department
shall be replaced by the staff of the Engineering Department and all such removals and replacements
shall be reported to the Assistant Electrical Engineer, Traction Distribution in charge, concerned
without delay.
j) Working of Cranes:- No crane shall be worked except on the authorized 'permit-to-work'. In every
case of working of a crane, arrangement should be made for the presence of authorised overhead
equipment staff to ensure that all safety precautions are taken.
k) Inspection of Tunnels: - For inspection of roofs and sides of a tunnel, the overhead equipment
shall be rendered 'dead'. Special insulated apparatus should be used if sounding the unlined portions
to locate loose rock in the roof and sides, is required to be carried out, when the overhead equipment
is 'live'.
I) As far as possible closed wagons shall be used for material trains. In case open or hopper wagons
are used, loading and unloading of such wagons in electrified tracks shall be done under the
supervision of an Engineering official not below the rank of a Permanent Way Mistry, who shall
personally ensure that no tool or any part of body of the worker comes within the' danger zone', i.e.
within 2 meters of OHE.
m) Steel tapes or metallic tapes with woven metal reinforcement should not be used in electrified
tracks. Linen tapes are safer and, therefore, should be used even though they are not accurate.
n) The top of foundation blocks in electrified structures should be kept clear of all materials.
1) During maintenance or renewal of track, continuity of the rails serving electrified tracks shall
invariably be maintained. For bridging gaps, which may be caused during removal of fish-plates or
rails, temporary metallic jumpers of approved design shall be provided as under. The Electrical
Department on requisition will provide the necessary jumper.
2) In case of rail fracture, the two ends of the fractured rail shall be first temporary connected by a
temporary metallic jumper of approved design (as shown in the sketch below). In all cases of
discontinuity of rails, the two parts of the rail shall not be touched with bare hands; Gloves of approved
quality shall be used.
3) In the case of track renewals temporary connection shall be made as showed above.
4) In the case of defective or broken rail bond, a temporary connection shall be made as shown above.
285 Catch Sidings: - Normally all catch sidings except those, which are sanded, shall be kept alive.
On sanded catch siding, the rails shall be kept clear of sand for a length of 21.5 meters, beyond the
section insulators in the overhead lines and the switches controlling the sanded catch sidings shall be
kept in the neutral position. If an electric engine or single or multiple unit train runs into the sanded
length of a catch siding, it may possible be insulated from earth except through the buffers or couplings
if connected to other vehicles, therefore, these sidings shall not be made alive when an electric engine
or single or multiple unit train or any vehicle coupled thereto are standing in the sanded track until all
staff have been moved away from positions where they are likely to make contact between the
permanent way formation and any part of the locomotive or single or multiple unit train or coupled
vehicles. No person shall attempt to enter, or leave or in any other way make contact between the
permanent way formation and the electric engine or single or multiple unit train or any vehicles coupled
thereto while one overhead equipment of the sanded length of siding is alive.
286 Additional precautions in AC Traction Area: - The following additional precautions are required
to be taken in AC traction areas :-
1) Build-up of potential due to induction in metallic bodies situated close to O.H.E : - It is important to
note that dangerous voltage may be induced in metallic masses such as fencing posts in the vicinity of
traction conductors. To avoid possibility of shock due to such voltages, the metallic structures are
bonded together and earthed.
2) Unloading of rails: - When unloading rails along tracks, care shall be taken to ensure that rails do
not touch each other to form a continuos metallic mass of length greater than 300 meters.
3) Permanent way staff are advised to keep clear of the tracks and avoid contact with the rails when an
electrically hauled train is within 250 meters.
288 Permanent Way Tools: - Permanent Way tools (insulated and un-insulated) along with gloves
shall be used in the manner as approved by the Chief Engineer of the Railway.
289 Treatment of persons suffering from Electric Shock: - When persons receive electric shock,
practically in every case, they can be revived with the prompt application of First Aid.
Method of Resuscitation: - The method of resuscitation resorted to should be that known as artificial
respiration.
Continuity of Treatment:- The efforts to restore breathing must be continued regularly and with
perseverance, and must not be discontinued until a Doctor has taken charge of the case.
290 Accident to power lines of outside bodies: - The Engineering Inspector shall be in possession
of the name and address of the officer-in-charge of each power line across Railway land to enable an
immediate report of any defect or accident appertaining thereto being made, under advise to the
Assistant Engineer/Divisional Engineer.
(c) Dynamic Speed Profile: The speed/distance profile that a train may
follow without violating the static speed profile and/or the end of
movement authority.
(f) Limit of Authority: The place beyond which the train has not
information but to which the train is authorised to run with a defined
target speed higher than zero. The train is expected to receive new
information before passing the limit of authority.
(g) Most Restricted Speed Profile: The speed which a train must not
exceed. It is the lowest speed taking into account all the various
speed profiles.
(i) Normal Brake: It is the brake command which reduces the Brake
Pipe pressure to apply normal brakes.
(n) Service Brake: It is the brake command which reduces the Brake
Pipe pressure to 1.5 Kg/Cm2
(o) Static Speed Profile: The description of the fixed speed restrictions
of a given line. The speed restrictions can be related to such items as
maximum line speed, gradients, curves, points, tunnel profiles,
bridges etc.
(p) Target: Location where the train speed should be below the given
target speed.
(r) Track Side Equipment: The equipment with the aim of exchanging
information with the vehicle for safely supervising train circulation.
The information exchanged between track and trains can be either
continuous or intermittent according to the ATP level and to the
nature of the information itself (In ETCS Level-1, the communication
of information is from track side to train only).
(t) Train Integrity: The level of belief in the train being complete and
not having left coaches or wagons behind.
(u) Train Interface Unit: The unit, inside the on-board equipment, that
provides the interface between the on-board equipment of ATP and
the train.
23.1.1.1 There are two types of ATP Systems. European Train Control System
(ETCS) and National ATP System. ETCS has four levels. Train Collision
Avoidance System (TCAS) is Indian Railways ATP System.
23.1.1.2 ATP systems shall confirm to latest specification and shall be of approved
type.
23.1.1.3 ATP systems shall be suitable for working on Electrified and Non-
Electrified sections.
23.1.1.5 ATP systems shall have two sub-systems viz. Trackside and On-board.
23.1.2.0 Trackside:
23.1.3.0 On-board:
23.1.3.1 The On-board equipment of the ATP shall be correctly and effectively
interfaced to existing Air/Vacuum/Dual/Electropneumatic brake system of
Diesel and Electric Locomotives as well as other self-propelled vehicles
treated as train.
23.1.3.2 The On-board vital computer (OBC) shall calculate the maximum
permitted speed for the track section ahead based on a dynamic speed
profile taking into account the train running/braking characteristics which
are known on-board and the MA and track description data received from
trackside.
23.1.3.3 It shall continuously supervise the train speed and apply brakes if the train
speed exceeds the most restrictive speed by a pre-defined speed margin.
23.1.3.4 It shall give a warning to the Loco Pilot to enable him to react and to avoid
intervention from on-board equipment for application of service brake.
23.1.3.5 It shall not be possible to mute the warning and to stop automatic brake
applications by prior operation on Driver Machine Interface (DMI).
23.1.3.6 It shall not be possible to cancel the Emergency brake application initiated
by interrupting the power supply to the system.
23.1.3.7 The speed sensors shall be provided on the locomotive itself or on the
coach housing the on board equipment for EMU/MEMU.
23.1.4.1 The track side and on-board equipment shall not in any way infringe the
schedule of dimensions being followed by the Indian Railways.
23.1.5.2 Onboard: The On board equipment of the ATP shall work on the DC
power supply available in the locomotive.
23.1.6.1 The current mode of On-board equipment shall be indicated to the Loco
Pilot by means of suitable indications on the DMI
23.1.6.2 In case of mode transition, when the responsibility of the loco pilot
increases due to result of such automatic transition, the OBC shall seek
an acknowledgement from the loco pilot, irrespective of the train is
stationary or moving. In case the transition has to be acknowledged and
the loco pilot fails to acknowledge as required, the OBC shall initiate a
brake application.
23.1.7.3 Factory Acceptance Testing shall be carried out on the application logic
before uploading it in track side or On-board.
23.1.7.4 Version Control and checksum shall be effectively implemented for both
Application and executive logic.
23.1.7.5 Zonal Railways shall set up a system to implement the changes in signal
interlocking and track description data for effective functioning of ATP
system.
23.1.8.1 The on-board equipment shall perform an automatic self-test when the
equipment is switched ON.
23.1.8.2 This self-test shall not require any action on the part of the Loco Pilot/
operator.
23.1.9.1 On-board system shall have provision for isolation to cater for failure
situation which shall result in disconnection of the system from the
locomotive braking system. This shall be indicated to the Loco Pilot by
means of a visual indication which shall be available even if DMI has
failed.
23.1.10.1 On board as well as Track side system shall be provided with data logging
for diagnostic functions. (To be updated with logged data security)
23.2.11.1 Level 0: A level of ATP defined to cover instances when the ATP on-
board equipment is operating in an area where the trackside is not fitted
with operational ATP equipment.
23.2.11.2 Level 1: A level of ATP overlaid onto conventional track side signalling
that uses balises / loop / Radio Infill to pass movement authorities to the
train whilst relying on conventional means to determine train position and
integrity.
23.2.11.3 Level 2: A level of ATP that uses radio to pass movement authorities to
the train whilst relying on trackside conventional means to determine train
position and integrity.
23.2.11.4 Level 3: A level of ATP that uses radio to pass movement authorities to
the train. Level 3 uses train reported position and integrity to determine if it
is safe to issue the movement authority.
23.2.12.2 In Level 0 it is authorized to operate trains without any train control system
and therefore line side fixed signals are to be followed by Loco Pilot.
23.2.12.3 Train detection and train integrity supervision are performed by the
trackside equipment of the underlying signalling system (interlocking, track
circuits etc).
23.2.12.5 No supervisory information is indicated on the DMI except the train speed.
Train data has to be entered in order not to have to stop a train at a level
transition to ATP equipped area and to supervise maximum train speed in
unfitted areas.
(a) Balises
(c) Communication link (data cable) between the LEU & the balise
23.2.13.4 The track-side system shall interface with the signalling system through
LEU without affecting normal working & safety of signalling system. LEU
shall take input regarding signal aspect through potential free contacts of
the Lamp Checking Relays (ECRs).
23.2.13.5 Because of the spot transmission of data, the train must travel over the
balise to obtain the next movement authority.
23.2.13.6 The fixing arrangement of the balise on the sleeper shall be such that it
does not require any drilling to the sleeper.
23.2.13.8 Train detection and train integrity supervision are performed by the
trackside equipment of the underlying signalling system (interlocking, track
circuits etc.) and are outside the scope of level-1 ATP system.
(c) If the current train speed exceeds the Release Speed, emergency
brake shall be applied by the Level 1.
(a) Balises.
23.2.14.5 Based on inputs received from Signalling interlocking, Radio Block Centre
generates Movement Authorities which are transmitted to the train via
radio.
23.2.14.6 Train detection and train integrity supervision are performed by the
trackside equipment of the underlying signalling system (interlocking, track
circuits etc.) and are outside the scope of Level 2.
23.2.14.8 Train movements shall be supervised continually by the radio block centre
in its territory.
23.2.14.9 The radio block centre which provides the information to the trains shall
know each ATP controlled train individually by the unique identity of its
leading ATP on-board equipment.
23.2.14.11 The balises act as reference points and are used only to correct the
accumulated odometry error. Between two balises, the train determines its
position via speed sensors (Pulse Generators, accelerometer, radar).
23.2.14.12 The on-board computer continuously compares the train speed with the
23.2.15.0 Level 3
(a) The Driver Machine Interface shall be applicable for all the levels. A
typical overall view of the main window of DMI during start of mission
(i.e., start of travel) is shown below..
(c) A typical overview of the objects in the planning area during running of
the train is shown below. This is in the right side of Driver Machine
interface.
(c) Radio
(d) Loco Radio Unit consisting of two Radio Modems in hot standby with
separate cables and antennae for each radio
23.3.16.4 Stationary unit of IRATP shall have feasibility to interface with relay based
Interlocking and Electronic Interlocking.
23.3.16.5 Train detection and train integrity supervision are performed by the
trackside equipment of the underlying signalling system (interlocking, track
circuits etc.) and are outside the scope of IRATP.
23.3.16.6 DMI of onboard unit of IRATP shall provide assistance to Loco Pilots by
means of real-time display of aspect of approaching signal.
23.3.16.9 The Stationary unit which provides the information to the trains shall know
each ATP controlled train individually by the identity of its leading ATP on-
board equipment.
23.3.16.11 The RFID Tags act as reference points and shall be used to correct the
accumulated odometry error. Between two RFID Tags, the train shall
determine its position via Pulse Generators.
23.3.16.12 The fixing arrangement of the RFID Tag on the sleeper shall be such that
it does not require any drilling to the sleeper.
23.3.16.13 The on-board computer shall continuously compare the train speed with
the permitted speed and commands the brake application, if necessary.
23.4.18.0 This is an old generation system which is not governed by any level of
ATP. Presently, this is prevailing in suburban sections of Central and
Western Railways. To sustain the existing installations, RDSO has also
issued a specification for Advanced Auxiliary Warning system (AAWS).
23.5.19.0 Definitions:
23.5.19.1
(c) Train Graph: Train Graph is a tool to plan and track trains based on
train ID number, indicating when the train is arriving or departing each
station.
Servers:
23.5.19.3 Operation
(b) The CTC Controller shall be able to perform all the operations of
the panel/VDU of any station under the territory of CTC.
(c) CTC Controller and the ASM at station must be able to hand
over/take over the control of station both in normal and in
emergency conditions.
(d) CTC Controller must be able to communicate with ASM and the
gateman of stations of his territory by secured means of
communication.
(b) Occupancy of various track sections along with the train ID and
train description shall be displayed. Train IDs shall be indicated in
different colours for suburban, Long distance, Goods & other types
of trains. In case train ID is not keyed-in, the same shall be shown
as flashing unknown train identifier mark along with Alarm. Alarm
will stop as soon as the train number is keyed in by the controller /
way side ASM.
(c) If a train has stopped at any point enroute for more than the
prescribed time, an alarm should be raised to draw attention of the
controller.
(e) A section controller can log in, as predefined section controller and
the display of the controlled section will then change.
(f) Work stations shall have visual display of suitable size with
specified features.
(h) Big yards can be divided in parts, for display on one more than one
screens. with provision of selecting any one part on a screen with
facility of scrolling to see the full yard on one or more screens.
(i) If train identification has not been entered by the train arriving/
dispatching station, all Section Controllers shall have facility for
entering it on getting Alarm.
(j) It shall be possible to view train graphs. The train graph shall also
cover advance charting showing traffic blocks. Train graph
lines/Train ID box should have tag with detail of train, crew etc.
(k) In case of unusual events and delays of trains, system will inform
promptly the controller to enter the reason and other details in the
prescribed format.
(n) All the required traffic alarms shall be available on all concerned
controllers terminals.
(a) TMS facilitates “On Line” display of the Trains' status on Visual Display
Units at stations.
(c) The response time of TMS from change of any event at stations to
display at centralized location shall be minimum, as prescribed.
(ii) Interfacing with the train indicator boards at various stations for
minute to minute train arrival information to commuters
(a) It shall have provision of ‘On line’ display of movement status of all
trains along with their identification.
(c) It shall have the provision of feeding data regarding unusual and
incidences.
(a) Train Describer Module: For assigning and displaying train IDs.
(b) MIS report Generator: For plotting train control chart and generation
of Punctuality reports.
(d) Time Table Editor: For identifying path to introduce new train
services etc.
Note : For Brief information on Computer Based Train Control System (CBTC), Please
refer to Annexure 23/5
Note :- This Chapter has under mentioned Annexures for further study
2 In order to achieve safety with a number of trains using the same line, it became
essential to provide information to the driver by some sort of “signals” about
where to stop or how fast the train can go etc.
3 To derive the information required to convey to the driver through “signals”, some
form of train detection was essential, to know where exactly the train in question
is with reference to other trains or other hurdles.
4 To provide means for more than one train to use the same line, it became
necessary to divide the line into “blocks” and ensure there is only one train in
each “block”.
5 To control the trains and allow precedence between slow and fast trains, it
became necessary to have stations with turnouts and loops.
6 To ensure the points and crossings of a turnout were set within safety limits for
prevention of derailment, it was necessary to ‘detect’ the point by the signaling
system before allowing train movement i.e it was necessary to “interlock” the
signal with the points. The interlocking may be achieved through Relay based or
Microprocessor based.
8 The rolling stock must have automatic train protection to eliminate driver errors.
9 The need for high frequency of train service necessitate automation of train
supervision and route setting for quick turn round in terminal stations.
10 In Communication Based Train Control (CBTC) signaling system the primary train
detection is purely based on failsafe communication link between the train and the
control centre with the train communicating its position continuously and the
control centre communicates the position to other trains for maintain the safety
distance between two trains. Track circuits or axle counters if any are used only
as a secondary detection in case the Metro operator desires a fall back system.
12 Considering the need for higher order of safety, as well due to the presence of
halts at frequent intervals of even less than a KM length, Primarily the train
detection is done by communication, based on the train location, the movement of
authority is to be updated which is known as a moving block, which include a
safety envelope behind and in front of a train, always moving along with the train.
14 CBTC uses Cab signaling in which the signal aspects were made available right
inside the driver’s cab by way of displays. Information to be displayed had to be
provided from track side to the equipment on-board the train. The information
exchange between track to train is done through
15 (a) by fixing coils on the track as well as underneath the cab and transferring
information by magnetic induction.
18 or
20 The rolling stock must have on-board electronic/computing equipment for cab
signalling equipped with Automatic Train Protection (ATP) for eliminating
accidents due to SPAD.
22 The rolling stock must have on-board electronic/computing equipment for cab
signalling equipped with Automatic Train Protection (ATP)
24 Automatic Train Protection (ATP) comprises of the sub-systems which provide the
basic safety by way of fail-safe detection of dangerous conditions and controlling
and stopping the train when required independent of any action by the driver
when the train is being driven manually. ATP also ensures similar fail safe
protection even when train is being driven automatically.
27 ATS works with the driver if the train is manually driven to keep him informed
about when to leave a station. In case of ATO operation, the ATS will work with
ATO and control the movements of all trains in the network. The Traffic Controller
can manually intervene and take over the functions any time as required, due to
any emergencies or disruptions in the network