RISK ASSESSMENT
TITLE OF THE ACTIVITY: Temporary electrical installation
RISK ASSESSMENT REFERENCE NUMBER: ASCON/HSE/RA/MEP/014
ASSESSOR: Risk Assessment Committee Assessed Date: 06.12.2006 Reviewed Dated:
RISK RATING SCORE Risk After Action By Remarks
HAZARD Likelihood Severity Risk taking Whom
HAZARDS CONTROL MEASURES
EFFECT Rating Control
measures
Using Electric shock – 5 6 30 Mention proper rating while raising indent for 1x6=6
improper minor/major/fat procurement of any electrical system/device by
rated/defect al injury, Fire, a competent person.
ive Burn. Before installing/commissioning, competent
electrical person must check the rating and standard of
system and all the electrical system/devices.
device. All electrical installation should be checked
periodically by competent person (preferably
MEP co-ordinators at ASCON sites).
Ensure Earth Leakage Circuit Breaker (ELCB)
of 30mA .
Ensure Minimum resistance of earth pit is <5
Ohms.
Ensure system voltage as low as possible.
Improper Slip-trip-fall , 5 6 30 Place all power cables overhead as far as 1x6=6
cable Electric shock. possible.
routing Never pass cables through water/metallic part
like steel etc.
Do not tie cable with metallic wire
(GI/binding wire) – cable tie should be used.
Cable should be taken through cable gland and
lugs should be used for joining the cable with
panel.
Do not expose live part of cable .
Cable joint should be avoided as far as possible
– joint should be allowed only with proper lugs
and male-female plug system.
Do not allow joining of cable with insulation
tape .
RISK ASSESSMENT
TITLE OF THE ACTIVITY: Temporary electrical installation
RISK ASSESSMENT REFERENCE NUMBER: ASCON/HSE/RA/MEP/014
ASSESSOR: Risk Assessment Committee Assessed Date: 06.12.2006 Reviewed Dated:
RISK RATING SCORE Risk After Action By Remarks
HAZARD Likelihood Severity Risk taking Whom
HAZARDS CONTROL MEASURES
EFFECT Rating Control
measures
Power cable never be crisscrossed with
welding cable/gas cutting hose.
Exposure Short circuit/ 3 5 15 Only approved Electrical installations should 1x5=5
to water, failure of be used for outdoor application (weather &
dust and tripping fire proof)
heat. device/fire/elect Provide Hood / overhead protection to prevent
rical shock from rain water.
Ensure proper cable glands and rubber sleeves
to prevent dust entry.
Electrical panel door must be always kept
closed.
Physical Material 3 5 15 Ensure hard barrication around the D.B
damage to damage. Provide warning signs . 1x5=5
electrical Clear the access and avoid any material
installation stacking nearby D.B.
s. Canopy should be provided to protect from
falling objects.
Electric Electric Burn, 4 6 24 Repairing/Maintenance should be done by 1x6=6
shock, fire. Material competent/authorized electricians only.
Damage & LOTO (Lock out & Tag out) system should be
Fatality followed during repairing/maintenance.
Signature: ___________ Signature:___________
Safety Engineer. Project Manager (ASCON)
RISK ASSESSMENT
TITLE OF THE ACTIVITY: Temporary electrical installation
RISK ASSESSMENT REFERENCE NUMBER: ASCON/HSE/RA/MEP/014
ASSESSOR: Risk Assessment Committee Assessed Date: 06.12.2006 Reviewed Dated:
RISK RATING SCORE Risk After Action By Remarks
HAZARD Likelihood Severity Risk taking Whom
HAZARDS CONTROL MEASURES
EFFECT Rating Control
measures
Likelihood ( L) Severity ( S) Risk Rating ( Lx S)
1 Very unlikely 1 Negligible 1–7 Low
Risk Likelihood
2 Unlikely 2 First-aid (Acceptable) Rating 1 2 3 4 5 6
Injury 1 1 2 3 4 5 6
2 2 4 6 8 10 12
Severity
3 May happen 3 Minor injury 8 – 16 Medium 3 3 6 9 12 15 18
4 Likely 4 Major (Unacceptable) 4 4 8 12 16 20 24
5 5 10 15 20 25 30
5 Very likely 5 Severe 17- High 6 6 12 18 24 30 36
6 Certain or imminent 6 Fatality 36