Service Manual For Dynacon Vector II N Control Voltage Unit
Service Manual For Dynacon Vector II N Control Voltage Unit
DYNACON VECTOR II
CONTROL VOLTAGE UNIT
D2R REV 5.2 CON3V040
HU4.07.0095en / rev. A / 01.07.2011
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not be
reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011) Konecranes Plc.
All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
m CAUTION:
4. High voltages are present in this device. Switch the power off and after the display turns off,
wait 5 minutes before opening the cover.
6. Do not make any measurements inside the device when it is connected to the main supply.
7. Do not touch the components on the circuit boards. Static voltage discharge may cause
damage or destroy the IC-circuits.
8. Check that all of the ventilation holes are clear and uncovered.
9. Do not make any inspections unless the supply has been disconnected by the main switch.
10. It is forbidden to use radiophones or portable phones near this device with the doors open.
11. All the doors and covers must be closed during crane operation.
This manual is valid for DynACon revision 5.2. The release number of this document is HU4.07.0095en. The
parameter numbers are based on the software version Con3V040.
2/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
Table of contents
1 GENERAL .................................................................................................................................................. 4
1.1 Technical data ................................................................................................................................... 4
1.2 Type mark coding .............................................................................................................................. 5
1.3 Basic description................................................................................................................................ 6
1.4 Main components .............................................................................................................................. 6
1.5 Functional description........................................................................................................................ 7
1.6 EMC ................................................................................................................................................... 8
1.6.1 Fulfilled EMC-standards ................................................................................................................ 8
2 INSTALLATION ......................................................................................................................................... 9
2.1 Cooling............................................................................................................................................... 9
2.2 Power cabling .................................................................................................................................... 9
2.3 Sinus filter ........................................................................................................................................ 10
2.4 EMC compatible grounding ............................................................................................................. 10
3 START-UP PROCEDURE ....................................................................................................................... 11
3.1 Visual checks................................................................................................................................... 11
3.2 Test run............................................................................................................................................ 11
3.3 After the test run .............................................................................................................................. 11
4 PARAMETER ADJUSTMENTS............................................................................................................... 12
4.1 Control keypad operation................................................................................................................. 12
4.1.1 Navigation on the control keypad ................................................................................................ 13
4.1.2 Value line editing ......................................................................................................................... 13
4.1.3 Special button functions............................................................................................................... 14
4.2 Passwords ....................................................................................................................................... 15
4.3 Basic parameters adjustment .......................................................................................................... 15
4.3.1 Automatic mode ........................................................................................................................... 15
5 PARAMETER DESCRIPTIONS............................................................................................................... 16
6 COMPONENTS........................................................................................................................................ 19
6.1 DynACon spare parts list ................................................................................................................. 19
6.2 Inverter............................................................................................................................................. 19
6.2.1 Inverter main circuit diagram ....................................................................................................... 19
6.2.2 Power supply unit (PSU).............................................................................................................. 20
6.2.3 Control unit (CSU) ....................................................................................................................... 20
6.2.4 Relay / Thermistor board (Slot B) ................................................................................................ 21
6.2.5 Profibus board (Slot E) ................................................................................................................ 22
7 TROUBLESHOOTING ............................................................................................................................. 23
7.1 Field repair actions .......................................................................................................................... 23
7.2 Troubleshooting actions................................................................................................................... 23
7.3 Inverter fault codes .......................................................................................................................... 24
7.3.1 Fault time data record.................................................................................................................. 28
7.3.2 Fault Counter ............................................................................................................................... 28
8 SERVICE .................................................................................................................................................. 29
8.1 DC-bus electrolytic capacitors ......................................................................................................... 29
8.1.1 Re-forming after a long storage period ........................................................................................ 29
9 DRAWINGS.............................................................................................................................................. 30
9.1 Description of terminals ................................................................................................................... 30
9.2 Layouts, dimensions and weights.................................................................................................... 31
9.3 Circuit diagrams............................................................................................................................... 32
3/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
1 GENERAL
Supply
Supply voltage 380-500 VAC or 513-800 VDC
Supply frequency 45 - 66 Hz or DC
Control features
Control principle Vector control
Control modes Profibus-DP, keypad, automatic
Protections
Overload protection Fault is detected if the current momentarily exceeds 280% of rated current
Undervoltage / blown fuse Fault is detected if DC voltage drops below 333 V or in special applications 200 V
Overvoltage protection Fault is detected if DC voltage exceeds 911 V
Momentary power loss Immediate fault stop
Inverter overtemperature Temperature sensor on the heat sink
Earth fault Provided by electronic circuitry
Supply side short circuit protection External fuses or circuit breaker
Ambient conditions
Ambient temperature -10°C ... +40°C (14°F ... 104°F) for ED≤100%
Storage temperature -40°C ... +60°C (-40°F ... 140°F) dry. Power on >1h in a year.
Humidity <95%RH (no condensation)
Altitude Maximum 1000m at In. Above 1000m: In reduces 1% per each 100 m.
Above 3000m: consult factory.
Vibration Operation: maximum displacement amplitude 1mm at 5 – 15.8 Hz.
Maximum acceleration amplitude 1G (9.81 m/s²) at 15.8 – 150 Hz
4/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
F Supply voltage
F 380 - 500 VAC, 50/60 Hz
0 Control voltage
0 42 - 230 VAC, 50/60 Hz
52 Revision code
The latest revision may differ
D2R 045 F V 52 E R 0 D L
Braking type
E No braking E
Mounting
R Spread mounting R
Supply network
0 Unlimited (non-grounded network) 0
Special
L Varnished boards L
5/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
6/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
Start is possible only after power off if the control place is changed to Automatic by parameter P2.1.8 or
“select+enter” button combination. Power off is also needed if P2.1.6 DC Start Limit is changed.
If the control place is changed to Profibus by parameter P2.1.8 Control Place start is possible after the RUN
command has been disabled.
7/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
1.6 EMC
"EMC" stands for the Electro Magnetic Compatibility. According to the EMC directive "the apparatus shall be
so constructed that:
a) The electromagnetic disturbance it generates does not exceed a level allowing other apparatus to
operate as intended
b) The apparatus has an adequate level of intrinsic immunity of electromagnetic disturbance to enable it to
operate as intended."
Technical The technical construction file describes how the frequency converters have
construction file been constructed to comply with the directive and standard requirements.
Declaration With the declaration of conformity the manufacturer informs that device is
of conformity manufactured to fulfill required EMC standards.
CE-mark The CE marking is a declaration by a manufacturer or importer located in the
European Economic Area that a product complies with the safety and health
requirements of the directive in question. The manufacturer demonstrates for
the authorities that the product complies with the safety requirements within the
EU.
EMC Plan EMC Plan for inverters is intend to use as a guide in cases when disturbance
problems appears in crane installations, in the crane itself or in other device in
installation environment.
Environments Immunity and emission requirements are divided in two levels in the product
standard according to the environments.
First environment means environment that includes domestic premises and
also establishments directly connected to a low-voltage power supply network.
The first environment is divided in to categories C1 and C2.
DynACon is not intended to be used on a low-voltage public network, which
PDS supplies domestic premises. It may cause radio frequency interference to other
devices if used on such a network.
Second environment means environment that includes all establishments other
than those directly connected a low-voltage power supply network. The second
environment is divided in to categories C3 and C4.
If rated current of the crane supply is less than 400 A, the inverters belong to
the category C3, otherwise they belong to the category C4.
PDS Power drive system (PDS) means a system consisting of power and control
equipment, including DynACon.
8/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
2 INSTALLATION
2.1 Cooling
The need of cooling arrangements for the DynACon varies by application. The actual thermal loading of the
enclosure has to be estimated based on the loading conditions and duty cycles. The power losses are listed
in the below table.
Shielded cable There is no need to use shielded cables in DynACon power supply.
Cable selection Cabling for DynACon can be done using normal crane cables. All the cables
must be dimensioned according to local regulations. Ambient temperature,
cabling method (size of bunches etc.) and allowable current for the cable in use
must be taken into consideration. If there are no other regulations, following
values can be used (three phase 400V supply).
The table below is based on ED ≤ 60% and ambient temperature +40°C
(104°F). A higher ambient temperature may require increased cable sizes. The
continuous current (Icont) of DynACon is selected to be the dimensioning
current. If the actual load current is below DynACon continuous current, then
the AC fuses and the supply cable may be dimensioned according to the load
current.
Dimensioning of the DC-fuse should not be changed.
Cable protection To protect the AC-supply cables against short circuit there must be fuses or
motor circuit breakers (MCCBs) installed at the generator end of the AC-supply
cable. Dimensioning of the fuses or MCCBs depends on the cable used and on
the type of primary fuses or MCCBs. If there are no other regulations, the
values given in this section can be used to dimension fuses (three phase 400V
supply).
The fuses of the supply provide the short circuit protection.
DC-bus protection DC-bus is protected against short circuits by DC-fuses.
Each unit connected to the common DC-bus has its own DC-fuses.
All control cables must be placed as far from the power cables as possible.
9/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
Construction All metal construction parts of the cubicle must be electrically connected to
connections each other using largest possible surface area. Paint to paint connection must
not be used.
Cable connections Control cables and power cables should be separated and routed separately
for eliminating noise coupling. Cable lengths should be kept as short as
possible to minimize coupling capacitances and inductances.
Shielded control Shielded control cables should be grounded in both ends. The shield must be
cables connected to the ground using the largest possible surface area. Extra
intermediary terminators cutting the shield are not allowed, the shield should be
as integrity as possible. Spare conductors should be grounded in the both
ends. All shielded cable shields should be 360 degree grounded.
10/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
3 START-UP PROCEDURE
If any problems or malfunctions occur during the start-up, refer to chapter “Troubleshooting”, to find out the
reason. All problems must be solved before continuing.
cm WARNING: High voltages inside the device. Wait for at least five minutes after the
supply voltage has been switched off before doing any service actions. The display in
the operating condition (lights on) indicates a dangerous voltage on the DC-bus. When
display turns off, the DC-bus voltage is approximately 100 Vdc. Note also that there is
always a dangerous voltage in the braking resistor when the DC-bus is charged.
Do not connect any AC voltage to the DC-bus terminals of DynACon (B+ and B-). Otherwise, the inverter
will be damaged.
Do not connect any DC voltage to the line terminals of DynACon (L1, L2, L3). Otherwise, the inverter will
be damaged.
The overload protection of DynACon protects the output cables. The fuses or motor circuit breaker of the
supply provide short circuit protection.
Fuses in DC-bus provide circuit protection when DC-supply is used.
CAUTION: Make sure that polarity of the DC-bus connections is correct. Otherwise, the inverter will
be damaged.
The parameters are properly set after factory tests and no adjustments are needed except for the
parameters that depend on the application, the sinus filter or the load.
Check the power supply voltage (nominal voltage +/- 10%).
Turn on the power from the main switch.
Check that DC-bus is charged. (If DC-supply is used).
Check that DynACon comes in READY state (green status indicator turns on).
In a fault situation, the red FAULT status indicator blinks and the display shows a fault code.
Check that DynACon comes in RUN state (green status indicator turns on). This happens automatically if
P2.1.8 Control place is Auto and DC voltage is above P2.1.6 DC start limit. For other control alternatives
see chapter 1.5 Functional description.
Measure the AC voltage after the sinus filter. If necessary make adjustments with P2.1.5 Output Voltage.
Turn off the power from the main switch.
11/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
4 PARAMETER ADJUSTMENTS
m WARNING: Do not change to keypad control during crane operation. This may cause
hazardous situation.
12/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
M5. Auto
S5.2. Auto
M4. Auto
H4.1. Auto
T4.1.1. Auto
M3. Auto
Active Faults
F0
STOP READY STOP READY STOP READY
G2. Auto
G2.1. Auto
P2.1.6. Auto
G1. Auto
V1.1. Auto
DC Stop Limit
enter
400 V
m WARNING: Changing parameter settings during running may cause a hazardous situation.
Parameter settings must not be changed during running.
13/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
>3
Displays the software version.
seconds
>3
START Password level changes to Level 3 Engineering.
seconds
>0
select enter seconds
Switches start function between selected control place and keypad.
>1
enter seconds
Resets whole H4 Fault History when display in any level of H4 menu.
m WARNING: Do not change to keypad control during crane operation. This may cause
hazardous situation.
14/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
4.2 Passwords
Drive cannot produce the desired output voltage if the DC link voltage is too low. To avoid undervoltage
situations in the output DC Stop Limit is defined. Drive stops driving if the DC link voltage drops below the
limit. Following table shows the minimum value for the limit according to output voltage and maximum
acceptable voltage drop.
Notice that the voltage drops in sinus filter and transformers when adjusting the P2.1.7 DC Stop Limit.
P2.1.6 DC start limit Set to 1.2 …1.3 x AC supply voltage. DC start limit should be at least 5 V higher than DC Stop
Limit (P2.1.7). Limit cannot be set lower than P2.1.7.
15/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
5 PARAMETER DESCRIPTIONS
Below are listed the default values for parameters in DynACon. Also are listed the password lock levels for
parameter P2.1.1. This parameter list is based on the software version Con3V040.
022F 022F 045F 045F
G1 Monitoring 260V 50Hz 260V 60Hz 400V 50Hz 480V 60Hz Unit PW 1 Description
V1.1 Output Voltage V 1
V1.2 Output Current A 1
V1.3 Output Frequency Hz 1
V1.4 DC Link Volt V 1
V1.5 Unit Temperature °C 1
V1.6 Power kW 1
G1.7 Parameter Backup 260V 50Hz 260V 60Hz 400V 50Hz 480V 60Hz Unit PW 1 Description
B1.7.1 Load Default Par 1 Enter
Loading
B1.7.2 Save User Par 1 Enter
Saving
B1.7.3 Load User Par 1 Enter
Loading
B1.7.4 Save Default Par 260V 50Hz 260V 60Hz 400V 50Hz 480V 60Hz Unit PW 4 Description
B1.7.4.1 Save Default Par 4 Enter
Saving
G1.8 Relay Output 260V 50Hz 260V 60Hz 400V 50Hz 480V 60Hz Unit PW 1 Description
V1.8.1 ROB1 State 1
V1.8.2 ROB2 State 1
G1.9 Operate Counters 260V 50Hz 260V 60Hz 400V 50Hz 480V 60Hz Unit PW 1 Description
V1.9.1 Output MWh MWh 1
V1.9.2 Runtime (h) h 1
G1.10 Fault Counters 260V 50Hz 260V 60Hz 400V 50Hz 480V 60Hz Unit PW 1 Description
V1.10.1 F1 Overcurrent 1
V1.10.2 F2 Overvoltage 1
V1.10.3 F3 Earth Fault 1
V1.10.4 F7 Saturation 1
V1.10.5 F9 Undervoltage 1
V1.10.6 F10 Input Phase 1
V1.10.7 F11 Output Phase 1
V1.10.8 F13 Undertemp 1
V1.10.9 F14 Overtemp 1
V1.10.10 F25 Watchdog 1
V1.10.11 F31 IGBT Temp HW 1
V1.10.12 F41 IGBT Temp 1
V1.10.13 F53 Profibus 1
V1.10.14 F57 Thermistor 1
V1.10.15 Other faults 1
V1.10.16 Total Faults 1
G1.11 Bus Control 260V 50Hz 260V 60Hz 400V 50Hz 480V 60Hz Unit PW 1 Description
V1.11.1 Run Request 1
V1.11.2 Profibus status 1
G1.12 Service 260V 50Hz 260V 60Hz 400V 50Hz 480V 60Hz Unit PW 3 Description
V1.12.1 HeatSinkTempMax °C 3
V1.12.2 HeatSinkTempMin °C 3
V1.12.3 IGBT Temp Max °C 3
V1.12.4 IGBT Temperature °C 3
G1.12.5 Max Current 260V 50Hz 260V 60Hz 400V 50Hz 480V 60Hz Unit PW 3 Description
V1.12.5.1 Max Current A 3
V1.12.5.2 Max Current Freq Hz 3
G1.13 Multimonitor 260V 50Hz 260V 60Hz 400V 50Hz 480V 60Hz Unit PW 1 Description
N1.13.1 V/A/Hz 1
G2 Parameters
G2.1 Basic Parameters 260V 50Hz 260V 60Hz 400V 50Hz 480V 60Hz Unit PW 1 Description
P2.1.1 Password 0 0 0 0 1
V2.1.2 Supply Voltage 1 2 = J 200V - 240V
5 = F 380V - 500V
6 = K 525V - 690V
V2.1.3 Device 1 1 = Control
P2.1.4 Output Frequency 1 2 1 2 1 0 = None
1 = 50 Hz
2 = 60 Hz
P2.1.5 Output Voltage 260 260 400 480 V 1
P2.1.6 DC Start Limit 450 450 600 600 V 1
P2.1.7 DC Stop Limit 340 340 550 560 V 1
P2.1.8 Control Place 1 1 1 1 1 0 = Panel
1 = Auto
2 = Bus
P2.1.9 Current Limit 72.0 72.0 84.0 84.0 A 1
P2.1.10 Voltage Boost 0 0 0 0 % 1
16/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
17/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
18/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
6 COMPONENTS
022
045
POS DESCRIPTION ID NAME REMARKS
INVERTER
Inverter D2V022RF00D6 1
D2V045RF00D6 1
D2V includes PSU ( power unit ) and CSU ( control unit )
A2 Power supply unit PSU* 1 1
PSU is not available separately
Fan 52371615 D2VSP-EPP01062 24VDC 1
Fan 52355592 D2VSP-EPP01063 24VDC 1
A1 Control unit CSUD6 1 1
Display keypad 52413337 D2VSP-ENXPAN_A 1 1
Relay / Thermistor Board 52335565 D2V-NXOPTA3L Slot B1 1 1
Profibus Board 52355625 D2V-NXOPTC5L Slot E1 1 1
F1, F2 Main fuse of DC-supply 52415975 170M1571 690VAC/250A 2
6.2 Inverter
Inverter (D2V) includes Power supply unit (PSU) and Control unit (CSU), which are separate parts. PSU
includes supply, brake resistor and output connections. IGBTs are placed to PSU. Microprocessors and
ASIC are placed to CSU. Same CSU can be used in every power class.
1min Frame Dimension Dimension Weight Weight
D2V PSU CSU In Imax size mm (WxHxD) in (WxHxD) kg lbs
D2V022RF00D6 PSU022NF002 CSU06 48 72 Fr6 195x558x237 7.68x21.97x9.33 20 44
D2V045RF00D6 PSU045NF002 CSU06 90 135 Fr7 237x630x257 9.33x24.80x10.12 34 82
BR B+ B-
DC+
L1 U/T1
L2 V/T2
L3 W/T3
DC-
19/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
Output voltage
Terminal Description
U/T1 Output phase U
V/T2 Output phase V
W/T3 Output phase W
Green Status
ON PSU ready
OFF PSU not ready
A B C D E
20/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
D2V-NXOPTA3
Terminal Signal name Description
21 ROB1
22 ROB1 Relay output, 250 V 8 A
23 ROB1
21 22 23 25 26 28 29
21/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
D2V-NXOPTC5
Terminal Signal name Description
1 Shield Cable shield
3 RxD/TxD-P Receive/Transmit data – plus (B = red wire)
5 DGND Data Ground (reference potential for VP)
6 VP Supply voltage – plus (5 V)
8 RxD/TxD-N Receive/Transmit data – minus (A = green wire)
YELLOW
X6
GREEN
Jumpers X4 and X6 are for the bus termination. As default the bus
RED
termination setting is OFF. The default position for the jumpers is
shown beside.
The three LED indicators on the board are located next to the bus
connector. In the normal Profibus communication the red LED is
OFF, the yellow LED is blinking once a second and the green LED is
also blinking once a second.
22/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
7 TROUBLESHOOTING
cm WARNING: High voltages inside the device. Wait for at least five minutes after the
supply voltage has been switched off before doing any service actions.
This chapter describes how to detect DynACon failures. The purpose is to find out which components are
damaged and how to replace them to restore proper operation. Advice is also given to find possible external
failures that affect DynACon function.
23/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
F3 Current measurement has sensed unbalance in Reset has an additional 5 s time delay.
Earth fault output phase currents. Supervision level is 5% of Check:
inverter nominal current • load insulation
• not symmetric load • cable insulation (phase-ground, phase-phase)
• insulation failure in the load or the cables
F5 Charging switch is open when START command Check:
Charging switch becomes active • control unit and power unit connections
• interference fault • charging resistors (external)
• component failure If the fault comes again, change the control unit.
F7 Very high overload or defective component Reset: switch power off and restart after the lamps of
Saturation trip keypad are off.
Check:
• load and cable insulation
• measure main circuit diodes and IGBT transistors
If the fault comes again, change the unit.
24/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
25/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
26/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
27/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
28/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
8 SERVICE
In the normal operation DynACon do not require regular maintenance. The following actions are
recommended:
Action Note
1. Check the fault history of the inverter • Find out reasons of possible faults
• Record faults and clear the fault history
2. Clean the heat sink of the inverter • Prevent the dust to spread inside cubicles
• Lock the fans before blowing compressed air
3. Check the operation of the main cooling fan. Pay attention
on extra noise and vibrations.
4. Tighten all screws and connectors • Avoid too high tightening torques
5. Clean dust from PC-boards
m WARNING: Due to high leakage resistance the dangerous voltage can remain in capacitor a
long time. If the DC-power supply is not able to dissipate the voltage after re-forming,
discharge the capacitor by using a resistor (minimum 100 kΩ 2 W). Discharging will take
several minutes and resistor will get hot. Measure the voltage before touching the capacitor
terminals.
29/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
9 DRAWINGS
Power unit
Name Description, signal level
L1 Generator, phase 1
L2 Generator, phase 2
L3 Generator, phase 3
B+ DC-output, positive
B- DC-output, negative
U Output, phase 1
V Output, phase 2
W Output, phase 3
PE Protective earth
30/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
D2R022F
Weight 20 kg (44.1 lbs)
D2R045F
Weight 37 kg (81.6 lbs)
630 mm (24.80 in)
614 mm (24.17 in)
31/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.
HU4.07.0095en / Rev. A / 01.07.2011 / Con3V040
F1 A1
DC+ B+
L3
R- L2
F2 L1
DC- B-
U U1 U2 U
V V1 V2 V
W W1 W2 W
E1 B
PROFIBUS
T1 28
T2 29
21
23
ROB1
22
25
ROB2
26
32/32
This document and the information contained herein, is the exclusive property of Konecranes Plc and represents a non-public, confidential and proprietary trade secret that may not
be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of Konecranes Plc. Copyright © (2011)
Konecranes Plc. All rights reserved.