Submittal Package
FTA1300 / FTA950
Wye-Delta Open Transition Starting
Mark IIXG Electric Fire Pump Controller With Power Transfer Switch
(DRAWINGS INCLUDED IN THIS PACKAGE ARE FOR STANDARD
CONTROLLERS. ACTUAL “AS BUILT” DRAWINGS MAY DIFFER
FROM THOSE SEEN HERE).
3412 Apex Peakway
Apex, North Carolina 27502
P 919 460-5200
F 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for
damages resulting from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2019
Firetrol, Inc., All Rights Reserved.
Publication SBP1300-61 Rev. J
Firetrol Mark IIxg Electric Fire Pump Controller
FTA1300 - Wye-Delta Open Transition Starting
Specifications
1.0 Main Fire Pump Controller
The main fire pump controller shall be a factory assembled, wired and tested unit. The
controller shall be of the combined manual and automatic type designed for wye-del-
ta open transition starting of the fire pump motor having the horsepower, voltage,
phase and frequency rating shown on the plans and drawings.
1.1 Standards, Listings & Approvals
The controller shall conform to all the requirements of the latest editions of:
NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection
NFPA 70, National Electrical Code
The controller shall be listed by:
Underwriters Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Con-
trollers Canadian Standards Association CSA-C22.2, Standard for Industrial Control
Equipment (cUL)
CE - Low Voltage Directive
The controller shall be approved by:
Factory Mutual (IEC 62091)
The City of New York for fire pump service
1.2 Enclosure
The controller components shall be housed in a NEMA Type 2 (IEC IP22) drip-proof, wall
mounted enclosure.
1.3 Withstand Ratings (Short Circuit Current Ratings)
All controller components shall be front mounted, wired and front accessible for main-
tenance. The minimum withstand rating of the controllers shall not be less than 100,000
Amps RMS Symmetrical at 200-600 Volts*. If the available system fault current exceeds
these ratings, the controllers shall be supplied with a withstand rating of 150,000 or
200,000 Amps RMS Symmetrical, as required.
*Note: 100,000 Amp withstand rating not available in some larger horsepowers. Consult factory for details.
1.4 Isolation Switch and Circuit Breaker
The controller shall include a motor rated combination isolating disconnect switch/cir-
cuit breaker, mechanically interlocked and operated with a single, externally mounted
handle. When moving the handle from OFF to ON, the interlocking mechanism shall
sequence the isolating disconnect switch ON first, and then the circuit breaker. When
the handle is moved from ON to OFF, the interlocking mechanism shall sequence the
circuit breaker OFF first, and then the isolating disconnect switch.
The isolating disconnect switch/circuit breaker shall be mechanically interlocked so
that the enclosure door cannot be opened with the handle in the ON position except
by a hidden tool operated bypass mechanism. The isolating disconnect switch/cir-
cuit breaker shall be capable of being padlocked in the OFF position for installation
and maintenance safety, and shall also be capable of being locked in the ON position
without affecting the tripping characteristics of the circuit breaker. The controller door
shall have a locking type handle and three point cam and roller vault type hardware.
The circuit breaker trip curve adjustment shall be factory set, tested and sealed for the
full load amps of the connected motor. The circuit breaker shall be capable of being
field tested to verify actual pick up, locked rotor, and instantaneous trip points after field
installation without disturbing incoming line and load conductors.
1.5 Operator Interface
The fire pump controller shall feature an operator interface with user keypad. The
interface shall monitor and display motor operating conditions, including all alarms,
events, and pressure conditions. All alarms, events, and pressure conditions shall be
displayed with a time and date stamp. The display shall be a 128x64 Backlit LCD capa-
ble of customized graphics. The display and interface shall be NEMA rated for Type 2,
3R, 4, 4X, and 12 protection and shall be fully accessible without opening the controller
door. The display and user interface shall utilize multiple levels of password protection
for system security. A minimum of 3 password levels shall be provided.
1.6 Ammeter/Voltmeter
The fire pump controller operator interface shall be capable of displaying true RMS
digital motor voltage and current measurements for all three phases simultaneously.
Displays requiring push-button and selector switches to toggle between phases or
current and voltage shall not be accepted.
Voltage and current shall be measured by True RMS technology to provide the most
accurate measurement for all sine waves, including non-sinusoidal waveforms. Aver-
age responding meters will not be accepted.
1.7 Digital Status/Alarm Messages
The digital display shall indicate text messages for the status and alarm conditions of:
• Motor On • Sequential Start Time • Minimum Run Time
• Local Start / Off Delay Time • Remote Start
• Fail to Start • System Battery Low • Under Voltage
• Over Voltage • Locked Rotor Trip • Over Frequency
• Emergency Start • Motor Over 320% • Drive Not Installed
• Motor Overload • Disk Error • Printer Error
• Disk Near Full • Pressure Error
The Sequential Start Timer and Minimum Run Timer/Off Delay Timer shall be displayed
as numeric values reflecting the value of the remaining time.
1.8 LED Visual Indicators
LED indicators, visible with the door closed, shall indicate:
• Power Available • Alarm• Pump Running • System Pressure Low
• Remote Start • Transfer Switch Normal • Deluge Open
• Transfer Switch Emergency • Phase Failure
• Phase Reversal • Interlock On • Fail To Start
• Motor Overload • Emerg. Iso. Switch Off • Automatic Shutdown Disabled
• Overvoltage • Undervoltage
1.9 Data Logging
The digital display shall monitor the system and log the following data:
• Motor Calls/Starts • Pump Total Run Time • Pump Last Run Time
• Total Controller Pwr On Time • Last Pump Start
• Min/Max System Pressure • Last Phase Fail/Reversal
• Last Locked Rotor Trip • Last Locked Rotor Current • Min/Max Frequency
• Max Starting Currents • Max Run Currents
• Min/Max Voltage per Phase while idle (not running) • Min Voltage per Phase during
Start
• Min/Max Voltage per Phase during Run
2.0 Event Recording
Memory - The controller shall record all operational and alarm events to system memory.
All events shall be time and date stamped and include an index number. The system
memory shall have the capability of storing 3000 events and allow the user access to
the event log via the user interface. The user shall have the ability to scroll through the
stored messages in groups of 1 or 10.
2.1 USB Host Controller
The controller shall have a built-in USB Host Controller. A USB port capable of accepting
a USB Flash Memory Disk shall be provided. The controller shall save all operational and
alarm events to the flash memory on a daily basis. Each saved event shall be time and
date stamped. The total amount of historical data saved shall solely depend on the
size of the flash disk utilized. The controller shall have the capability to save settings
and values to the flash disk on demand via the user interface.
2.2 Serial Communications
The controller shall feature a RS485 serial communications port for use with 2 or 4 wire
Modbus RTU communications.
2.3 Solid State Pressure Transducer
The controller shall be supplied with a solid state pressure transducer with a range of
0-300 psi (0-20.7 bar) ±1 psi. The solid state pressure switch shall be used for both display
of the system pressure and control of the fire pump controller. Systems using analog
pressure devices or mercury switches for operational control will not be accepted.
The START, STOP and SYSTEM PRESSURE shall be digitally displayed and adjustable through
the user interface. The pressure transducer shall be mounted inside the controller to
prevent accidental damage. The pressure transducer shall be directly pipe mounted
to a bulkhead pipe coupling without any other supporting members. Field connections
shall be made externally at the controller coupling to prevent distortion of the pressure
switch element and mechanism.
2.4 Seismic Certification
The controller shall be certified to meet or exceed the requirements of the 2012 Inter-
national Building Code and the 2013 California Building Code for Importance Factor 1.5
Electrical Equipment for Sds equal to 1.88 or less severe seismic regions. Qualifications
shall be based upon successful tri-axial shake-table testing in accordance with ICC-ES
AC-156. Certification without testing shall be unacceptable. Controller shall be clearly
labeled as rated for installation in seismic areas and a Certificate of Conformance shall
be provided with the controller.
NOTE: Not available on Model FTA1500 Controllers
2.5 Controller Operation
A digitally set On Delay (Sequential Start) timer shall be provided as standard. Upon
a call to start, the user interface shall display a message indicating the remaining time
value of the On Delay timer.
The controller shall be field programmable for manual stop or automatic stop. If set
for automatic stopping, the controller shall allow the user to select either a Minimum
Run Timer or an Off Delay Timer. Both timers shall be programmable through the user
interface.
A nonadjustable restart delay timer shall be provided to allow the residual voltage of
the motor to decay prior to restarting the motor. At least 2 seconds, but no more than
3 seconds, shall elapse between stopping and restarting the pump motor.
A weekly test timer shall be provided as standard. The controller shall have the ability
to program the time, date, and frequency of the weekly test. In addition, the controller
shall have the capability to display a preventative maintenance message for a service
inspection. The message text and frequency of occurrence shall be programmable
through the user interface.
A Lamp Test feature shall be included. The user interface shall also have the ability
to display the status of the system inputs and outputs.
An Audible Test feature shall be included to test the operation of the audible alarm
device.
The controller shall not start the fire pump motor under a single-phase condition. If
the motor is already running when a phase loss occurs, the controller shall continue to
run the motor, but still display a Phase Failure alarm.
The fire pump controller software shall be automatically upgraded through the USB
port by simply inserting a flash disk with the new software. Fire pump controllers that
require laptop computers, handheld equipment or specialized devices for software
upgrades shall be prohibited.
2.6 Manufacturer
The controller shall be a Firetrol brand.
3412 Apex Peakway
Apex, North Carolina 27502
P +1 919 460 5200
F +1 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-
ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2019 Firetrol, Inc., All Rights Reserved.
Publication SP1300-50 Rev. G
Automatic Power Transfer Switch for use with
Electric Fire Pump Controller
FTA950
Specifications
1.0 Main Fire Pump Controller with Transfer Switch
The main fire pump controller with transfer switch shall be a factory assembled, wired
and tested as a single unit. The controller shall be of the combined manual and auto-
matic type designed for full voltage starting of the fire pump motor having the horse-
power, voltage, phase and frequency rating shown on the plans and drawings.
1.1 Standards, Listings & Approvals
The controller with transfer switch shall conform to all the requirements of the latest
editions of:
NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection
NFPA 70, National Electrical Code
The controller with transfer switch shall be approved by:
Factory Mutual
The controller with transfer switch shall be listed by:
Underwriters Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Con-
trollers Canadian Standards Association CSA-C22.2, Standard for Industrial Control
Equipment (cUL)
1.2 Enclosure
The power transfer switch shall be housed within the fire pump controller enclosure
or in a NEMA Type 2 (IEC IP22) drip-proof enclosure attached directly to the fire pump
controller. Where the power transfer switch is provided in an attached enclosure, the
enclosures shall be fitted so that the assembly constitutes a single unit. The fire pump
controller/power transfer switch shall be factory assembled, wired and tested as a unit
prior to shipment.
1.3 Circuit Breaker
The power transfer switch shall include a motor rated combination isolating disconnect
switch/circuit breaker, mechanically interlocked and operated with a single, externally
mounted handle. When moving the handle from OFF to ON, the interlocking mechanism
shall sequence the isolating disconnect switch closed first, and then the circuit breaker.
When the handle is moved from ON to OFF, the interlocking mechanism shall sequence
the circuit breaker open first, and then the isolating disconnect switch.
The isolating disconnect switch/circuit breaker shall be mechanically interlocked so
that the enclosure door cannot be opened with the handle in the ON position except
by a hidden tool operated bypass mechanism. The isolating disconnect switch/cir-
cuit breaker shall be capable of being padlocked in the OFF position for installation
and maintenance safety, and shall also be capable of being locked in the ON position
without affecting the tripping characteristics of the circuit breaker.
The circuit breaker trip curve adjustment shall be factory set, tested and sealed for the
connected full load amps of the motor.
The circuit breaker shall be capable of being field tested to verify actual pick up, locked
rotor, and instantaneous trip points after field installation without disturbing incoming
line and load conductors.
1.4 Operator Interface
The transfer switch control panel shall have a 4 line, 20 character LCD display and key-
pad for viewing all available data and setting desired operational parameters. Volt-
age and frequency on both the normal and emergency sources shall be continuously
monitored. The normal source pick up shall be set at 95% of nominal voltage and the
emergency source pick up set at 90% of nominal voltage and 95% nominal frequency.
Source status screens shall be provided for both normal & emergency to provide digital
readout of voltage, frequency and phase rotation on all 3 phases.
1.5 Automatic Transfer Switch
The automatic transfer switch shall consist of an inherently double throw power transfer
switch mechanism and a microprocessor control panel to provide automatic oper-
ation. The transfer switch and control panel shall be of the same manufacturer. The
automatic transfer switch shall be an ASCO 7000 series with a group 5 control panel.
The transfer switch shall be electrically operated and mechanically held. The electrical
operator shall be a momentarily energized, single solenoid mechanism. The switch shall
be mechanically interlocked to ensure only two possible positions, normal or emergency.
Switches having a neutral position shall not be permitted.
The switch shall be positively locked and unaffected by momentary outages, so that
contact pressure is maintained at a constant value and contact temperature rise is
minimized for maximum reliability and operating life. All main contacts shall be silver
composition and inspection of all contacts shall be possible from the front of the switch
without disassembly of operating linkages and without disconnection of power.
Designs utilizing components of molded case circuit breakers, contactors, or parts
thereof, which are not intended for continuous duty, repetitive switching or transfer
between two active power sources are not acceptable.
A selector switch shall be supplied to manually test the transfer to emergency and the
re-transfer to normal power.
1.6 Remote Alarm Contacts
Remote alarm contacts shall be supplied as standard for the following conditions:
• Emergency Source Isolation Switch Open
• Normal Power Available
• Emergency Power Available
• Transfer Switch Position
1.7 Visual Indicators
Indicators, visible with the door closed, shall indicate:
• Transfer Switch in Normal
• Transfer Switch in Emergency
• Normal Source Accepted
• Emergency Source Accepted
• Emergency Isolation Switch Open
1.8 Audible Alarm Indication
An audible alarm shall sound for the following conditions:
• Emergency Isolation Switch Open
• Transfer Switch in Emergency
A Silence Alarm push-button shall be supplied.
1.9 Seismic Certification
The controller shall be certified to meet or exceed the requirements of the 2012 Inter-
national Building Code and the 2013 California Building Code for Importance Factor 1.5
Electrical Equipment for Sds equal to 1.88 or less severe seismic regions. Qualifications
shall be based upon successful tri-axial shake-table testing in accordance with ICC-ES
AC-156. Certification without testing shall be unacceptable. Controller shall be clearly
labeled as rated for installation in seismic areas and a Certificate of Conformance shall
be provided with the controller.
2.0 Manufacturer
The transfer switch shall be a Firetrol brand model FTA950.
3412 Apex Peakway
Apex, North Carolina 27502
P +1 919 460 5200
F +1 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-
ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2019 Firetrol, Inc., All Rights Reserved.
Publication SP950-50 Rev. D
Product Description
FTA1300
Mark IIxg Electric Fire Pump Controllers Wye-Delta Open Transition Starting
• Emergency Manual Run Mechanism to me-
chanically close motor contactor contacts in
an emergency condition
• Built-in Start and Stop push-buttons to bypass
automatic start circuits
• Minimum Run Timer / Off Delay Timer
• Daylight Savings Time Option
• Weekly Test Timer
• Elapsed Time Meter
• Door mounted display/interface panel fea-
turing a 128 x 64 pixel backlit LCD Graphical
Display, Membrane Type User Control Push-
buttons and easy to read LED Indicators for:
• POWER AVAILABLE
• ALARM
• TRANSFER SWITCH NORMAL (If unit ordered
with Automatic Power Transfer Switch)
Description—Firetrol® FTA1300 Wye-Delta, Open • TRANSFER SWITCH EMERGENCY (If unit ordered
Transition Starting Fire Pump Controllers are used with Automatic Power Transfer Switch)
with delta-wound squirrel cage motors. FTA1300 • SYSTEM PRESSURE LOW
controllers are of the open circuit transition • PUMP RUNNING
type in which the motor circuit is opened during • DELUGE OPEN
the transition from start to run. The controller • REMOTE START
monitors, displays and records fire pump system • INTERLOCK ON
information. • FAIL TO START
Actuating the controller by the pressure switch, • MOTOR OVERLOAD
START push-button or deluge valve contact • EMERGENCY ISO SWITCH OFF (If unit ordered
closes the start contactor connecting the mo- with Automatic Power Transfer Switch)
tor to the line in the wye connection. The motor • PHASE FAILURE
will draw approximately 33% of its normal inrush • PHASE REVERSAL
current and develop approximately 33% of its • AUTOMATIC SHUTDOWN DISABLED
normal starting torque. After a time delay, the • OVERVOLTAGE
motor is automatically reconnected in delta, ap- • UNDERVOLTAGE
plying full voltage to the motor windings. These • Digital Pressure Display
controllers are recommended especially for use • USB Host Controller and Port
• Solid State Pressure Transducer
with generator sets.
• Data Log
Approvals – Firetrol fire pump controllers are • Event Log (3000 Events)
listed by Underwriters’ Laboratories, Inc., in ac- • True RMS Metering with simultaneous 3 Phase
cordance with UL218, Standard for Fire Pump Display of Amps, Volts, Frequency, Pressure
Controllers, CSA, Standard for Industrial Control and Alarm Messages
Equipment, and approved by Factory Mutual. • Disk Error message
They are built to meet or exceed the require- • Disk Near Full message
ments of the approving authorities as well as • Pressure Error message
NEMA and the latest editions of NFPA 20, Instal- • Motor Over 320% message
lation of Centrifugal Fire Pumps, and NFPA 70, • Local Start message
National Electrical Code. • Remote Start message
• Emergency Start message
Standard Features—The following are included • Fail To Start message
as standard with each controller: • Undervoltage message
• Voltage surge protector • Overvoltage message
• Main Disconnect Switch sized for connected • NEMA Type 2 (IEC IP22) enclosure
motor horsepower and voltage • Suitable for use as Service Equipment
• Fire pump Circuit Breaker • Each standard controller comes with user set
• Single handle Isolating Disconnect Switch/ options for:
Circuit Breaker mechanism • Interlock Alarm • Low Pressure Audible
• Motor contactor • Low Suction • Pump Run
• User Defined Input • Weekly Test
Product Description - Options & Modifications
SPECIAL ENCLOSURES -BW Alarm Output Contacts, Phase Failure/Phase Reversal
-E Enclosure, NEMA Type 4 (IP66), Painted Steel -BY Alarm Output Contacts, Pump Overload
-F Enclosure, NEMA Type 4X (IP66), #304 Stainless Steel, -COM Alarm, Audible/Visible/Output Contacts, Low Suction
Brushed Finish Pressure with Manual Reset Option, Pressure Switch
-FD Enclosure, NEMA Type 4X (IP66), #316 Stainless Steel, Not Included (Do Not Use Options AH or AY)
Brushed Finish -CTS Alarm, Audible/Visible/Output Contacts, Low Suction
-FDB Enclosure, NEMA Type 4X (IP66), #316 Stainless Steel, Pressure Shutdown with Manual Reset Option and
12 Gauge, Seam-Welded, Brushed Finish Pressure Switch (Do Not Use Options AH or AY)
-FDP Enclosure, NEMA Type 4X (IP66), #316 Stainless Steel, -EG Alarm, Audible/Visible, Relief Valve Discharge
Painted Finish -EH Alarm Output Contacts, Relief Valve Discharge
-FXP Enclosure, NEMA Type 4X (IP66), #304 Stainless Steel, (Requires option -EG)
Painted Finish -EJ Alarm, Audible/Visible, Flow Meter On
-G Enclosure, NEMA Type 12 (IP54), Painted Steel -EK Alarm Output Contacts, Flow Meter On (Requires
-T Enclosure, NEMA Type 3R (IP24), Painted Steel option -EJ)
-KH Alarm Output Contacts, Common Alarm
CIRCUIT BREAKER OPTION -JR Visible Indicator, Jockey Pump Operating
-N Intermediate withstand rating -JT Alarm, Audible/Visible, Jockey Pump Trouble
150,000 Amps RMS Sym. -P Alarm, Audible/Visible, Built-In 120V Supervisory
-P High withstand rating System (Includes visible supervisory voltage normal
200,000 Amps RMS Sym indication and audible pump operating, phase fail-
Note: Intermediate and High withstand ratings may not ure and phase reversal indication)
be available for all horsepowers and voltages. -PE Alarm Output Contacts, Low System Pressure (pump
Consult factory for availability. on demand)
-PT Alarm, Audible/Visible, Built-in 240V Supervisory
ANTI-CONDENSATION SPACE HEATERS System (Includes visible supervisory voltage normal
-H Space Heater, 120V Externally Powered with indication and audible pump operating, phase fail-
Circuit Breaker ure and phase reversal indication)
-J Space Heater, 120V Externally Powered with Circuit
Breaker and Thermostat MISCELLANEOUS
-K Space Heater, 120V Externally Powered with Circuit -AZ Thermostat, Low Pump Room Temperature, Mount-
Breaker and Humidistat ed and Wired
-L Space Heater, 240V Externally Powered with -ED Output Contacts, Load Shed (Selectable power
Circuit Breaker source and adjustable time delay to remove non-
-M Space Heater, 240V Externally Powered with Circuit critical loads before starting)
Breaker and Thermostat -EL Series Pumping Operation, High Zone Controller
-N Space Heater, 240V Externally Powered with Circuit -EM Series Pumping Operation, Mid Zone Controller
Breaker and Humidistat -EN Series Pumping Operation, Low Zone Controller
-FZX Rating, Nameplate to be marked 380-400V (Use
PRESSURE TRANSDUCERS with voltage code ‘F’ or ‘FZ’)
-B Wetted Parts Including Pressure Sensor, 600 psi (42 -IEC Marking, CE with External Wet Parts (Requires NEMA
Bar) Fresh Water Type 12 (IP54) Enclosure as minimum)
-C Wetted Parts Including Pressure Sensor, 300 psi (21 -IECI Marking, CE with Internal Wet Parts (Requires NEMA
Bar) Sea Water Type 12 (IP54) Enclosure as minimum)
-D Wetted Parts Including Pressure Sensor, 600 psi (42 -OSP OSHPD Seismic Certification (State of California)
Bar) Fresh Water (Requires Option -SEI)
-MZN Neutral Lug, Service Entrance, Non-insulated Bonded
COMBINED AUTOMATIC POWER TRANSFER SWITCHES to Enclosure
-TSA FTA950 Automatic Transfer Switch, Group 5 -PK Terminal Blocks, Extra Remote Start
-TSAB FTA951 Automatic Transfer Switch, J-Bypass -PY Output Contacts, Motor Space Heater Circuit,
Isolation, Group 5 Externally Powered
-S Tropicalization
ALARMS -SEI Marking, Seismic Certified (in accordance with IBC)
-AC Alarm Output Contacts Extra, Pump Operating (Note: Not available on model FTA1500)
(1 Form A, 1 Form B) -USBX Data Port, External USB
-AF Alarm, Audible/Visible, Low Pump Room Temperature -ZPA Scheduled Service Message (when factory pro-
-AG Alarm, Audible/Visible, Reservoir Low grammed or programmed by Firetrol representative
-AH Alarm, Audible/Visible, Low Suction Pressure during start-up)
-AM Alarm Output Contacts, Fail to Start -ZPM Data Port, Serial Modbus RTU Over 2-Wire or 4-Wire
-AV Alarm Output Contacts, Low Pump Room RS485
Temperature (Requires option -AF) -ZPN Data Port, Serial Modbus RTU Over Ethernet TCP/IP
-AW Alarm Output Contacts, Reservoir Low
(Requires option -AG)
-AY Alarm Output Contacts, Low Suction Pressure Export packaging (Wooden crating to conform
(Requires option -AH) to IPPC Standards)
FTA1000 - 1930
3412 Apex Peakway
Apex, North Carolina 27502
P +1 919 460 5200
F +1 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-
ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2019 Firetrol, Inc., All Rights Reserved.
Publication PD1300-50 Rev. L
Product Description
FTA950
Assembled With Electric
Power Transfer Switch Fire Pump Controller
Standard Features—The following are included
as standard with each transfer switch:
• Emergency power source disconnect switch
sized for connected motor horsepower and
voltage
• Fire pump circuit breaker
• Mark II monitors for overcurrent tripping (non-
thermal) of circuit breaker and alarm indicator
for phase failure/phase reversal
• 3-pole, double throw transfer switch mecha-
nism, electrically operated, mechanically held
• ASCO Power Tech. Group 5 Control module
providing for the following:
-Door mounted operator interface panel with
4 line LCD display
-In-phase monitor
-Programmable engine exerciser
-Transfer switch data logging
Description—Firetrol® Power Transfer Switches -Differential voltage sensing on all phases of
are available completely assembled with Firet- the normal power source
rol Electric Fire Pump Controllers; full or reduced -Voltage sensing of the emergency power
voltage types. The power transfer switches are source
built for use with generator set or 2nd utility use. -Frequency sensing of the emergency power
The entire package of power transfer switch and source
controller is completely factory assembled, wired, -Transfer time delay to compensate for
tested and shipped as a complete unit for easy momentary power outages of the normal
field connection to the power sources and the source
fire pump motor. -Retransfer from emergency to normal source
is automatically delayed unless the emer-
Approvals—Firetrol power transfer switches are gency source fails
listed by Underwriters’ Laboratories, Inc., in ac- -Cool-down timer for unloaded running of the
cordance with UL218, Standard for Fire Pump generator set after retransfer to the normal
Controllers; UL1008, Automatic Transfer Switches; power source
UL508, Industrial Control Equipment, CSA, Stan- -Instantaneous retransfer to normal if the
dard for Industrial Control Equipment; and ap- emergency source fails and the normal
proved by Factory Mutual. They are built to meet source is available
or exceed the requirements of the approving -3 second transfer restart delay to reduce
authorities as well as NEMA and the latest editions current surges when transferring to or from
of NFPA 20, Installation of Centrifugal Fire Pumps, the emergency source
and NFPA 70, National Electrical Code. -NO and NC engine control contacts to start
the generator set when the normal power
source fails
• Transfer Switch Normal LED
• Transfer Switch Emergency LED
• Emergency Isolating Switch Open LED
• Test Selector Switch
• Transfer By-pass Switch
• Silence Alarm Push-button
• Emergency Isolating Switch Open and Transfer
Switch in Emergency Audible Alarms
• Output contacts (NO and NC) for Generator
Start, Emergency Isolating Switch Open and
Transfer Switch position indicators
• NEMA Type 2 enclosure (IEC IP22)
Product Description - Options & Modifications
Options—The following are available as options Anti-condensation Space Heaters
to FTA950 Power Transfer Switches: (Note: The -H 120 Volt space heater
short circuit current rating for the normal power -J 120 Volt space heater with thermostat
source and the emergency power source side -K 120 Volt space heater with humidistat
of the power transfer switch will be the same as -L 240 Volt space heater
the rating of the fire pump controller assembled -M 240 Volt space heater with thermostat
with the power transfer switch.) -N 240 Volt space heater with humidistat
Circuit Breaker Option Alarms
-M Standard withstand rating -EC Extra contacts for remote indication, trans-
200-600V - 100,000 Amps, RMS Sym. fer switch position
-N Intermediate withstand rating -BX Contacts for remote indication, second
200-600V - 150,000 Amps, RMS Sym. utility source phase failure/phase reversal
-P High withstand rating (FTA950 only)
200-600V - 200,000 Amps, RMS Sym.
-Q Standard intermediate withstand rating Miscellaneous
200-480V - 65,000 Amps RMS Sym. -ED Load shed circuits
-R Standard low withstand rating -TN As above, with serial communications port
550-600V - 42,000 Amps RMS Sym. -S Tropicalization
Modifications—The following are available as
modifications to all transfer switches:
Special Enclosures
-E Enclosure, NEMA Type 4 (IP66), Painted
Steel
-F Enclosure, NEMA Type 4X (IP66), #304
Stainless Steel, Brushed Finish
-FD Enclosure, NEMA Type 4X (IP66), #316
Stainless Steel, Brushed Finish
-FDB Enclosure, NEMA Type 4X (IP66), #316
Stainless Steel, 12 Gauge, Seam-Welded,
Brushed Finish
-FDP Enclosure, NEMA Type 4X (IP66), #316
Stainless Steel, Painted Finish
-FXP Enclosure, NEMA Type 4X (IP66), #304
Stainless Steel, Painted Finish
-G Enclosure, NEMA Type 12 (IP54), Painted
Steel
-T Enclosure, NEMA Type 3R (IP24), Painted
Steel
3412 Apex Peakway
Apex, North Carolina 27502
P +1 919 460 5200
F +1 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-
ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2019 Firetrol, Inc., All Rights Reserved.
Publication PD950-50 Rev. F
Model Number Selection
Guide
FTA1000 - FTA1930
Mark IIxg Electric Fire Pump Controllers
FTA1000, 1250, 1300, 1350, 1500, 1800, 1930
ELECTRIC FIRE PUMP CONTROLLERS
Example: FTA1300-AM75HH-xx
Starting Method
1000 - Across-the-line (direct on line)
1250 - Part Winding (50%-50% windings)
1300 - Wye-delta (star-delta), open transition Modifications
1350 - Wye-delta (star-delta), closed See Back
transition
1500 - Primary resistor
1800 - Autotransformer
1930 - Digital Solid-state soft start/stop
Start/Stop Options
A - Automatic start with timed permissive
stop after minimum run time and manual
start with manual stop, field convertible
to automatic start and manual start with
manual stop only
B - Automatic start and manual start with
manual stop
C - Manual start and stop
Short Circuit Current Rating Three Phase Voltage
M - Standard short circuit rating A - 220-240 Volt, 60 Hertz (230 V)
100,000 Amperes RMS Sym. at 200 - 600 V AZ - 220-230 Volt, 50 Hertz
N - Intermediate short circuit rating B - 440-480 Volt, 60 Hertz (460 V)
150,000 Amperes RMS Sym. at 200 - 600 V BZ - 415 Volt, 50 Hertz
P - High short circuit rating C - 550-600 Volt, 60 Hertz (575 V)
200,000 Amperes RMS Sym. at 200 - 600 V F - 380 Volt, 60 Hertz
Q - Standard intermediate short circuit rating FZ - 380 Volt, 50 Hertz
65,000 Amperes RMS Sym. at 550 - 600 V H - 208 Volt, 60 Hertz
R - Standard low short circuit rating HH - 200 Volt, 60 Hertz
42,000 Amperes RMS Sym. at 550 - 600 V
Horsepower Rating
03 - 3 HP 100 - 100 HP
05 - 5 HP 125 - 125 HP
07 - 7 1/2 HP 150 - 150 HP
10 - 10 HP 200 - 200 HP
15 - 15 HP 250 - 250 HP
20 - 20 HP 300 - 300 HP
25 - 25 HP 350 - 350 HP
30 - 30 HP 400 - 400 HP
40 - 40 HP 450 - 450 HP
50 - 50 HP 500 - 500 HP
60 - 60 HP 600 - 600 HP
75 - 75 HP 700 - 700 HP
Model Number Selection Guide - Options & Modifications
SPECIAL ENCLOSURES -BW Alarm Output Contacts, Phase Failure/Phase Re-
-E Enclosure, NEMA Type 4 (IP66), Painted Steel versal
-F Enclosure, NEMA Type 4X (IP66), #304 Stainless Steel, -BY Alarm Output Contacts, Pump Overload
Brushed Finish -COM Alarm, Audible/Visible/Output Contacts, Low Suc-
-FD Enclosure, NEMA Type 4X (IP66), #316 Stainless Steel, tion Pressure with Manual Reset Option, Pressure
Brushed Finish Switch Not Included (Do Not Use Options AH or AY)
-FDB Enclosure, NEMA Type 4X (IP66), #316 Stainless Steel, -CTS Alarm, Audible/Visible/Output Contacts, Low Suc-
12 Gauge, Seam-Welded, Brushed Finish tion Pressure Shutdown with Manual Reset Option
-FDP Enclosure, NEMA Type 4X (IP66), #316 Stainless Steel, and Pressure Switch (Do Not Use Options AH or AY)
Painted Finish -EG Alarm, Audible/Visible, Relief Valve Discharge
-FXP Enclosure, NEMA Type 4X (IP66), #304 Stainless Steel, -EH Alarm Output Contacts, Relief Valve Discharge
Painted Finish (Requires option -EG)
-G Enclosure, NEMA Type 12 (IP54), Painted Steel -EJ Alarm, Audible/Visible, Flow Meter On
-T Enclosure, NEMA Type 3R (IP24), Painted Steel -EK Alarm Output Contacts, Flow Meter On (Requires
option -EJ)
CIRCUIT BREAKER OPTION -KH Alarm Output Contacts, Common Alarm
-N Intermediate withstand rating -JR Visible Indicator, Jockey Pump Operating
150,000 Amps RMS Sym. -JT Alarm, Audible/Visible, Jockey Pump Trouble
-P High withstand rating -P Alarm, Audible/Visible, Built-In 120V Supervisory Sys-
200,000 Amps RMS Sym tem (Includes visible supervisory voltage normal
Note: Intermediate and High withstand ratings may not indication and audible pump operating, phase
be available for all horsepowers and voltages. failure and phase reversal indication)
Consult factory for availability. -PE Alarm Output Contacts, Low System Pressure
(pump on demand)
ANTI-CONDENSATION SPACE HEATERS -PT Alarm, Audible/Visible, Built-in 240V Supervisory
-H Space Heater, 120V Externally Powered with Circuit System (Includes visible supervisory voltage nor-
Breaker mal indication and audible pump operating, phase
-J Space Heater, 120V Externally Powered with Circuit failure and phase reversal indication)
Breaker and Thermostat
-K Space Heater, 120V Externally Powered with Circuit MISCELLANEOUS
Breaker and Humidistat -AZ Thermostat, Low Pump Room Temperature, Mount-
-L Space Heater, 240V Externally Powered with Circuit ed and Wired
Breaker -ED Output Contacts, Load Shed (Selectable power
-M Space Heater, 240V Externally Powered with Circuit source and adjustable time delay to remove non-
Breaker and Thermostat critical loads before starting)
-N Space Heater, 240V Externally Powered with Circuit -EL Series Pumping Operation, High Zone Controller
Breaker and Humidistat -EM Series Pumping Operation, Mid Zone Controller
-EN Series Pumping Operation, Low Zone Controller
PRESSURE TRANSDUCERS -FZX Rating, Nameplate to be marked 380-400V (Use
-B 0-600 psi (0-42.25 bar) Pressure Transducer for with voltage code ‘F’ or ‘FZ’)
Fresh Water Service -IEC Marking, CE with External Wet Parts (Requires NEMA
-C 0-300 psi (0-21.1 bar) Pressure Transducer for Type 12 (IP54) Enclosure as minimum)
Copper Corrosive Service -IECI Marking, CE with Internal Wet Parts (Requires NEMA
-D 0-600 psi (0-42.25 bar) Pressure Transducer for Type 12 (IP54) Enclosure as minimum)
Corrosive Service -OSP OSHPD Seismic Certification (State of California)
(Requires Option -SEI)
COMBINED AUTOMATIC POWER TRANSFER SWITCHES -MZN Neutral Lug, Service Entrance, Non-insulated
-TSA FTA950 Automatic Transfer Switch, Group 5 Bonded to Enclosure
-TSAB FTA951 Automatic Transfer Switch, J-Bypass Isola- -PK Terminal Blocks, Extra Remote Start
tion, Group 5 -PY Output Contacts, Motor Space Heater Circuit, Exter-
nally Powered
ALARMS -S Tropicalization
-AC Alarm Output Contacts Extra, Pump Operating (1 -SEI Marking, Seismic Certified (in accordance with IBC)
Form A, 1 Form B) (Note: Not available on model FTA1500)
-AF Alarm, Audible/Visible, Low Pump Room Temperature -USBX Data Port, External USB
-AG Alarm, Audible/Visible, Reservoir Low -ZPA Scheduled Service Message (when factory pro-
-AH Alarm, Audible/Visible, Low Suction Pressure grammed or programmed by Firetrol representa-
-AM Alarm Output Contacts, Fail to Start tive during start-up)
-AV Alarm Output Contacts, Low Pump Room Temper- -ZPM Data Port, Serial Modbus RTU Over 2-Wire or 4-Wire
ature (Requires option -AF) RS485
-AW Alarm Output Contacts, Reservoir Low -ZPN Data Port, Serial Modbus RTU Over Ethernet TCP/IP
(Requires option -AG)
-AY Alarm Output Contacts, Low Suction Pressure
(Requires option -AH) Export packaging (Wooden crating to conform
to IPPC Standards)
FTA1000 - 1930
3412 Apex Peakway
Apex, North Carolina 27502
P +1 919 460 5200
F +1 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-
ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2019 Firetrol, Inc., All Rights Reserved.
Publication SD1000-50 Rev. L
Model Number
Selection Guide
FTA950
Assembled With Electric
Power Transfer Switches Fire Pump Controller
FIRE PUMP POWER TRANSFER SWITCH
FTA950
FTA950 -A_ __ __ __ (Example: FTA950-AM150H-G)
Catalog Number Short-Circuit Current Rating (Withstand)
FTA950 FTA950
M = Standard Short Circuit Rating
100,000 A RMS Sym., 200-600V
N = Intermediate Short Circuit Rating
150,000 A RMS Sym., 200-600V
AMPERE RATING P = High Short Circuit Rating
200,000 A RMS Sym., 200-600V
Horse- 200- 220- 380- 440- 550- Q = Standard Intermediate Short Circuit Rating
power 208V 240V 415V 480V 600V 65,000 A RMS Sym., 200-480V
15-25 100 100 100 100 100 R = Standard Low Short Circuit Rating
30 150 100 100 100 100 42,000 A RMS Sym., 550-600V
40 150 150 100 100 100
50 225 150 100 100 100
60 225 225 150 100 100
75 260 225 150 150 100
100 400 400 225 150 150
125 600 400 260 225 150
150 600 600 400 225 225
200 800 600 400 400 225
250 800 800 600 400 400
300 — 800 600 600 400
350 — — 800 600 400
400 — — 800 600 600
450 — — 1000 600 600
MODIFICATIONS - See back.
500 — — — 800 800
600 — — — 1000 800
700 — — — — 800
3-Phase Operating
Voltage
A = 220-240V, 60 Hz
AZ = 220-230V, 50 Hz
B = 440-480V, 60 Hz
BZ = 415V, 50 Hz
C = 550-600V, 60 Hz
F = 380V, 60 Hz
FZ = 380V, 50 Hz
H = 208V, 60 Hz
HH = 200V, 60 Hz
Model Number Selection Guide - Options & Modifications
SPECIAL ENCLOSURES
Transfer Switch NEMA Type enclosure
will be the same as selected for the Fire
Pump Controller.
ANTI-CONDENSATION SPACE HEATERS
-H 120 Volt Space Heater
-J 120 Volt Space Heater With
Thermostat
-K 120 Volt Space Heater With
Humidistat
-L 240 Volt Space Heater
-M 240 Volt Space Heater With
Thermostat
-N 240 Volt Space Heater With
Humidistat
MISCELLANEOUS
-EC Extra contacts for remote indication,
transfer switch position
indicator
-ED Load shed contacts
-TN Microprocessor based (Group 5)
control module with serial
communications port
-S Tropicalization
3412 Apex Peakway
Apex, North Carolina 27502
P +1 919 460 5200
F +1 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-
ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2019 Firetrol, Inc., All Rights Reserved.
Publication SD950-50 Rev. E
General Starting
Configuration
FTA1300
Mark IIxg Electric Fire Pump Controllers Wye-Delta Open Transition Starting
Circuit
Switch Breaker
Mechanically Interlocked in
200-600 VAC 3Ø
Power Supply
Voltage and Current
Sensing
Aux Run Contacts = 2M
Contactors
2M 2 1M 1** Manual Emergency Run
Operator mechanically linked
to contact carrier of
Running 2M contactors
1S Mechanically and Electrically Interlocked
1M Control Relays
1S 1
2* 10 sec 1CR 6CR
Default = 2 sec
**Indicates number of auxiliary Aux Contact = 1M
contacts supplied with contactor.
3 Pole Shorting bar
Fire Pump
General Starting Configuration
900
750
Full Voltage S
% Full Load Current
600 tart
450
300
Wye-Delta Start
150
20 40 60 80 100
% Synchronous Speed
3412 Apex Peakway
Apex, North Carolina 27502
P +1 919 460 5200
F +1 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-
ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2019 Firetrol, Inc., All Rights Reserved.
Publication GS1300-01 Rev. C
Dimensions and
Shipping Weight
FTA1300 / FTA950
Wye-Delta Open Transition Starting
Mark IIXG Electric Fire Pump Controllers With Power Transfer Switch
Field Connections
FTA1300 / FTA950
Wye-Delta Open Transition Starting
Mark IIXG Electric Fire Pump Controllers With Power Transfer Switch
Field Connections
FTA1300 / FTA950
Wye-Delta Open Transition Starting
Mark IIXG Electric Fire Pump Controllers With Power Transfer Switch
Field Connections
FTA1300
Wye-Delta Open Transition Starting
Mark IIXG Electric Fire Pump Controllers Line & Motor Wire Terminal Capacity
Field Connections
FTA950
Assembled With Electric
Power Transfer Switches Fire Pump Controllers
Typical Motor
Connection Diagram
FTA1300 / FTA1350
Mark IIXG Electric Fire Pump Controllers Wye-Delta Starting (12-Lead Motors)
Wiring Schematic
FTA1300 / FTA950
Wye-Delta Open Transition Starting
Mark IIXG Electric Fire Pump Controllers With Power Transfer Switch
Wiring Schematic
FTA950
Assembled With Electric
Power Transfer Switches Fire Pump Controllers