Project: ETAP Page: 1

5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

Electrical Transient Analyzer Program

Short-Circuit Analysis

IEC 909 Standard


3-Phase Fault Currents
Maximum Short-Circuit Current

Swing V-Control Load Total


Number of Buses: 4 0 16 20

XFMR2 XFMR3 Reactor Line/Cable Impedance Tie PD Total


Number of Branches: 3 4 0 8 0 0 15

Synchronous Power Synchronous Induction Lumped


Generator Grid Motor Machines Load Total
Number of Machines: 3 2 0 8 0 13

System Frequency: 50 Hz

Unit System: English

Project Filename: 61A,61B(62A,62B)

Output Filename: D:\work\2003.8至今\电厂\东方工程\naga\司令图\施工图图纸\F295S-D0101 总的部分 邓鹏\龙湾计


算书\Untitled.SI1
Project: ETAP Page: 2
5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

Adjustments

Apply Individual
Tolerance Adjustments /Global Percent
Transformer Impedance: Yes Individual

Reactor Impedance: Yes Individual

Overload Heater Resistance: No

Transmission Line Length: No

Cable Length: No

Apply Individual
Temperature Correction Adjustments /Global Degree C
Transmission Line Resistance: Yes Individual

Cable Resistance: Yes Individual


Project: ETAP Page: 3
5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

Bus Input Data

Bus Initial Voltage


ID Type Nom. kV Base kV Sub-sys %Mag. Ang.

Bus 01A Load 6.000 6.000 1 100.00 .00


Bus 1A Load 6.000 5.429 1 100.00 .00
Bus 01B Load 6.000 6.000 1 100.00 .00
Bus 1B Load 6.000 5.429 1 100.00 .00
Bus 2A Load 6.000 5.429 1 100.00 .00
Bus 2B Load 6.000 5.429 1 100.00 .00
Bus 3A Load 6.000 5.429 1 100.00 .00
Bus 3B Load 6.000 5.429 1 100.00 .00
Bus4 SWNG 20.000 18.095 1 100.00 .00
Bus7 Load 6.000 5.429 1 100.00 .00
Bus8 Load 6.000 5.429 1 100.00 .00
Bus12 Load 6.000 5.429 1 100.00 .00
Bus13 Load 6.000 5.429 1 100.00 .00
Bus14 Load 6.000 5.429 1 100.00 .00
Bus15 Load 6.000 5.429 1 100.00 .00
Bus16 Load 6.000 6.000 1 100.00 .00
Bus17 Load 6.000 6.000 1 100.00 .00
Bus1 20 SWNG 20.000 18.095 1 100.00 .00
Bus 150 SWNG 150.000 150.000 1 100.00 .00
Bus2 20 SWNG 20.000 18.095 1 100.00 .00

20 Buses Total

All voltages reported by PowerStation are in % of bus Nominal kV.


Base kV values of buses are calculated and used internally by PowerStation.
Project: ETAP Page: 4
5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

Line/Cable Input Data

Ohms or Siemens/1000 ft per Conductor (Cable) or per Phase (Line)


Line/Cable Length
ID Library Size Adj. (ft) % Tol. #/Phase T (°C) R X Y
Cable1 492.1 0 3 40 0.04136 0.05090 0.0000000
Cable3 492.1 0 3 40 0.04136 0.05090 0.0000000
Cable4 492.1 0 3 40 0.04136 0.05090 0.0000000
Cable5 492.1 0 3 40 0.04136 0.05090 0.0000000
Cable6 492.1 0 3 40 0.04136 0.05090 0.0000000
Cable7 492.1 0 3 40 0.04136 0.05090 0.0000000
Cable8 492.1 0 3 40 0.04136 0.05090 0.0000000
Cable9 492.1 0 3 40 0.04136 0.05090 0.0000000

Line / Cable resistances are listed at the specified temperatures.


Project: ETAP Page: 5
5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

2-Winding Transformer Input Data

Transformer Rating Z Variation % Tap Setting Adjusted Phase Shift


ID MVA Prim. kV Sec. kV % Z X/R + 5% - 5% % Tol. Prim. Sec. % Z Type Angle
GT-1 370.000 150.000 20.000 14.00 15.00 5.00 -5.00 -10.0 5.000 -5.000 12.6000 Std Pos. Seq. 0.0
GT-2 370.000 150.000 20.000 14.00 15.00 5.00 -5.00 -5.0 5.000 -5.000 13.3000 Std Pos. Seq. 0.0
T4 370.000 150.000 20.000 14.00 15.00 5.00 -5.00 -5.0 5.000 -5.000 13.3000 Std Pos. Seq. 0.0

3-Winding Transformer Input Data

Transformer Rating Tap Impedance Z Variation Phase Shift


ID Winding MVA kV % % Z X/R MVAb % Tol. + 5% - 5% Type Angle
T1 Primary: 40.000 150.000 0 Zps = 17.00 40.00 40.000 -5.0 5.00 -5.00
Secondary: 25.000 6.000 0 Zpt = 17.00 40.00 40.000 -5.0 Std Pos. Seq. 0.0
Tertiary: 25.000 6.000 0 Zst = 31.70 40.00 40.000 -5.0 Std Pos. Seq. 0.0
T5 Primary: 31.500 20.000 0 Zps = 15.00 40.00 31.500 -5.0 5.00 -5.00
Secondary: 16.000 6.000 0 Zpt = 15.00 40.00 31.500 -5.0 Std Pos. Seq. 0.0
Tertiary: 16.000 6.000 0 Zst = 28.00 40.00 31.500 -5.0 Std Pos. Seq. 0.0

UAT1 Primary: 40.000 20.000 0 Zps = 16.00 40.00 40.000 -5.0 5.00 -5.00
Secondary: 25.000 6.000 0 Zpt = 16.00 40.00 40.000 -5.0 Std Pos. Seq. 0.0
Tertiary: 25.000 6.000 0 Zst = 29.90 40.00 40.000 -5.0 Std Pos. Seq. 0.0

UAT2 Primary: 40.000 20.000 0 Zps = 16.00 40.00 40.000 -5.0 5.00 -5.00
Secondary: 25.000 6.000 0 Zpt = 16.00 40.00 40.000 -5.0 Std Pos. Seq. 0.0
Tertiary: 25.000 6.000 0 Zst = 29.90 40.00 40.000 -5.0 Std Pos. Seq. 0.0
Project: ETAP Page: 6
5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

Branch Connections

CKT/Branch Connected Bus ID % Impedance, Pos. Seq., 100 MVAb


ID Type From Bus To Bus R X Z Y
GT-1 2W XFMR Bus 150 Bus1 20 0.24 3.64 3.65
GT-2 2W XFMR Bus 150 Bus2 20 0.26 3.83 3.84
T4 2W XFMR Bus 150 Bus4 0.26 3.83 3.84
T1 3W Xfmr Bus 150 Bus 01A 1.09 43.60 43.61
3W Xfmr Bus 150 Bus 01B 1.09 43.60 43.61
3W Xfmr Bus 01A Bus 01B 7.06 282.26 282.35
T5 3W Xfmr Bus4 Bus 3A 1.50 59.90 59.92
3W Xfmr Bus4 Bus 3B 1.50 59.90 59.92
3W Xfmr Bus 3A Bus 3B 10.36 414.42 414.55
UAT1 3W Xfmr Bus1 20 Bus 1A 1.25 50.17 50.19
3W Xfmr Bus1 20 Bus 1B 1.25 50.17 50.19
3W Xfmr Bus 1A Bus 1B 8.48 339.17 339.28
UAT2 3W Xfmr Bus2 20 Bus 2A 1.25 50.17 50.19
3W Xfmr Bus2 20 Bus 2B 1.25 50.17 50.19
3W Xfmr Bus 2A Bus 2B 8.48 339.17 339.28
Cable1 Cable Bus 1B Bus7 2.30 2.83 3.65
Cable3 Cable Bus 1A Bus8 2.30 2.83 3.65
Cable4 Cable Bus 3B Bus15 2.30 2.83 3.65
Cable5 Cable Bus 3A Bus14 2.30 2.83 3.65
Cable6 Cable Bus 2A Bus12 2.30 2.83 3.65
Cable7 Cable Bus 2B Bus13 2.30 2.83 3.65
Cable8 Cable Bus 01A Bus16 1.88 2.32 2.99
Cable9 Cable Bus 01B Bus17 1.88 2.32 2.99
Project: ETAP Page: 7
5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

Power Grid Input Data

% Impedance
Power Grid Connected Bus Rating 100 MVA Base
ID ID MVASC kV R X" R/X
Tangerang Baru Substation Bus 150 1889.000 150.000 0.23897 5.28841 0.05
Teluk naga Substation Bus 150 4344.000 150.000 0.10701 2.29954 0.05

Total Connected Power Grids ( = 2 ): 6233.000 MVA

Synchronous Generator Input Data


% Impedance in Machine Base
Synchronous Generator Connected Bus Rating Xd" Excitation
ID Type ID MVA kV RPM % PF R Adj. Tol. R/X Xd, sat Type
Gen1 Turbo Bus1 20 371.584 20.000 3000 85.00 0.324 16.20 0.0 0.02 195.30
Turbine 130%
Gen2 Turbo Bus2 20 371.584 20.000 3000 85.00 0.324 16.20 0.0 0.02 195.30
Turbine 130%
Gen5 Turbo Bus4 371.584 20.000 3000 85.00 0.324 16.20 0.0 0.02 195.30
Turbine 130%

Total Connected Synchronous Generators ( = 3 ) : 1,114.752 MVA


Project: ETAP Page: 8
5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

Induction Machine Input Data

% Impedance
Induction Machine Connected Bus Rating (Motor Base) mFact.
ID Type Qty ID HP/kW kVA kV Amp PF R X" R/X" MW/PP
Mtr26 Motor 1 Bus7 14350.00 18126.00 6.0001744.00 87.00 2.10 16.53 0.13 7.18
Mtr24 Motor 1 Bus8 13885.00 17733.08 6.0001706.00 87.00 2.10 16.53 0.13 6.94
Mtr28 Motor 1 Bus12 13885.00 17733.08 6.0001706.00 87.00 2.10 16.53 0.13 6.94
Mtr21 Motor 1 Bus13 14350.00 18326.95 6.0001764.00 87.00 2.10 16.53 0.13 7.18
Mtr29 Motor 1 Bus14 12885.00 16456.00 6.0001583.00 87.00 2.10 16.53 0.13 6.44
Mtr30 Motor 1 Bus15 8765.00 11194.13 6.0001077.00 87.00 2.10 16.53 0.13 4.38
Mtr32 Motor 1 Bus16 13885.00 17733.08 6.0001706.00 87.00 2.10 16.53 0.13 6.94
Mtr34 Motor 1 Bus17 14350.00 18326.95 6.0001764.00 87.00 2.10 16.53 0.13 7.18

Total Connected Induction Machines ( = 8 ): 135629.3 kVA


Project: ETAP Page: 9
5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

SHORT-CIRCUIT REPORT

3-Phase fault at bus: Bus 01A

Nominal kV = 6.000 Voltage c Factor = 1.10 (Maximum If)

Peak Value = 95.991 kA (Method C)


Steady State = 25.140 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus % V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude
Bus 01A Total 0.00 2.263 -37.793 16.7 37.860

Bus16 Bus 01A 3.10 1.559 -10.853 7.0 10.964


Bus 150 Bus 01A 97.32 0.605 -23.612 39.0 23.620
Bus 01B Bus 01A 88.81 0.099 -3.328 33.7 3.329

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc


0.01 36.981 55.930 41.959
0.02 36.647 50.407 34.610
0.03 36.286 46.091 28.420
0.04 35.904 42.965 23.598
0.05 35.503 41.864 22.185
0.06 35.170 40.073 19.208
0.07 34.655 38.479 16.722
0.08 34.151 37.148 14.618
0.09 33.660 36.017 12.817
0.10 33.180 35.926 13.775
0.15 32.105 33.123 8.146
0.20 31.085 31.462 4.858
0.25 30.122 30.262 2.902
0.30 30.002 30.052 1.734
Project: ETAP Page: 10
5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

3-Phase fault at bus: Bus 1A

Nominal kV = 6.000 Voltage c Factor = 1.10 (Maximum If)

Peak Value = 98.106 kA (Method C)


Steady State = 25.876 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus % V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude
Bus 1A Total 0.00 2.297 -38.591 16.8 38.659

Bus8 Bus 1A 3.10 1.559 -10.853 7.0 10.964


Bus1 20 Bus 1A 94.77 0.636 -24.410 38.4 24.419
Bus 1B Bus 1A 87.34 0.101 -3.327 32.9 3.329

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc


0.01 37.780 57.193 42.939
0.02 37.445 51.584 35.479
0.03 37.085 47.189 29.181
0.04 36.703 43.999 24.265
0.05 36.301 42.874 22.812
0.06 35.968 41.041 19.765
0.07 35.454 39.413 17.217
0.08 34.950 38.056 15.058
0.09 34.458 36.903 13.208
0.10 33.979 36.829 14.207
0.15 32.904 33.963 8.413
0.20 31.884 32.277 5.023
0.25 30.921 31.067 3.003
0.30 30.801 30.853 1.796
Project: ETAP Page: 11
5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

3-Phase fault at bus: Bus 01B

Nominal kV = 6.000 Voltage c Factor = 1.10 (Maximum If)

Peak Value = 96.717 kA (Method C)


Steady State = 25.164 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus % V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude
Bus 01B Total 0.00 2.319 -38.141 16.4 38.211

Bus17 Bus 01B 3.20 1.616 -11.206 6.9 11.322


Bus 150 Bus 01B 97.32 0.605 -23.611 39.0 23.619
Bus 01A Bus 01B 88.71 0.099 -3.324 33.7 3.325

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc


0.01 37.304 56.308 42.177
0.02 36.959 50.683 34.682
0.03 36.588 46.309 28.388
0.04 36.193 43.154 23.501
0.05 35.779 42.052 22.097
0.06 35.470 40.284 19.097
0.07 34.937 38.680 16.598
0.08 34.417 37.342 14.488
0.09 33.908 36.203 12.685
0.10 33.413 36.108 13.688
0.15 32.300 33.292 8.067
0.20 31.243 31.609 4.796
0.25 30.246 30.381 2.855
0.30 30.122 30.170 1.700
Project: ETAP Page: 12
5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

3-Phase fault at bus: Bus 1B

Nominal kV = 6.000 Voltage c Factor = 1.10 (Maximum If)

Peak Value = 98.584 kA (Method C)


Steady State = 25.894 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus % V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude
Bus 1B Total 0.00 2.334 -38.820 16.6 38.890

Bus7 Bus 1B 3.16 1.597 -11.086 6.9 11.201


Bus1 20 Bus 1B 94.77 0.636 -24.410 38.4 24.418
Bus 1A Bus 1B 87.27 0.101 -3.324 32.9 3.326

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc


0.01 37.993 57.442 43.082
0.02 37.651 51.765 35.525
0.03 37.283 47.331 29.158
0.04 36.893 44.121 24.199
0.05 36.483 42.996 22.752
0.06 36.177 41.188 19.690
0.07 35.650 39.554 17.134
0.08 35.135 38.192 14.970
0.09 34.632 37.034 13.119
0.10 34.142 36.958 14.149
0.15 33.041 34.082 8.360
0.20 31.996 32.381 4.981
0.25 31.010 31.152 2.972
0.30 30.886 30.937 1.774
Project: ETAP Page: 13
5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

3-Phase fault at bus: Bus 2A

Nominal kV = 6.000 Voltage c Factor = 1.10 (Maximum If)

Peak Value = 98.039 kA (Method C)


Steady State = 25.842 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus % V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude
Bus 2A Total 0.00 2.296 -38.566 16.8 38.634

Bus12 Bus 2A 3.10 1.559 -10.853 7.0 10.964


Bus2 20 Bus 2A 94.68 0.636 -24.387 38.3 24.395
Bus 2B Bus 2A 87.32 0.101 -3.326 32.8 3.328

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc


0.01 37.755 57.153 42.907
0.02 37.420 51.545 35.449
0.03 37.060 47.153 29.153
0.04 36.678 43.964 24.239
0.05 36.277 42.840 22.788
0.06 35.944 41.009 19.743
0.07 35.429 39.382 17.197
0.08 34.925 38.026 15.040
0.09 34.434 36.874 13.191
0.10 33.954 36.801 14.193
0.15 32.879 33.937 8.405
0.20 31.859 32.252 5.018
0.25 30.896 31.042 3.000
0.30 30.776 30.829 1.794
Project: ETAP Page: 14
5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

3-Phase fault at bus: Bus 2B

Nominal kV = 6.000 Voltage c Factor = 1.10 (Maximum If)

Peak Value = 98.761 kA (Method C)


Steady State = 25.868 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus % V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude
Bus 2B Total 0.00 2.353 -38.913 16.5 38.984

Bus13 Bus 2B 3.20 1.616 -11.206 6.9 11.322


Bus2 20 Bus 2B 94.68 0.636 -24.385 38.4 24.393
Bus 2A Bus 2B 87.21 0.101 -3.322 32.9 3.324

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc


0.01 38.077 57.528 43.123
0.02 37.732 51.819 35.518
0.03 37.360 47.368 29.119
0.04 36.966 44.150 24.141
0.05 36.552 43.026 22.698
0.06 36.242 41.217 19.631
0.07 35.710 39.581 17.072
0.08 35.190 38.217 14.908
0.09 34.681 37.058 13.057
0.10 34.185 36.981 14.106
0.15 33.073 34.104 8.325
0.20 32.016 32.397 4.955
0.25 31.019 31.159 2.953
0.30 30.894 30.944 1.761
Project: ETAP Page: 15
5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

3-Phase fault at bus: Bus 3A

Nominal kV = 6.000 Voltage c Factor = 1.10 (Maximum If)

Peak Value = 84.619 kA (Method C)


Steady State = 22.011 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus % V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude
Bus 3A Total 0.00 2.050 -33.400 16.3 33.463

Bus14 Bus 3A 2.88 1.438 -10.092 7.0 10.194


Bus4 Bus 3A 95.47 0.533 -20.594 38.6 20.600
Bus 3B Bus 3A 87.06 0.080 -2.714 34.1 2.716

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc


0.01 32.644 49.226 36.845
0.02 32.333 44.238 30.193
0.03 31.997 40.378 24.629
0.04 31.641 37.603 20.318
0.05 31.268 36.618 19.059
0.06 30.888 34.982 16.422
0.07 30.410 33.577 14.234
0.08 29.943 32.406 12.391
0.09 29.487 31.410 10.822
0.10 29.043 31.332 11.756
0.15 28.049 28.883 6.891
0.20 27.106 27.411 4.077
0.25 26.217 26.328 2.417
0.30 26.107 26.146 1.433
Project: ETAP Page: 16
5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

3-Phase fault at bus: Bus 3B

Nominal kV = 6.000 Voltage c Factor = 1.10 (Maximum If)

Peak Value = 78.060 kA (Method C)


Steady State = 21.774 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus % V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude
Bus 3B Total 0.00 1.569 -30.281 19.3 30.322

Bus15 Bus 3B 1.97 0.953 -6.924 7.3 6.990


Bus4 Bus 3B 95.51 0.534 -20.604 38.6 20.611
Bus 3A Bus 3B 88.28 0.083 -2.752 33.2 2.754

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc


0.01 29.757 45.813 34.832
0.02 29.542 41.746 29.496
0.03 29.311 38.449 24.883
0.04 29.066 35.961 21.175
0.05 28.631 34.840 19.852
0.06 28.301 33.244 17.442
0.07 27.978 31.930 15.387
0.08 27.663 30.832 13.617
0.09 27.355 29.902 12.077
0.10 27.055 29.834 12.572
0.15 26.395 27.481 7.649
0.20 25.768 26.191 4.686
0.25 25.178 25.341 2.875
0.30 25.109 25.171 1.764
Project: ETAP Page: 17
5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

3-Phase fault at bus: Bus4

Nominal kV = 20.000 Voltage c Factor = 1.10 (Maximum If)

Peak Value = 410.686 kA (Method C)


Steady State = 92.497 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus % V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude
Bus4 Total 0.00 6.535 -151.803 23.2 151.943

Bus 150 Bus4 83.57 4.708 -76.317 16.2 76.462


Bus 3A Bus4 31.51 0.214 -2.029 9.5 2.040
Bus 3B Bus4 25.19 0.176 -1.621 9.2 1.630
Gen5 Bus4 100.00 1.437 -71.836 50.0 71.851

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc


0.01 145.995 243.278 194.602
0.02 143.723 228.084 177.105
0.03 141.290 214.231 161.033
0.04 138.718 201.814 146.582
0.05 136.024 192.156 135.726
0.06 134.995 183.390 124.130
0.07 133.948 175.649 113.624
0.08 132.885 168.803 104.097
0.09 131.806 162.738 95.449
0.10 130.712 159.820 91.960
0.15 129.056 142.910 61.384
0.20 127.359 133.949 41.497
0.25 125.636 128.802 28.382
0.30 123.896 125.440 19.618
Project: ETAP Page: 18
5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

3-Phase fault at bus: Bus7

Nominal kV = 6.000 Voltage c Factor = 1.10 (Maximum If)

Peak Value = 92.933 kA (Method C)


Steady State = 24.356 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus % V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude
Bus7 Total 0.00 3.315 -37.449 11.3 37.595

Bus 1B Bus7 7.37 1.865 -26.029 14.0 26.096


Mtr26 Bus7 100.00 1.450 -11.420 7.9 11.512

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc


0.01 36.652 53.518 38.998
0.02 36.292 46.458 29.003
0.03 35.906 41.865 21.528
0.04 35.498 38.949 16.029
0.05 35.069 37.196 12.398
0.06 34.752 35.989 9.358
0.07 34.208 34.933 7.082
0.08 33.677 34.102 5.372
0.09 33.158 33.408 4.085
0.10 32.652 32.823 3.349
0.15 31.523 31.536 0.917
0.20 30.451 30.452 0.257
0.25 29.440 29.440 0.073
0.30 29.313 29.313 0.021
Project: ETAP Page: 19
5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

3-Phase fault at bus: Bus8

Nominal kV = 6.000 Voltage c Factor = 1.10 (Maximum If)

Peak Value = 92.366 kA (Method C)


Steady State = 24.339 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus % V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude
Bus8 Total 0.00 3.284 -37.204 11.3 37.349

Bus 1A Bus8 7.37 1.865 -26.032 14.0 26.099


Mtr24 Bus8 100.00 1.419 -11.172 7.9 11.262

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc


0.01 36.426 53.209 38.785
0.02 36.074 46.208 28.876
0.03 35.697 41.649 21.457
0.04 35.297 38.751 15.993
0.05 34.878 37.010 12.381
0.06 34.533 35.777 9.354
0.07 34.002 34.732 7.086
0.08 33.483 33.912 5.380
0.09 32.976 33.229 4.094
0.10 32.482 32.655 3.358
0.15 31.379 31.393 0.922
0.20 30.333 30.335 0.260
0.25 29.347 29.347 0.074
0.30 29.224 29.224 0.021
Project: ETAP Page: 20
5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

3-Phase fault at bus: Bus1 20

Nominal kV = 20.000 Voltage c Factor = 1.10 (Maximum If)

Peak Value = 420.713 kA (Method C)


Steady State = 95.397 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus % V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude
Bus1 20 Total 0.00 6.803 -155.635 22.9 155.784

Bus 150 Bus1 20 82.45 4.867 -79.170 16.3 79.319


Bus 1A Bus1 20 29.93 0.248 -2.300 9.3 2.314
Bus 1B Bus1 20 30.31 0.251 -2.329 9.3 2.343
Gen1 Bus1 20 100.00 1.437 -71.836 50.0 71.851

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc


0.01 149.835 249.223 199.151
0.02 147.564 233.505 180.967
0.03 145.131 219.207 164.282
0.04 142.559 206.436 149.308
0.05 139.865 196.592 138.153
0.06 138.836 187.613 126.187
0.07 137.789 179.707 115.363
0.08 136.726 172.736 105.564
0.09 135.647 166.578 96.684
0.10 134.553 163.690 93.220
0.15 132.897 146.628 61.953
0.20 131.200 137.678 41.735
0.25 129.477 132.570 28.468
0.30 127.738 129.239 19.638
Project: ETAP Page: 21
5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

3-Phase fault at bus: Bus 150

Nominal kV = 150.000 Voltage c Factor = 1.10 (Maximum If)

Peak Value = 103.168 kA (Method C)


Steady State = 37.509 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus % V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude
Bus 150 Total 0.00 1.781 -38.892 21.8 38.932

Bus1 20 Bus 150 37.86 0.207 -4.852 23.5 4.857


Bus2 20 Bus 150 38.98 0.205 -4.750 23.2 4.755
Bus4 Bus 150 38.69 0.200 -4.715 23.6 4.719
Bus 01A Bus 150 31.23 0.032 -0.301 9.4 0.303
Bus 01B Bus 150 31.80 0.033 -0.307 9.4 0.309
Tangerang Baru Substation Bus 150 100.00 0.328 -7.263 22.1 7.271
Teluk naga Substation Bus 150 100.00 0.777 -16.702 21.5 16.720

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc


0.01 38.932 61.543 47.664
0.02 38.932 56.759 41.302
0.03 38.932 52.871 35.772
0.04 38.932 49.756 30.983
0.05 38.932 47.331 26.917
0.06 38.932 45.386 23.328
0.07 38.932 43.869 20.217
0.08 38.932 42.694 17.522
0.09 38.932 41.789 15.186
0.10 38.932 41.125 13.248
0.15 38.932 39.471 6.502
0.20 38.932 39.063 3.192
0.25 38.932 38.964 1.567
0.30 38.932 38.940 0.770
Project: ETAP Page: 22
5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

3-Phase fault at bus: Bus2 20

Nominal kV = 20.000 Voltage c Factor = 1.10 (Maximum If)

Peak Value = 413.182 kA (Method C)


Steady State = 92.612 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus % V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude
Bus2 20 Total 0.00 6.642 -152.781 23.0 152.925

Bus 150 Bus2 20 83.55 4.704 -76.298 16.2 76.443


Bus 2A Bus2 20 29.95 0.248 -2.302 9.3 2.315
Bus 2B Bus2 20 30.51 0.252 -2.345 9.3 2.359
Gen2 Bus2 20 100.00 1.437 -71.836 50.0 71.851

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc


0.01 146.977 244.744 195.697
0.02 144.705 229.400 178.003
0.03 142.273 215.413 161.745
0.04 139.700 202.894 147.139
0.05 137.006 193.223 136.252
0.06 135.977 184.402 124.556
0.07 134.930 176.619 113.965
0.08 133.868 169.744 104.367
0.09 132.789 163.658 95.661
0.10 131.694 160.786 92.243
0.15 130.038 143.845 61.496
0.20 128.341 134.894 41.531
0.25 126.618 129.761 28.385
0.30 124.879 126.409 19.610
Project: ETAP Page: 23
5.0.0C
Location: Date: 12-04-2008
Contract: SN: SOWESTEPDI
Engineer: Revision:Base
Study Case: SC
Filename: 61A,61B(62A,62B) Config.: Normal

Short-Circuit Summary Report

3-Phase Fault Currents

Bus Device Device Capacity (kA) Short-Circuit Current (kA)


ID kV ID Type Making Ib sym Ib asym Idc I"k ip Ib sym Ib asym Idc Ik
Bus 01A 6.000Bus 01A SwchG 37.860 95.991 25.140
Bus 1A 6.000Bus 1A SwchG 38.659 98.106 25.876
Bus 01B 6.000Bus 01B SwchG 38.211 96.717 25.164
Bus 1B 6.000Bus 1B SwchG 38.890 98.584 25.894
Bus 2A 6.000Bus 2A SwchG 38.634 98.039 25.842
Bus 2B 6.000Bus 2B SwchG 38.984 98.761 25.868
Bus 3A 6.000Bus 3A SwchG 33.463 84.619 22.011
Bus 3B 6.000Bus 3B SwchG 30.322 78.060 21.774
Bus4 20.000Bus4 Bus 151.943 410.686 92.497
Bus7 6.000Bus7 Bus 37.595 92.933 24.356
Bus8 6.000Bus8 Bus 37.349 92.366 24.339
Bus1 20 20.000Bus1 20 Bus 155.784 420.713 95.397
Bus 150 150.000Bus 150 Bus 38.932 103.168 37.509
Bus2 20 20.000Bus2 20 Bus 152.925 413.182 92.612

ip is calculated using method C


Ib does not include decay of non-terminal faulted indunction motors
Ik is the maximum steady state fault current
Idc is based on X/R from Method C and Ib as specified above

* Indicates a device with calculated duty exceeding the device capability.


# Indicates a device with calculated duty exceeding the device marginal limit. ( 95 % times device capability)

Short-Circuit Summary Report

3-Phase
Short-Circuit
Device Capacity
Current
Bus ID Device ID Ithr (kA) Tkr (sec.) Ith (kA)

Ithr = Rated short-circuit withstand current


Tkr = Rated short-time
Ith = Thermal equivalent short-time current
* Indicates a device with calculated duty exceeding the device capability.
# Indicates a device with calculated duty exceeding the device marginal limit. ( 95 % times device capability)