Service Manual Haier MRV5-H Auszengerate
Service Manual Haier MRV5-H Auszengerate
1. Safety considerations......................................................................................................................................... 1
1.1 Caution in repair............................................................................................................................................. 1
1.2 Cautions regarding rroducts after repair......................................................................................................... 4
1.3 Inspection after repair..................................................................................................................................... 6
2. General information............................................................................................................................................ 7
2.1 Feature........................................................................................................................................................... 7
2.2 Products lineup............................................................................................................................................... 9
3. Specification...................................................................................................................................................... 16
4. Dimension.......................................................................................................................................................... 91
5. Center of gravity................................................................................................................................................ 93
6. Piping diagram.................................................................................................................................................. 95
7. Refrigerant flow................................................................................................................................................. 98
8. Functional parts layout................................................................................................................................... 100
9. Wiring diagram................................................................................................................................................ 103
10. Capacity calculation due to capacity modification coefficient................................................................. 106
11. Selection procedure...................................................................................................................................... 112
12. Operation range............................................................................................................................................. 113
13. Noise level...................................................................................................................................................... 114
14. Installation..................................................................................................................................................... 116
14.1 Safety....................................................................................................................................................... 116
14.2 Installation instruction............................................................................................................................... 118
14.3 Installation procedure............................................................................................................................... 128
14.4 Electric wiring and the application............................................................................................................ 138
15. Branch pipe dimension................................................................................................................................. 143
16. Gather pipe dimension................................................................................................................................. 145
17. Trial operation................................................................................................................................................ 146
17.1 Confirmation by electrifying...................................................................................................................... 146
17.2 Rated operation ....................................................................................................................................... 146
17.3 Trial operation confirmation...................................................................................................................... 147
18. Startup............................................................................................................................................................ 155
18.1 Startup procedure..................................................................................................................................... 155
18.2 Installation checking................................................................................................................................. 155
18.3 Wiring-dip switch...................................................................................................................................... 157
18.4 Power on.................................................................................................................................................. 158
18.5 Search and lock outdoor \ indoor unit....................................................................................................... 158
18.6 Trial operation and parameters record..................................................................................................... 158
18.7 MRV 5 system startup report.................................................................................................................... 159
19. Outdoor control board photo ...................................................................................................................... 164
20. Outdoor PCB dip switch setting ................................................................................................................. 169
21. Outdoor system control function ................................................................................................................ 179
21.1 Compressor control.................................................................................................................................. 179
21.2 Electronic expansion valve control........................................................................................................... 179
21.3 Fan motor control .................................................................................................................................... 179
21.4 Start Control............................................................................................................................................. 180
21.5 Oil return control........................................................................................................................................ 183
21.6 Defrosting control...................................................................................................................................... 183
21.7 Pump down operation............................................................................................................................... 184
21.8 High pressure protection........................................................................................................................... 184
21.9 Low pressure protection............................................................................................................................ 185
21.10 The temperature of discharge too high control........................................................................................ 185
21.15 Target pressure control............................................................................................................................ 187
21.16 Overheating protection control................................................................................................................ 187
21.17 Current protection control........................................................................................................................ 188
21.18 Heating is prohibited................................................................................................................................ 188
22. Failure code.................................................................................................................................................... 189
23. Troubleshooting ............................................................................................................................................ 195
23.1 Flow chart.................................................................................................................................................. 195
23.2 Lack of refrigerant judgment method......................................................................................................... 244
23.3 The checking method for the valve........................................................................................................... 245
23.4 The 4-way valve reversing condition......................................................................................................... 245
23.5 Fan motor detection standard................................................................................................................... 246
23.6 Power module detection standard............................................................................................................. 248
23.7 Compressor detection standard................................................................................................................ 249
23.8 Sensor resistance table ............................................................................................................................ 250
24. Parts Replacement Instructions .................................................................................................................. 259
24.1 Compressor replacement.......................................................................................................................... 259
25. Smartlink..................................................................................................................................................... 262
25.1 Smartlink Introduction................................................................................................................................ 262
25.2 Smartlink benefits...................................................................................................................................... 264
25.3 Smartlink specification............................................................................................................................... 265
25.4 Wiring figure ............................................................................................................................................. 265
25.5 Dimension................................................................................................................................................. 266
25.6 The installation requirement of Smartlink.................................................................................................. 267
25.7 The debugging guidance of Smartlink....................................................................................................... 268
26. Central control & BMS system for MRV5-H................................................................................................. 271
26.1 Central control system............................................................................................................................... 271
26.2 BMS system.............................................................................................................................................. 273
26.3 Dip switch setting for address................................................................................................................... 276
1. Safety considerations
Read these SAFETY CONSIDERATIONS carefully before installing air conditioning equipment, and be sure to
install it correctly. After completing the installation, make sure that the unit operates properly during the start-up
operation.
Instruct the customer how to operate and maintain the unit.
Inform customers that they should store this Installation Manual with the Operation Manual for future reference.
Always use a licensed installer or contractor to install this product. Improper installation can result in water or
refrigerant leakage, electrical shock, fire, or explosion.
Meanings of DANGER, WARNING, CAUTION, and NOTE Symbols:
DANGER ............... Indicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury.
WARNING ............. Indicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury.
CAUTION .............. Indicates a potentially hazardous situation, if not avoided, may result in minor or
moderate injury. It may also be used to alert against unsafe practices.
NOTE .....................Indicates situations that may result in equipment or property-damage accidents only. Be
sure to read the following safety cautions before conducting repair work.
Warning
Be sure to disconnect the power cable plug from the plug socket
before disassembling the equipment for a repair.
Working on the equipment that is connected to a power supply can
cause an electrical shock.
If it is necessary to supply power to the equipment to conduct the
repair or inspecting the circuits, do not touch any electrically charged
sections of the equipment.
If the refrigerant gas discharges during the repair work, do not touch
the discharging refrigerant gas.
The refrigerant gas can cause frostbite.
1
Warning
If the refrigerant gas leaks during the repair work, ventilate the
area. The refrigerant gas can generate toxic gases when it contacts
flames.
2
Caution
Do not clean the air conditioner by splashing water. Washing the unit
with water can cause an electrical shock.
Be sure to turn off the power switch and unplug the power cable
when cleaning the equipment.
The internal fan rotates at a high speed, and can cause injury.
Be sure to check that the refrigerating cycle section has cooled down
sufficiently before conducting repair work.
Working on the unit when the refrigerating cycle section is hot can
cause burns.
3
1.2 Cautions regarding rroducts after repair
Warning
Be sure to use parts listed in the service parts list of the applicable
model and appropriate tools to conduct repair work. Never attempt
to modify the equipment. The use of inappropriate parts or tools can
cause an electrical shock, excessive heat generation or fire.
When relocating the equipment, make sure that the new installation
site has sufficient strength to withstand the weight of the equipment.
If the installation site does not have sufficient strength and if the
installation work is not conducted securely, the equipment can fall
and cause injury.
When connecting the cable between the indoor and outdoor units,
make sure that the terminal cover does not lift off or dismount
because of the cable.
If the cover is not mounted properly, the terminal connection section
can cause an electrical shock, excessive heat generation or fire.
4
Warning
Do not mix air or gas other than the specified refrigerant (R-410A) in
the refrigerant system.
If air enters the refrigerating system, an excessively high pressure
results, causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leak and repair it
before charging the refrigerant. After charging refrigerant, make sure
that there is no refrigerant leak.
If the leak cannot be located and the repair work must be stopped,
be sure to perform pump-down and close the service valve,
to prevent the refrigerant gas from leaking into the room. The
refrigerant gas itself is harmless, but it can generate toxic gases
when it contacts flames, such as fan and other heaters, stoves and
ranges.
Caution
5
1.3 Inspection after repair
Warning
Check to make sure that the power cable plug is not dirty or loose,
then insert the plug into a power outlet all the way.
If the plug has dust or loose connection, it can cause an electrical
shock or fire.
Caution
Check to see if the parts and wires are mounted and connected
properly, and if the connections at the soldered or crimped terminals
are secure.
Improper installation and connections can cause excessive heat
generation, fire or an electrical shock.
Be sure to check the drainage of the indoor unit after the repair.
Faulty drainage can cause the water to enter the room and wet the
furniture and floor.
6
2. General information
2.1 Feature
. ENERGY SAVING
Compared with normal compressor, the capacity of compressor is increased by 27%, COP is increased by 19%,
the whole unit capacity is increased by 25% in -20OC.
The compressor is built-in one-way valve, and COP performance can be improved by 5% under low frequency
operation
Full DC inverter technology. Quick start, fast cooling and heating; soft start, low start current, little impact on power
grid; when the room temperature is reached, the compressor automatically turns to low speed operation with low
power consumption
Ordinary type
Oil return
Time
7
Door type electric control box design
Rotating electric control box, can be opened to the side, compressor, tank and valve body maintenance is
convenient
Enhanced Vapor Injection technology, low temperature heating and high temperature
cooling.
The unit adopts EVI compressor, which can increase the refrigerant circulation by 15%, and improve the heating
effect by 30% compared with the normal type. Meanwhile, the one-way valve built in, and the efficiency of the unit
can be increased by 5%. The heating temperature in winter can be -27 OC, and the heating temperature in summer
can be 52OC.
8
2.2 Products lineup
Indoor units
AB052MCERA(M) AB052MAERA
AB072MCERA(M) AB072MAERA
AB092MCERA(M) AB092MAERA
AB122MCERA(M)
AB162MCERA(M) AB122MAERA
AB182MCERA(M)
AD182MSERA AD182MSERA(D)
AD242MSERA AD242MSERA(D)
9
MED ESP DUCT TYPE (80/120Pa) MED ESP DUCT TYPE (50/96Pa)
AD182MZERA AD182MMERA
AD242MZERA AD242MMERA
AD282MZERA AD282MMERA
AD302MNERA AD302MMERA
AD382MNERA AD382MMERA
AD482MNERA AD482MMERA
MED ESP DUCT TYPE (50/100Pa) CONSTANT AIR VOLUME DUCT TYPE
AD052MJERA AD072MQERA
AD072MJERA AD092MQERA
AD092MJERA AD122MQERA
AD122MJERA AD152MQERA
AD162MJERA AD182MQERA
AD182MJERA AD242MQERA
AD242MJERA AD282MQERA
AD282MJERA AD302MQERA
AD362MQERA
AD422MQERA
AD302MJERA AD482MQERA
AD382MJERA AD542MQERA
AD482MJERA
10
FRESH AIR BUILIT-IN FLOOR STANDING
AD482MPERA AE072MLERA
AE092MLERA
AE122MLERA
AE162MLERA
AD722MPERA AE182MLERA
AD962MPERA AE242MLERA
AF072MAERA AS072MGERA
AF092MAERA AS092MGERA
AF122MAERA AS122MGERA
AF182MAERA AS162MGERA
AS182MGERA
AS242MGERA
N HIGH WALL
AS052MNERA AS052MFERA
AS072MNERA AS072MFERA
AS092MNERA AS092MFERA
AS122MNERA AS122MFERA
AS052MNERAB AS052MFERAB
AS072MNERAB AS072MFERAB
AS092MNERAB AS092MFERAB
AS122MNERAB AS122MFERAB
AS162MNERA AS162MFERA
AS182MNERA AS182MFERA
AS242MNERA AS242MFERA
AS282MNERA
AS302MNERA
AD052MJERAB
AD072MJERAB
AD092MJERAB
AD122MJERAB
AD162MJERAB
AD182MJERAB
AD242MJERAB
AD282MJERAB
11
Outdoor units
AV08/10/12/14/16NMVETA AV18/20/22/24/26NMVETA
AV28/30/32/MVETA AV34NMVETA
AV36/38/40/42/44/46/48/50/52NMVETA AV54/56/58/60/62/64/66NMVETA
AV68/70/72/74/76/78NMVETA
AV80/82/84/86/88/90/92NMVETA
AV94/96/98/100/102/104NMVETA
12
Power supply
Appearance Model Capacity(kW) Refrigerant
(Ph, V, Hz)
AV08NMVETA 25.2
AV10NMVETA 28.0
AV12NMVETA 33.5
AV14NMVETA 40.0
AV16NMVETA 45.0
AV18NMVETA 50.4
AV20NMVETA 56.0
AV22NMVETA 61.5
AV24NMVETA 68.0
AV26NMVETA 73.5
AV28NMVETA 80.0
3Ph,380-415V,
AV30NMVETA 85.0 R410A
50/60Hz
AV32NMVETA 90.0
AV34NMVETA 95.4
AV36NMVETA 100.8
13
Power supply
Appearance Model Capacity(kW) Refrigerant
(Ph, V, Hz)
AV38NMVETA 106.4
AV40NMVETA 112.0
AV42NMVETA 117.5
AV44NMVETA 123.0
AV46NMVETA 129.5
AV48NMVETA 136.0
AV50NMVETA 141.5
AV52NMVETA 147.0
AV54NMVETA 151.2
AV56NMVETA 156.8
3Ph,380-415V,
AV58NMVETA 162.4 R410A
50/60Hz
AV60NMVETA 168.0
AV62NMVETA 173.5
AV64NMVETA 179.0
AV66NMVETA 184.5
AV68NMVETA 191.0
AV70NMVETA 197.5
AV72NMVETA 204.0
AV74NMVETA 209.5
AV76NMVETA 215.0
AV78NMVETA 220.5
14
Power supply
Appearance Model Capacity(kW) Refrigerant
(Ph, V, Hz)
AV80NMVETA 224.0
AV82NMVETA 229.5
AV84NMVETA 235.0
AV86NMVETA 240.5
AV88NMVETA 246.0
AV90NMVETA 252.5
AV92NMVETA 259.0
AV94NMVETA 265.5
3Ph,380-415V,
AV96NMVETA 272.0 R410A
50/60Hz
AV98NMVETA 277.5
AV100NMVETA 283.0
AV102NMVETA 288.5
AV104NMVETA 294.0
15
3. Specification
Model AV08NMVETA AV10NMVETA
HP 8 10
Combination / /
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 25.2 28.0
Rated capacity kBtu/h 85.99 95.54
Rated power input kW 6.24 7.37
Max. power input kW 14.30 15.10
Cooling
Rated current A 10.53 12.44
Max. current A 23.81 25.14
EER 4.04 3.80
AEER 7.25 7.09
Rated capacity kw 25.2 28.0
Rated capacity kBtu/h 85.99 95.54
Rated power input kW 5.56 6.32
Max. power input kW 11.69 12.19
Heating
Rated current A 9.67 10.99
Max. current A 19.47 20.30
COP 4.53 4.43
ACOP 4.61 4.51
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
Model ANB66FZXMT ANB66FZXMT
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 1INV 1INV
Capacity W 21300 21300
Power Input W 6600 6600
Compressor
Rated current(RLA) A 21.5 21.5
Speed rps 60 60
Crankcase Heater W 66 66
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
Refrigerant oil charge ml 2300+1500 2300+1500
Brand BROAD-OCEAN BROAD-OCEAN
Model ZWK924D500007 ZWK924D500007
Voltage DC540V DC540V
IP Class IP44 IP44
Type/quantity DC/1 DC/1
Outdoor fan Insulation class B B
motor Safe class I I
Power Input W 1600 1600
Output W 1300 1300
Rated current A
Caoacitor μF / /
Speed rpm 0~1100 0~1100
16
Model AV08NMVETA AV10NMVETA
Brand Shun wei Shun wei
Model / /
Material ABS+20%GF ABS+20%GF
Outdoor fan
Type Axial Axial
Diameter mm Φ700 Φ700
Height mm 204 204
Mumber of rows 3 3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) Hydrophilic aluminum Hydrophilic aluminum
Fin coating Type Optional Clear Iacquer Clear Iacquer
Outdoor coil Salt Spray Test Duration Hour 168 168
INNERGROOVE TUBE INNERGROOVE TUBE
Tube outside dia.and type mm
Φ7 Φ7
2245*1260+2158*1260 2245*1260+2158*1260
Coil length x height mm
+2065*1260 +2065*1260
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 11000 11000
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 81 82
Diamension(W*D*H) mm 980/750/1690 980/750/1690
Packing(W*D*H) mm 1070/850/1858 1070/850/1858
Outdoor unit
Net weight kg 255 255
Gross weight kg 280 280
Type R410A R410A
Refrigerant
Charged volume kg 10 10
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
17
Model AV08NMVETA AV10NMVETA
Liquid pipe mm 9.52 9.52
Gas pipe mm 19.05 22.22
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 13 16
Max. fuse current A 25.0 32.0
Connection Min. wiring current A 20.30 21.80
wiring Power wiring mm2 6 6
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
18
Model AV12NMVETA AV14NMVETA
HP 12 14
Combination / /
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 33.5 40.0
Rated capacity kBtu/h 114.31 136.49
Rated power input kW 9.31 11.94
Max. power input kW 16.32 17.58
Cooling
Rated current A 15.71 20.16
Max. current A 27.17 29.27
EER 3.60 3.35
AEER 6.69 6.60
Rated capacity kw 33.5 40.0
Rated capacity kBtu/h 114.31 136.49
Rated power input kW 7.71 9.71
Max. power input kW 12.69 16.10
Heating
Rated current A 13.40 16.88
Max. current A 21.13 26.81
COP 4.35 4.12
ACOP 4.51 4.31
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
Model ANB66FZXMT ANB78FZXMT
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 1INV 1INV
Capacity W 21300 25200
Power Input W 6600 7700
Compressor
Rated current(RLA) A 21.5 26
Speed rps 60 60
Crankcase Heater W 66 66
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
Refrigerant oil charge ml 2300+1500 2300+1500
Brand BROAD-OCEAN BROAD-OCEAN
Model ZWK924D500007 ZWK924D500007
Voltage DC540V DC540V
IP Class IP44 IP44
Type/quantity DC/1 DC/1
Outdoor fan Insulation class B B
motor Safe class I I
Power Input W 1600 1600
Output W 1300 1300
Rated current A
Caoacitor μF / /
Speed rpm 0~1100 0~1100
19
Model AV12NMVETA AV14NMVETA
Brand Shun wei Shun wei
Model / /
Material ABS+20%GF ABS+20%GF
Outdoor fan
Type Axial Axial
Diameter mm Φ700 Φ700
Height mm 204 204
Mumber of rows 3 3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) Hydrophilic aluminum Hydrophilic aluminum
Fin coating Type Optional Clear Iacquer Clear Iacquer
Outdoor coil Salt Spray Test Duration Hour 168 168
INNERGROOVE TUBE INNERGROOVE TUBE
Tube outside dia.and type mm
Φ7 Φ7
2245*1260+2158*1260 2245*1260+2158*1260
Coil length x height mm
+2065*1260 +2065*1260
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 12000 13500
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 88 88
Diamension(W*D*H) mm 980/750/1690 980/750/1690
Packing(W*D*H) mm 1070/850/1858 1070/850/1858
Outdoor unit
Net weight kg 255 255
Gross weight kg 280 280
Type R410A R410A
Refrigerant
Charged volume kg 10 10
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
20
Model AV12NMVETA AV14NMVETA
Liquid pipe mm 12.7 12.7
Gas pipe mm 25.4 25.4
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 20 24
Max. fuse current A 32.0 40.0
Connection Min. wiring current A 23.30 27.70
wiring Power wiring mm2 6 10
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
21
Model AV16NMVETA AV18NMVETA
HP 16 18
Combination / /
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 45.0 50.4
Rated capacity kBtu/h 153.55 171.97
Rated power input kW 13.24 15.70
Max. power input kW 20.69 25.90
Cooling
Rated current A 22.34 26.51
Max. current A 34.50 40.30
EER 3.40 3.21
AEER 6.36 6.78
Rated capacity kw 45.0 50.4
Rated capacity kBtu/h 153.55 171.97
Rated power input kW 10.92 12.81
Max. power input kW 19.56 21.93
Heating
Rated current A 18.99 22.27
Max. current A 32.57 36.51
COP 4.12 3.93
ACOP 4.10 4.31
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
Model ANB78FZXMT ANB52FZJMT*2
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 1INV 2INV
Capacity W 25200 16800*2
Power Input W 7700 5250*2
Compressor
Rated current(RLA) A 26 16.5*2
Speed rps 60 60
Crankcase Heater W 66 132
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
Refrigerant oil charge ml 2300+1500 (2300+1500)*2
Brand BROAD-OCEAN BROAD-OCEAN
ZWK924D500002
Model ZWK924D500007
+ZWK924D500002
Voltage DC540V DC540V
IP Class IP44 IP44
Type/quantity DC/1 DC/2
Outdoor fan
Insulation class B B
motor
Safe class I I
Power Input W 1600 2320
Output W 1300 1800
Rated current A 8
Caoacitor μF / /
Speed rpm 0~1100 0~1180
22
Model AV16NMVETA AV18NMVETA
Brand Shun wei Tian Da
Model / /
Material ABS+20%GF ABS+20%GF
Outdoor fan
Type Axial Axial
Diameter mm Φ700 Φ642
Height mm 204 198
Mumber of rows 3 3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) Hydrophilic aluminum Hydrophilic aluminum
Fin coating Type Optional Clear Iacquer Clear Iacquer
Outdoor coil Salt Spray Test Duration Hour 168 168
INNERGROOVE TUBE INNERGROOVE TUBE
Tube outside dia.and type mm
Φ7 Φ7
2245*1260+2158*1260 2843*1260+2757*1260
Coil length x height mm
+2065*1260 +2669*1260
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 13500 17000
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 88 88
Diamension(W*D*H) mm 980/750/1690 1410/750/1690
Packing(W*D*H) mm 1070/850/1858 1515/850/1858
Outdoor unit
Net weight kg 255 385
Gross weight kg 280 410
Type R410A R410A
Refrigerant
Charged volume kg 10 10
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
23
Model AV16NMVETA AV18NMVETA
Liquid pipe mm 12.7 15.88
Gas pipe mm 28.58 28.58
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 27 30
Max. fuse current A 40.0 50.0
Connection Min. wiring current A 32.40 36.10
wiring Power wiring mm2 10 10
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
24
Model AV20NMVETA AV22NMVETA
HP 20 22
Combination / /
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 56.0 61.5
Rated capacity kBtu/h 191.08 209.85
Rated power input kW 16.62 18.30
Max. power input kW 28.91 31.82
Cooling
Rated current A 28.05 30.90
Max. current A 46.30 51.91
EER 3.37 3.36
AEER 6.75 6.54
Rated capacity kw 56.0 61.5
Rated capacity kBtu/h 191.08 209.85
Rated power input kW 14.23 16.14
Max. power input kW 24.70 25.69
Heating
Rated current A 24.75 28.06
Max. current A 41.13 42.78
COP 3.93 3.81
ACOP 4.38 4.39
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
Model ANB52FZJMT*2 ANB66FZXMT*2
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 2INV 2INV
Capacity W 16800*2 21300*2
Power Input W 5250*2 6600*2
Compressor
Rated current(RLA) A 16.5*2 21.5*2
Speed rps 60 60
Crankcase Heater W 132 132
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
Refrigerant oil charge ml (2300+1500)*2 (2300+1500)*2
Brand BROAD-OCEAN BROAD-OCEAN
ZWK924D500002 ZWK924D500002
Model
+ZWK924D500002 +ZWK924D500002
Voltage DC540V DC540V
IP Class IP44 IP44
Type/quantity DC/2 DC/2
Outdoor fan
Insulation class B B
motor
Safe class I I
Power Input W 2320 2320
Output W 1800 1800
Rated current A 8 8
Caoacitor μF / /
Speed rpm 0~1180 0~1180
25
Model AV20NMVETA AV22NMVETA
Brand Tian Da Tian Da
Model / /
Material ABS+20%GF ABS+20%GF
Outdoor fan
Type Axial Axial
Diameter mm Φ642 Φ642
Height mm 198 198
Mumber of rows 3 3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) Hydrophilic aluminum Hydrophilic aluminum
Fin coating Type Optional Clear Iacquer Clear Iacquer
Outdoor coil Salt Spray Test Duration Hour 168 168
INNERGROOVE TUBE INNERGROOVE TUBE
Tube outside dia.and type mm
Φ7 Φ7
2843*1260+2757*1260 2843*1260+2757*1260
Coil length x height mm
+2669*1260 +2669*1260
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 17000 18000
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 88 88
Diamension(W*D*H) mm 1410/750/1690 1410/750/1690
Packing(W*D*H) mm 1515/850/1858 1515/850/1858
Outdoor unit
Net weight kg 385 385
Gross weight kg 410 410
Type R410A R410A
Refrigerant
Charged volume kg 10 10
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
26
Model AV20NMVETA AV22NMVETA
Liquid pipe mm 15.88 15.88
Gas pipe mm 28.58 28.58
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 33 36
Max. fuse current A 50.0 63.0
Connection Min. wiring current A 42.40 48.10
wiring Power wiring mm2 16 16
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
27
Model AV24NMVETA AV26NMVETA
HP 24 26
Combination / /
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 68.0 73.5
Rated capacity kBtu/h 232.03 250.79
Rated power input kW 21.94 24.75
Max. power input kW 32.81 35.35
Cooling
Rated current A 31.42 35.87
Max. current A 54.12 58.86
EER 3.10 2.97
AEER 5.97 5.68
Rated capacity kw 68.0 73.5
Rated capacity kBtu/h 232.03 250.79
Rated power input kW 18.86 21.62
Max. power input kW 30.40 32.45
Heating
Rated current A 32.80 37.60
Max. current A 50.62 54.03
COP 3.61 3.40
ACOP 4.34 3.88
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
Model ANB66FZXMT*2 ANB78FZXMT*2
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 2INV 2INV
Capacity W 21300*2 25200*2
Power Input W 6600*2 7700*2
Compressor
Rated current(RLA) A 21.5*2 26*2
Speed rps 60 60
Crankcase Heater W 132 132
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
Refrigerant oil charge ml (2300+1500)*2 (2300+1500)*2
Brand BROAD-OCEAN BROAD-OCEAN
ZWK924D500002 ZWK924D500002
Model
+ZWK924D500002 +ZWK924D500002
Voltage DC540V DC540V
IP Class IP44 IP44
Type/quantity DC/2 DC/1+DC/1
Outdoor fan
Insulation class B B
motor
Safe class I I
Power Input W 2320 2320
Output W 1800 1800
Rated current A 8 8
Caoacitor μF / /
Speed rpm 0~1180 0~1180
28
Model AV24NMVETA AV26NMVETA
Brand Tian Da Tian Da
Model / /
Material ABS+20%GF ABS+20%GF
Outdoor fan
Type Axial Axial
Diameter mm Φ642 Φ642
Height mm 198 198
Mumber of rows 3 3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) Hydrophilic aluminum Hydrophilic aluminum
Fin coating Type Optional Clear Iacquer Clear Iacquer
Outdoor coil Salt Spray Test Duration Hour 168 168
INNERGROOVE TUBE INNERGROOVE TUBE
Tube outside dia.and type mm
Φ7 Φ7
2843*1260+2757*1260 2843*1260+2757*1260
Coil length x height mm
+2669*1260 +2669*1260
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 18000 19000
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 90 90
Diamension(W*D*H) mm 1410/750/1690 1410/750/1690
Packing(W*D*H) mm 1515/850/1858 1515/850/1858
Outdoor unit
Net weight kg 385 385
Gross weight kg 410 410
Type R410A R410A
Refrigerant
Charged volume kg 10 10
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
29
Model AV24NMVETA AV26NMVETA
Liquid pipe mm 15.88 15.88
Gas pipe mm 28.58 28.58
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 40 43
Max. fuse current A 63.0 63.0
Connection Min. wiring current A 49.10 55.80
wiring Power wiring mm2 25 25
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
30
Model AV28NMVETA AV30NMVETA
HP 28 30
Combination 14+14 14+16
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 80.0 85.0
Rated capacity kBtu/h 272.97 290.03
Rated power input kW 23.88 25.18
Max. power input kW 35.16 38.27
Cooling
Rated current A 40.32 42.50
Max. current A 58.54 63.77
EER 3.35 3.38
AEER 5.68 6.54
Rated capacity kw 80.0 85.0
Rated capacity kBtu/h 272.97 290.03
Rated power input kW 19.42 20.63
Max. power input kW 32.20 35.66
Heating
Rated current A 33.76 35.87
Max. current A 53.61 59.38
COP 4.12 4.12
ACOP 4.31 4.19
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
Model ANB78FZXMT+ANB78FZXMT ANB78FZXMT+ANB78FZXMT
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 2INV 2INV
Capacity W 25200+25200 25200+25200
Power Input W 7700+7700 7700+7700
Compressor
Rated current(RLA) A 26+26 26+26
Speed rps 60 60
Crankcase Heater W 66+66 66+66
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
Refrigerant oil charge ml (2300+1500)*2 (2300+1500)*2
Brand BROAD-OCEAN BROAD-OCEAN
ZWK924D500007 ZWK924D500007
Model
+ZWK924D500007 +ZWK924D500007
Voltage DC540V DC540V
IP Class IP44 IP44
Type/quantity DC/1+DC/1 DC/1+DC/1
Outdoor fan
Insulation class B B
motor
Safe class I I
Power Input W 1600+1600 1600+1600
Output W 1300+1300 1300+1300
Rated current A 8+8 8+8
Caoacitor μF / /
Speed rpm 0~1180 0~1180
31
Model AV28NMVETA AV30NMVETA
Brand Shun wei+Shun wei Shun wei+Shun wei
Model / /
Material ABS+20%GF ABS+20%GF
Outdoor fan
Type Axial Axial
Diameter mm Φ700+Φ700 Φ700+Φ700
Height mm 204+204 204+204
Mumber of rows 3+3 3+3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) Hydrophilic aluminum Hydrophilic aluminum
Fin coating Type Optional Clear Iacquer Clear Iacquer
Salt Spray Test Duration Hour 168 168
Outdoor coil INNERGROOVE TUBE INNERGROOVE TUBE
Tube outside dia.and type mm
Φ7 Φ7
(2245*1260+2158*1260 (2245*1260+2158*1260
+2065*1260)+(2245*1260+ +2065*1260)+(2245*1260+
Coil length x height mm
2158*1260 2158*1260
+2065*1260) +2065*1260)
Number or circuits 2601900 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 27000 27000
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 91 91
980/750/1690 980/750/1690
Diamension(W*D*H) mm
+980/750/1690 +980/750/1690
1070/850/1858 1070/850/1858
Outdoor unit Packing(W*D*H) mm
+1070/850/1858 +1070/850/1858
Net weight kg 255+255 255+255
Gross weight kg 280+280 280+280
Type R410A R410A
Refrigerant
Charged volume kg 20 20
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
32
Model AV28NMVETA AV30NMVETA
Liquid pipe mm 15.88 19.05
Gas pipe mm 28.58 31.8
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 47 50
Max. fuse current A 80.00 80.00
Connection Min. wiring current A 55.40 60.10
wiring Power wiring mm2 10+10 10+10
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
33
Model AV32NMVETA AV34NMVETA
HP 32 34
Combination 16+16 16+18
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 90.0 95.4
Rated capacity kBtu/h 307.09 325.52
Rated power input kW 26.47 28.94
Max. power input kW 41.38 46.59
Cooling
Rated current A 44.69 48.85
Max. current A 69.00 74.80
EER 3.40 3.30
AEER 6.42 6.63
Rated capacity kw 90.0 95.4
Rated capacity kBtu/h 307.09 325.52
Rated power input kW 21.84 23.73
Max. power input kW 39.12 41.49
Heating
Rated current A 37.98 41.27
Max. current A 65.14 69.08
COP 4.12 4.01
ACOP 4.10 4.21
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
ANB78FZXMT ANB78FZXMT
Model
+ANB78FZXMT ANB52FZJMT*2
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 2INV 3INV
Capacity W 25200+25200 25200+(16800*2)
Power Input W 7700+7700 7700+5250*2
Compressor
Rated current(RLA) A 26+26 26+16.5*2
Speed rps 60 60
Crankcase Heater W 66+66 66+132
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
(2300+1500)
Refrigerant oil charge ml (2300+1500)*2
+(2300+1500)*2
Brand BROAD-OCEAN BROAD-OCEAN
ZWK924D500007 ZWK924D500007+(ZWK924D
Model
+ZWK924D500007 500002+ZWK924D500002)
Voltage DC540V DC540V
IP Class IP44 IP44
Type/quantity DC/1+DC/2 DC/2+DC/2
Outdoor fan
Insulation class B B
motor
Safe class I I
Power Input W 1600+1600 1600+2320
Output W 1300+1300 1300+1800
Rated current A 8+8 8+8
Caoacitor μF / /
Speed rpm 0~1180 0~1180
34
Model AV32NMVETA AV34NMVETA
Brand Shun wei+Shun wei Shun wei+Tian Da
Model / /
Material ABS+20%GF ABS+20%GF
Outdoor fan
Type Axial Axial
Diameter mm Φ700+Φ700 Φ700+Φ642
Height mm 204+204 204+198
Mumber of rows 3+3 3+3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) Hydrophilic aluminum Hydrophilic aluminum
Fin coating Type Optional Clear Iacquer Clear Iacquer
Salt Spray Test Duration Hour 168 168
Outdoor coil INNERGROOVE TUBE INNERGROOVE TUBE
Tube outside dia.and type mm
Φ7 Φ7
(2245*1260+2158*1260 (2245*1260+2158*1260
+2065*1260)+(2245*1260+ +2065*1260)+(2843*1260+
Coil length x height mm
2158*1260 2757*1260
+2065*1260) +2669*1260)
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 27000 30500
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 91 91
980/750/1690 980/750/1690
Diamension(W*D*H) mm
+980/750/1690 +1410/750/1690
1070/850/1858 1070/850/1858
Outdoor unit Packing(W*D*H) mm
+1070/850/1858 +1515/850/1858
Net weight kg 255+255 255+385
Gross weight kg 280+280 280+410
Type R410A R410A
Refrigerant
Charged volume kg 20 20
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
35
Model AV32NMVETA AV34NMVETA
Liquid pipe mm 19.05 19.05
Gas pipe mm 31.8 31.8
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 53 56
Max. fuse current A 80.00 90.00
Connection Min. wiring current A 64.80 68.50
wiring Power wiring mm2 10+10 10+10
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
36
Model AV36NMVETA AV38NMVETA
HP 36 38
Combination 18+18 18+20
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 100.8 106.4
Rated capacity kBtu/h 343.94 363.05
Rated power input kW 31.40 32.32
Max. power input kW 51.80 54.81
Cooling
Rated current A 53.01 54.56
Max. current A 80.60 86.60
EER 3.21 3.29
AEER 6.84 6.82
Rated capacity kw 100.8 106.4
Rated capacity kBtu/h 343.94 363.05
Rated power input kW 25.62 27.04
Max. power input kW 43.86 46.63
Heating
Rated current A 44.55 47.02
Max. current A 73.03 77.64
COP 3.93 3.93
ACOP 4.31 4.34
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
ANB52FZJMT*2 ANB52FZJMT*2
Model
+ANB52FZJMT*2 +ANB52FZJMT*2
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 4INV 4INV
Capacity W 16800*2+16800*2 16800*2+16800*2
Power Input W 5250*2+5250*2 5250*2+5250*2
Compressor
Rated current(RLA) A 16.5*2+16.5*2 16.5*2+16.5*2
Speed rps 60 60
Crankcase Heater W 132+132 132+132
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
(2300+1500)*2 (2300+1500)*2
Refrigerant oil charge ml
+(2300+1500)*2 +(2300+1500)*2
Brand BROAD-OCEAN BROAD-OCEAN
(ZWK924D500002+ZWK924D (ZWK924D500002+ZWK924D
Model 500002)+(ZWK924D500002+ 500002)+(ZWK924D500002+
ZWK924D500002) ZWK924D500002)
Voltage DC540V DC540V
IP Class IP44 IP44
Outdoor fan Type/quantity DC/2+DC/2 DC/2+DC/2
motor Insulation class B B
Safe class I I
Power Input W 2320+2320 2320+2320
Output W 1800+1800 1800+1800
Rated current A 8+8 8+8
Caoacitor μF / /
Speed rpm 0~1180 0~1180
37
Model AV36NMVETA AV38NMVETA
Brand Tian Da+Tian Da Tian Da+Tian Da
Model / /
Material ABS+20%GF ABS+20%GF
Outdoor fan
Type Axial Axial
Diameter mm Φ642+Φ642 Φ642+Φ642
Height mm 198+198 198+198
Mumber of rows 3+3 3+3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) Hydrophilic aluminum Hydrophilic aluminum
Fin coating Type Optional Clear Iacquer Clear Iacquer
Salt Spray Test Duration Hour 168 168
Outdoor coil
INNERGROOVE TUBE INNERGROOVE TUBE
Tube outside dia.and type mm
Φ7 Φ7
(2843*1260+2757*1260 (2843*1260+2757*1260
Coil length x height mm +2669*1260)+(2843*1260+ +2669*1260)+(2843*1260+
2757*1260+2669*1260) 2757*1260+2669*1260)
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 34000 34000
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 91 91
1410/750/1690 1410/750/1690
Diamension(W*D*H) mm
+1410/750/1690 +1410/750/1690
1515/850/1858 1515/850/1858
Outdoor unit Packing(W*D*H) mm
+1515/850/1858 +1515/850/1858
Net weight kg 385+385 385+385
Gross weight kg 410+410 410+410
Type R410A R410A
Refrigerant
Charged volume kg 20 20
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
38
Model AV36NMVETA AV38NMVETA
Liquid pipe mm 19.05 19.05
Gas pipe mm 38.1 38.1
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 59 63
Max. fuse current A 100.00 100.00
Connection Min. wiring current A 72.20 78.50
wiring Power wiring mm2 10+10 10+16
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
39
Model AV40NMVETA AV42NMVETA
HP 40 42
Combination 20+20 20+22
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 112.0 117.5
Rated capacity kBtu/h 382.16 400.93
Rated power input kW 33.23 34.92
Max. power input kW 57.82 60.73
Cooling
Rated current A 56.11 58.95
Max. current A 92.60 98.21
EER 3.37 3.36
AEER 6.80 6.69
Rated capacity kw 112.0 117.5
Rated capacity kBtu/h 382.16 400.93
Rated power input kW 28.47 30.37
Max. power input kW 49.40 50.39
Heating
Rated current A 49.50 52.81
Max. current A 82.25 83.90
COP 3.93 3.86
ACOP 4.38 4.38
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
ANB52FZJMT*2 ANB52FZJMT*2
Model
+ANB52FZJMT*2 +ANB66FZXMT*2*2
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 4INV 4INV
Capacity W 16800*2+16800*2 16800*2+21300*2
Power Input W 5250*2+5250*2 5250*2+6650*2
Compressor
Rated current(RLA) A 16.5*2+16.5*2 16.5*2+21.5*2
Speed rps 60 60
Crankcase Heater W 132+132 132+132
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
(2300+1500)*2 (2300+1500)*2
Refrigerant oil charge ml
+(2300+1500)*2 +(2300+1500)*2
Brand BROAD-OCEAN BROAD-OCEAN
(ZWK924D500002 (ZWK924D500002
+ZWK924D500002) +ZWK924D500002)
Model
+(ZWK924D500002 +(ZWK924D500002
+ZWK924D500002) +ZWK924D500002)
Voltage DC540V DC540V
IP Class IP44 IP44
Outdoor fan Type/quantity DC/2+DC/2 DC/2+DC/2
motor
Insulation class B B
Safe class I I
Power Input W 2320+2320 2320+2320
Output W 1800+1800 1800+1800
Rated current A 8+8 8+8
Caoacitor μF / /
Speed rpm 0~1180 0~1180
40
Model AV40NMVETA AV42NMVETA
Brand Tian Da+Tian Da Tian Da+Tian Da
Model / /
Material ABS+20%GF ABS+20%GF
Outdoor fan
Type Axial Axial
Diameter mm Φ642+Φ642 Φ642+Φ642
Height mm 198+198 198+198
Mumber of rows 3+3 3+3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) Hydrophilic aluminum Hydrophilic aluminum
Fin coating Type Optional Clear Iacquer Clear Iacquer
Salt Spray Test Duration Hour 168 168
Outdoor coil INNERGROOVE TUBE INNERGROOVE TUBE
Tube outside dia.and type mm
Φ7 Φ7
(2843*1260+2757*1260 (2843*1260+2757*1260
+2669*1260)+(2843*1260+ +2669*1260)+(2843*1260+
Coil length x height mm
2757*1260 2757*1260
+2669*1260) +2669*1260)
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 34000 35000
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 91 92
1410/750/1690 1410/750/1690
Diamension(W*D*H) mm
+1410/750/1690 +1410/750/1690
1515/850/1858 1515/850/1858
Outdoor unit Packing(W*D*H) mm
+1515/850/1858 +1515/850/1858
Net weight kg 385+385 385+385
Gross weight kg 410+410 410+410
Type R410A R410A
Refrigerant
Charged volume kg 20 20
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
41
Model AV40NMVETA AV42NMVETA
Liquid pipe mm 19.05 19.05
Gas pipe mm 38.1 38.1
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 64 64
Max. fuse current A 100.00 113.00
Connection Min. wiring current A 84.80 90.50
wiring Power wiring mm2 16+16 16+16
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
42
Model AV44NMVETA AV46NMVETA
HP 44 46
Combination 22+22 22+24
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 123.0 129.5
Rated capacity kBtu/h 419.69 441.87
Rated power input kW 36.61 36.91
Max. power input kW 63.64 64.63
Cooling
Rated current A 61.80 62.32
Max. current A 103.82 106.03
EER 3.36 3.51
AEER 6.59 6.76
Rated capacity kw 123.0 129.5
Rated capacity kBtu/h 419.69 441.87
Rated power input kW 32.27 35.00
Max. power input kW 51.38 56.09
Heating
Rated current A 56.12 60.86
Max. current A 85.55 93.39
COP 3.81 3.69
ACOP 4.39 4.36
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
ANB66FZXMT*2 ANB66FZXMT*2
Model
+ANB66FZXMT*2 +ANB66FZXMT*2
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 4INV 4INV
Capacity W 21300*2+21300*2 21300*2+21300*2
Power Input W 6600*2+6600*2 6600*2+6600*2
Compressor
Rated current(RLA) A 21.5*2+21.5*2 21.5*2+21.5*2
Speed rps 60 60
Crankcase Heater W 132+132 132+132
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
(2300+1500)*2 (2300+1500)*2
Refrigerant oil charge ml
+(2300+1500)*2 +(2300+1500)*2
Brand BROAD-OCEAN BROAD-OCEAN
(ZWK924D500002 (ZWK924D500002
+ZWK924D500002) +ZWK924D500002)
Model
+(ZWK924D500002 +(ZWK924D500002
+ZWK924D500002) +ZWK924D500002)
Voltage DC540V DC540V
IP Class IP44 IP44
Outdoor fan Type/quantity DC/2+DC/2 DC/2+DC/2
motor
Insulation class B B
Safe class I I
Power Input W 2320+2320 2320+2320
Output W 1800+1800 1800+1800
Rated current A 8+8 8+8
Caoacitor μF / /
Speed rpm 0~1180 0~1180
43
Model AV44NMVETA AV46NMVETA
Brand Tian Da+Tian Da Tian Da+Tian Da
Model / /
Material ABS+20%GF ABS+20%GF
Outdoor fan
Type Axial Axial
Diameter mm Φ642+Φ642 Φ642+Φ642
Height mm 198+198 198+198
Mumber of rows 3+3 3+3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) Hydrophilic aluminum Hydrophilic aluminum
Fin coating Type Optional Clear Iacquer Clear Iacquer
Salt Spray Test Duration Hour 168 168
Outdoor coil
INNERGROOVE TUBE INNERGROOVE TUBE
Tube outside dia.and type mm
Φ7 Φ7
(2843*1260+2757*1260 (2843*1260+2757*1260
Coil length x height mm +2669*1260)+(2843*1260+ +2669*1260)+(2843*1260+
2757*1260+2669*1260) 2757*1260+2669*1260)
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 36000 36000
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 93 93
1410/750/1690 1410/750/1690
Diamension(W*D*H) mm
+1410/750/1690 +1410/750/1690
1515/850/1858 1515/850/1858
Outdoor unit Packing(W*D*H) mm
+1515/850/1858 +1515/850/1858
Net weight kg 385+385 385+385
Gross weight kg 410+410 410+410
Type R410A R410A
Refrigerant
Charged volume kg 20 20
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
44
Model AV44NMVETA AV46NMVETA
Liquid pipe mm 19.05 19.05
Gas pipe mm 38.1 38.1
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 64 64
Max. fuse current A 126.00 126.00
Connection Min. wiring current A 96.20 97.20
wiring Power wiring mm2 16+16 16+25
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
45
Model AV48NMVETA AV50NMVETA
HP 48 50
Combination 24+24 24+26
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 136.0 141.5
Rated capacity kBtu/h 464.05 482.82
Rated power input kW 37.22 39.86
Max. power input kW 65.62 68.16
Cooling
Rated current A 62.84 67.29
Max. current A 108.24 112.98
EER 3.65 3.55
AEER 6.97 6.87
Rated capacity kw 136.0 141.5
Rated capacity kBtu/h 464.05 482.82
Rated power input kW 37.73 40.49
Max. power input kW 60.80 62.85
Heating
Rated current A 65.60 70.40
Max. current A 101.23 104.65
COP 3.60 3.49
ACOP 4.34 4.08
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
ANB66FZXMT*2 ANB66FZXMT*2
Model
+ANB66FZXMT*2 +ANB78FZXMT*2
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 4INV 4INV
Capacity W 21300*2+21300*2 21300*2+25200*2
Power Input W 6600*2+6600*2 6600*2+7700*2
Compressor
Rated current(RLA) A 21.5*2+21.5*2 21.5*2+26*2
Speed rps 60 60
Crankcase Heater W 132+132 132+132
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
(2300+1500)*2 (2300+1500)*2
Refrigerant oil charge ml
+(2300+1500)*2 +(2300+1500)*2
Brand BROAD-OCEAN BROAD-OCEAN
(ZWK924D500002 (ZWK924D500002
+ZWK924D500002) +ZWK924D500002)
Model
+(ZWK924D500002 +(ZWK924D500002
+ZWK924D500002) +ZWK924D500002)
Voltage DC540V DC540V
IP Class IP44 IP44
Outdoor fan Type/quantity DC/2+DC/2 DC/2+DC/2
motor
Insulation class B B
Safe class I I
Power Input W 2320+2320 2320+2320
Output W 1800+1800 1800+1800
Rated current A 8+8 8+8
Caoacitor μF / /
Speed rpm 0~1180 0~1180
46
Model AV48NMVETA AV50NMVETA
Brand Tian Da+Tian Da Tian Da+Tian Da
Model / /
Material ABS+20%GF ABS+20%GF
Outdoor fan
Type Axial Axial
Diameter mm Φ642+Φ642 Φ642+Φ642
Height mm 198+198 198+198
Mumber of rows 3+3 3+3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) Hydrophilic aluminum Hydrophilic aluminum
Fin coating Type Optional Clear Iacquer Clear Iacquer
Salt Spray Test Duration Hour 168 168
Outdoor coil
INNERGROOVE TUBE INNERGROOVE TUBE
Tube outside dia.and type mm
Φ7 Φ7
(2843*1260+2757*1260 (2843*1260+2757*1260
Coil length x height mm +2669*1260)+(2843*1260+ +2669*1260)+(2843*1260+
2757*1260+2669*1260) 2757*1260+2669*1260)
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 36000 37000
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 93 93
1410/750/1690 1410/750/1690
Diamension(W*D*H) mm
+1410/750/1690 +1410/750/1690
1515/850/1858 1515/850/1858
Outdoor unit Packing(W*D*H) mm
+1515/850/1858 +1515/850/1858
Net weight kg 385+385 385+385
Gross weight kg 410+410 410+410
Type R410A R410A
Refrigerant
Charged volume kg 20 20
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
47
Model AV48NMVETA AV50NMVETA
Liquid pipe mm 19.05 19.05
Gas pipe mm 38.1 38.1
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 64 64
Max. fuse current A 126.00 126.00
Connection Min. wiring current A 98.20 104.90
wiring Power wiring mm2 25+25 25+25
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
48
Model AV52NMVETA AV54NMVETA
HP 52 54
Combination 26+26 18+18+18
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 147.0 151.2
Rated capacity kBtu/h 501.58 515.92
Rated power input kW 42.49 47.10
Max. power input kW 70.70 77.70
Cooling
Rated current A 71.73 79.52
Max. current A 117.72 120.90
EER 3.46 3.21
AEER 6.78 6.85
Rated capacity kw 147.0 151.2
Rated capacity kBtu/h 501.58 515.92
Rated power input kW 43.25 38.43
Max. power input kW 64.90 65.79
Heating
Rated current A 75.20 66.82
Max. current A 108.06 109.54
COP 3.39 3.93
ACOP 3.88 4.31
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
ANB52FZJMT*2
ANB78FZXMT*2
Model +ANB52FZJMT*2
+ANB78FZXMT*2
+ANB52FZJMT*2
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 4INV 6INV
Capacity W 25200*2+25200*2 16800*2+16800*2+16800*2
Power Input W 7700*2+7700*2 5250*2+5250*2+5250*2
Compressor
Rated current(RLA) A 26*2+26*2 16.5*2+16.5*2+16.5*2
Speed rps 60 60
Crankcase Heater W 132+132 132+132+132
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
(2300+1500)*2
(2300+1500)*2
Refrigerant oil charge ml +(2300+1500)*2
+(2300+1500)*2
+(2300+1500)*2
Brand BROAD-OCEAN BROAD-OCEAN
(ZWK924D500002
+ZWK924D500002) (ZWK924D500002
Model
+(ZWK924D500002 +ZWK924D500002)*3
+ZWK924D500002)
Voltage DC540V DC540V
IP Class IP44 IP44
Outdoor fan Type/quantity DC/2+DC/2 DC/2+DC/2+DC/2
motor
Insulation class B B
Safe class I I
Power Input W 2320+2320 2320+2320+2320
Output W 1800+1800 1800+1800+1800
Rated current A 8+8 8+8+8
Caoacitor μF / /
Speed rpm 0~1180 0~1180
49
Model AV52NMVETA AV54NMVETA
Brand Tian Da+Tian Da Tian Da+Tian Da+Tian Da
Model / /
Material ABS+20%GF ABS+20%GF
Outdoor fan
Type Axial Axial
Diameter mm Φ642+Φ642 Φ642+Φ642+Φ642+Φ642
Height mm 198+198 198+198+198
Mumber of rows 3+3 3+3+3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) Hydrophilic aluminum Hydrophilic aluminum
Fin coating Type Optional Clear Iacquer Clear Iacquer
Salt Spray Test Duration Hour 168 168
Outdoor coil INNERGROOVE TUBE INNERGROOVE TUBE
Tube outside dia.and type mm
Φ7 Φ7
(2843*1260+2757*1260
(2843*1260+2757*1260 +2669*1260)+(2843*1260
Coil length x height mm +2669*1260)+(2843*1260 +2757*1260+2669*1260)
+2757*1260+2669*1260) +(2843*1260+2757*1260
+2669*1260)
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 38000 51000
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 93 93
1410/750/1690 1410/750/1690+1410/750/1
Diamension(W*D*H) mm
+1410/750/1690 690+1410/750/1690
1515/850/1858 1515/850/1858+1515/850/1
Outdoor unit Packing(W*D*H) mm
+1515/850/1858 858+1515/850/1858
Net weight kg 385+385 385+385+385
Gross weight kg 410+410 410+410+410
Type R410A R410A
Refrigerant
Charged volume kg 20 30
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
50
Model AV52NMVETA AV54NMVETA
Liquid pipe mm 19.05 19.05
Gas pipe mm 38.1 38.1
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 64 64
Max. fuse current A 126.00 150.00
Connection Min. wiring current A 111.60 108.30
wiring Power wiring mm2 25+25 10+10+10
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
51
Model AV56NMVETA AV58NMVETA
HP 56 58
Combination 18+18+20 18+20+20
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 156.8 162.4
Rated capacity kBtu/h 535.02 554.13
Rated power input kW 48.02 48.94
Max. power input kW 80.71 83.72
Cooling
Rated current A 81.07 82.61
Max. current A 126.90 132.90
EER 3.27 3.32
AEER 6.84 6.83
Rated capacity kw 156.8 162.4
Rated capacity kBtu/h 535.02 554.13
Rated power input kW 39.85 41.27
Max. power input kW 68.56 71.33
Heating
Rated current A 69.30 71.77
Max. current A 114.15 118.76
COP 3.93 3.93
ACOP 4.33 4.36
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
ANB52FZJMT*2 ANB52FZJMT*2
Model +ANB52FZJMT*2 +ANB52FZJMT*2
+ANB52FZJMT*2 +ANB52FZJMT*2
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 6INV 6INV
Capacity W 16800*2+16800*2+16800*2 16800*2+16800*2+16800*2
Power Input W 5250*2+5250*2+5250*2 5250*2+5250*2+5250*2
Compressor
Rated current(RLA) A 16.5*2+16.5*2+16.5*2 16.5*2+16.5*2+16.5*2
Speed rps 60 60
Crankcase Heater W 132+132+132 132+132+132
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
(2300+1500)*2 (2300+1500)*2
Refrigerant oil charge ml +(2300+1500)*2 +(2300+1500)*2
+(2300+1500)*2 +(2300+1500)*2
Brand BROAD-OCEAN BROAD-OCEAN
(ZWK924D500002 (ZWK924D500002
Model
+ZWK924D500002)*3 +ZWK924D500002)*3
Voltage DC540V DC540V
IP Class IP44 IP44
Type/quantity DC/2+DC/2+DC/2 DC/2+DC/2+DC/2
Outdoor fan
Insulation class B B
motor
Safe class I I
Power Input W 2320+2320+2320 2320+2320+2320
Output W 1800+1800+1800 1800+1800+1800
Rated current A 8+8+8 8+8+8
Caoacitor μF / /
Speed rpm 0~1180 0~1180
52
Model AV56NMVETA AV58NMVETA
Brand Tian Da+Tian Da+Tian Da Tian Da+Tian Da+Tian Da
Model / /
Material ABS+20%GF ABS+20%GF
Outdoor fan
Type Axial Axial
Diameter mm Φ642+Φ642+Φ642+Φ642 Φ642+Φ642+Φ642+Φ642
Height mm 198+198+198 198+198+198
Mumber of rows 3+3+3 3+3+3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) Hydrophilic aluminum Hydrophilic aluminum
Fin coating Type Optional Clear Iacquer Clear Iacquer
Salt Spray Test Duration Hour 168 168
Outdoor coil INNERGROOVE TUBE INNERGROOVE TUBE
Tube outside dia.and type mm
Φ7 Φ7
(2843*1260+2757*1260 (2843*1260+2757*1260
+2669*1260)+(2843*1260 +2669*1260)+(2843*1260
Coil length x height mm +2757*1260+2669*1260) +2757*1260+2669*1260)
+(2843*1260+2757*1260 +(2843*1260+2757*1260
+2669*1260) +2669*1260)
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 51000 51000
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 93 93
1410/750/1690+1410/750/1 1410/750/1690+1410/750/1
Diamension(W*D*H) mm
690+1410/750/1690 690+1410/750/1690
1515/850/1858+1515/850/1 1515/850/1858+1515/850/1
Outdoor unit Packing(W*D*H) mm
858+1515/850/1858 858+1515/850/1858
Net weight kg 385+385+385 385+385+385
Gross weight kg 410+410+410 410+410+410
Type R410A R410A
Refrigerant
Charged volume kg 30 30
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
53
Model AV56NMVETA AV58NMVETA
Liquid pipe mm 19.05 19.05
Gas pipe mm 38.1 41.3
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 64 64
Max. fuse current A 150.00 150.00
Connection Min. wiring current A 114.60 120.90
wiring Power wiring mm2 10+10+16 10+16+16
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
54
Model AV60NMVETA AV62NMVETA
HP 60 62
Combination 20+20+20 20+20+22
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 168.0 173.5
Rated capacity kBtu/h 573.24 592.01
Rated power input kW 49.85 51.54
Max. power input kW 86.73 89.64
Cooling
Rated current A 84.16 87.01
Max. current A 138.90 144.51
EER 3.37 3.37
AEER 6.81 6.74
Rated capacity kw 168.0 173.5
Rated capacity kBtu/h 573.24 592.01
Rated power input kW 42.70 44.60
Max. power input kW 74.10 75.09
Heating
Rated current A 74.25 77.56
Max. current A 123.38 125.03
COP 3.93 3.88
ACOP 4.38 4.38
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
ANB52FZJMT*2 ANB52FZJMT*2
Model +ANB52FZJMT*2 +ANB52FZJMT*2
+ANB52FZJMT*2 +ANB66FZXMT*2
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 6INV 6INV
Capacity W 16800*2+16800*2+16800*2 16800*2+16800*2+21300*2
Compressor Power Input W 5250*2+5250*2+5250*2 5250*2+5250*2+6600*2
Rated current(RLA) A 16.5*2+16.5*2+16.5*2 16.5*2+16.5*2+21.5*2
Speed rps 60 60
Crankcase Heater W 132+132+132 132+132+132
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
(2300+1500)*2+(2300 (2300+1500)*2+(2300
Refrigerant oil charge ml
+1500)*2+(2300+1500)*2 +1500)*2+(2300+1500)*2
Brand BROAD-OCEAN BROAD-OCEAN
(ZWK924D500002 (ZWK924D500002
Model
+ZWK924D500002)*3 +ZWK924D500002)*3
Voltage DC540V DC540V
IP Class IP44 IP44
Type/quantity DC/2+DC/2+DC/2 DC/2+DC/2+DC/2
Outdoor fan
Insulation class B B
motor
Safe class I I
Power Input W 2320+2320+2320 2320+2320+2320
Output W 1800+1800+1800 1800+1800+1800
Rated current A 8+8+8 8+8+8
Caoacitor μF / /
Speed rpm 0~1180 0~1180
55
Model AV60NMVETA AV62NMVETA
Brand Tian Da+Tian Da+Tian Da Tian Da+Tian Da+Tian Da
Model / /
Material ABS+20%GF ABS+20%GF
Outdoor fan
Type Axial Axial
Diameter mm Φ642+Φ642+Φ642+Φ642 Φ642+Φ642+Φ642+Φ642
Height mm 198+198+198 198+198+198
Mumber of rows 3+3+3 3+3+3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) Hydrophilic aluminum Hydrophilic aluminum
Fin coating Type Optional Clear Iacquer Clear Iacquer
Salt Spray Test Duration Hour 168 168
Outdoor coil INNERGROOVE TUBE INNERGROOVE TUBE
Tube outside dia.and type mm
Φ7 Φ7
(2843*1260+2757*1260 (2843*1260+2757*1260
+2669*1260)+(2843*1260 +2669*1260)+(2843*1260+
Coil length x height mm +2757*1260+2669*1260) 2757*1260+2669*1260)
+(2843*1260+2757*1260 +(2843*1260+2757*1260
+2669*1260) +2669*1260)
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 51000 52000
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 93 93.5
1410/750/1690+1410/750/1 1410/750/1690+1410/750/1
Diamension(W*D*H) mm
690+1410/750/1690 690+1410/750/1690
1515/850/1858+1515/850/1 1515/850/1858+1515/850/1
Outdoor unit Packing(W*D*H) mm
858+1515/850/1858 858+1515/850/1858
Net weight kg 385+385+385 385+385+385
Gross weight kg 410+410+410 410+410+410
Type R410A R410A
Refrigerant
Charged volume kg 30 30
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
56
Model AV60NMVETA AV62NMVETA
Liquid pipe mm 19.05 19.05
Gas pipe mm 41.3 41.3
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 64 64
Max. fuse current A 150.00 163.00
Connection Min. wiring current A 127.20 132.90
wiring Power wiring mm2 16+16+16 16+16+16
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
57
Model AV64NMVETA AV66NMVETA
HP 64 66
Combination 20+22+22 22+22+22
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 179.0 184.5
Rated capacity kBtu/h 610.77 629.54
Rated power input kW 53.22 54.91
Max. power input kW 92.55 95.46
Cooling
Rated current A 89.85 92.70
Max. current A 150.12 155.73
EER 3.36 3.36
AEER 6.67 6.60
Rated capacity kw 179.0 184.5
Rated capacity kBtu/h 610.77 629.54
Rated power input kW 46.51 48.41
Max. power input kW 76.08 77.08
Heating
Rated current A 80.87 84.18
Max. current A 126.68 128.33
COP 3.84 3.81
ACOP 4.39 4.39
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
ANB52FZJMT*2+ANB66FZX ANB66FZXMT*2+ANB66FZX
Model
MT*2+ANB66FZXMT*2 MT*2+ANB66FZXMT*2
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 6INV 6INV
Capacity W 16800*2+21300*2+21300*2 21300*2+21300*2+21300*2
Power Input W 5250*2+6600*2+6600*2 6600*2+6600*2+6600*2
Compressor Rated current(RLA) A 16.5*2+21.5*2+21.5*2 21.5*2+21.5*2+21.5*2
Speed rps 60 60
Crankcase Heater W 132+132+132 132+132+132
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
(2300+1500)*2 (2300+1500)*2
Refrigerant oil charge ml +(2300+1500)*2 +(2300+1500)*2
+(2300+1500)*2 +(2300+1500)*2
Brand BROAD-OCEAN BROAD-OCEAN
(ZWK924D500002 (ZWK924D500002
Model
+ZWK924D500002)*3 +ZWK924D500002)*3
Voltage DC540V DC540V
IP Class IP44 IP44
Type/quantity DC/2+DC/2+DC/2 DC/2+DC/2+DC/2
Outdoor fan
Insulation class B B
motor
Safe class I I
Power Input W 2320+2320+2320 2320+2320+2320
Output W 1800+1800+1800 1800+1800+1800
Rated current A 8+8+8 8+8+8
Caoacitor μF / /
Speed rpm 0~1180 0~1180
58
Model AV64NMVETA AV66NMVETA
Brand Tian Da+Tian Da+Tian Da Tian Da+Tian Da+Tian Da
Model / /
Material ABS+20%GF ABS+20%GF
Outdoor fan
Type Axial Axial
Diameter mm Φ642+Φ642+Φ642+Φ642 Φ642+Φ642+Φ642+Φ642
Height mm 198+198+198 198+198+198
Mumber of rows 3+3+3 3+3+3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) Hydrophilic aluminum Hydrophilic aluminum
Fin coating Type Optional Clear Iacquer Clear Iacquer
Salt Spray Test Duration Hour 168 168
Outdoor coil INNERGROOVE TUBE INNERGROOVE TUBE
Tube outside dia.and type mm
Φ7 Φ7
(2843*1260+2757*1260 (2843*1260+2757*1260
+2669*1260)+(2843*1260 +2669*1260)+(2843*1260+
Coil length x height mm +2757*1260+2669*1260) 2757*1260+2669*1260)
+(2843*1260+2757*1260 +(2843*1260+2757*1260
+2669*1260) +2669*1260)
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 53000 54000
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 94 95
1410/750/1690+1410/750/1 1410/750/1690+1410/750/1
Diamension(W*D*H) mm
690+1410/750/1690 690+1410/750/1690
1515/850/1858+1515/850/1 1515/850/1858+1515/850/1
Outdoor unit Packing(W*D*H) mm
858+1515/850/1858 858+1515/850/1858
Net weight kg 385+385+385 385+385+385
Gross weight kg 410+410+410 410+410+410
Type R410A R410A
Refrigerant
Charged volume kg 30 30
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
59
Model AV64NMVETA AV66NMVETA
Liquid pipe mm 19.05 19.05
Gas pipe mm 41.3 41.3
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 64 64
Max. fuse current A 176.00 189.00
Connection Min. wiring current A 138.60 144.30
wiring Power wiring mm2 16+16+16 16+16+16
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
60
Model AV68NMVETA AV70NMVETA
HP 68 70
Combination 22+22+24 22+24+24
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 191.0 197.5
Rated capacity kBtu/h 651.72 673.90
Rated power input kW 55.22 55.53
Max. power input kW 96.45 97.44
Cooling
Rated current A 93.22 93.74
Max. current A 157.94 160.15
EER 3.46 3.56
AEER 6.80 6.86
Rated capacity kw 191.0 197.5
Rated capacity kBtu/h 651.72 673.90
Rated power input kW 51.14 53.86
Max. power input kW 81.78 86.49
Heating
Rated current A 88.92 93.66
Max. current A 136.17 144.01
COP 3.73 3.66
ACOP 4.37 4.35
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
ANB66FZXMT*2+ANB66FZX ANB66FZXMT*2+ANB66FZX
Model
MT*2+ANB66FZXMT*2 MT*2+ANB66FZXMT*2
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 6INV 6INV
Capacity W 21300*2+21300*2+21300*2 21300*2+21300*2+21300*2
Power Input W 6600*2+6600*2+6600*2 6600*2+6600*2+6600*2
Compressor
Rated current(RLA) A 21.5*2+21.5*2+21.5*2 21.5*2+21.5*2+21.5*2
Speed rps 60 60
Crankcase Heater W 132+132+132 132+132+132
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
(2300+1500)*2+(2300+1500)* (2300+1500)*2+(2300+1500)*
Refrigerant oil charge ml
2+(2300+1500)*2 2+(2300+1500)*2
Brand BROAD-OCEAN BROAD-OCEAN
(ZWK924D500002 (ZWK924D500002
Model
+ZWK924D500002)*3 +ZWK924D500002)*3
Voltage DC540V DC540V
IP Class IP44 IP44
Type/quantity DC/2+DC/2+DC/2 DC/2+DC/2+DC/2
Outdoor fan
Insulation class B B
motor
Safe class I I
Power Input W 2320+2320+2320 2320+2320+2320
Output W 1800+1800+1800 1800+1800+1800
Rated current A 8+8+8 8+8+8
Caoacitor μF / /
Speed rpm 0~1180 0~1180
61
Model AV68NMVETA AV70NMVETA
Brand Tian Da+Tian Da+Tian Da Tian Da+Tian Da+Tian Da
Model / /
Material ABS+20%GF ABS+20%GF
Outdoor fan
Type Axial Axial
Diameter mm Φ642+Φ642+Φ642+Φ642 Φ642+Φ642+Φ642+Φ642
Height mm 198+198+198 198+198+198
Mumber of rows 3+3+3 3+3+3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) Hydrophilic aluminum Hydrophilic aluminum
Fin coating Type Optional Clear Iacquer Clear Iacquer
Salt Spray Test Duration Hour 168 168
Outdoor coil INNERGROOVE TUBE INNERGROOVE TUBE
Tube outside dia.and type mm
Φ7 Φ7
(2843*1260+2757*1260 (2843*1260+2757*1260
+2669*1260)+(2843*1260+ +2669*1260)+(2843*1260+
Coil length x height mm 2757*1260+2669*1260) 2757*1260+2669*1260)
+(2843*1260+2757*1260 +(2843*1260+2757*1260
+2669*1260) +2669*1260)
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 54000 54000
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 95 95
1410/750/1690+1410/750/1 1410/750/1690+1410/750/1
Diamension(W*D*H) mm
690+1410/750/1690 690+1410/750/1690
1515/850/1858+1515/850/1 1515/850/1858+1515/850/1
Outdoor unit Packing(W*D*H) mm
858+1515/850/1858 858+1515/850/1858
Net weight kg 385+385+385 385+385+385
Gross weight kg 410+410+410 410+410+410
Type R410A R410A
Refrigerant
Charged volume kg 30 30
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
62
Model AV68NMVETA AV70NMVETA
Liquid pipe mm 22.2 22.2
Gas pipe mm 44.5 44.5
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 64 64
Max. fuse current A 189.00 189.00
Connection Min. wiring current A 145.30 146.30
wiring Power wiring mm2 16+16+25 16+25+25
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
63
Model AV72NMVETA AV74NMVETA
HP 72 74
Combination 24+24+24 24+24+26
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 204.0 209.5
Rated capacity kBtu/h 696.08 714.84
Rated power input kW 55.83 58.47
Max. power input kW 98.43 100.97
Cooling
Rated current A 94.26 98.71
Max. current A 162.36 167.10
EER 3.65 3.58
AEER 6.98 6.92
Rated capacity kw 204.0 209.5
Rated capacity kBtu/h 696.08 714.84
Rated power input kW 56.59 59.35
Max. power input kW 91.20 93.25
Heating
Rated current A 98.40 103.20
Max. current A 151.85 155.26
COP 3.60 3.52
ACOP 4.34 4.16
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
ANB66FZXMT*2+ANB66FZX ANB66FZXMT*2+ANB66FZX
Model
MT*2+ANB66FZXMT*2 MT*2+ANB78FZXMT*2
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 6INV 6INV
Capacity W 21300*2+21300*2+21300*2 21300*2+21300*2+25200*2
Power Input W 6600*2+6600*2+6600*2 6600*2+6600*2+7700*2
Compressor
Rated current(RLA) A 21.5*2+21.5*2+21.5*2 21.5*2+21.5*2+26*2
Speed rps 60 60
Crankcase Heater W 132+132+132 132+132+132
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
(2300+1500)*2+(2300+1500)* (2300+1500)*2+(2300+1500)*
Refrigerant oil charge ml
2+(2300+1500)*2 2+(2300+1500)*2
Brand BROAD-OCEAN BROAD-OCEAN
(ZWK924D500002 (ZWK924D500002
Model
+ZWK924D500002)*3 +ZWK924D500002)*3
Voltage DC540V DC540V
IP Class IP44 IP44
Type/quantity DC/2+DC/2+DC/2 DC/2+DC/2+DC/2
Outdoor fan
Insulation class B B
motor
Safe class I I
Power Input W 2320+2320+2320 2320+2320+2320
Output W 1800+1800+1800 1800+1800+1800
Rated current A 8+8+8 8+8+8
Caoacitor μF / /
Speed rpm 0~1180 0~1180
64
Model AV72NMVETA AV74NMVETA
Brand Tian Da+Tian Da+Tian Da Tian Da+Tian Da+Tian Da
Model / /
Material ABS+20%GF ABS+20%GF
Outdoor fan
Type Axial Axial
Diameter mm Φ642+Φ642+Φ642+Φ642 Φ642+Φ642+Φ642+Φ642
Height mm 198+198+198 198+198+198
Mumber of rows 3+3+3 3+3+3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) Hydrophilic aluminum Hydrophilic aluminum
Fin coating Type Optional Clear Iacquer Clear Iacquer
Salt Spray Test Duration Hour 168 168
Outdoor coil INNERGROOVE TUBE INNERGROOVE TUBE
Tube outside dia.and type mm
Φ7 Φ7
(2843*1260+2757*1260 (2843*1260+2757*1260
+2669*1260)+(2843*1260+ +2669*1260)+(2843*1260+
Coil length x height mm 2757*1260+2669*1260) 2757*1260+2669*1260)
+(2843*1260+2757*1260 +(2843*1260+2757*1260
+2669*1260) +2669*1260)
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 54000 55000
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 95 95
1410/750/1690+1410/750/1 1410/750/1690+1410/750/1
Diamension(W*D*H) mm
690+1410/750/1690 690+1410/750/1690
1515/850/1858+1515/850/1 1515/850/1858+1515/850/1
Outdoor unit Packing(W*D*H) mm
858+1515/850/1858 858+1515/850/1858
Net weight kg 385+385+385 385+385+385
Gross weight kg 410+410+410 410+410+410
Type R410A R410A
Refrigerant
Charged volume kg 30 30
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
65
Model AV72NMVETA AV74NMVETA
Liquid pipe mm 22.2 22.2
Gas pipe mm 44.5 44.5
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 64 64
Max. fuse current A 189.00 189.00
Connection Min. wiring current A 147.30 154.00
wiring Power wiring mm2 25+25+25 25+25+25
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
66
Model AV76NMVETA AV78NMVETA
HP 76 78
Combination 24+26+26 26+26+26
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 215.0 220.5
Rated capacity kBtu/h 733.61 752.38
Rated power input kW 61.10 63.74
Max. power input kW 103.51 106.05
Cooling
Rated current A 103.15 107.60
Max. current A 171.84 176.57
EER 3.52 3.46
AEER 6.85 6.79
Rated capacity kw 215.0 220.5
Rated capacity kBtu/h 733.61 752.38
Rated power input kW 62.11 64.87
Max. power input kW 95.30 97.35
Heating
Rated current A 108.00 112.80
Max. current A 158.67 162.09
COP 3.46 3.39
ACOP 4.01 3.88
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
ANB66FZXMT*2+ANB78FZX ANB78FZXMT*2+ANB78FZX
Model
MT*2+ANB78FZXMT*2 MT*2+ANB78FZXMT*2
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 6INV 6INV
Capacity W 21300*2+25200*2+25200*2 25200*2+25200*2+25200*2
Power Input W 6600*2+7700*2+7700*2 7700*2+7700*2+7700*2
Compressor
Rated current(RLA) A 21.5*2+26*2+26*2 26*2+26*2+26*2
Speed rps 60 60
Crankcase Heater W 132+132+132 132+132+132
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
(2300+1500)*2+(2300+1500)* (2300+1500)*2+(2300+1500)*
Refrigerant oil charge ml
2+(2300+1500)*2 2+(2300+1500)*2
Brand BROAD-OCEAN BROAD-OCEAN
(ZWK924D500002 (ZWK924D500002
Model
+ZWK924D500002)*3 +ZWK924D500002)*3
Voltage DC540V DC540V
IP Class IP44 IP44
Type/quantity DC/2+DC/2+DC/2 DC/2+DC/2+DC/2
Outdoor fan
Insulation class B B
motor
Safe class I I
Power Input W 2320+2320+2320 2320+2320+2320
Output W 1800+1800+1800 1800+1800+1800
Rated current A 8+8+8 8+8+8
Caoacitor μF / /
Speed rpm 0~1180 0~1180
67
Model AV76NMVETA AV78NMVETA
Brand Tian Da+Tian Da+Tian Da Tian Da+Tian Da+Tian Da
Model / /
Material ABS+20%GF ABS+20%GF
Outdoor fan
Type Axial Axial
Diameter mm Φ642+Φ642+Φ642+Φ642 Φ642+Φ642+Φ642+Φ642
Height mm 198+198+198 198+198+198
Mumber of rows 3+3+3 3+3+3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) Hydrophilic aluminum Hydrophilic aluminum
Fin coating Type Optional Clear Iacquer Clear Iacquer
Salt Spray Test Duration Hour 168 168
Outdoor coil INNERGROOVE TUBE INNERGROOVE TUBE
Tube outside dia.and type mm
Φ7 Φ7
(2843*1260+2757*1260 (2843*1260+2757*1260
+2669*1260)+(2843*1260+ +2669*1260)+(2843*1260+
Coil length x height mm 2757*1260+2669*1260) 2757*1260+2669*1260)
+(2843*1260+2757*1260 +(2843*1260+2757*1260
+2669*1260) +2669*1260)
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 56000 57000
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 95 95
1410/750/1690+1410/750/1 1410/750/1690+1410/750/1
Diamension(W*D*H) mm
690+1410/750/1690 690+1410/750/1690
1515/850/1858+1515/850/1 1515/850/1858+1515/850/1
Outdoor unit Packing(W*D*H) mm
858+1515/850/1858 858+1515/850/1858
Net weight kg 385+385+385 385+385+385
Gross weight kg 410+410+410 410+410+410
Type R410A R410A
Refrigerant
Charged volume kg 30 30
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
68
Model AV76NMVETA AV78NMVETA
Liquid pipe mm 22.2 22.2
Gas pipe mm 44.5 44.5
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 64 64
Max. fuse current A 189.00 189.00
Connection Min. wiring current A 160.70 167.40
wiring Power wiring mm2 25+25+25 25+25+25
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
69
Model AV80NMVETA AV82NMVETA
HP 80 82
Combination 20+20+20+20 20+20+20+22
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 224.0 229.5
Rated capacity kBtu/h 764.32 783.09
Rated power input kW 66.47 68.16
Max. power input kW 115.64 118.55
Cooling
Rated current A 112.21 115.06
Max. current A 185.20 190.81
EER 3.37 3.37
AEER 6.82 6.76
Rated capacity kw 224.0 229.5
Rated capacity kBtu/h 764.32 783.09
Rated power input kW 56.93 58.84
Max. power input kW 98.80 99.79
Heating
Rated current A 98.99 102.31
Max. current A 164.50 166.15
COP 3.93 3.90
ACOP 4.38 4.38
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
ANB52FZJMT*2+ANB52FZJMT*2 ANB52FZJMT*2+ANB52FZJMT*2
Model
+ANB52FZJMT*2+ANB52FZJMT*2 +ANB52FZJMT*2+ANB66FZXMT*2
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 8INV 8INV
16800*2+16800*2 16800*2+16800*2
Capacity W
+16800*2+16800*2 +16800*2+21300*2
5250*2+5250*2 5250*2+5250*2
Compressor Power Input W
+5250*2+5250*2 +5250*2+6600*2
Rated current(RLA) A 16.5*2+16.5*2+16.5*2+16.5*2 16.5*2+16.5*2+16.5*2+21.5*2
Speed rps 60 60
Crankcase Heater W 132+132+132+132 132+132+132+132
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
(2300+1500)*2+(2300+1500)*2 (2300+1500)*2+(23 00+1500)*2
Refrigerant oil charge ml
+(2300+1500)*2+(2300+1500)*2 +(2300+1500)*2+(2300+1500)*2
Brand BROAD-OCEAN BROAD-OCEAN
(ZWK924D500002 (ZWK924D500002
Model
+ZWK924D500002)*4 +ZWK924D500002)*4
Voltage DC540V DC540V
IP Class IP44 IP44
Type/quantity DC/2+DC/2+DC/2+DC/2 DC/2+DC/2+DC/2+DC/2
Outdoor fan
Insulation class B B
motor
Safe class I I
Power Input W 2320+2320+2320+2320 2320+2320+2320+2320
Output W 1800+1800+1800+1800 1800+1800+1800+1800
Rated current A 8+8+8+8 8+8+8+8
Caoacitor μF / /
Speed rpm 0~1180 0~1180
70
Model AV80NMVETA AV82NMVETA
Tian Da+Tian Da+Tian Tian Da+Tian Da+Tian
Brand
Da+Tian Da Da+Tian Da
Model / /
Outdoor fan Material ABS+20%GF ABS+20%GF
Type Axial Axial
Diameter mm Φ642+Φ642+Φ642+Φ642 Φ642+Φ642+Φ642+Φ642
Height mm 198+198+198+198 198+198+198+198
Mumber of rows 3+3+3+3 3+3+3+3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) Hydrophilic aluminum 21×18.186
Fin coating Type Optional Clear Iacquer 1.6
Salt Spray Test Duration Hour 168 168
INNERGROOVE TUBE INNERGROOVE TUBE
Outdoor coil Tube outside dia.and type mm
Φ7 Φ7
(2843*1260+2757*1260 (2843*1260+2757*1260
+2669*1260)+(2843*1260+ +2669*1260)+(2843*1260+
2757*1260+2669*1260) 2757*1260+2669*1260)
Coil length x height mm
+(2843*1260+2757*1260 +(2843*1260+2757*1260
+2669*1260)+(2843*1260+ +2669*1260)+(2843*1260+
2757*1260+2669*1260) 2757*1260+2669*1260)
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 68000 69000
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 94 95
1410/750/1690+1410/750/1 1410/750/1690+1410/750/1
Diamension(W*D*H) mm 690+1410/750/1690+1410/ 690+1410/750/1690+1410/
750/1690 750/1690
1515/850/1858+1515/850/1 1515/850/1858+1515/850/1
Outdoor unit
Packing(W*D*H) mm 858+1515/850/1858+1515/ 858+1515/850/1858+1515/
850/1858 850/1858
Net weight kg 385+385+385+385 385+385+385+385
Gross weight kg 410+410+410+410 410+410+410+410
Type R410A R410A
Refrigerant
Charged volume kg 40 40
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
71
Model AV80NMVETA AV82NMVETA
Liquid pipe mm 22.2 22.2
Gas pipe mm 44.5 44.5
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 64 64
Max. fuse current A 200.00 213.00
Connection Min. wiring current A 169.60 175.30
wiring Power wiring mm2 16+16+16+16 16+16+16+16
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
72
Model AV84NMVETA AV86NMVETA
HP 84 86
Combination 20+20+22+22 20+22+22+22
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 235.0 240.5
Rated capacity kBtu/h 801.85 820.62
Rated power input kW 69.84 71.53
Max. power input kW 121.46 124.37
Cooling
Rated current A 117.91 120.75
Max. current A 196.42 202.03
EER 3.36 3.36
AEER 6.71 6.65
Rated capacity kw 235.0 240.5
Rated capacity kBtu/h 801.85 820.62
Rated power input kW 60.74 62.65
Max. power input kW 100.78 101.78
Heating
Rated current A 105.62 108.93
Max. current A 167.81 169.46
COP 3.86 3.83
ACOP 4.38 4.39
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
ANB52FZJMT*2+ANB52FZJMT*2+ ANB52FZJMT*2+ANB66FZXMT*2+A
Model
ANB66FZXMT*2+ANB66FZXMT*2 NB66FZXMT*2+ANB66FZXMT*2
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 8INV 8INV
16800*2+16800*2 16800*2+21300*2
Capacity W
+21300*2+21300*2 +21300*2+21300*2
5250*2+5250*2 5250*2+6600*2
Compressor Power Input W
+6600*2+6600*2 +6600*2+6600*2
Rated current(RLA) A 16.5*2+16.5*2+21.5*2+21.5*2 16.5*2+21.5*2+21.5*2+21.5*2
Speed rps 60 60
Crankcase Heater W 132+132+132+132 132+132+132+132
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
(2300+1500)*2+(2300+1500)*2+(23 (2300+1500)*2+(2300+1500)*2+(23
Refrigerant oil charge ml
00+1500)*2+(2300+1500)*2 00+1500)*2+(2300+1500)*2
Brand BROAD-OCEAN BROAD-OCEAN
(ZWK924D500002 (ZWK924D500002
Model
+ZWK924D500002)*4 +ZWK924D500002)*4
Voltage DC540V DC540V
IP Class IP44 IP44
Type/quantity DC/2+DC/2+DC/2+DC/2 DC/2+DC/2+DC/2+DC/2
Outdoor fan
Insulation class B B
motor
Safe class I I
Power Input W 2320+2320+2320+2320 2320+2320+2320+2320
Output W 1800+1800+1800+1800 1800+1800+1800+1800
Rated current A 8+8+8+8 8+8+8+8
Caoacitor μF / /
Speed rpm 0~1180 0~1180
73
Model AV84NMVETA AV86NMVETA
Tian Da+Tian Da+Tian Tian Da+Tian Da+Tian
Brand
Da+Tian Da Da+Tian Da
Model / /
Outdoor fan Material ABS+20%GF ABS+20%GF
Type Axial Axial
Diameter mm Φ642+Φ642+Φ642+Φ642 Φ642+Φ642+Φ642+Φ642
Height mm 198+198+198+198 198+198+198+198
Mumber of rows 3+3+3+3 3+3+3+3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) 21×18.186 21×18.186
Fin coating Type Optional 1.6 1.6
Salt Spray Test Duration Hour 168 168
INNERGROOVE TUBE INNERGROOVE TUBE
Outdoor coil Tube outside dia.and type mm
Φ7 Φ7
(2843*1260+2757*1260 (2843*1260+2757*1260
+2669*1260)+(2843*1260 +2669*1260)+(2843*1260
+2757*1260+2669*1260) +2757*1260+2669*1260)
Coil length x height mm
+(2843*1260+2757*1260 +(2843*1260+2757*1260
+2669*1260)+(2843*1260 +2669*1260)+(2843*1260
+2757*1260+2669*1260) +2757*1260+2669*1260)
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 70000 71000
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 95 96
1410/750/1690+1410/750/1 1410/750/1690+1410/750/1
Diamension(W*D*H) mm 690+1410/750/1690+1410/ 690+1410/750/1690+1410/
750/1690 750/1690
1515/850/1858+1515/850/1 1515/850/1858+1515/850/1
Outdoor unit
Packing(W*D*H) mm 858+1515/850/1858+1515/ 858+1515/850/1858+1515/
850/1858 850/1858
Net weight kg 385+385+385+385 385+385+385+385
Gross weight kg 410+410+410+410 410+410+410+410
Type R410A R410A
Refrigerant
Charged volume kg 40 40
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
74
Model AV84NMVETA AV86NMVETA
Liquid pipe mm 22.2 25.4
Gas pipe mm 44.5 50.8
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 64 64
Max. fuse current A 226.00 239.00
Connection Min. wiring current A 181.00 186.70
wiring Power wiring mm2 16+16+16+16 16+16+16+16
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
75
Model AV88NMVETA AV90NMVETA
HP 88 90
Combination 22+22+22+22 22+22+22+24
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 246.0 252.5
Rated capacity kBtu/h 839.39 861.57
Rated power input kW 73.21 73.52
Max. power input kW 127.28 128.27
Cooling
Rated current A 123.60 124.12
Max. current A 207.64 209.85
EER 3.36 3.43
AEER 6.61 6.70
Rated capacity kw 246.0 252.5
Rated capacity kBtu/h 839.39 861.57
Rated power input kW 64.55 67.28
Max. power input kW 102.77 107.48
Heating
Rated current A 112.24 116.98
Max. current A 171.11 178.95
COP 3.81 3.75
ACOP 4.39 4.38
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
ANB66FZXMT*2+ANB66FZXMT*2+ ANB66FZXMT*2+ANB66FZXMT*2+
Model
ANB66FZXMT*2+ANB66FZXMT*2 ANB66FZXMT*2+ANB66FZXMT*2
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 8INV 8INV
21300*2+21300*2 21300*2+21300*2
Capacity W
+21300*2+21300*2 +21300*2+21300*2
6600*2+6600*2 6600*2+6600*2
Compressor Power Input W
+6600*2+6600*2 +6600*2+6600*2
Rated current(RLA) A 21.5*2+21.5*2+21.5*2+21.5*2 21.5*2+21.5*2+21.5*2+21.5*2
Speed rps 60 60
Crankcase Heater W 132+132+132+132 132+132+132+132
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
(2300+1500)*2+(2300+1500)*2+(23 (2300+1500)*2+(2300+1500)*2
Refrigerant oil charge ml
00+1500)*2+(2300+1500)*2 +(2300+1500)*2+(2300+1500)*2
Brand BROAD-OCEAN BROAD-OCEAN
(ZWK924D500002 (ZWK924D500002
Model
+ZWK924D500002)*4 +ZWK924D500002)*4
Voltage DC540V DC540V
IP Class IP44 IP44
Type/quantity DC/2+DC/2+DC/2+DC/2 DC/2+DC/2+DC/2+DC/2
Outdoor fan
Insulation class B B
motor
Safe class I I
Power Input W 2320+2320+2320+2320 2320+2320+2320+2320
Output W 1800+1800+1800+1800 1800+1800+1800+1800
Rated current A 8+8+8+8 8+8+8+8
Caoacitor μF / /
Speed rpm 0~1180 0~1180
76
Model AV88NMVETA AV90NMVETA
Tian Da+Tian Da+Tian Tian Da+Tian Da+Tian
Brand
Da+Tian Da Da+Tian Da
Model / /
Outdoor fan Material ABS+20%GF ABS+20%GF
Type Axial Axial
Diameter mm Φ642+Φ642+Φ642+Φ642 Φ642+Φ642+Φ642+Φ642
Height mm 198+198+198+198 198+198+198+198
Mumber of rows 3+3+3+3 3+3+3+3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) 21×18.186 21×18.186
Fin coating Type Optional 1.6 1.6
Salt Spray Test Duration Hour 168 168
INNERGROOVE TUBE INNERGROOVE TUBE
Outdoor coil Tube outside dia.and type mm
Φ7 Φ7
(2843*1260+2757*1260 (2843*1260+2757*1260
+2669*1260)+(2843*1260 +2669*1260)+(2843*1260
+2757*1260+2669*1260) +2757*1260+2669*1260)
Coil length x height mm
+(2843*1260+2757*1260 +(2843*1260+2757*1260
+2669*1260)+(2843*1260 +2669*1260)+(2843*1260
+2757*1260+2669*1260) +2757*1260+2669*1260)
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 72000 72000
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 96 96
1410/750/1690+1410/750/1 1410/750/1690+1410/750/1
Diamension(W*D*H) mm 690+1410/750/1690+1410/ 690+1410/750/1690+1410/
750/1690 750/1690
1515/850/1858+1515/850/1 1515/850/1858+1515/850/1
Outdoor unit
Packing(W*D*H) mm 858+1515/850/1858+1515/ 858+1515/850/1858+1515/
850/1858 850/1858
Net weight kg 385+385+385+385 385+385+385+385
Gross weight kg 410+410+410+410 410+410+410+410
Type R410A R410A
Refrigerant
Charged volume kg 80 80
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
77
Model AV88NMVETA AV90NMVETA
Liquid pipe mm 25.4 25.4
Gas pipe mm 50.8 50.8
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 64 64
Max. fuse current A 252.00 252.00
Connection Min. wiring current A 192.40 193.40
wiring Power wiring mm2 16+16+16+16 16+16+16+25
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
78
Model AV92NMVETA AV94NMVETA
HP 92 94
Combination 22+22+24+24 22+24+24+24
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 259.0 265.5
Rated capacity kBtu/h 883.74 905.92
Rated power input kW 73.83 74.14
Max. power input kW 129.26 130.25
Cooling
Rated current A 124.64 125.16
Max. current A 212.06 214.27
EER 3.51 3.58
AEER 6.80 6.90
Rated capacity kw 259.0 265.5
Rated capacity kBtu/h 883.74 905.92
Rated power input kW 70.00 72.73
Max. power input kW 112.18 116.89
Heating
Rated current A 121.72 126.46
Max. current A 186.79 194.63
COP 3.69 3.65
ACOP 4.36 4.35
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
ANB66FZXMT*2+ANB66FZXMT*2+ ANB66FZXMT*2+ANB66FZXMT*2
Model
ANB66FZXMT*2+ANB66FZXMT*2 +ANB66FZXMT*2+ANB66FZXMT*2
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 8INV 8INV
21300*2+21300*2 21300*2+21300*2
Capacity W
+21300*2+21300*2 +21300*2+21300*2
6600*2+6600*2 6600*2+6600*2
Compressor Power Input W
+6600*2+6600*2 +6600*2+6600*2
Rated current(RLA) A 21.5*2+21.5*2+21.5*2+21.5*2 21.5*2+21.5*2+21.5*2+21.5*2
Speed rps 60 60
Crankcase Heater W 132+132+132+132 132+132+132+132
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
(2300+1500)*2+(2300+1500)*2 (2300+1500)*2+(2300+1500)*2
Refrigerant oil charge ml
+(2300+1500)*2+(2300+1500)*2 +(2300+1500)*2+(2300+1500)*2
Brand BROAD-OCEAN BROAD-OCEAN
(ZWK924D500002 (ZWK924D500002
Model
+ZWK924D500002)*4 +ZWK924D500002)*4
Voltage DC540V DC540V
IP Class IP44 IP44
Type/quantity DC/2+DC/2+DC/2+DC/2 DC/2+DC/2+DC/2+DC/2
Outdoor fan
Insulation class B B
motor
Safe class I I
Power Input W 2320+2320+2320+2320 2320+2320+2320+2320
Output W 1800+1800+1800+1800 1800+1800+1800+1800
Rated current A 8+8+8+8 8+8+8+8
Caoacitor μF / /
Speed rpm 0~1180 0~1180
79
Model AV92NMVETA AV94NMVETA
Tian Da+Tian Da+Tian Tian Da+Tian Da+Tian
Brand
Da+Tian Da Da+Tian Da
Model / /
Outdoor fan Material ABS+20%GF ABS+20%GF
Type Axial Axial
Diameter mm Φ642+Φ642+Φ642+Φ642 Φ642+Φ642+Φ642+Φ642
Height mm 198+198+198+198 198+198+198+198
Mumber of rows 3+3+3+3 3+3+3+3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) 21×18.186 21×18.186
Fin coating Type Optional 1.6 1.6
Salt Spray Test Duration Hour 168 168
INNERGROOVE TUBE INNERGROOVE TUBE
Outdoor coil Tube outside dia.and type mm
Φ7 Φ7
(2843*1260+2757*1260 (2843*1260+2757*1260
+2669*1260)+(2843*1260 +2669*1260)+(2843*1260
+2757*1260+2669*1260) +2757*1260+2669*1260)
Coil length x height mm
+(2843*1260+2757*1260 +(2843*1260+2757*1260
+2669*1260)+(2843*1260 +2669*1260)+(2843*1260
+2757*1260+2669*1260) +2757*1260+2669*1260)
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 72000 72000
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 96 96
1410/750/1690+1410/750/1 1410/750/1690+1410/750/1
Diamension(W*D*H) mm 690+1410/750/1690+1410/ 690+1410/750/1690+1410/
750/1690 750/1690
1515/850/1858+1515/850/1 1515/850/1858+1515/850/1
Outdoor unit
Packing(W*D*H) mm 858+1515/850/1858+1515/ 858+1515/850/1858+1515/
850/1858 850/1858
Net weight kg 385+385+385+385 385+385+385+385
Gross weight kg 410+410+410+410 410+410+410+410
Type R410A R410A
Refrigerant
Charged volume kg 80 80
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
80
Model AV92NMVETA AV94NMVETA
Liquid pipe mm 25.4 25.4
Gas pipe mm 50.8 50.8
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 64 64
Max. fuse current A 252.00 252.00
Connection Min. wiring current A 194.40 195.40
wiring Power wiring mm2 16+16+25+25 16+25+25+25
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
81
Model AV96NMVETA AV98NMVETA
HP 96 98
Combination 24+24+24+24 24+24+24+26
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 272.0 277.5
Rated capacity kBtu/h 928.10 946.87
Rated power input kW 74.44 77.08
Max. power input kW 131.24 133.78
Cooling
Rated current A 125.68 130.13
Max. current A 216.48 221.22
EER 3.65 3.60
AEER 6.99 6.94
Rated capacity kw 272.0 277.5
Rated capacity kBtu/h 928.10 946.87
Rated power input kW 75.45 78.21
Max. power input kW 121.60 123.65
Heating
Rated current A 131.20 136.00
Max. current A 202.46 205.88
COP 3.60 3.54
ACOP 4.34 4.20
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
ANB66FZXMT*2+ANB66FZXMT*2 ANB66FZXMT*2+ANB66FZXMT*2
Model
+ANB66FZXMT*2+ANB66FZXMT*2 +ANB66FZXMT*2+ANB78FZXMT*2
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 8INV 8INV
21300*2+21300*2 21300*2+21300*2
Capacity W
+21300*2+21300*2 +21300*2+25200*2
Compressor Power Input W 6600*2+6600*2+6600*2+6600*2 6600*2+6600*2+6600*2+7700*2
Rated current(RLA) A 21.5*2+21.5*2+21.5*2+21.5*2 21.5*2+21.5*2+21.5*2+26*2
Speed rps 60 60
Crankcase Heater W 132+132+132+132 132+132+132+132
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
(2300+1500)*2+(2300+1500)*2 (2300+1500)*2+(2300+1500)*2
Refrigerant oil charge ml
+(2300+1500)*2+(2300+1500)*2 +(2300+1500)*2+(2300+1500)*2
Brand BROAD-OCEAN BROAD-OCEAN
(ZWK924D500002 (ZWK924D500002
Model
+ZWK924D500002)*4 +ZWK924D500002)*4
Voltage DC540V DC540V
IP Class IP44 IP44
Type/quantity DC/2+DC/2+DC/2+DC/2 DC/2+DC/2+DC/2+DC/2
Outdoor fan
Insulation class B B
motor
Safe class I I
Power Input W 2320+2320+2320+2320 2320+2320+2320+2320
Output W 1800+1800+1800+1800 1800+1800+1800+1800
Rated current A 8+8+8+8 8+8+8+8
Caoacitor μF / /
Speed rpm 0~1180 0~1180
82
Model AV96NMVETA AV98NMVETA
Tian Da+Tian Da+Tian Tian Da+Tian Da+Tian
Brand
Da+Tian Da Da+Tian Da
Model / /
Outdoor fan Material ABS+20%GF ABS+20%GF
Type Axial Axial
Diameter mm Φ642+Φ642+Φ642+Φ642 Φ642+Φ642+Φ642+Φ642
Height mm 198+198+198+198 198+198+198+198
Mumber of rows 3+3+3+3 3+3+3+3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) 21×18.186 21×18.186
Fin coating Type Optional 1.6 1.6
Salt Spray Test Duration Hour 168 168
INNERGROOVE TUBE INNERGROOVE TUBE
Outdoor coil Tube outside dia.and type mm
Φ7 Φ7
(2843*1260+2757*1260 (2843*1260+2757*1260
+2669*1260)+(2843*1260 +2669*1260)+(2843*1260
+2757*1260+2669*1260) +2757*1260+2669*1260)
Coil length x height mm
+(2843*1260+2757*1260 +(2843*1260+2757*1260
+2669*1260)+(2843*1260 +2669*1260)+(2843*1260
+2757*1260+2669*1260) +2757*1260+2669*1260)
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 72000 73000
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 96 96
1410/750/1690+1410/750/1 1410/750/1690+1410/750/1
Diamension(W*D*H) mm 690+1410/750/1690+1410/ 690+1410/750/1690+1410/
750/1690 750/1690
1515/850/1858+1515/850/1 1515/850/1858+1515/850/1
Outdoor unit
Packing(W*D*H) mm 858+1515/850/1858+1515/ 858+1515/850/1858+1515/
850/1858 850/1858
Net weight kg 385+385+385+385 385+385+385+385
Gross weight kg 410+410+410+410 410+410+410+410
Type R410A R410A
Refrigerant
Charged volume kg 80 80
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
83
Model AV96NMVETA AV98NMVETA
Liquid pipe mm 25.4 25.4
Gas pipe mm 50.8 54.1
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 64 64
Max. fuse current A 252.00 252.00
Connection Min. wiring current A 196.40 203.10
wiring Power wiring mm2 25+25+25+25 25+25+25+25
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
84
Model AV100NMVETA AV102NMVETA
HP 100 102
Combination 24+24+26+26 24+26+26+26
Power supply Ph/V/Hz 3/380~415/50/60 3/380~415/50/60
Rated capacity kW 283.0 288.5
Rated capacity kBtu/h 965.64 984.40
Rated power input kW 79.71 82.35
Max. power input kW 136.32 138.86
Cooling
Rated current A 134.57 139.02
Max. current A 225.96 230.69
EER 3.55 3.50
AEER 6.89 6.84
Rated capacity kw 283.0 288.5
Rated capacity kBtu/h 965.64 984.40
Rated power input kW 80.97 83.73
Max. power input kW 125.70 127.75
Heating
Rated current A 140.80 145.60
Max. current A 209.29 212.70
COP 3.49 3.44
ACOP 4.08 3.98
MITSUBISHI MITSUBISHI
Brand
ELECTRIC ELECTRIC
ANB66FZXMT*2+ANB66FZXMT*2+ ANB66FZXMT*2+ANB78FZXMT*2+
Model
ANB78FZXMT*2+ANB78FZXMT*2 ANB78FZXMT*2+ANB78FZXMT*2
Type DC INV. SCROLL DC INV. SCROLL
Compressor quantity 8INV 8INV
21300*2+21300*2 21300*2+25200*2
Capacity W
+25200*2+25200*2 +25200*2+25200*2
Compressor Power Input W 6600*2+6600*2+7700*2+7700*2 6600*2+7700*2+7700*2+7700*2
Rated current(RLA) A 21.5*2+21.5*2+26*2+26*2 21.5*2+26*2+26*2+26*2
Speed rps 60 60
Crankcase Heater W 132+132+132+132 132+132+132+132
IDEMITSUKOSAN IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD CO.,LTD
Refrigerant oil type FVC68D FVC68D
(2300+1500)*2+(2300+1500)*2 (2300+1500)*2+(2300+1500)*2
Refrigerant oil charge ml
+(2300+1500)*2+(2300+1500)*2 +(2300+1500)*2+(2300+1500)*2
Brand BROAD-OCEAN BROAD-OCEAN
(ZWK924D500002 (ZWK924D500002
Model
+ZWK924D500002)*4 +ZWK924D500002)*4
Voltage DC540V DC540V
IP Class IP44 IP44
Type/quantity DC/2+DC/2+DC/2+DC/2 DC/2+DC/2+DC/2+DC/2
Outdoor fan
Insulation class B B
motor
Safe class I I
Power Input W 2320+2320+2320+2320 2320+2320+2320+2320
Output W 1800+1800+1800+1800 1800+1800+1800+1800
Rated current A 8+8+8+8 8+8+8+8
Caoacitor μF / /
Speed rpm 0~1180 0~1180
85
Model AV100NMVETA AV102NMVETA
Tian Da+Tian Da+Tian Tian Da+Tian Da+Tian
Brand
Da+Tian Da Da+Tian Da
Model / /
Outdoor fan Material ABS+20%GF ABS+20%GF
Type Axial Axial
Diameter mm Φ642+Φ642+Φ642+Φ642 Φ642+Φ642+Φ642+Φ642
Height mm 198+198+198+198 198+198+198+198
Mumber of rows 3+3+3+3 3+3+3+3
Tube pitch(a)x row pitch(b) mm 21×18.186 21×18.186
Fin spacing mm 1.6 1.6
Fin type(code) 21×18.186 21×18.186
Fin coating Type Optional 1.6 1.6
Salt Spray Test Duration Hour 168 168
INNERGROOVE TUBE INNERGROOVE TUBE
Outdoor coil Tube outside dia.and type mm
Φ7 Φ7
(2843*1260+2757*1260 (2843*1260+2757*1260
+2669*1260)+(2843*1260 +2669*1260)+(2843*1260
+2757*1260+2669*1260) +2757*1260+2669*1260)
Coil length x height mm
+(2843*1260+2757*1260 +(2843*1260+2757*1260
+2669*1260)+(2843*1260 +2669*1260)+(2843*1260
+2757*1260+2669*1260) +2757*1260+2669*1260)
Number or circuits 29 29
Coating type Powerr Coating Powerr Coating
Salt Spray Test Duration Hour 72 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 1 1
Control panel enclosure IP class standard IP24 IP24
Outdoor air flow (cooling/heating) m³/h 74000 75000
External static pressure Pa 110 110
Outdoor sound level(sound power level) (H) dB(A) 96 96
1410/750/1690+1410/750/1 1410/750/1690+1410/750/1
Diamension(W*D*H) mm 690+1410/750/1690+1410/ 690+1410/750/1690+1410/
750/1690 750/1690
1515/850/1858+1515/850/1 1515/850/1858+1515/850/1
Outdoor unit
Packing(W*D*H) mm 858+1515/850/1858+1515/ 858+1515/850/1858+1515/
850/1858 850/1858
Net weight kg 385+385+385+385 385+385+385+385
Gross weight kg 410+410+410+410 410+410+410+410
Type R410A R410A
Refrigerant
Charged volume kg 80 80
Throttle type EXV EXV
Design pressure Mpa 4.15 4.15
86
Model AV100NMVETA AV102NMVETA
Liquid pipe mm 25.4 25.4
Gas pipe mm 54.1 54.1
Oil pipe mm / /
Total pipe length m 1000 1000
Max. pipe
m 260/220 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90 110/90
uint*1
Standard Diff. indoor/
m 50/40 50/40
outdoor unit
Max./standard Diff.
m 30/18 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130 50~130
Maximum indoor units Piece 64 64
Max. fuse current A 252.00 252.00
Connection Min. wiring current A 209.80 216.50
wiring Power wiring mm2 25+25+25+25 25+25+25+25
Signal wiring mm2 2×0.75 2×0.75
Cooling:-5~52 Cooling:-5~52
Operation Range ℃
Heating:-27~21 Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
87
Model AV104NMVETA
HP 104
Combination 26+26+26+26
Power supply Ph/V/Hz 3/380~415/50/60
Rated capacity kW 294.0
Rated capacity kBtu/h 1003.17
Rated power input kW 84.98
Max. power input kW 141.40
Cooling
Rated current A 143.47
Max. current A 235.43
EER 3.46
AEER 6.80
Rated capacity kw 294.0
Rated capacity kBtu/h 1003.17
Rated power input kW 86.50
Max. power input kW 129.80
Heating
Rated current A 150.40
Max. current A 216.12
COP 3.39
ACOP 3.88
MITSUBISHI
Brand
ELECTRIC
ANB78FZXMT*2+ANB78FZXMT*2
Model
+ANB78FZXMT*2+ANB78FZXMT*2
Type DC INV. SCROLL
Compressor quantity 8INV
Capacity W 25200*2+25200*2+25200*2+25200*2
Power Input W 7700*2+7700*2+7700*2+7700*2
Compressor
Rated current(RLA) A 26*2+26*2+26*2+26*2
Speed rps 60
Crankcase Heater W 132+132+132+132
IDEMITSUKOSAN
Refrigerant oil brand
CO.,LTD
Refrigerant oil type FVC68D
(2300+1500)*2+(2300+1500)*2
Refrigerant oil charge ml
+(2300+1500)*2+(2300+1500)*2
Brand BROAD-OCEAN
Model (ZWK924D500002+ZWK924D500002)*4
Voltage DC540V
IP Class IP44
Type/quantity DC/2+DC/2+DC/2+DC/2
Outdoor fan Insulation class B
motor Safe class I
Power Input W 2320+2320+2320+2320
Output W 1800+1800+1800+1800
Rated current A 8+8+8+8
Caoacitor μF /
Speed rpm 0~1180
88
Model AV104NMVETA
Brand Tian Da+Tian Da+Tian Da+Tian Da
Model /
Material ABS+20%GF
Outdoor fan
Type Axial
Diameter mm Φ642+Φ642+Φ642+Φ642
Height mm 198+198+198+198
Mumber of rows 3+3+3+3
Tube pitch(a)x row pitch(b) mm 21×18.186
Fin spacing mm 1.6
Fin type(code) 21×18.186
Fin coating Type Optional 1.6
Salt Spray Test Duration Hour 168
Outdoor coil INNERGROOVE TUBE
Tube outside dia.and type mm
Φ7
(2843*1260+2757*1260+2669*1260)
+(2843*1260+2757*1260+2669*1260)
Coil length x height mm
+(2843*1260+2757*1260+2669*1260)
+(2843*1260+2757*1260+2669*1260)
Number or circuits 29
Coating type Powerr Coating
Salt Spray Test Duration Hour 72
Cabinet coating
Sheet Metal Meterial Hot zinc plate
Sheet Metal Thickness mm 1
Control panel enclosure IP class standard IP24
Outdoor air flow (cooling/heating) m³/h 76000
External static pressure Pa 110
Outdoor sound level(sound power level) (H) dB(A) 96
1410/750/1690+1410/750/1690
Diamension(W*D*H) mm
+1410/750/1690+1410/750/1690
1515/850/1858+1515/850/1858
Outdoor unit Packing(W*D*H) mm
+1515/850/1858+1515/850/1858
Net weight kg 385+385+385+385
Gross weight kg 410+410+410+410
Type R410A
Refrigerant
Charged volume kg 80
Throttle type EXV
Design pressure Mpa 4.15
89
Model AV104NMVETA
Liquid pipe mm 25.4
Gas pipe mm 54.1
Oil pipe mm /
Total pipe length m 1000
Max. pipe
m 260/220
Frigerant length(Equivalent/Actual)
piping Max. Diff. indoor/outdoor
m 110/90
uint*1
Standard Diff. indoor/
m 50/40
outdoor unit
Max./standard Diff.
m 30/18
indoor/indoor unit*1
Connectable indoor unit ratio % 50~130
Maximum indoor units Piece 64
Max. fuse current A 252.00
Connection Min. wiring current A 223.20
wiring Power wiring mm2 25+25+25+25
Signal wiring mm2 2×0.75
Cooling:-5~52
Operation Range ℃
Heating:-27~21
Nominal condition: indoor temperature (cooling): 27℃ DB/19℃ WB, indoor temperature (heating):
20℃ DB/14.5℃ WB.
Outdoor temperature(cooling): 35℃ DB/24℃ WB, outdoor temperature(heating): 7℃ DB/6℃ WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is
from 50 to 110m or the height difference between the indoor units is from 18 to 30m, you Must contact your local
distributor/dealer for individual design and production.
90
4. Dimension
AV08/10/12/14/16NMVETA
91
AV18/20/22/24/26NMVETA
92
5. Center of gravity
AV08/10/12/14/16NMVETA
Coordinate position (x, y, z: 471, 375, 725)
93
AV18/20/22/24/26NMVETA
94
6. Piping diagram
AV08/10/12/14/16NMVETA
95
AV18/20/22/24/26NMVETA
96
Part name Sign Function Data Remark
ANB52FZJMT: 0.31Ω
Capacity control, to meet indoor load through
Compressor / ANB66FZXMT: 0.23Ω 20°C
frequency adjustment.
ANB78FZXMT: 0.23Ω
Pressure switch HPS1/i Protection control for high pressure. 4.15Mpa, OFF setting
In heating, compressor frequency adjustment
PD 0~4.15MPa.
and protection control for abnormal pressure.
Pressure sensor
In cooling, compressor frequency adjustment
PS 0~1.7MPa.
and protection control for abnormal pressure.
Electronic expansion
LEVA1, 2 Refrigerant flow control in heating. HAM-BD30SM-2
valve
1. Balance between high and low pressures
when the compressor starts and stops;
SV1 AC220V 2A
2. Protection to prevent high and low
pressures.
Started when the compressor discharging
temperature and oil temperature are too
SV3 AC220V 6A
high to carry out temperature reduction by
refrigerant spraying.
In the heating mode, the high pressure side
SV4 refrigerant is bypassed to the condenser for AC220V 6A
Solenoid valve frosting
SV5 AC220V 6A
SV7 Enhanced vapor injection of compressor 1 AC220V 6A
SV8 Enhanced vapor injection of compressor 2 AC220V 6A
Outdoor unit SV10 for oil suction starts
SV10 during oil balance; for pressure relief to AC220V 2A
prevent explosion of pipe group.
The outdoor unit for oil discharging starts
SV9 SV9 for oil balancing during oil balance AC220V 2A
among modules.
AC220V Power on
during heating and
Four-way valve 4WV Switch between cooling and heating.
power off during
cooling or defrosting.
To detect the temperature of refrigeration
Toil1/2
lubricant at the compressor bottom. R (80°C) - 50K
To detect the top temperature of inverter/ON- B (25/80°C)=4450K
Td1/Td2
OFF compressor.
To detect the frosting of outdoor heat
Tdef1/Tdef2
exchanger.
To detect the temperature of condenser main
Toci1
gas pipe to control LEVa1, 2 during heating.
Temperature sensor
Tliqsc/Tsco Detect SH temp. of subcooler
R(25°C)=10K,
B(25°C/50°C) =3700K
Tsci Detect SH temp. of LEVb outlet
To detect the inlet temperature of gas-liquid
Tsacc
segregator.
To detect ambient temperature and control
Tao
the initial air speed and defrosting conditions.
Used to heat the compressor oil in the 33W, 220V, 2 pieces/
Heater HEAT1/2
inverter compressor. compressor.
97
7. Refrigerant flow
Cooling operation
98
Heating operation
99
8. Functional parts layout
AV08/10/12/14/16NMVETA
100
AV18/20/22/24/26NMVETA
101
Electric control box assy. parts layout
AV08/10/12/14/16/18NMVETA
AV20/22/24/26NMVETA
102
9. Wiring diagram
103
104
Description of the main board port definition
No. Port Port description
1 L/N/G AC Power input
2 SV3 Liquid jetting to compressor
3 SV10 Drain the oil from compressor 2
4 SV9 Drain the oil from compressor 1
5 SV1 Balance pressure(Load-OFF)
6 4WV Hot and cold switching
7 HEAT1 Heating band of compressor 1
8 HEAT2 Heating band of compressor 2
9 HPS2 High Pressure Switch of Compressor 2
10 HPS1 High Pressure Switch of Compressor 1
11 PS Low pressure sensor
12 PD High pressure sensor
13 Td1 Compressor 1 exhaust temperature
14 Td2 Compressor 2 exhaust temperature
15 Tdef1 Detect the defrosting temp
16 Tao Ambient temperature
17 Toil2 Detect the oil temp. of compressor 2
18 Toil1 Detect the oil temp. of compressor 1
19 Toci1/Ts Detect SH temp. in heating
20 LEVA1 SH control in heating
21 LEVA2 SH control in heating
22 DC12V Output DC12V
23 BT Output DC5V/Conmunication
24 P/Q Indoor unit and outdoor unit com. port
25 ABC Outdoor and outdoor com. port
26 BUS-B BUS-A Centralized control port
27 STOP Emergency stop switch
28 ZIGBEE Wireless module com. port
29 INV-COM INV module com. port
30 Low Power Low standby power consumption
31 BM1 Outdoor and indoor searching Outdoor address setting
32 BM2 Wireless communication
33 BM3 HP setting of outdoor units
34 BM4 Set the control address
35 SW4/5/6/7 Special function control keys
36 DC12V Input DC12V
37 L/N AC Power Input
38 SV4 Continuous heating
39 SV5 Continuous heating
40 SV7 Enhanced vapor injection of compressor 1
41 SV8 Enhanced vapor injection of compressor 2
42 Toci2 Detect SH temp. in heating
43 Tdef2 Detect the defrosting temp
44 Tx Rx Input DC5V/Communication
45 Tliqsc/Tsco Detect SH temp. of subcooler
46 LEVB Control subcooler
105
10. Capacity calculation due to capacity modification coefficient
1.2
Capacity modification coefficient
1.1
1.1 1.0
0.9
1.0
0.8
0.9
0.7
0.8 0.6
15 20 24
0.5
-5 0 5 10 15 20 25 30 35 40 45 50
Indoor air wet-bulb temperature ●
1.1 100
80
1.0
60
0.9
80 90 100 110 120 40
Standard capacity
0
●
20 40 60 80 100 120 135
Total capacity of indoor units(%)
●
106
E: Capacity compensation value at different piping length and drop
Cooling compensation factor
AV10NMVETA
0.90 0.90
Liquid pipe: φ9.52 Liquid pipe:φ9.52
0.85 Gas pipe:φ19.05 0.85 Gas pipe:φ22.22
0.80 0.80
0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 20 40 60 80 100 120 140 160 180 200 220 240 260
Pipe length of single way (m) Pipe length of single way (m)
AV12NMVETA AV14NMVETA
Cooling compensation factor
0.90 0.90
Liquid pipe:φ12.7 Liquid pipe:φ12.7
0.85 Gas pipe:φ25.4 0.85 Gas pipe:φ25.4
0.80 0.80
0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 20 40 60 80 100 120 140 160 180 200 220 240 260
Pipe length of single way (m) Pipe length of single way (m)
Cooling compensation factor
AV16NMVETA
AV16IMVEVA AV18NMVETA
AV18IMVEVA
1.00 1.00
Liquid pipe:φ15.88 Liquid pipe:φ19.05
0.95 Gas pipe:φ31.8 0.95 Gas pipe:φ31.8
0.90 0.90
Liquid pipe:φ12.7 Liquid pipe:φ15.88
0.85 Gas pipe:φ28.58 0.85 Gas pipe:φ28.58
0.80 0.80
0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 20 40 60 80 100 120 140 160 180 200 220 240 260
Pipe length of single way (m) Pipe length of single way (m)
AV20NMVETA AV22NMVETA
Cooling compensation factor
AV20IMVEVA AV22IMVEVA
1.00 1.00
Liquid pipe:φ19.05 Liquid pipe:φ19.05
0.95 Gas pipe:φ31.8 0.95 Gas pipe:φ31.8
0.90 0.90
Liquid pipe:φ15.88 Liquid pipe:φ15.88
0.85 Gas pipe:φ28.58 0.85 Gas pipe:φ28.58
0.80 0.80
0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 20 40 60 80 100 120 140 160 180 200 220 240 260
Pipe length of single way (m) Pipe length of single way (m)
AV24NMVETA AV26NMVETA
Cooling compensation factor
AV24IMVEVA
Cooling compensation factor
AV26IMVEVA
1.00 1.00
Liquid pipe:φ19.05 Liquid pipe:φ19.05
0.95 Gas pipe:φ31.8 0.95 Gas pipe:φ31.8
0.90 0.90
Liquid pipe:φ15.88 Liquid pipe:φ15.88
0.85 Gas pipe:φ28.58 0.85 Gas pipe:φ28.58
0.80 0.80
0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 20 40 60 80 100 120 140 160 180 200 220 240 260
Pipe length of single way (m)
Pipe length of single way (m)
107
Cooling compensation factor
Cooling compensation factor
AV28NMVETA
AV28IMVEVA AV30NMVETA
AV30IMVEVA
1.00 1.00
Liquid pipe:φ19.05 Liquid pipe:φ22.22
0.95 Gas pipe:φ31.8 0.95 Gas pipe:φ38.1
0.90 0.90
Liquid pipe:φ15.88 Liquid pipe:φ19.05
0.85 Gas pipe:φ28.58 0.85 Gas pipe:φ31.8
0.80 0.80
0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 20 40 60 80 100 120 140 160 180 200 220 240 260
Pipe length of single way (m) Pipe length of single way (m)
AV32NMVETA
AV32IMVEVA AV34NMVETA
AV34IMVEVA
1.00 1.00
Liquid pipe:φ22.22 Liquid pipe:φ22.22
0.95 Gas pipe:φ38.1 0.95 Gas pipe:φ38.1
0.90 0.90
Liquid pipe:φ19.05 Liquid pipe:φ19.05
0.85 Gas pipe:φ31.8 0.85 Gas pipe:φ31.8
0.80 0.80
0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 20 40 60 80 100 120 140 160 180 200 220 240 260
Pipe length of single way (m) Pipe length of single way (m)
Cooling compensation factor
Cooling compensation factor
AV36NMVETA
AV36IMVEVA AV38NMVETA
AV38IMVEVA
1.00 1.00
Liquid pipe:φ22.22 Liquid pipe:φ22.22
0.95 Gas pipe:φ38.1 0.95 Gas pipe:φ38.1
0.90 0.90
Liquid pipe:φ19.05 Liquid pipe:φ19.05
0.85 Gas pipe:φ38.1 0.85 Gas pipe:φ38.1
0.80 0.80
0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 20 40 60 80 100 120 140 160 180 200 220 240 260
Pipe length of single way (m) Pipe length of single way (m)
Cooling compensation factor
Cooling compensation factor
AV40NMVETA
AV40IMVEVA AV42NMVETA
AV42IMVEVA
1.00 1.00
Liquid pipe:φ22.22 Liquid pipe:φ22.22
0.95 Gas pipe:φ38.1 0.95 Gas pipe:φ38.1
0.90 0.90
Liquid pipe:φ19.05 Liquid pipe:φ19.05
0.85 Gas pipe:φ38.1 0.85 Gas pipe:φ38.1
0.80 0.80
0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 20 40 60 80 100 120 140 160 180 200 220 240 260
Pipe length of single way (m) Pipe length of single way (m)
Cooling compensation factor
AV44NMVETA AV46NMVETA
Cooling compensation factor
AV44IMVEVA AV46IMVEVA
1.00 1.00
Liquid pipe:φ22.22 Liquid pipe:φ22.22
0.95 Gas pipe:φ38.1 0.95 Gas pipe:φ38.1
0.90 0.90
Liquid pipe:φ19.05 Liquid pipe:φ19.05
0.85 Gas pipe:φ38.1 0.85 Gas pipe:φ38.1
0.80 0.80
0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 20 40 60 80 100 120 140 160 180 200 220 240 260
Pipe length of single way (m) Pipe length of single way (m)
108
Cooling compensation factor
AV48NMVETA AV50NMVETA
AV50IMVEVA
0.90 0.90
Liquid pipe:φ19.05 Liquid pipe:φ19.05
Gas pipe:φ38.1 0.85 Gas pipe:φ38.1
0.85
0.80 0.80
0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 20 40 60 80 100 120 140 160 180 200 220 240 260
Pipe length of single way (m) Pipe length of single way (m)
AV52NMVETA AV54NMVETA
Cooling compensation factor
0.90 0.90
Liquid pipe:φ19.05 Liquid pipe:φ19.05
0.85 Gas pipe:φ38.1 0.85 Gas pipe:φ38.1
0.80 0.80
0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 20 40 60 80 100 120 140 160 180 200 220 240 260
Pipe length of single way (m) Pipe length of single way (m)
Cooling compensation factor
AV56NMVETA
AV56IMVEVA AV58NMVETA
AV58IMVEVA
Cooling compensation factor
1.00 1.00
Liquid pipe:φ22.22 Liquid pipe:φ22.22
0.95 Gas pipe:φ41.3 0.95 Gas pipe:φ44.5
0.90 0.90
Liquid pipe:φ19.05 Liquid pipe:φ19.05
0.85 Gas pipe:φ38.1 0.85 Gas pipe:φ41.3
0.80 0.80
0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 20 40 60 80 100 120 140 160 180 200 220 240 260
Pipe length of single way (m) Pipe length of single way (m)
Cooling compensation factor
AV60NMVETA
AV60IMVEVA AV62NMVETA
AV62IMVEVA
1.00 1.00
Liquid pipe:φ22.22 Liquid pipe:φ22.22
0.95 Gas pipe:φ44.5 0.95 Gas pipe:φ44.5
0.90 0.90
Liquid pipe:φ19.05 Liquid pipe:φ19.05
0.85 Gas pipe:φ41.3 0.85 Gas pipe:φ41.3
0.80 0.80
0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 20 40 60 80 100 120 140 160 180 200 220 240 260
Pipe length of single way (m) Pipe length of single way (m)
Cooling compensation factor
Cooling compensation factor Cooling compensation factor
AV64NMVETA
AV64IMVEVA AV66NMVETA
AV66IMVEVA
1.00 1.00
Liquid pipe:φ22.22 Liquid pipe:φ22.22
0.95 Gas pipe:φ44.5 0.95 Gas pipe:φ44.5
0.90 0.90
Liquid pipe:φ19.05 Liquid pipe:φ19.05
0.85 Gas pipe:φ41.3 0.85 Gas pipe:φ41.3
0.80 0.80
0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 20 40 60 80 100 120 140 160 180 200 220 240 260
Pipe length of single way (m) Pipe length of single way (m)
Cooling compensation factor
AV68NMVETA
AV68IMVEVA AV70NMVETA
AV70IMVEVA
1.00 1.00
Liquid pipe:φ25.4 Liquid pipe:φ25.4
0.95 Gas pipe:φ50.8 0.95 Gas pipe:φ50.8
0.90 0.90
Liquid pipe:φ22.22 Liquid pipe:φ22.22
0.85 Gas pipe:φ44.5 0.85 Gas pipe:φ44.5
0.80 0.80
0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 20 40 60 80 100 120 140 160 180 200 220 240 260
Pipe length of single way (m) Pipe length of single way (m)
109
Cooling compensation factor
AV72NMVETA
AV72IMVEVA AV74NMVETA
0.90 0.90
Liquid pipe:φ22.22 Liquid pipe:φ22.22
0.85 Gas pipe:φ44.5 0.85 Gas pipe:φ44.5
0.80 0.80
0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 20 40 60 80 100 120 140 160 180 200 220 240 260
Pipe length of single way (m) Pipe length of single way (m)
AV76NMVETA AV78NMVETA
Cooling compensation factor
0.80 0.80
0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 20 40 60 80 100 120 140 160 180 200 220 240 260
Pipe length of single way (m) Pipe length of single way (m)
Cooling compensation factor
AV80NMVETA AV82NMVETA
Cooling compensation factor
AV80IMVEVA AV82IMVEVA
1.00 Liquid pipe:φ25.4 1.00
Liquid pipe:φ25.4
Gas pipe:φ50.8 Gas pipe:φ50.8
0.95 0.95
0.80 0.80
0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 20 40 60 80 100 120 140 160 180 200 220 240 260
Pipe length of single way (m) Pipe length of single way (m)
Cooling compensation factor
AV84NMVETA
AV84IMVEVA AV86-90NMVETA
AV86-90IMVEVA
1.00 1.00
Liquid pipe:φ25.4 Liquid pipe:φ25.4
Gas pipe:φ50.8 Gas pipe:φ54.1
0.95 0.95
0.80 0.80
0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 20 40 60 80 100 120 140 160 180 200 220 240 260
Pipe length of single way (m)
Pipe length of single way (m)
Cooling compensation factor
AV92-96NMVETA
Cooling compensation factor
AV92-96IMVEVA AV98-104NMVETA
AV98-104IMVEVA
1.00 1.00
Liquid pipe:φ25.4
Gas pipe:φ54.1
0.95 0.95
0.80 0.80
0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 20 40 60 80 100 120 140 160 180 200 220 240 260
Pipe length of single way (m) Pipe length of single way (m)
Note:
1. The refrigerant pipe should be thickened when the single way length is over 90m.
2. When in cooling mode, outdoor is lower than indoor; or when in heating mode, outdoor is higher than indoor,
the compensation factor should be decreased the below value from the above figure.
Vertical height
drop between
5m 10m 15m 20m 25m 30m 35m 40m 45m 50m 60m 70m 80m 90m 100m 110m
indoor and
outdoor
Adjustment factor 0.003 0.006 0.009 0.012 0.015 0.018 0.021 0.024 0.027 0.03 0.033 0.036 0.039 0.042 0.045 0.05
110
(2) Calculation method of heating capacity---Heating capacity to be known=Heating capacity x(AxBxCxDxExF) W
A. Capacity modification value B. Capacity modification value under outdoor air C. Capacity modification value
under indoor air dry-bulb wet-bulb temperature condition. under airflow variation rate of
temperature condition. indoor unit group.
1.2
1.0
Capacity modification
1.1 1.1
0.9
1.0 1.0
0.8
coefficient
0.9 0.9
coefficient
0.7
80 90 100 110 120
0.8 0.6
Airflow variation rate(%)
15 20 24 0.5
Indoor air dry-bulb temperature(°C) 0.4
-23 -20 -15 -10 -5 0 5 10 15
1.0
0.8
0.6 0.9
0.4
capacity
Standard
0.2
0.8
0 20 40 60 80 100 120 140 -15 -10 -5 0 5 10
1.00
0.98
0.96
0.94
0.92
factor
0.90
0 20 40 60 80 100 120 140 160 180 200220 240 260
Pipe length of single way (m)
(3) Calculation method of refrigeration capacity-Only one indoor unit running
stand by indoor normal capacity
Outdoor modified capacity with a single indoor running=outdoor modified capacity*
indoor total normal capacity.
Outdoor modified capacity heating or outdoor capacity after modify item 1 and 2 )
111
11. Selection procedure
Yes
Yes
Finish
112
Outdoor temperature (°CDB)
-5
10
15
0
30
35
50
52
20
25
40
45
1510
12. Operation range
20
Continuous operation range Cooling
25
Suction decompression operation range
30
113
-5
-15
5
10
15
0
20
-10
25
-27
-25
-20
10
Compressor operation range
15
Continuous operation range
20
Heating
25
30
1m
1m
1m
114
2) Octave band level
AV08/10NMVETA
AV08/10IMVEVA AV12/14NMVETA
AV12/14IMVEVA
70 70
NC-60 NC-60
60 60
NC-50 NC-50
50 50
NC-40 NC-40
40 40
NC-30 NC-30
30 30
NC-20 NC-20
H
20 H 20
Limit of M
Limit of M
L
audible L audible
continuous continuous
noise noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
AV16NMVETA
AV16IMVEVA AV18/20/22NMVETA
AV18/20/22IMVEVA
70 70
Octave band sound pressure level dB
NC-60 NC-60
60 60
NC-50 NC-50
50 50
NC-40 NC-40
40 40
NC-30 NC-30
30 30
NC-20 NC-20
20 20
Limit of Limit of
audible H audible
H
continuous M continuous M
noise L
noise L
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
AV24/26NMVETA
AV24/26IMVEVA
70
Octave band sound pressure level dB
NC-60
60
NC-50
50
NC-40
40
NC-30
30
H
M
L
NC-20
20
Limit of
audible
continuous
noise
10
63 125 250 500 1000 2000 4000 8000
115
14. Installation
14.1 Safety
• If the air conditioner is transferred to the others, this manual should be transferred together.
• Before installation, please read "Safety precaution" carefully to confirm the correct installation.
• The mentioned precaution includes " WARNING" and " CAUTION". The precaution caused death or heavy
injury for faulty installation will be listed in " WARNING". Even the cautions listed in " CAUTION" also may
cause serious accident. So both of them are related to the safety, and should be executed severely.
• After installation, perform a trial and confirm everything normal, then introduce the operation manual to the user.
Besides, put the manual to the user and ask them to preserve it carefully.
WARNING
• The installation or the maintenance should be performed by the authorized agency. Or the non-specialized
operation will cause water leakage, electric shock or fire etc. accidents.
• The installation should be executed as per the manual, or the faulty installation will cause water leakage, electric
shock or fire etc. accidents.
• Please install the unit at the space which can bear the weight. Or the unit will drop down to cause the human
injury.
• The installation should defend against the typhoon, and the earthquake etc. Abnormal installation will cause the
unit fall down.
• Use the correct cable and make reliable earthing. Fix the terminal firmly and the loose connection will cause
heating or fire etc. accident.
• The wiring should be in shape and can not be raised. Be earthed firmly and can not be clipped by the electric box
cover or the other plate. The incorrect installation will cause heating or fire.
• When setting or transferring the unit, there should not be other air into the refrigerant system except for R410A.
The gas mixture will cause the abnormal high pressure which will cause break or human injury etc. accidents.
• When installation, please use the accessories with the unit or the special parts, or it will cause water leakage,
electric shock, fire, refrigerant leakage etc. accidents.
• Don't lead the water drainage pipe into the drainage groove with the poisonous gas, such as sulphur. Or the
poisonous gas will enter indoor.
• In installation or after installation, please confirm if there is refrigerant leakage, please take measures for
ventilation. The refrigerant will cause poisonous gas as meeting fire.
• Don't install the unit at the place where there may be flammable gas leakage. In case the gas leaks and gather
around the unit, it will cause fire.
• The drainage pipe should be installed as per the manual to confirm the fluent drainage. Also take measures for
heat insulation against dew drop. Incorrect water pipe installation will cause water leakage even and make the
things wet.
• For the liquid pipe and the gas pipe, take measures for heat insulation too. If there is no heat insulation, the dew
drop will wet the things.
116
CAUTION
• Execute earthing for the unit. But the earthing wire can not be connected to the gas pipe, water pipe, lightening
rod or the telephone earthing wire. Improper earthing will cause electric shock.
• Don't install the unit at the place where leaks the flammable gas. Or it will cause fire.
• Execute the water drainage pipe according to the manual, improper installation will cause water leakage to wet
the family things.
• The outdoor fan can not face to the flower or the other vegetable, or the blowing gas will make the flower dried
up.
• Please ensure the maintenance room, if not, it will cause the maintenance person damaged.
• When installing the unit on the roof or the other high place, to prevent the person falling down, please set the
fixed ladder and the railing at the passage.
• Use the two-end spanner, and fasten the nut at proper torque. Don't fasten the nut excessively against the flared
section broken. Or it will cause refrigerant leakage and lack of oxygen.
• Take measures for heat insulation to the refrigerant pipe, or there will be water leakage or dew drop to wet the
family things.
• After finishing the refrigerant pipe, make leakage test by charging the nitrogen. In case the refrigerant leaks in a
small room and exceeds the limited concentration, it will cause lack of oxygen.
• Don't use the other refrigerant except for R410A. The R410A pressure is 1.6 times higher than R22 pressure. The
refrigerant R410A tank is marked with pink sign.
• Against charging different refrigerant, we changed the stop valve diameter of the R410A unit. To enhance
the compression consistence, we also changed the flared pipe dimension. Prepare the R410A specially tools
according to the below table.
• When charging refrigerant, the refrigerant must be taken out as liquid state from the tank.
• When installing indoor unit, outdoor, power cable and connecting wire, leave them at least 1m away from the TV
set or the radio against interference for the image or the noise.
• In the room with fluorescent lamp (reverse phase or rapid start type), the remote signal may be not reach the pre-
set distance. The farther that indoor is away from fluorescent lamp, the better.
• The tightening torque of the stop valve refer to the following table
Operating valve size Fastening torque Fastening angle Recommended tool length
(mm) (N.m) (°) (mm)
Ø6.35 14~18 45~60 150
Ø9.52 34~42 30~45 200
Ø12.7 49~61 30~45 250
Ø15.88 68~82 15~20 300
Ø19.05 84~98 15~20 300
• When loaded into a refrigerant, be sure to take it out of the tank.
• Installation of indoor, outdoor, power lines and connections must be at least 1m away from the TV or radio to
avoid image interference or noise.
• In a room equipped with fluorescent lamps (RP or fast start), the remote control signal transmission distance may
not reach a predetermined value. The farther away the indoor machine is, the better it is.
117
14.2 Installation instruction
In installation, please check specially the below items:
• If the connected units quantity and the total capacity is in the allowable range?
• If the refrigerant pipe length is in the limited range?
• If the pipe size is proper? And if the pipe is installed horizontally?
• If the branch pipe is installed horizontally or vertically?
• If the additional refrigerant is counted correctly and weighed by the standard balance?
• If there is refrigerant leakage?
• If all the indoor power supplies can be on/off simultaneously?
• If the power voltage is in compliance with the data marked on the rating label?
• If the address of indoors and outdoors has been set?
Before installation
1) Before installation, check if the model, power supply, pipe, wires and parts purchased respectively are correct.
2) Check if the indoors and outdoors can be combined as the following.
Indoor
Allow The most Combined
Gather
Capacity the most recommended Total indoor capacity
HP Combination Type pipe
(W) connected indoor unit capacity(100W) range
indoor units number
8 25200 single 15 8 126~328 -
10 28000 single 17 10 140~364 -
12 33500 single 20 11 168~436 -
14 40000 single 24 13 200~520 -
16 45000 single 27 15 225~585 -
18 50400 single 30 17 252~655 -
20 56000 single 33 18 280~728 -
22 61500 single 36 20 308~800 -
24 68000 single 40 22 340~884 -
26 73500 single 43 24 368~956 -
28 80000 combination(14+14) 47 26 400~1040
30 85000 combination(14+16) 50 28 425~1105
32 90000 combination(16+16) 53 30 450~1170 50%~130%
34 95400 combination(16+18) 56 31 477~1240
36 100800 combination(18+18) 59 33 504~1310
38 106400 combination(18+20) 63 35 532~1383
40 112000 combination(20+20) 66 38 560~1456 HZG-20B
42 117500 combination(20+22) 69 42 588~1528
44 123000 combination(22+22) 72 44 620~1612
46 129500 combination(22+24) 76 46 648~1684
48 136000 combination(24+24) 80 49 680~1768
50 141500 combination(24+26) 83 51 707~1840
52 147000 combination(26+26) 86 52 735~1911
54 151200 combination(18+18+18) 89 54 756~1966
HZG-30B
56 156800 combination(18+18+20) 92 59 784~2038
118
Indoor
Allow The most Combined
Capacity the most recommended Total indoor Gather pipe capacity
HP Combination type range
(W) connected indoor unit capacity (HP)
indoor units number
58 162400 combination(18+20+20) 96 61 812~2111
60 168000 combination(20+20+20) 99 63 840~2184
62 173500 combination(20+20+22) 100 64 868~2256
64 179000 combination(20+22+22) 100 64 895~2327
66 184500 combination(22+22+22) 100 64 922~2398
68 191000 combination(22+22+24) 100 70 955~2483 HZG-30B
70 197500 combination(22+24+24) 100 70 988~2568
72 204000 combination(24+24+24) 100 70 1020~2652
74 209500 combination(24+24+26) 100 70 1048~2723
76 215000 combination(24+26+26) 100 70 1075~2795
78 220500 combination(26+26+26) 100 76 1103~2867
80 224000 combination(20+20+20+20) 100 76 1120~2912
50%~130%
82 229500 combination(20+20+20+22) 100 76 1148~2984
84 235000 combination(20+20+22+22) 100 76 1175~3055
86 240500 combination(20+22+22+22) 100 76 1203~3127
88 246000 combination(22+22+22+22) 100 76 1230~3198
90 252500 combination(22+22+22+24) 100 85 1263~3283
HZG-30B
92 259000 combination(22+22+24+24) 100 85 1295~3367
FQG-B2040A
94 265500 combination(22+24+24+24) 100 85 1328~3452
96 272000 combination(24+24+24+24) 100 85 1360~3536
98 277500 combination(24+24+24+26) 100 85 1388~3608
100 283000 combination(24+24+26+26) 100 85 1415~3679
102 288500 combination(24+26+26+26) 100 89 1443~3751
104 294000 combination(26+26+26+26) 100 89 1470~3822
Note:
a. If all the indoor units operate at the same time in one system, the total indoor units capacity should be less
than or equal to the total outdoor units capacity. Otherwise,overloading operations may occur in bad operating
condition or some special conditions. If all the indoor units don't operate at the same time in one system,the total
indoor units capacity should be no more than 130% of the total outdoor units capacity.
c. If the system operates in high heat load or cold area (Ambient Temperature below -10°C), the total indoor units
capacity should be less than the total outdoor units capacity.
d. To choose combinations' wires and air switches according to the Max. operating current of the combinations.
Air-conditioner can't be installed in The unit should be installed at the The unit should be installed at
the place with inflammable gas. Or place with good ventilation. No the strong enough place. Or it will
it will cause fire hazard. obstacle at the air inlet/outlet. And no cause vibration and noise.
strong wind blows the unit.
119
The unit should be installed at the • The place where the water can • The unit is better not be installed
place where the cold/hot air or flow fluently. at the below places, or it will cause
noise will not interfere the • The place where no other heat damage.
neighbours. source will affect the unit. • The place where there is corrosive
• Pay attention to the snow gas (spa area etc.).
against clogging the outdoor. • The place blowing salty air (seaside
• In installation, install the anti- etc.).
vibration rubber between the • Exists the strong coal smoke.
unit and the bracket. • The place with high humidity.
• The place where there is device
emitting Hertzian waves.
• The place where voltage changes
greatly.
Transportation
• In transportation, please don't dismantle the packaging, and move the unit to the installation location as closely as
possible.
• Don't hang the unit only at two points. When hanging the unit, don't sit on the unit. The unit should be upright.
When removing the unit with the forklift, put the fork into the special hole at bottom of the unit. When being
hanged, the rope should be 4 pieces of steel cable with over 8mm diameter. Put the cushion at the contact
section between steel cable and the unit against the distortion or damage.
Steel cable
Cushion
Hoisting hole diameter Ø40mm, distance730mm Hoisting hole diameter Ø40mm, distance1042mm
AV08~16NMVETA AV18~26NMVETA
120
Outline and installation dimensions
755mm
750mm
980mm
70mm
Exhaust duct
connection position
1690mm
Drain hole
755mm
1410mm 750mm
70mm
Exhaust duct
connection position
1690mm
121
Outdoor unit installation
Standard accessories
Please check the attachment is complete, please be sure to use.
Place
No. definition Graphic Quantity Remarks
position
Installation Accessory
1 1
instruction bag
(8HP)(Ø22.22)
Reducing (8~10HP)(Ø25.4) Accessory
4 1 Reducing pipe
pipe bag
(8~14HP)(Ø28.58)
Gas liquid
Wiring Accessory
5 4 pipe insulation
harness bag
binding
1. Choose a place that can carry the weight of the unit to install and fix, so that the unit will not shake or fall. The
unit shall be installed in a flat area (below 1/100).
2. Do not install the unit in the areas where there may be flammable, explosive, corrosive gas leakage.
3. Indoor and outdoor machines should be close to each other as much as possible to reduce the length of the
refrigerant pipeline and the number of bends.
4. The installation should be to ensure that units from the sun and rain, dust, typhoon, earthquake proof place.
In the area of snow, the machine should be installed in the frame or under the snow cover, so as to avoid the
machine snow. See Figure 1.
5. Make sure that there is enough room for maintenance.
6. Measures should be taken to avoid contact with children.
7. The refrigerant pipe by the unit below should be used when the overhead, overhead part height 200mm above.
See Figure 2
Seasonal wind
Aerial part
The base height should be height above
considered the maximum 200mm
snowfall locally, Prevent snow
Please use M12 fixed anchor bolts, each unit needs 4, and
height cxceeds the unit angle.
use shock absorbers or shock absorbers to reduce noise
Figure 1 Figure 2
122
Combination installation dimensions
• There should be no obstacles in 2000mm above the top of outdoor unit;
• Obstacles around outdoor should be less than 900mm to the bottom of unit.
• When multiple modules are installed, the outdoor should be in ranked as the capacity, the larger capacity is closer
to the main pipe of gather pipe.
1. Single installation
˃2000mm
Right
Left
˃900mm
˃300mm
˃300mm
Front
˃1000mm
2. Combination installation
Unit can be installed in the same or opposite direction
m
m
00
˃3
m
0m
00
˃300mm
˃1
˃200mm
123
˃300mm
˃200mm
˃300mm ˃1000mm
˃300mm
˃200mm
˃300mm ˃1000mm
HD External air
duct
H
h
˃1000mm
124
Place without air inlet hole
Notes:
a. Set a 500~1000mm bracket.
b. Air outlet height HD=H-h and below 1m.
˃300mm
H
h
500~1000
4. The outdoor machine installation should consider the impact of seasonal wind, don't let the wind directly into the
unit return air, otherwise it will affect the unit defrosting and related functions.
125
Install snow cover Outlet snow cover
Snowfall area, please install snow cover, see the right
picture, to be unaffected by the snow, it is important to set Inlet snow cover
up a high platform, which is calculated according to the
maximum amount of snow in the area. At the same time, the
outdoor defrost setting change to be easy to frost setting,
detailed see the digital tube setting.
1. Remove the screw with a screwdriver and remove the repair wrench from the bottom of the machine (or use a
self-prepared screwdriver).
3. Along the direction of the arrow, after repair plate rotating about 40 °, the maintenance from the fixed orifice plate
on the right side of card claw, can complete repair plate disassembly.
126
Install air ducting
There are no obstacles in the 2000mm above the outdoor unit; When there are obstacles in the outer plane,
there must be a pilot channel, and the wind will be free, the wind will not be short-circuited, and the external static
pressure will be 110Pa. Airway design dimensions are as follows:
C A
Channel size (pattern 1)
D
B
E
AV08~16NMVETA AV18~26NMVETA
A The inner diameter 980 The inner diameter 1410
F
B The inner diameter750 The inner diameter 750
C ≤10000 ≤10000
D E+750 E+750
E ≥300 ≥300
F ≥320 ≥320
C
A
D
Channel size (pattern 2)
B
E
AV08~16NMVETA AV18~26NMVETA
A The inner diameter 750 The inner diameter 750
F
Note:
Before installing the wind channel, the unit should be removed from the wind protection network. At the same time,
the outdoor air tube static press is set up to "have static pressure" mode. The above is just an example, the length
of the wind tunnel should be calculated according to the shape of the wind channel.
127
14.3 Installation procedure
A. Refrigerant pipe connection
Anti-fouling measures
First, clean the pipe.
Position Installation period Measures
More than 1 month Flat the pipe end
Outdoor
Less than 1 month
Flat the pipe end or seal with adhesive tape
Indoor Nothing to do with period
128
Pipe specification
Outdoor Indoor
A
A
Liquid pipe Gas pipe Liquid pipe
B
Gas Liquid pipe E Gas pipe Gas pipe Liquid pipe C
pipe
D D B
E D D C B
B
1. Pipe "A" diameter (between indoor and branch pipe) (depends on indoor pipe)
Indoor rated Gas pipe Connecting Liquid Connecting Note
capacity (x100w) method pipe method
15~28 Ø9.52 Ø6.35
AS07/092MGERA gas pipe should be
36~56 Ø12.7 Flared Ø6.35
Ø12.7
71~140 Ø15.88 Ø9.52 Flared
AS182MGERA gas / liquid pipe should be
226~300 Ø25.4 Ø9.52
Braze Ø15.88 / Ø9.52
450~600 Ø28.58 Ø12.7
(1) When pipe length between indoor & nearest branch pipe ≥15m, adjust in accordance with following criteria:
① If indoor rated capacity≤5.6kW, change gas / liquid pipe diameter to Ø15.88 / Ø9.52
② If 16.8kW≥ indoor rated capacity>5.6kW, change gas / liquid pipe diameter to Ø19.05 / Ø9.52
③ If indoor rated capacity>16.8kW, change liquid pipe diameter to Ø12.7
(2) When pipe length between first branch pipe & farthest indoor is over 40m, pipe b (between first branch pipe
& farthest indoor) should be enlarged one size.
(3) The distance between the nearest indoor unit distance between the indoor unit ≤ 40 meters.
129
3. Pipe “c” diameter (main pipe, between outdoor gather pipe and the first branch pipe)
Outdoor Main pipe Enlarged main pipe Outdoor Main pipe Enlarged main pipe
capacity Liquid Liquid capacity Liquid
Gas pipe Gas pipe Gas pipe Gas pipe Liquid pipe
(W) pipe pipe (W) pipe
25200 Ø19.05 Ø9.52 Ø22.22 Ø12.7 162400 Ø41.3 Ø19.05 Ø44.5 Ø22.22
28000 Ø22.22 Ø9.52 Ø25.4 Ø12.7 168000 Ø41.3 Ø19.05 Ø44.5 Ø22.22
33500 Ø25.4 Ø12.7 Ø28.58 Ø15.88 173500 Ø41.3 Ø19.05 Ø44.5 Ø22.22
40000 Ø25.4 Ø12.7 Ø28.58 Ø15.88 179000 Ø41.3 Ø19.05 Ø44.5 Ø22.22
45000 Ø28.58 Ø12.7 Ø31.8 Ø15.88 184500 Ø41.3 Ø19.05 Ø44.5 Ø22.22
50400 Ø28.58 Ø15.88 Ø31.8 Ø19.05 191000 Ø44.5 Ø22.22 Ø50.8 Ø25.4
56000 Ø28.58 Ø15.88 Ø31.8 Ø19.05 197500 Ø44.5 Ø22.22 Ø50.8 Ø25.4
61500 Ø28.58 Ø15.88 Ø31.8 Ø19.05 204000 Ø44.5 Ø22.22 Ø50.8 Ø25.4
68000 Ø28.58 Ø15.88 Ø31.8 Ø19.05 209500 Ø44.5 Ø22.22 Ø50.8 Ø25.4
73500 Ø28.58 Ø15.88 Ø31.8 Ø19.05 215000 Ø44.5 Ø22.22 Ø50.8 Ø25.4
80000 Ø28.58 Ø15.88 Ø31.8 Ø19.05 220500 Ø44.5 Ø22.22 Ø50.8 Ø25.4
85000 Ø31.8 Ø19.05 Ø38.1 Ø22.22 224000 Ø44.5 Ø22.22 Ø50.8 Ø25.4
90000 Ø31.8 Ø19.05 Ø38.1 Ø22.22 229500 Ø44.5 Ø22.22 Ø50.8 Ø25.4
95400 Ø31.8 Ø19.05 Ø38.1 Ø22.22 235000 Ø44.5 Ø22.22 Ø50.8 Ø25.4
100800 Ø38.1 Ø19.05 Ø38.1 Ø22.22 240500 Ø50.8 Ø25.4 Ø54.1 Ø25.4
106400 Ø38.1 Ø19.05 Ø38.1 Ø22.22 246000 Ø50.8 Ø25.4 Ø54.1 Ø25.4
112000 Ø38.1 Ø19.05 Ø38.1 Ø22.22 252500 Ø50.8 Ø25.4 Ø54.1 Ø25.4
117500 Ø38.1 Ø19.05 Ø38.1 Ø22.22 259000 Ø50.8 Ø25.4 Ø54.1 Ø25.4
123000 Ø38.1 Ø19.05 Ø38.1 Ø22.22 265500 Ø50.8 Ø25.4 Ø54.1 Ø25.4
129500 Ø38.1 Ø19.05 Ø38.1 Ø22.22 272000 Ø50.8 Ø25.4 Ø54.1 Ø25.4
136000 Ø38.1 Ø19.05 Ø38.1 Ø22.22 277500 Ø54.1 Ø25.4 Ø54.1 Ø25.4
141500 Ø38.1 Ø19.05 Ø38.1 Ø22.22 283000 Ø54.1 Ø25.4 Ø54.1 Ø25.4
147000 Ø38.1 Ø19.05 Ø38.1 Ø22.22 288500 Ø54.1 Ø25.4 Ø54.1 Ø25.4
151200 Ø38.1 Ø19.05 Ø41.3 Ø22.22 294000 Ø54.1 Ø25.4 Ø54.1 Ø25.4
156800 Ø38.1 Ø19.05 Ø41.3 Ø22.22
Note: When the distance from outdoor to the longest indoor is over 90m, the main pipe diameter should be
enlarged.
4. Pipe “D” diameter (between gather pipes) 5. Pipe “e” diameter (between outdoor and the gather pipe)
Total horse Gas pipe Liquid pipe
power of Outdoor
Gas pipe Liquid pipe Pipe Connection Pipe Connection Remarks
connected (HP)
diameter method diameter method
outdoors 8 Ø19.05 Flared joint Ø9.52
≤78.5kW Ø28.58 Ø9.52
10 Ø22.22 Ø9.52 Please use
85.0~96.0kW Ø31.8 Ø19.05 the attached
101.0~157.0kW Ø38.1 Ø19.05 12 Ø25.4 Ø12.7 connection
162.4~185.5kW Ø41.3 Ø19.05 pipe
192.0~235.0kW Ø44.5 Ø22.22 14 Ø25.4 Ø12.7 diameter
240.5~272.0kW Ø50.8 Ø25.4 16 Ø28.58 Ø12.7 Flared joint
Brazing
> 272.0kW Ø54.1 Ø25.4 18 Ø28.58 Ø15.88
20 Ø28.58 Ø15.88
22 Ø28.58 Ø15.88
24 Ø28.58 Ø15.88
26 Ø28.58 Ø15.88
130
Allowable piping length and drop between indoor and outdoor
L4 L6
L1 L2 L3 L5
气管 气管 气管 气管
131
Proper installation Wrong installation
In order to avoid damage to the pipe, the size of the return bend is referred to as the drawing.
R R Pipe diameter Bending radius Vertical heigh
D R H
Ø19.05 ≥31 ≤150
Ø22.22 ≥31 ≤150
H H Ø25.4 ≥45 ≤150
Ø28.58 ≥45 ≤150
Ø31.8 ≥60 ≤250
D
Ø38.1 ≥60 ≤350
Ø41.3 ≥80 ≤450
D
Ø44.5 ≥80 ≤500
Ø50.8 ≥90 ≤500
Ø54.1 ≥90 ≤500
L7
Indoor machine and outdoor unit of
L4
the Height difference H ≤ 90m
L3 L6
Indoor unit and indoor unit of
L8
the Height difference ≤ 30m
L2 L9 L11
L5 L10 L12
L1
132
Allowable
Pipe length and drop (m) For example Remarks
value
Total pipe length ≤1100 L1+L2+L3+L4+…+L24
Outdoor to the farthest Actual length ≤220
L1+L2+L3+L6+L8
indoor length Equivalent length ≤260
The outdoor unit to the first branch pipe
≤130 L1
length (main piping)
The first branch pipe to the farthest indoor
≤90 L2+L3+L6+L8
unit pipe length
The distance between the nearest indoor
≤40 L2+L3+L6+L8-L2-L5-L10
unit and the farthest indoor
Height difference Outdoor unit
≤90
between above
H
indoor and outdoor Outdoor unit
≤110
H under
Indoor machine maximum drop
≤30 h
h
The indoor unit and the nearest branch L4\L8\L9\L10\L11\L12\L14\L17\L19\L20\L21\
≤10
length L23\L24
Note:
Indoor unit as much as possible to install on both sides of the differences between the two sides.
Branch pipe
Branch pipe selection:
Total indoor capacity (100W) Model (optional)
Less than 335 FQG-B335A
More than 335, less than 506 FQG-B506A
More than 506, less than 730 FQG-B730A
More than 730, less than 1360 FQG-B1350A
More than 1360 FQG-B2040A
Horizontal
Floor
Cut off at the middle Floor
Right Wrong
133
Pipe installation
Important
• Please don't let the pipe and the parts in the unit collide each other.
• When connecting the pipes, close the valves fully.
• Protect the pipe end against the water, impurity into the pipes (welding after being flat, or being sealed with
adhesive tape).
• Bend the pipe as large semi-diameter as possible(over 4 times of the pipe diameter).
• The connection between outdoor liquid pipe and the distributing pipe is flared type. Please expand the pipe with
the special tool for R410A after installing the expanding nut. But if the projecting pipe length has been adjusted
with the copper pipe gauge, you can use the original tool to expand the pipe.
• Since the unit is with R410A, the expanding oil is ester oil, not the mineral oil.
• When connecting the expanding pipe, fasten the pipes with double-spanner. The torque refers to the former info.
Expanding pipe: A(mm) Projecting length of pipe to be expanded: B(mm)
Pipe outer diameter 0 Pipe outer When it is hard pipe
A
(mm) -0.4 diameter Special tool The former
Ø6.35 9.1 (mm) for R410A tool
Ø9.52 13.2 Ø6.35
Ø12.7 16.6 Ø9.52
0-0.5 1.0-1.5
Ø15.88 19.7 Ø12.7
Ø15.88
• The outdoor gas pipe and the refrigerant distributing pipe, as well the refrigerant distributing pipe and the branch
pipe should be welded with hard solder.
• Weld the pipe at the same time charge the nitrogen. Or it will cause a number of impurity (a film of oxidation) to
clog the capillary and the expansion valve, further cause the deadly failure.
Operation procedure
• Weld the pipe at the same time charge the Seal the pipe end with adhesive tape or the stopper to
nitrogen. Or it will cause a number of impurity increase the resistance, fill up the pipe with nitrogen.
(a film of oxidation) to clog the capillary and the
expansion valve, further cause the deadly failure. Taping <N2>
• Protect the pipe end against water and impurities (welding after being flatted, or being sealed with adhesive
tape).
Flat
• When welding the valve and the pipes, use the wet cloth to cool down the
valve and the pipes.
134
B. Leakage test
1. The outdoor unit has been executed the leakage test in the factory. The pipe should be executed leakage test
individually and forbidden to test after connecting with stop valve.
2. Refer to the below figure to charge the nitrogen into the unit to take a test. Never use the chlorin, oxygen,
flammable gas in the leakage test. Apply pressure both on the gas pipe and the liquid pipe.
3. Apply the pressure step by step to the target pressure.
a. Apply the pressure to 0.5MPa for more than 5 minutes, confirm if pressure goes down.
b. Apply the pressure to 1.5MPa for more than 5 minutes, confirm if pressure goes down.
c. Apply the pressure to the target pressure (4.15MPa), record the temp. and the pressure.
d. Leave it at 4.15MPa for over 1 day, if pressure does not go down, the test is passed. Meanwhile, when the temp.
changes for 1degree, pressure will change 0.01MPa as well. Correct the pressure.
e. After confirmation of a~d, if pressure goes down, there is leakage. Check the brazing position, flared position
by laying on the soap. Modify the leakage point and take another leakage test.
4. After leakage test, do execute the evacuation.
To indoor
Gauge manifold
Lo Hi
Nitrogen Lo handle Hi handle
C. Evacuation
Evacuate at the check valve of liquid stop valve and both sides of the gas stop valve. The oil equalization pipe also
must be vacuum (executed at the oil equalization pipe and check valve respectively).
Operation procedure:
Leakage test passed
Charge refrigerant
Evacuation begins
Evacuation ends
Check vacuum
135
Tighten torque as the table below:
Stop valve diameter Fastening torque Fastening angle Recommended tool length
(mm) (N.m) (°) (mm)
Ø6.35 14~18 45~60 150
Ø9.52 34~42 30~45 200
Ø12.7 49~61 30~45 250
Ø15.88 68~82 15~20 300
Ø19.05 84~98 15~20 300
136
• This product contains fluorinated greenhouse gases in hermetically sealed system. Do not vent into the
atmosphere. Refrigerant type: R410A. See the table above for the mass of charged refrigerant. GWP (Global
• Warming Potential): 2088.
• A leak check for refrigerant shall be carried out at least every 12 months and by natural persons certified in
accordance with the European rules.
Heat insulation
• HP gas pipe, Suction gas pipe and liquid pipe should be heat insulated separately.
• The material for HP gas pipe and Suction gas pipe should endure the high temperature over 120°C. That for
liquid pipe should be over 70°C.
• The material thickness should be over 10mm, when ambient temp. is 30°C, and the relative humidity is over 80%,
the material thickness should be over 20mm.
• The material should cling the pipe closely without gap, then be wrapped with adhesive tape. The connection wire
can not be put together with the heat insulation material and should be far at least 20cm.
Connection wire
Over 20cm
Adhesive tape
Gas pipe
Liquid pipe
Heat insulator
137
14.4 Electric wiring and the application
Note:
1. Please follow the national electrical standards, all provided parts, raw materials must comply with local laws
and regulations. And please professional electrician installation.
2. Power supply must use the rated voltage and air conditioning unit dedicated power supply, power fluctuations
in the power supply ratio of less than 2%, and were designed indoor unit, outdoor machine dedicated power.
3. The power cord should be reliably fastened to prevent the terminals from being stressed. Please do not force
the power cord.
4. The power line diameter should be large enough, the ground wire should be reliable, should be connected to
the building's special grounding device.
5. The air switch and earth leakage switch that can be cut off the entire system must be installed. Air switch
should also have a magnetic trip and thermal trip function to ensure that short circuit and overload are
protected, Should use "D" type circuit breaker.
6. Do not add the phase-connected capacitor to prevent overheating of the capacitor due to high frequency
waves.
7. Please follow the instructions in accordance with the requirements of the power cord connection, so as to avoid
a security incident.
8. The unit must be reliably grounded to meet the relevant requirements of GB 50169.
9. All electrical installations must be carried out by professionals in accordance with local laws, regulations and
corresponding instructions.
Power
Circuit breaker
L1 L2 L3 N
138
Indoor Power Supply:
230V/1Ph/50-60HZ
L1 N
MCB
139
Power line installation instructions
1. Air conditioning unit is class appliance, please be sure to take reliable grounding measures.
2. Earth resistance should meet the national standard GB 50169 requirement.
3. The yellow and green double color line of air conditioning unit is ground wire, do not move for other use, do not
cut it. Cannot be fixed with self-tapping screw. Otherwise, the risk of electric shock will be electric.
4. The user's power supply must provide reliable grounding. Please don't connect the ground wire to the following
places. (1) water pipe (2) gas pipe; (3) drainage pipe; (4) The other places where professionals think are
unreliable.
5. The power cord and the communication line should not be interwoven together, the distance should be greater
than 20cm apart, or it may cause the crew communication to be abnormal.
Note:
Please follow the following guidelines:
Please connect the power cord with the appropriate circular terminal.
PQ is non-polar, ABC has polarity, must be correct when connecting.
The route is as follows:
Use attachment's
sheath for walking
protection
140
Power line installation instructions
Note:
When connecting the power cord, please be sure to set aside enough length in the outdoor, which is convenient for
turning over the electrical box.
After the maintenance, remove the 5 fixing screws, the When connecting the power cord, please be sure
electric appliance box body is lifted up slightly, and the box to set aside enough length in the outdoor, which is
body is rotated to the left, and the steel wire rope in the convenient for turning over the electrical box.
column is used to check the box to prevent the turning.
Left column
C
hook
B C
P Q A B C P Q A B C P Q A B C P Q A B C
Note:
• Outdoor using 3 core, 0.75m2 shielding wire connection, polarity
• Indoor using 2 core, 0.75m2 shielding wire connection, non polarity. The signal line shield must be grounded at
one end, and the communication line between the indoor and outdoor machine is 1500 meters long.
• The communication line must be hand-in-hand serial connection, not using star connection.
• When the length of the single line of communication is not sufficient, the joint connection must be pressed or
solder.
141
Communication wiring figure (wireless)
IGU11
5V
Indoor 1
Indoor 2 Indoor 3 Indoor 4 Indoor n
P Q CN34 CN34 CN34 CN34 CN34
PQ PQ PQ PQ
Note:
If the system unit adopts Zigbee wireless communication, it must adopt wireless and wired hybrid mode.
The PQ cable must be connected to the IDU which one with the smallest address number
142
15. Branch pipe dimension
Unit: mm ID: inner diameter OD: outer diameter
Liquid side
Gas side connection connection of
Model Gas side branch pipe Liquid side branch pipe of branch pipe branch pipe
384
Ø22.22
238
Φ9.53
Ø12.7
104 104
ID9.7
100
55 55
ID16.1
ID19.3
FQG-B335A
ID22.4
ID12.9
ID22.4
ID16.1
Ø25.4
ID19.3
ID6.5
ID9.7
ID9.7
Φ12.7
Ø15.88
Φ9.53
ID12.9
ID9.7
Ø15.88
ID12.9
ID9.7
ID9.7
ID9.7
Φ6.35
Φ6.35
Ø19.05 ID9.7
ID16.1 ID6.5
ID12.9
323
238
Ø22.2
Φ9.53
ID12.9
ID12.9
Ø12.7
180
100 55
ID28.8
ID25.6
ID9.7
Ø25.4
ID25.6
ID28.8
FQG-B506A Φ9.52
ID9.7
Ø22.22
Φ6.35
Φ12.7
Ø28.58
ID22.4
ID9.7
ID25.6
ID16.1
ID12.9
ID22.4 ID12.9 ID19.3
ID9.7
ID19.3 ID6.5
ID16.1
ID12.9
388
323
180
ID16.1
Φ19.05
Ø22.2
ID12.9
Φ6.35
ID9.7
Φ25.4
100
ID28.8
ID25.6
Ø55
ID22.4
ID9.7
ID25.6
ID9.7
Ø28.58
Φ12.7
ID12.9
ID16.1
ID19.3
ID25.6
ID28.8
FQG-B730A
Ø25.4
ID16.1
Ø22.22 Φ19.05
ID22.4 ID16.1
ID19.3
ID12.9
ID16.1 ID9.7
ID12.9
ID6.5
143
Model
FQG-B2040A
FQG-B1350A
ID51.1 ID38.3
ID44.8 ID32
ID41.5
150
Ø31.75
41.3*41.3*38.1
Φ44.5*1.5
485
38.1*1.3
366
Φ44.5*1.5
Ø28.6
ID28.8
ID38.4 ID44.8
ID32 ID41.6 Ø31.75
ID28.8 ID38.4
Gas side branch pipe
ID32
ID25.6 ID32
130 ID38.3
ID22.4 ID9.7
ID12.9
ID25.6
ID16.1
71
ID19.3
ID22.4
Ø22.22
41.3*41.3*38.1
Φ44.5*1.5
405
38.1*1.3
ID6.5
ID9.7
290
270
ID12.9
Φ19.05
ID16.1
Φ44.5*1.5
144
ID22.4 ID22.4
ID19.2
Φ25.4
ID19.2
ID16.1
ID16.1 ID22.4
Liquid side branch pipe
ID12.9 ID19.3
70
Ø28.58
Ø22.22
ID19.3 ID25.6
ID22.4
138
ID16.1
180
ID12.9 ID19.3
ID16.1
ID12.9
of branch pipe
ID35.1 Ø31.75
ID49
Φ12.7
Gas side connection
ID28.8
100
140
ID9.7 ID25.6
φ38.1 ID22.4
Φ6.35
55
ID9.7
Liquid side
branch pipe
connection of
HZG-30B HZG-20B
Model
Liquid side Suction gas side Liquid side Suction gas side
Side
F E D C B A
Mark
16. Gather pipe dimension
+0.15
+0.15 +0.15 ID32 0
+0.15 ID32 0 ID19.2 0
ID19.2 0 +0.2
+0.15 ID44.8 0
ID25.6 0 +0.2
+0.2 +0.15 ID38.3 0
65
+0.15 ID38.3 0 ID22.4 0
ID22.4 0
86
117
86
117
147
φ25.4*1
52
47
47
75
75
φ22.22*1
86
φ44.5*1.5
φ22.22*1
Φ38.1*1.3
Φ38.1*1.3
355 -5
+5
235 -5
+5
360 -5
+5
235 -5
+5
355 -5
+5
Φ28.58*1.1
383 -5
+5
205 -5
+5
360 -5
+5
Φ28.58*1.1
285 -5
+5
285 -5.
+5.
403 -5
+5
φ19.05*1
270 -5
+5
φ15.88*1
φ15.88*1
φ38.1*1.3
φ15.88*1
145
φ15.88*1
+0.15
+0.15
φ15.88*1
φ28.58*1.1
+0.15 ID28.8 0
ID19.2 0 ID28.8 0
Gather pipe
ID16.1 0 ID38.3 0
+0.15
Φ28.58*1.1
ID16.1 0
+0.15 +0.15 ID25.6 0
+0.15 ID25.6 0 ID16.1 0
ID16.1 0 +0.15 +0.15
+0.15 +0.15 ID12.9 0 +0.15
ID12.9 0 ID16.1 0 ID12.9 0 +0.15
+0.15 ID22.4 0
+0.15 ID22.4 0
+0.15 ID12.9 0
ID12.9 0 ID32 0
+0.15
ID28.8 0 +0.15
+0.15 +0.15 +0.15 ID19.2 0
+0.15 +5 ID19.2 0 ID9.7 0
ID9.7 0 ID9.7 0 90 +5 +0.15 +0.15
+5 +0.15 +0.15 ID9.7 0 ID28.8 0
68 -5 ID9.7 0 ID28.8 0
+5
+5 +5 +5 82 +5
70 +5 82 +5 70 +5
OD28.58*1.1
OD15.88*1
Φ28.58*1.1
+0.15
ID25.6 0
103
42
+0.15
double
ID22.4 0
double
+0.15
ID25.6 0
+0.15 +0.15
101
gather pipe
+0.15
ID19.2 0
Gather pipe is used for combination of outdoor unit. HZG-20B (for 2 basic modules); HZG-30B(for 3 basic
modules). Unit: mm, ID: inner diameter; OD: outer diameter. Note: Cut off the pipe from its middle when using
17. Trial operation
17.1 Confirmation by electrifying
No. Contents to be confirmed Result
Whether there is power on interface board of the outdoor unit, whether the digital tube is
1
displaying and whether the displayed data on dip switch panel and the tube are variable.
For MRV outdoor unit, indoor unit number displayed on the digital tube is consistent with the
2 actual number when dip switch panels SW1, SW2 and SW3 are turned to “0 3 2”, and dip
switch code BM1-2 is turned from OFF to ON.
For MRV outdoor unit system, outdoor unit number displayed on the digital tube is consistent
3 with the actual number when dip switch panels SW1, SW2 and SW3 are turned to “0 2 2”,
and dip switch code BM1-1 is turned from OFF to ON.
For MRV outdoor unit system, the HP of outdoor unit sets displayed on the digital tube is
consistent with the actual unit type when dip switch panels SW1, SW2 and SW3 are turned
to “0 1 2”
AV08NMVETA shows “1-8.0”
AV10NMVETA shows “1-10.0”
AV12NMVETA shows “1-12.0”
4 AV14NMVETA shows “1-14.0”
AV16NMVETA shows “1-16.0”
AV18NMVETA shows “1-18.0”
AV20NMVETA shows “1-20.0”
AV22NMVETA shows “1-22.0”
AV24NMVETA shows “1-24.0”
AV26NMVETA shows “1-26.0”
Check whether the parameters, such as parameters of outdoor unit sensors, number of
indoors connected and the opening of electronic expansion valves, etc., are correct through
5
dip switch on the outdoor unit interface board or by using testing equipment and computer
software.
Check whether the parameters, such as parameters of indoor unit sensors, the opening of
6 electronic expansion valves, etc., are correct through dip switch on the outdoor unit interface
board or by using testing equipment and computer software.
Note: If the indoor unit cannot be searched or the number of the searched units isn't consistent with the actual
number of indoor units in the system within four and a half minutes, it will be reported as communication fault 26-X.
17.2 Rated operation
Startup control on indoor and outdoor units and operation condition inspection for outdoor units can be completed
through rated operation. In case of inspection on single indoor unit, wired controller or remote controller of indoor
unit will be adopted for control.
Rated cooling operation: when SW1, SW2 and SW3 dip switches are turned to 0, 13, 2, the indoor units will be
started up automatically and be forced to turn to cooling operation.
Rated heating operation: when SW1, SW2 and SW3 dip switches are turned to 0, 14, 2, the indoor units will be
started up automatically and be forced to turn to heating operation.
146
17.3 Trial operation confirmation
The test run confirmation, in principle, shows that all the indoor units should be confirmed one by one. The
improper connection of refrigeration pipe and control wire cannot be confirmed when all the indoor units are
running simultaneously. So all the other indoor units should be set in "stopped condition".
No
Whether the operation light of wired controller is on *3
Yes
Whether the LCD "standby" of wired controller is No
turned on *2
Yes
Whether the overhaul code of wired controller is
displayed *1
Yes
Please refer to maintenance code displayed of wired
controller and fault method. For detailed
of operation condition, please refer to
self-diagnosing function of outdoor unit.
147
PCB board of indoor unit
is in bad condition;
Wires around the PCB
board of indoor unit are
broken and the insertion
No of socket is poor.
*1
No
Whether there Whether
Whether
Whether the fan No Yes is AC15V voltage No there is AC15V
another indoor
is rotating in air supply between terminal B and voltage between
unit starts
mode C of wired controller terminal B and C
operating
of indoor unit
Yes
No
Wires around the
PCB board of indoor
unit are broken
and the insertion of
socket is poor.
148
Normal
Yes
No
The abnormity of Indoor unit
Indoor unit PCB board is in bad condition;
Wired controller is in bad condition.
No
*3
Whether there
PCB board in wired controller is in bad condition; Yes is AC15V voltage
Wires around the PCB board of indoor unit are broken between terminal blocks
and the insertion of socket is poor. A and B of wired
controller
No
Whether there
Wrong connection between indoor unit and wired Yes is AC15V voltage
between terminal blocks A
controller
and B of indoor unit
149
B. Air blower operation confirmation
Start
Yes
No
Normal
150
C. Cooling operation confirmation
Start
Check all indoor units one by one.
Set the operation to cooling mode and hold Once stop, the outdoor
down the operation switch for more than 5 unit can’t restart until 3
seconds in shutdown mode. to 5 minutes later.
Yes
Whether air circulation is in good No
condition rotation direction of the blade
Yes
Make all the indoor units operate
simultaneously
Yes
Whether the operating voltage is No Check and the power supply
proper (380 V ± 10%) voltage and circuit
Yes
Whether the operating current No Check the temperature of indoor and outdoor;
is at ± 15% of the standard value (at
Check pipe length and charging amount of the
maximum frequency) (Note 2)
refrigerant;
Yes Check operating frequency of the compressor
and operating condition of the outdoor fan;
Whether operating pressure is No Check whether there is abnormal sound in the
normal (Note 3) compressor.
Yes
Normal
151
D. Heating operation confirmation
Start
Check all indoor units one by one.
Set the operation to heating mode and hold Once stop, the outdoor
down the operation switch for more than 5 unit can't restart until 3
seconds in shutdown mode. to 5 minutes later.
Yes
Whether the air circulation is in No
good condition rotation direction of the blade.
Yes
Make all indoor units operate simultaneously
Yes
Whether the operating voltage is No Check and the power supply
proper (380 V ± 10%) voltage and circuit
Yes
Whether the operating current No Check the temperature of indoor and outdoor;
is at ± 15% of the standard value (at
Check pipe length and charging amount of the
maximum frequency) (Note 2)
refrigerant;
Yes Check operating frequency of the compressor
and operating condition of the outdoor fan;
Whether the operating pressure is No Check whether there is abnormal sound in the
normal (Note 3) compressor.
Yes
Normal
152
(Note 1)The general standard for temperature difference between inlet and outlet air
In "cooling" operation, it is normal that the dry bulb temperature difference between inlet air and outlet air of the
air conditioner is over 10°C (at the maximum frequency) after 30 minutes at least.
In "heating" operation, it is normal that the dry bulb temperature difference between inlet air and outlet air of the
air conditioner is over 14°C (at the maximum frequency) after 30 minutes at least.
Values after 15-minute operation (the temperature therein refers to dry bulb temperature with unit of °C)
The transformation trend of high pressure and low pressure due to change of operation condition
Refrigeration/heating: indoor temperature rises – high/low pressure rises
Indoor temperature drops – high/low pressure drops
Outdoor temperature rises – high/low pressure rises
Outdoor temperature drops – high/low pressure drops
Evaluating unit through test device
153
1. Connecting methods of device: Position of inserting test device (CN47)
Insert one end of data line into the terminal of main
PCB CN31 with a two-core terminal, one end connects
with 485 device or Gangda device, the other end of the
device connects computer.
2. The data that can acquire through device Outdoor unit:
The frequency of outdoor unit compressor /Outdoor fan
speed/Opening of outdoor electronic expansion valve/ High
pressure of outdoor unit/Corresponding saturation
temperature of outdoor unit’s high pressure/Low pressure
of outdoor unit/Corresponding saturation temperature
Data
of outdoor unit’s low pressure/Discharging temperature/
measuring
Suction temperature/Oil temperature/ Temperature of
condenser outlet pipe/Ambient temperature/Temperature of
defrosting sensor/Starting of all kinds of solenoid valve
Indoor unit: Temperatures of gas pipe and liquid pipe,
opening angle of electronic expansion valve /Display of
failure
It is normal if there is high pressure frequency
3.Test device can display failures of the unit during
limitation or high discharging temperature
operation, moreover it can realize a function of storing data
in real time, and the test data can be stored in computer. frequency limitation when outdoor ambient
4.Prepare a report according to the test data and submit it temperature is high and all the indoor units are
to user. operating.
The confirmation of running data/Timing and recording of
the measurement.
After the measurement is begun, check the system
pressure through detection software. Generally, the cooling
low pressure is about 7.5kg and the heating high pressure
is about 28kg under rated cooling and heating modes.
Then observe if operation under each parameter is normal.
There is a picture about cooling operating parameters’ data
Confirmation in the right column, after operating about half hour, the unit
of the data remains stable.
Check if there is a blockage in capillary during operation, if
any, replace it.
Check if there is contact between refrigerant piping and
capillary tube, if any, deal with it.
Check if wires of sensor (such as wiring, pressure sensor,
etc.) are too tight, or contact with vibrating pipe, if so, deal
with it.
Check if the value of sensor is correct.
154
18. Startup
18.1 Startup procedure
1. The materials preparation before on-site commissioning
--Printed drawing of architectural design
--Printed installation checking list and system start request
--Startup manual
--MRV 5 service manual
--Trouble shooting and error code
3. Installation checking
--installation checking
--Parameter standard checking list
4. Operation
--Dip switch setting for indoor units
--Dip switch setting for outdoor units
--Dip switch setting for controllers
--Power on
--Locking quantity of indoor and outdoor units (BM1-1/BM1-2)
5. Trail operation
--Startup of indoor units
--Running parameter checking
--Running parameter standard
--Completion of startup report
1. Piping
--Enough fixed supports
--Branch pipe installed horizontal way
--Welding (Nitrogen flow)
--Branch pipe distance,1m (39.37 inch) away from each other and 0.5m (19.7 inch) far from IDU
2. Drain
--1% gradient (indoor unit)
--Exhaust outlet for drain pipe (indoor unit)
--Aerial part height above 200mm (outdoor unit)
4. Electricity wire
--Independent wire line to each IDU
-- Same phase power supply
-- Add breaker for each IDU
-- Electricity wire installed to IDU and ODU correctly
155
5. Indoor unit
--Anti-dust protection during installation
--Installed on properly level
--Service space reserved at least 50X50cm
6. Outdoor unit
-- Installed an anti-vibration at the bottom
-- Space (20cm/7.87inch away from each other)
-- Gather pipe are the same level
-- Breaker
-- Communication cable (A / B / C, PQ)
7. Pre start up
-- 100% of the piping completed the pressure test
-- Vacuum test
-- The system have been with electric power more than 6h
-- Outdoor unit addressing (Master 0, slave 1, slave2)
-- Indoor units are addressing correctly
-- All the indoor units work correctly in Fan mode
156
18.3 Wiring-dip switch
1. Indoor dip switch setting—Indoor units for MRV5 and indoor units for MRV IV-C are the same, so indoor dip
switch setting is completely the same, please check with the service manual.
2. Controller dip switch setting- it’s the same as the controller dip switch setting of MRVIV, please check the service
manual.
IDU Dip switch setting
For different IDU PCB board, the setting is little different. When start up, check the below Dip switch setting:
SW01 (1~4 or 2~4)--------Set the master/slave unit when use wired controller in group control
SW01 (5~8)-----------------Set the capacity of the unit(default setting, no need to reset)
SW03 (1~8)------------------Set the communication address and central address(the default setting is set the address
by wired controller or automatically)
BM-2
BM-4
SW1
SW2
SW3 Check operating parameter & E2 control
157
18.4 Power on
1. For the protection of the compressor, It is required to preheat the compressor oil before start up the indoor and
outdoor units. 6 hours of preheating is the standard time for the preheating, the engineers have to wait for 6 hours
until the compressor oil reaches the required temp. The main PCB will show on the LED time counting down.
2. The outdoor and indoor units communication P, Q should be disconnected before turning on indoor units in case
of any unexpected operation.
158
18.7 MRV 5 system startup report
MRV 5-H
PROJECT:
CUSTOMER:
INSTALLER:
CITY/COUNTRY:
ADDRESS:
CONTACT TEL:
DATE: DD / MM / YY
PROJECT CONFIGURATION
COMMENTS:
INSTALLER: SIGNATURE:
DATE :
159
MRV 5-H
1. PREINSTALATION YES
1.1. REFRIGERATION PIPING
* Refrigerant piping are correctly insulated.
* Refrigerant piping have enough fixed supports.
* All welds were made with permanent nitrogen flow, to create an inert atmosphere.
* All branch pipes are installed in horizontal direction.
* There are at least the distance of 1m between branch and branch, and 0.5m far from the indoor units.
1.2. DRAIN
* Drain piping is correctly insulated.
* Exhaust outlet for drain pipe.
* A drop of at least 1% is guaranteed (1 cm per linear meter).
* Drain's piping diameter is according to requirements.
* Drain piping is separated for unit with drain pump.
160
MRV 5-H
2. PRE START UP
* 100% Of the piping completed the pressure test at 80 psi (5.5 Kg/cm2) during 3 Minutes
* 100% Of the piping completed the pressure test at 250 psi (17.5 Kg/cm2) during 2 Hours
* 100% Of the piping completed the pressure test at 590 psi (40.5 Kg/cm2) during 24 Hours
* The system have been with Electric power more than 6 hours before de start up.
* Indoor units are addressed properly.
* Outdoor units are addressed according the position Master, Slave 1, Slave 2 y Slave 3.
* Once the system is connected to electric power, the master outdoor unit display show the indoor units quantity
connected.
* All the Indoor units and vale boxes work correctly in Fan Mode.
161
MRV 5-H
162
MRV 5-H
163
19. Outdoor control board photo
PCB code: 0151800256C
SMG2 BM1
SMG1
SW4 BM2
(UP)
SW5 SW6
(START) (STOP)
SW7 BM3
(DOWN)
LED1
BM4
LED3
LED4
LED6 BUS-A
164
1
20
19
18
17
16
15
14
13
4 12
6 7
8 9 10 11
165
Compressor driver board: 0151800259C
8
1
5
4
No. Function
1 Connected reactor connector
2 Low-power standby control connector
3 Connect electrolytic capacitor PCB connector
4 Module three-phase power input connector
5 Module drive output connector
6 Dip switch
7 Programming connector
8 Main PCB and fan motor communicating connector
9 15VDC power output connector
166
Filter board: 0150401866
No. Function
1 Filter board output connector
2 Filter board ground wire connector
3 Filter board power input connector
167
Capacitor board:0150401863
1
3
No. Function
1 Electrolytic capacitor negative connector
2 Fan DC power supply connector
3 Electrolytic capacitor positive connector
168
20. Outdoor PCB dip switch setting
LED light definition:
• LED1: power supply lamp
Power on light
• LED3: electronic expansion valve LEVa1, LEVa2, fault lamp
No fault, not light
• LED4: electronic expansion valve LEVb, LEVc, fault lamp
No fault, not light
• LED5: communication lamp between outdoors
Communication is normal, flashing
• LED6: communication lamp between indoor and outdoor
Communication is normal, flashing
• LED7: communication lamp between PCB and power module
Communication is normal, flashing
Concept identification:
• Physical master unit: the outdoor unit, whose number is set as 0 by dip switch(BM1-7 and BM1-8), is
the communication sponsor and in charge of the communication with indoor unit, also works as initiator of
communication of the whole outdoor unit.
• Function master unit: the outdoor unit, whose priority is set as 0, operates with the highest priority.
• Physical slave unit: the outdoor unit, whose number is not set as 0 by dip switch(BM1-7 and BM1-8).
• Function slave unit: the outdoor unit, whose priority is set as 1~3, not operates with the highest priority.
• Setting of group class: the setting of physical master unit is valid for the whole unit.
• Setting of local class: it is only valid for this unit, not for the whole unit.
Dip switch introduction:
• BM1 is usually set by the engineer on site; BM2, BM3, BM4 are pre-set in the factory.
• BM1_1: Master outdoor unit searches the total outdoor units after power on at first time. The quantity of total
outdoor units is floating from right to left on digital tube SMG1 and SMG2. "1=0" is one outdoor unit, "2=01" is
two outdoor units, "3=012" is three outdoor units, "4=0123" is four outdoor units.
• BM1_2: Master outdoor unit searches the total indoor units after locked the quantity of the outdoor units. The
quantity of total indoor units is floating from right to left on digital tube SMG1 and SMG2. "-04-" is 4 indoor units,
"-06-" is 6 indoor units, "-15-" is 15 indoor units.
• BM1_3: The setting is OFF or ON. Default is ON. Once power off, unit software shall reset to "OFF"
automatically ignoring BM1_3 setting.
169
① BM1 introduction
Outdoor searching OFF Begin to search outdoor
BM1_1
after startup ON Stop searching outdoor and lock the quantity
Indoor searching OFF Begin to search indoor
BM1_2
after startup ON Stop searching indoor and lock the quantity
start up after pre- 0 Allow(must be electrified for 6 hours)
BM1_3 Group class
heating for 6 hours 1 Forbidden(can start up immediately)
(physical master
OFF Heat pump (default) unit is valid)
BM1_4 Outdoor mode setting
ON Cooling only
Outdoor static pressure OFF No static pressure, high speed (default)
BM1_5
selection ON Ultra high-speed
Communication protocol OFF New protocol (default)
BM1-6
between IDU & ODU ON Old
BM1_7 BM1_8 Outdoor address
OFF OFF 0# (physical master unit)
BM1_7
Outdoor address setting OFF ON 1#
BM1_8
ON OFF 2#
ON ON 3#
170
② BM2 introduction
BM2_1 BM2_2 New communication protocol type
New communication Group class
BM2_1 Wired 9600bps general protocol
protocol type setting (it is OFF OFF (physical master
BM2_2 (default)
valid when BM1_6 is OFF) unit is valid)
ON OFF Wireless 9600bps communication
Outdoor heat pump mode OFF Heat pump (default)
BM2_3 setting (it is valid when
BM1_4 is OFF) ON Heating only
171
③ BM3 introduction
BM3_1 BM3_1 BM3_2 BM3_3 Outdoor
BM3_2 Outdoor type selection Local class
BM3_3 OFF ON OFF MRV5-H outdoor unit
BM3_4 Reserved OFF Default
BM3_5 BM3_6 BM3_7 BM3_8 Outdoor horse
OFF OFF OFF ON 8HP
OFF OFF ON OFF 10HP
BM3_5 OFF OFF ON ON 12HP
BM3_6 OFF ON OFF OFF 14HP
Outdoor horse power
BM3_7 OFF ON OFF ON 16HP
setting
BM3_8 OFF ON ON OFF 18HP
OFF ON ON ON 20HP
ON OFF OFF OFF 22HP
ON OFF OFF ON 24HP
ON OFF ON OFF 26HP
172
Outdoor digital tube display settings
The contents of the display are defined as follows:
• Key parts: long press the left START (SW5) control to enter, short press above UP (SW4) data increase, short
press down DOWN (SW7) data reduction, long press the right STOP (SW6) control exit
• Dial: SW1, SW2, SW3: set the turntable dial switch is 0 - 15
• (Note: the dial plate, with the letters A for 10, B for 11, C for 12, D for 13, E for 14, F for 15)
• Display parts: LD1, LD2, LD3, LD4:4 digital tube from left to right
① Indoor unit parameter view
You can view the indoor machine 128 sets of parameters: SW1 and SW2 represent the indoor unit address, SW3
range is 3-14 can view the indoor unit parameters.
SW1 SW2 Address
0 1 to 16 (address 0#~15#)
1 17 to 32 (address 16#~31#)
2 33 to 48 (address 32#~47#)
3 49to 64 (address 48#~63#)
0-15
7 65 to 80 (address 64#~79#)
8 81 to 96 (address 80#~95#)
9 97 to 112(address 96#~111#)
10 113 to 128(address 112~127#)
SW3 Function Digital tube LD1 ~ 4 display
Communication normal display indoor unit program version (1 decimal), the
communication interrupted normal display “0000” (5 consecutive round of no
Indoor unit communication
3 communication success), communication has been abnormal display “---- ---
check and program version
-””.
For example: 3.9, means the indoor unit version is V3.9
4 Indoor unit failure Display indoor failure code; no failure, display 0
5 Indoor unit capacity The indoor unit capacity (unit: HP, one decimal), 1.5 HP displays 1.5
6 Indoor EEV open angle Electronic expansion valve (EEV) open angle (Unit: Pls)
7 Indoor ambient temp. Tai Ambient temperature (Unit: °C)
8 Indoor gas temperature Tc1 Gas pipe temperature (Unit: °C)
Indoor liquid temperature
9 Liquid pipe temperature (Unit: °C)
Tc2
LED1 shows startup mode ( O: Shutdown C: cooling H: Heating)
LED2 indicates actual fan speed of indoor unit (0 - stop, 1 - low wind, 2 -
Indoor startup mode, actual
medium wind and 3 - high wind)
10(A) fan speed and SCODE
LED3 and LED4 indicate SCODE code (0~15).
code
For example, C311 indicates cooling running at high wind, and the SCODE
is 11.
11(B) Indoor set temperature Tset Indoor set temperature (Unit: °C)
Display the indoor unit group number (0 means unassigned group number,
self control)
Method of setting group number is same with the <E2 control parameters
Indoor unit consistency display and setting>
12(C)
control setting (Note: all the indoor unit' simultaneously setting can be set by a dial 15-0-2.
0- indoor unit self control according to the group number, 1- all indoor unit
ON/OFF at the same time 2- indoor unit self control, forbidden control at the
same time)
Shows whether the indoor unit has this function, 0 - No 1 - Yes
Low temperature automatic Setting method is same with the <E2 control parameters display and setting>
13(D) running function of indoor (Note: all the indoor unit' simultaneously setting can be set by a dial 15-1-2.
unit Note: all within the machine at the same time setting can be set by dialing
15-1-0- self control, 1- all indoor are valid, 2- all indoor are invalid
173
SW3 Function Digital tube LD1 ~ 4 display
(1) press START (SW5) for 2 seconds, to enter setting state, the instruction
value is flashing displayed
Forced indoor cooling /
14(E) (2) press UP (SW4) or DOWN (SW7) to adjust instruction (COOL/HEAT/OFF).
heating / shutdown
(3) after finish the adjustment, press STOP (SW6) for 2 seconds, execute the
setting instruction and stop flashing
② Outdoor unit parameter view
0~3 SW1 is used to select the outdoor machine number, to select the different machine. SW3 range of 0, 1, 15,
expressed as the observation of outdoor machine parameters.
(the host can display the parameters of the other outdoor machine and the indoor machine parameters, and the
sub machine only displays the machine parameter SW1 is 0).
(1) The first boot, the first sub search engine, from left to right circular display 1:0, if found a table display 2:01 two
table display 3:012. "3:012" means a total of 3 units of the system, 012 said the address of the machine. (":" the
actual display "=").
(2) Lock machine units, start the search within the machine number, cycle "- in - machine units", such as "-6-" said
the system connects the 6 station machine
(3) After the search is completed, the display of the machine's fault code, the machine has no fault when the display
0.
SW1 SW2 SW3 Function Digital tube LD1 ~ 4 display
Failure code transmitted by outdoor bus data. If no failure, display the
time as second counting down from the 6 hours for pre-heating.
• Press START (SW5) for 2s continuously, display 1111, and access
the condition of history fault inquiry to inquire the recent 10 faults: with
fault sequence number and fault code displayed by flashing. Press
Display outdoor SW4 (UP) once, sequence number will go up 1; press SW7 (DOWN)
0 0
unit failure code once, sequence number will decrease 1; 2 min later, quit the setting
condition automatically.
• Press STOP (SW6) for 2s continuously, display 0000, then quit
query status and stop flashing.
• When dip switch panel is at 13,0,0, press START (SW5) for 2s
continuously, display 1111, thus history fault record can be cleared.
Display outdoor
LD1: Display priority of outdoor unit
unit priority and
1 0 LD2:Display “-”
outdoor unit
LD3-4:Display outdoor unit capacity (unit: HP)
capacity
Outdoor Display operation
unit mode and outdoor LD1 shows O: Stop C: Cooling H: Heating
2 0
address unit operation LD2 to LD4 show: 60 shows 60% capacity output
0-3 output ratio
Outdoor fan 1 345 representation 345rpm
3 0
speed • Press START (SW5) for 2s continuously, display 1111, then to set:
flashing. Press UP (SW4) once, wind speed will go up 1 level; press
DOWN (SW7) once, wind speed will decrease 1 level. 5 min later, quit
Outdoor fan 2
4 0 the setting condition automatically.
speed
• Press STOP (SW6) for 2s continuously, display 0000, then quit the
setting condition, and stop flashing.
Frequency
5 0 converter INV1 110 representation 110.0Hz
current frequency Press START (SW5) for 2 seconds, display 1111, enter the set state:
flashing display, each according to the 1 UP (SW4) frequency rise
1Hz, every 1 times DOWN (SW7) frequency drop 1Hz; 5min after
Frequency automatically quit the set state.
6 0 converter INV2 Press STOP (SW6) for 2 seconds, display 0000, quit the set state,
current frequency stop flashing display;
(When the system is faulty, the compressor is forbidden to start.)
174
SW1 SW2 SW3 Function Digital tube LD1 ~ 4 display
7 0 Outdoor unit LEVa1 open degree 0---470pluse
Press START (SW5) for 2 seconds, 1111, enter the
8 0 Outdoor unit LEVa2 open degree setting state: flashing, press UP (SW4) valve fully
open, press DOWN (SW7) the valve is fully closed;
9 0 Outdoor unit LEVb open degree 2min later automatically exit the setting state
Press STOP (SW6) for 2 seconds, display 0000, quit
10(A) 0 Outdoor unit LEVc open degree
the setting state, stop flashing display
LD1: 4WV : 1 ON 0 OFF
Outdoor unit solenoid valve LD2: SV1 : 1 ON 0 OFF
11(B) 0
output LD3: SV3: 1 ON 0 OFF
Outdoor LD4: Reserved,Display “-”
unit LD1: SV6: 1 ON 0 OFF
address 12(C) Outdoor unit solenoid valve LD2: SV9:1 ON 0 OFF
0
0-3 output LD3: SV10: 1 ON 0 OFF
LD4: SV11: 1 ON 0 OFF
LD1: SVX: 1 ON 0 OFF
Outdoor unit solenoid valve LD2: SVY: 1 ON 0 OFF
13(D) 0
output LD3: Reserved,Display “-”
LD4: Reserved,Display “-”
LD1: CH1: 1 ON 0 OFF
LD2: CH2: 1 ON 0 OFF
14(E) 0 Heater output
LD3: CHa : 1 ON 0 OFF
LD4:Reserved,Display “-”
15(F) 0 Program version 1 means Ver1.0
175
SW1 SW2 SW3 Function Digital tube LD1 ~ 4 display
Outdoor 14(E) 15(F) Inverter compressor INV1 module temperature
unit
Unit: oC
address
0-3 15(F) 15(F) Inverter compressor INV2 module temperature
176
E2 control parameters display and setting
Each need to be set, setting method:
(1)Press START (SW5) for 2 seconds, display 1111, enter the set state, flashing display the current value
(2)According to UP (SW4) or DOWN (SW7) adjustment parameters
(3)After the adjustment is completed
<A> In the current state of the code, effectively set the time by pressing STOP (SW6) for 2 seconds, showing 0000,
keeping the current settings and exit the set state, stop flashing display, waiting for 2 minutes after the power off
and then re power up
<B> The current set time is not set by STOP (SW6) or change the dial selection, do not save the current set value,
exit the set state, stop flashing display
<C> Effective time setting: the machine with the contract number and set off a low temperature automatic operation
function for 10 minutes, the other for 30 seconds..
Control
SW1 SW2 SW3 function Digital tube LD1 ~ 4 display
range
0- machine automatic control according to
the group number, all within the machine
In the same machine drive with
15(F) 0 2
off control selection 1- drive,
2- all in each machine control, drive off with
ban
Selection of low
0- within the machine automatic control,
temperature automatic
15(F) 1 2 1- all within the machine is valid,
operation control for indoor
2- all the inside of the machine is invalid
unit
0: short pipe length;
15(F) 2 2 Pipe length selection 1:middle pipe length;
2:long pipe length
Defrosting conditions 0- normal area,
15(F) 3 2
selection 1- area easy to frost
0- first open priority;
1- after opening priority
15(F) 4 2 Operation mode priority
2- cooling priority;
3- heating priority Group class
Capacity overmatch 0-shows no limitation, (physical
15(F) 5 2
selection 1-shows limitation master unit
Heating limit when is valid)
0-shows no limitation,
15(F) 6 2 Outdoor temp
1-shows limitation
Over 25 degree
0-without silent operation,
1- silent operation 1,
15(F) 7 2 Silent running option 2- silent operation 2,
3- silent operation 3,
4- silent operation 4
snow-proof operation 0-without snow-proof operation,
15(F) 8 2
setting 1- without snow-proof operation
When the main outdoor
machine is running, the 0-stop,
15(F) 9 2
choice of the operation of 1-run
the wind turbine is stopped.
Power limit operation 0- By E2 value,
15(F) 12(C) 2
control mode selection 1- By external contact DRM
Maximum capacity to allow the maximum
Power output ratio selection
15(F) 13(D) 2 number of files, a total of 11 stalls, 0 stalls
(E2 control method is valid)
for 10, 0%, 100%
177
Control
SW1 SW2 SW3 Function Digital tube LD1 ~ 4 display
range
15(F) 1 3 Low consumption mode 0-invalid 1-valid
Heating standby indoor unit
Group class
forced adjustment valve
15(F) 5 3 0-invalid 1-valid (physical
selection.(except three pipe
master unit
model)
is valid)
Selection of height between 0-no drop between indoor units.
15(F) 6 3
indoor units in cooling mode. 1-exist drop between indoor units
178
21. Outdoor system control function
21.1 Compressor control
Generally, the compressor frequency is controlled according to the target Ps during cooling.
During the control process, Pd, Td/TOIL, PS, etc. are given priority.
Generally, the compressor frequency is controlled according to the target Pd during heating.
During the control process, Pd, Td/TOIL, PS, etc. are given priority.
Single and double compressor switching based on system load and compressor frequency
during dual compressor operation
21.2 Electronic expansion valve control
Cooling: when startup, the electronic expansion valve is maintained at 100 pls and the electronic
expansion valve is fully open after startup.
Heating: When heating, the electronic expansion valve is usually superheated to 4 degrees. SH
= Toci1-ET=4 (°C)
21.3 Fan motor control
① Control of MRV 5-H series DC motor
The air supply speed of outdoor unit can be set from speed 0 to 22 in accordance with the operating mode.
The operating is commonly at speed 1 - 22, and it is CVT (Continuously Variable Transmission) control between
speed 1 and 22.
② Air supply motor: range of number and rotating speed (unit: rpm)
< Outdoor fan motor control (usually control / high static pressure control) >
Level Double fan Single fan
24 (high static pressure) 1100+1100 1000
22 1020+1020 1000
21 1000+1000 940
20 970+970 920
19 910+910 880
18 860+860 845
17 800+800 820
16 770+770 760
15 650+650 710
14 560+560 680
13 520+520 640
12 460+460 610
11 410+410 560
10 360+360 520
9 330+330 475
8 300+300 440
7 280+280 415
6 210+210 370
5 190+190 320
4 280 280
3 230 230
2 200 200
1 160 160
0 0 0
179
The highest speed for each model under normal running condition
Single fan
Horse power 8 10 12 14 16
Speed 0~16 0~16 0~17 0~19 0~19
Double fan
Horse power 18 20 22 24 26
Speed 0~19 0~20 0~21 0~22 0~22
a. In cooling mode
Startup procedure: When compressor starts up, if Ta≥35°C, the outdoor motor will run at the highest class; if
25°C≤Ta<35°C, the outdoor motor will run at the 15class; if 15°C≤Ta<25°C, the outdoor motor will run at the 6
class, if Ta<15°C, the outdoor motor off, the outdoor motor will run automatically after 45 seconds.
In operation, the motor control by the high pressure. If Pd<15kg, the motor will run at 1 class, off after 1min;
if15kg≤Pd<20kg, the motor will reduce 1 class every 20 seconds, until the lowest class; if 20kg≤Pd<25kg, the
motor run at the current speed, if 25kg≤Pd<32kg, the motor will raise 1 class every 20 seconds, if Pd≥32kg, the
motor will run at the highest class immediately.
b. In heating mode
When compressor starts up, if Ta<10°C, the outdoor motor will run at the highest class; if 10°C≤Ta<20°C, the
outdoor motor will run at the 5 class; if Ta≥20°C, the outdoor motor will run at the 1 class; the outdoor motor will
run automatically after 60 seconds.
In operation, the motor control by the high pressure. If Pd>37kg, the motor will be off immediately; if
33kg<Pd≤37kg, the motor will reduce 1 class every 20 seconds; if 28kg<Pd≤33kg, the motor run at the current
speed, if 24kg<Pd≤28kg, the motor will raise 1 class every 20 seconds, if Pd≤24kg, the motor will run at the
highest class immediately.
② Compressor start protecting control: Within the 3 min after starting, the operating frequency of compressor
keeps at 50rps or 60rps. 3 min later, if Td SH is higher than 25℃ , withdrawal from the starting process and
conduct target Pd or target Ps control; 3min later, if Td SH is lower than 25℃ , the frequency goes up to 100rps
and withdrawal from the starting until the Td SH is higher than25℃ or the starting time reaches 15min. In the
process of starting, protecting control has the priority.
180
[Note] Frequency maintained within the 3 min after starting is as follows:
⑤ Changes of the number of compressor (take the multiple connection of 3 double compressor of outdoor unit as
example)
Compressor shifts its number of operating with the different operating frequency according to the following pictures.
※ No.1 in the following picture represents the compressor with the highest priority, and outdoor unit 1 represents
the outdoor unit with the highest priority, and so on.
1. At first, when operating frequency of one compressor of the outdoor unit 1 is less than 75% of the highest
frequency, only No. 1 compressor works.
181
2. When operating frequency of one compressor rises up to the 75% of the highest frequency, two compressors in
the outdoor unit 1 will work at the same time.
3. When the operation output ratio of the outdoor unit 1 (actual operating frequency/total operating frequency)
continue to rise up to the 75%, two compressors in the outdoor unit 2 will also work at the same time.
4. When the total operation output ratio of the outdoor unit 1 and outdoor unit 2 (actual operating frequency/total
operating frequency) rises up to the 75%, two compressors in the outdoor unit 3 will also work at the same time.
5. When the total operation output ratio of the outdoor unit 1, outdoor unit 2 and outdoor unit 3 declines to the
25%, two compressors in the outdoor unit 3 will stop at the same time, outdoor unit 1 and outdoor unit 2 continue
to operate.
6. When the total operation output ratio of the outdoor unit 1 and outdoor unit 2 declines to the 25%, two
compressors in the outdoor unit 2 will stop at the same time, and the two compressors in outdoor unit 1 continue
to operate.
7. When the total operation output ratio of the outdoor unit 1 declines to the 25%, the No. 2 compressor of
outdoor unit 1 will stop and the No. 1 compressor continues to operate.
182
21.5 Oil return control
1. Entering condition
When outdoor total running capacity is over 25% and less than 75% for 4 hours, or outdoor total running
capacity is less than 25% for 2 hours, the system will enter oil return operation.
*When outdoor total running capacity is over 75% for 10minutes continuously, the oil return time will be cleared.
*In defrosting operation, when outdoor total running capacity is over 75% for 5 minutes continuously, the oil
return time will be cleared.
2. Oil return procedure:
All outdoors start up, and run with 75% of total capacity in cooling mode; In oil return course, outdoor leva1, 2
open to 250pls;
In oil return course, THERMO ON, indoor valves 250pls, THERMO OFF, indoor valves 125pls; when Tdi or Toil
is over 105°C, indoor valve will open larger 10%.
In oil return, Levb OFF.
Oil return quit condition:
After 8 minutes
&
< 3℃ 6
Defrost process
• In the case of Little frost and short defrosting time taken, the indoor units will keep running without any change,
defrosting is achieved by bypass heating;
• When the frost is small and the defrosting time is long, defrosting is achieved by hot bypass, and the indoor
units will enter the anti-cold air mode, and the air speed of the indoor units will be changed from high to mid or low
speed.
• When there is a heavy frost , no matter it happens to one condenser or more, whether it is single module or
combined module, the 4-way valve of the whole system will change direction together, defrosting will be achieved.
Indoor units fans stop running, there is no air out from the indoor units.
183
Quit condition:
The program reserves the enhanced defrosting control, to solve the problem of defrosting is not clean, the quit
condition is changed to
·>3.7MPa
Normal Pd=3.7MPa
Upper limitation control
operation
·& ·≤3.7MPa
·When the limitation control is completed
* Restart after 3 minutes
※1
High pressure
switch OFF Error stop
184
21.9 Low pressure protection
By SV1 and compressor operating frequency control to maintains the low pressure above a specified value.
Ps<0.1Mpa
·<0.15Mpa
Normal Compressor speed
operation SV1: ON upper limitation control
· ≥0.20Mpa ≥0.15Mp (Max. 30rps)
·<0.05Mpa ·<0.03Mpa
Protection stop Error stop
·Td high temperature side (≤120°C) is controlled by the “indoor unit SH correction + SV3 LEVb control +
compressor frequency control”. (Note) Compressor frequency control is performed by fuzzy control. .
When the discharge temperature Td≥95°C, the SV3 is turned on.
When the discharge temperature Td≥105°C, the compressor reduce the frequency
When the discharge temperature Td ≤ 90°C, Recovery usually control
In cooling:
·Td low temperature side (﹤CT+10°C) is controlled by the[the first stage is indoor unit SH control/ the second
stage is compressor output control/ the third stage is minimum number of outdoor units running control
Protection
Error stop
stop
185
In heating:
·Td low temperature side (﹤CT+10°C) is controlled by the[the first stage is indoor unit SH control/ the second
stage is compressor output control/ the third stage is
minimum number of outdoor units running control
·﹤CT+15°C ·﹤CT+10°
Compressor rps ※3 Min. number control
correction control of outdoor unit
(TdSH20°C constant)
Protection
Error stop
stop
CH: ON
OFF
Oil temperatureToil(°C) → 60 65
When the compressor oil temperature Toil is 60-65 ° C, it starts from ON.
CH: Heater (Crank Case Heater)
186
21.15 Target pressure control
① Cooling low pressure control
• During cooling, the operating frequency of compressor is fuzzy controlled based on target Ps.
• The frequency of compressor goes down and Ps goes up; the frequency of compressor goes up and Ps goes
down.
• During cooling, if the low pressure reaches 1.05MPa, control the LEV of all indoor units to make sure it will not
exceed 1.05MPa.
[Note] The one-way connection piping of unit is generally defined as: when the longest piping is less than 30m,
it is short piping; 30-90m, medium piping; more than 90m, long piping. The specific situation is determined by
installation in site.
① When the temperature at the top of compressor rises, the corresponding SV3 is started to conduct the liquid
bypass cooling.
(Refer to Figure) Td high temperature side ( ≦ 120℃ ) control / SV3 control
When Td ≥100℃ , in cooling, the indoor unit SH modification control, maximum modification value - 5
When Td ≥105, control the compressor frequency
187
21.17 Current protection control
① If the current of compressor exceeds the stipulated upper limit value, the operating frequency is reduced for
control before the current changes to exit value or below.
② When the current cannot reach the upper limit value or below even at the lowest rotating speed (20rps), the
compressor will stop operating.
③ If the current reaches the exit value or below, it will get back to the target rotating speed.
188
22. Failure code
Indication
Master unit
on wired Failure code
digital tube Failure description Remarks
controller definition
display
(hex)
AD value is below 11(open circuit) or over
1012(short circuit)for 60 seconds,in cooling
Defrosting temp.
20-0 14 mode,if the sensor is abnormal,the unit does Resumable
sensor Tdeffailure
not deal with it,besides,in defrosting and
within 3 minutes after defrosting,no alarm
Ambient temp.sensor
21 15
Ta failure AD value is below 11(open circuit) or over
Resumable
Suction temp.sensor 1012(short circuit)for 60 seconds
22-2 16
Ts(acc) failure
Discharging temp.
23-0 17
sensor Td1 failure AD value is below 11(open circuit) or over
Resumable
Discharging temp. 1012(short circuit)for 60 seconds
23-1 17
sensor Td2 failure
189
Master
Indication
unit
on wired Failure code
digital Failure description Remarks
controller definition
tube
(hex)
display
High pressure switch
30-0 1E
HPSi failure Once
If disconnect for 2s continuously,alarm.If alarm 3
confirmation un-
times in an hour,confirm the failure
High pressure switch resumable
30-1 1E
HPS2failure
Once
AT24C04 EEPROM data check failure(model
33-2 21 EEPROM failure confirmation un-
code,check sun etc)
resumable
AT24C04 EEPROM data check failure(data
33-3
beyond limit,reverse sequence etc)
Discharging temp.too Td ≧ 120℃ continuous 2sec exceeds the set
34-0 22
high protection(Td1)value after shutdown alarm; the alarm condition Once
after stopping the oil temperature below 10 confirmation un-
Discharging temp.too
34-1 22 degrees, automatic recovery after 2min50s. Four resumable
high protection(Td2)
times an hour to confirm the fault
After 4-way valve is electrified for 10 minutes,if
the below conditions can be met for continous
10 seconds,that is conversing successfully.
Once
4-way valve reversing This outdoor compressor is running normally
35-0 23 confirmation un-
failure Td1orTd2-Tdef1≥10℃& Toci-Tao≤5℃& Pd-
resumable
Ps≥0.3MPa
Otherwise,the system alarms reversing failure
If it occurs 3 times in an hour,confirm the failure
After the start of the main outdoor machine
Once
4-way valve reversing 20min still have a child of the four way valve
35-1 23 confirmation un-
failure is not on the electricity is reported 35-1 fault. 2
resumable
times an hour to confirm the fault。
Oil temp.too low In normal operation,if Toil < CT+10℃ for
36-0 24
protection(Toil1) continuous 5 minntes,the unit stop and Once
alarm.2 minutes and 50 seconds later,resume confirmation un-
Oil temp.too low automatically.If it occurs 3 times in an resumable
36-1 24
protection(Toil2) hour,confirm the failure
After compressor is running(except for residual
operation),if in cooling,Ps < 0.01MPa or in
Low pressure sensor heating,Ps < 0.05MPa for continuous 5
39-0 27
Ps too low protection minutes,alarm and stop。2 minutes and 50
seconds later,resume automatically。If it Once
occurs 3 times in an hour,confirm the failure。 confirmation un-
After compressor is running,compression ratio resumable
Compression ratio ε > 10.0 forcontinuous 5 minutes ,stop and
39-1 27 too high alarm。2 minutess and 50
Protection Seconds later,resume automatically。If it
occurs 4 times in an hour,confirm the failure。
If Pd≥4.15MPa,alarm and stop,2 minutes and Once
High pressure sensor
40 28 50 seconds later,resume automatically。If it confirmation un-
Pd too high protection
occurs 3 times in an hour,confirm the failure。 resumable
190
Indication
Master unit
on wired
digital tube Failure code definition Failure description Remarks
controller
display
(hex)
In normal operation,If Td < CT+10℃
Discharging temp.sensor
43-0 2B for continuous 5 minutes,the unit stops Once
Tdi too low protection
and alarms.2 minutes and 50 seconds confirmation un-
Discharging temp.sensor later,resume automatically.If it occurs 3 resumable
43-1 2B times in an hour,confirm the failure.
Td1 too low protection
Communication failure
45 2D Continuous 30 seconds no communication
between outdoors
Communication failure
46-0 Continuous 30 seconds no communication
with INV1 module board
Communication failure
46-1 Continuous 30 seconds no communication
with INV2 module board
2E resumable
Communication with fan 1
46-4 Continuous 30 seconds no communication
module board
76-1 Incorrect outdoor address The address of sub machine and host
4C data does not match the EEPROM set Reset
or capacity setting
The capacity setting of sub machine and
76-2 host data does not match the EEPROM
set
Incorrect parameter Outdoor machine type dial code settings
Non
83 53 setting or incorrect match error or with the host model does not
recoverable
of outdoor unit match
191
Indication
Master unit
on wired Failure code
digital tube Failure description Remarks
controller definition
display
(hex)
The normal
running mode
is stop\ cooling
99-0 System abnormality, chip interference.
\ heating, and
other modes are
abnormal.
The defrosting and
oil return process Resum-
63 The system is abnormal and does not meet
99-1 of the master able
the exit conditions. check the sensor.
unit exceeds the
normal time
The defrosting
and oil return
The system is abnormal and does not meet
99-2 process of the
the exit conditions. check the sensor.
slave unit exceeds
the normal time
The master unit 1.the high and low pressure differential of
start -up operation the slave unit does not meet the condition of
99-3
process exceeds <0.2MPa
the normal time 2.check the SV1 and pressure sensor
The master unit
stop operation The system is abnormal and does not meet
99-4 Resum-
63 process exceeds the exit conditions. check the sensor.
able
the normal time
The start-up and
1.the high and low pressure differential of
stop process of
the slave unit does not meet the condition of
99-5 the slave unit
<0.2MPa
exceeds the
2.check the SV1 and pressure sensor
normal time
Module rectifier side
-
108 6C software transient
overcurrent -0:
Module rectifier side compressor
109 6D current detection - module 1;
circuit anomaly -1:
compressor
Hardware over current of press drive module. module 2;
Module hardware -4: fan
110 6E
overcurrent module 1;
Instantaneous over current of module rectifier
-5: fan
side hardware.
module 2;
In the process of starting or running, the rotor (Other faults
Compressor out of position can not be detected for 6 times in a can be
111 6F
step row, and the INV control board is automatically recovered
restored after stopping 5S except 110
The temperature more than 94℃ fault alarm. fault which
High temperature of is locked
112 70 Automatic recovery of INV control board when
module radiator four times
temperature is 94℃
an hour.)
113 71 Module overload -
192
Indication
Master unit
on wired
digital tube Failure code definition Failure description Remarks
controller
display
(hex)
When the supply voltage is less than
DC420V, the fault alarm.
Module DC bus DC
114 72 When the voltage is greater than
undervoltage
DC420V, the INV control board is
automatically restored
When the supply voltage is greater
than DC642V, the fault alarm.
Module DC bus DC
115 73 When the voltage is less than DC642V,
overvoltage
the INV control board is automatically
restored.
For 30 seconds, the communication
Communication error
signal is not detected, and the INV
116 74 between module and
control board is recovered immediately -0: compressor
control board
after detection module 1;
Module rectifier side software -1: compressor
instantaneous overcurrent. module 2;
Modular software -4: fan module
117 75 Module overload.
overcurrent 1;
Module software over current. -5: fan module
118 76 Module boot failure Compressor 5 consecutive start failure 2;
The module rectifier side current (Other faults
detection circuit is abnormal. can be
recovered
Current detection circuit The sensor used for current detection
119 77 except 110 fault
fault. of frequency converter contriller is
which is locked
abnormal,disconnected or incorrectly
four times an
connected.
hour.)
Inverter controller power supply
120 78 Module power supply error
instantaneous interrupt
Module control board Inverter controller board power supply
121 79
power supply abnormal instantaneous interrupt
Module radiator
Temperature sensor resistance is
122 7A temperature sensor
abnormal or not connected
abnormal
Module rectifier side
123 7B hardware transient -
overcurrent
Three phase power supply
124 7C -
failure
193
Indication
Master unit
on wired Failure code
digital tube Failure description Remarks
controller definition
display
(hex)
(the current frequency is greater than or
Compressor
equal to INV or +3Hz target frequency
125-0/1 7D frequency resumable
(frequency) target actual frequency >0 & &
mismatch
=0) for 5 minutes
"Fan speed Operation below 20rpm lasts for 30s,or
125-4/5 7D mismatch less than 20% of the target value lasts for 2 resumable
(locked rotor)" minutes.
If the host detects sub machine MCU reset,
and the machine is in operation, the host
MCU reset the fault, the whole system
127 7F MCU reset fault down; if in the heating mode, then restart the resumable
4WV power, the system re 4WV reversing
operation. Four fault confirmation for one
hour
In the case of no fault, if the system does not meet the start-up conditions, the host digital display standby code:
Indoor machine capacity beyond the Indoor machine capacity beyond the outdoor
555.0 outdoor machine capacity of 150% or less machine capacity of 150% or less than 50%,
than 50%, standby system standby system
Ambient temperature above 26 degrees indoor
555.1 26 degree standby
heat can not boot
Refrigeration Ps<0.23Mpa or heating
555.2 Low pressure (gas) standby
Ps<0.12Mpa start, system standby
54 degrees above the cooling outdoor 54 degrees above the cooling outdoor machine resumable
555.3
machine is not running is not running
Power inhibit setting maximum capacity output
555.5 Power restriction
is 0%
Password lock system to set the maximum
555.6 Password lock
operating time to the system standby
555.8 No trial running No trial running
※Failure code distribution introduction
0 ~ 19:indoor unit failure
20 ~ 99:outdoor unit failure
108 ~ 125:inverter module failure
126 / 127:soft self-detect
194
23. Troubleshooting
23.1 Flow chart
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Defrosting temperature sensors:
digital 20 times Tdef failure
display tube:
20-0 LED1 LED2
Indoor wired Outdoor unit LED status
controller: Normal
Normal Normal
14
Diagnosis Troubleshooting
MRV 5 series
3. Abnormity confirmation
conditions
4. Possible causes
Y
◆ The connection of sensor is
not secure;
◆ The sensor is broken;
◆ The sensor is with
resistance drift;
Check if the temperature
◆ The temperature acquired Y
loop acquired by the Replace it correctly by after-
by PCB is not accurate.
computer board is normal sales personnel on site.
195
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Ambient temperature sensor:
digital 20 times Tao failure
display tube:
21 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
15
Diagnosis Troubleshooting
MRV 5 series
4. Possible causes
Y
196
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Suction temperature sensor:
digital 20 times Ts failure
display tube:
22-2
LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
16 Normal Normal
Diagnosis Troubleshooting
MRV 5 series
3. Abnormity confirmation Y
conditions
4. Possible causes
Y
197
FFailure LED5 Failure description:
code Indoor unit LED status Discharging temperature sensor:
Outdoor 20 times Td1and Td2 failure
digital
display tube: LED1 LED2
23-0,1
Indoor wired Outdoor unit LED status
controller: Normal Normal
17
Diagnosis Troubleshooting
MRV 5 series
3. Abnormity confirmation
conditions
Check if resistance
It is detected that the AD value characteristic of the sensor N Replace it correctly by after-
is below 11 (open circuit) or is normal sales personnel on site.
above 1012 (short circuit) for
60 seconds continuously. If
Ta≤-10°C the open circuit is
detected after 3 minutes of
compressor operation (AD Y
value is below 11).
4. Possible causes
198
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Oil temperature sensor:
digital display 20 times Th, Toil1 and Toil2 failure
tube: 24-0, 1, 2
Indoor wired LED1 LED2
controller: Outdoor unit LED status
18 Normal Normal
Diagnosis Troubleshooting
MRV 5 series
3. Abnormity confirmation Y
conditions
4. Possible causes
Y
199
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Heat exchanger inlet temperature:
digital 20 times Toci1 failure
display tube:
25-0 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
19
Diagnosis Troubleshooting
MRV 5 series
3. Abnormity confirmation Y
conditions
200
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Communication between indoor unit and
digital 20 times outdoor unit failure
display tube:
26-0, 1, 2 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
1A
Diagnosis Troubleshooting
MRV 5 series
◆ Grounded short-circuit
of communication wire, or
disconnected communication N
wire P and Q;
◆ Incorrect wiring of
communication wire P and Q; Check if the communication wire Y Replace it correctly by after-
◆ Uniform indoor unit power of outdoor unit is disconnected sales personnel on site.
supply, and partial indoor unit
being powered off.
◆ Larger interference and
unstable communication signal. N
◆ Failure in PCB of indoor and
outdoor unit results in unstable
communication.
Check if the communication
Y
wire P and Q of indoor and Replace it correctly by after-
3. Abnormity confirmation
outdoor unit is incorrect sales personnel on site.
conditions
4. Possible causes
Check if the computer board
N
communication port of indoor Adjust it correctly by after-
and outdoor unit is correct sales personnel on site.
201
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Outdoor compressor oil temperature too
digital 20 times high failure(Toil1 and Toil2)
display tube:
27-0, 1 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
1B
Diagnosis Troubleshooting
MRV 5 series
Toil1/Toil2≥120°C.
4. Possible causes
202
Failure code LED5 Failure description:
Outdoor Indoor unit LED status High pressure sensor Pd failure
digital 20 times
display tube:
28 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
1C
Diagnosis Troubleshooting
MRV 5 series
3. Abnormity confirmation Y
conditions
4. Possible causes
Y
203
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Low pressure sensor Ps failure
digital 20 times
display tube:
29 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
1D
Diagnosis Troubleshooting
MRV 5 series
3. Abnormity confirmation Y
conditions
4. Possible causes
Y
204
Failure code LED5 Failure description:
Outdoor Indoor unit LED status High pressure switch HPS1 and HPS2 fail-
digital 20 times ure
display tube:
30-0, 1 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
1E
Diagnosis Troubleshooting
MRV 5 series
205
FFailure LED5 Failure description:
code Indoor unit LED status Defrosting temperature sensor failure:
Outdoor 20 times Tsco and Tliqsc
digital
display tube: LED1 LED2
32-0, 1
Indoor wired Outdoor unit LED status
controller: Normal Normal
20
Diagnosis Troubleshooting
MRV 5 series
3. Abnormity confirmation Y
conditions
4. Possible causes
206
LED5 Failure description:
Failure code
Indoor unit LED status AT24C04 EEPROM communication failure
Outdoor AT24C04 EEPROM data check failure
20 times
digital display IM EEPROM data or communication failure
tube: 33-0, 2, 3
LED1 LED2
Indoor wired
Outdoor unit LED status
controller: 21
Normal Normal
Diagnosis Troubleshooting
MRV 5 series
EEPROM communication
error; EEPROM data check
error (model ID, checksum,
Y
etc.); EEPROM data logic error
(wider data range, wrong order,
etc.)
4. Possible causes
Replace EE.
◆ EEPROM is an old version,
while the program is a new
version.
207
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Outdoor compressor discharging tempera-
digital 20 times ture (Td1, Td2).too high failure
display tube:
34-0, 1 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
22
Diagnosis Troubleshooting
MRV 5 series
4. Possible causes
Y
208
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Four-way valve reversing failure
digital 20 times
display tube:
35-0, 1 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
23
Diagnosis Troubleshooting
MRV 5 series
4. Possible causes
Check if it operates normally N Replace the driver module
◆ The detection value of high/ after replacing with a normal correctly.
low pressure sensor is incorrect; driver module.
◆ The refrigerant in the system
is insufficient;
◆ The four-way valve cannot be Y
switched normally or with backflow.
◆ The filter of compressor Check if the allowed
suction pipe is blocked by operation range is exceeded.
foreign matters;
◆ The detection value of Tsuc or
Tdef1/2 sensor is incorrect; Y
The power module cannot drive the
compressor operating normally; Use the unit in accordance with
◆ The operation environment its allowed operation range.
is beyond the allowed range.
209
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Outdoor compressor oil temperature (Toil1,
digital 20 times Toil2) too low failure
display tube:
36-0, 1 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
24
Diagnosis Troubleshooting
MRV 5 series
210
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Low pressure sensor Ps too low protection
digital 20 times
display tube:
39-0 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
27
Diagnosis Troubleshooting
MRV 5 series
211
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Compressor ratio ε too high protection
digital 20 times
display tube:
39-1 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
27
Diagnosis Troubleshooting
MRV 5 series
4. Possible causes
N
◆ The detection value of high/
low pressure sensor is incorrect;
◆ The refrigerant in the system N Check if all the electronic
Check if the allowed operation
is insufficient or the system is range is exceeded. expansion valves of the indoor unit
with air leakage; can be turned on normally.
◆ The pipelines on the high
pressure side or liquid side of
Y
the unit are blocked;
◆ The outdoor unit cannot be Use the unit in accordance with
turned on normally due to failure its allowed operation range.
to open electronic expansion of
outdoor heat exchanger when
heating;
◆ The operation environment is
beyond the allowed range.
212
Failure code LED5 Failure description:
Outdoor Indoor unit LED status High pressure sensor Pd too high protec-
digital 20 times tion
display tube:
40 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
28
Diagnosis Troubleshooting
MRV 5 series
3. Abnormity confirmation Y
conditions
N
4. Possible causes
213
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Outdoor unit compressor discharging tem-
digital 20 times perature (Td1, Td2) too low failure
display tube:
43-0, 1 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
2B
Diagnosis Troubleshooting
MRV 5 series
Check if the terminal of outdoor unit N Replace the poor valve (with
4. Possible causes leakage) and fan correctly by after-
terminal LEVb, SV31 and SV32 is
connected properly or is closed tightly. sales personnel on site.
◆ The probe of oil temperature
sensor falls off or is with
unsecure connection;
Y
◆ The probe of oil temperature
sensor is misplaced;
◆ The oil temperature sensor Check if the outdoor unit LEVa1, N Replace it correctly by after-sales
is with resistance drift; 2 and LEVb are connected personnel on site.
◆ The outdoor unit LEVb, properly and correctly.
SV31 and SV32 are with
leakage;
Y
◆ The terminal of outdoor
unit LEVa1, 2 and LEVb is Check if the unit is filled with Check if the computer board
N
connected incorrectly; excessive refrigerant. can normally control the related
◆ For the unit, there is LEV electronic expansion valve and
leakage in shutdown indoor solenoid valve, if not, replace it.
unit and non-operation of fan in Y
operating indoor unit; Fill with refrigerant in
◆ The system is filled with accordance with standard
excessive refrigerant. quantity.
◆ The operation environment
is beyond the allowed range.
214
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Communications between outdoor units
digital 20 times failure.
display tube:
45 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
2D
Diagnosis Troubleshooting
MRV 5 series
Check if the communication wire N Replace it correctly by after-
2. Abnormity detection method between the outdoor units is normal.
sales personnel on site.
Y
3. Abnormity confirmation
conditions
No communication for 30s (E) Check if there is interference source in the Y Clear the interference
position where the outdoor unit is installed.
4. Possible causes source.
◆ Poor communication N
wire: short circuit or
disconnection;
◆ Non-corresponding
communication wire A, B and Power off the outdoor unit and research it.
C;
◆ Incorrect connection of
outdoor unit communication
port of PCB;
◆ Interference source, N
which causes unstable
communication of outdoor
unit.
Replace the outdoor unit PCB
215
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Communication with INV1 and INV2 module
digital 20 times board failure
display tube:
46-0, 1 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
2E
Diagnosis Troubleshooting
MRV 5 series
4. Possible causes
N
216
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Communication with fan motor module
digital 20 times board 1, 2 failure
display tube:
46-4, 5 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
2E
Diagnosis Troubleshooting
MRV 5 series
217
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Communication with wireless communicai-
digital 20 times ton module failure
display tube:
47 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
2F
Diagnosis Troubleshooting
MRV 5 series
Check if the dip switch of BM2-1 and N Change the dip switch by
BM2-2 is OFF position after-sales personnel on site.
3. Abnormity confirmation
conditions
4. Possible causes
218
Failure code LED5 Failure description:
Outdoor Indoor unit LED status LEVa1,2 and LEVb,c over current protection
digital 20 times
display tube:
51-0,1,2,3 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
33
Diagnosis Troubleshooting
MRV 5 series
4. Possible causes
N
219
Failure code LED5 Failure description:
Outdoor Indoor unit LED status LEVa1,2 and LEVb,c open circuit
digital 20 times
display tube:
52-0,1,2,3 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
34
Diagnosis Troubleshooting
MRV 5 series
N
2. Abnormity detection method Check if the electronic expansion Reconnected by after-sales
valve coil terminal plug well personnel on site.
4. Possible causes
N
220
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Emergency stop function switch failure
digital 20 times
display tube:
74 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
4A
Diagnosis Troubleshooting
MRV 5 series
3. Abnormity confirmation
conditions If the PCB CN18 is short N
Short circuit the CN18
circuit
4. Possible causes
221
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Pressure difference between high and low
digital 20 times pressure too low failure
display tube:
75-0 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
4B
Diagnosis Troubleshooting
MRV 5 series
222
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Incorrect settings of quantity, address or
digital 20 times capacity for outdoor unit
display tube:
76-0, 1, 2 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
4C
Diagnosis Troubleshooting
MRV 5 series
N
3. Abnormity confirmation
conditions
4. Possible causes
223
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Outdoor unit model are set incorrectly
digital 20 times
display tube:
83 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
53
Diagnosis Troubleshooting
MRV 5 series
4. Possible causes
224
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Compressor module hardware over current
digital 20 times
display tube:
110-0 ,1 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
6E
Diagnosis Troubleshooting
MRV 5 series
N
2. Abnormity detection method Check if the supply voltage is normal Rectify on site by after-sales
personnel.
◆ Check if the modules are in
normal conditions and if P and Y
N are short-circuited to U, V
and W.
◆ Check if the modules are
fixed securely and the heat Check if the electrical cabinet and
compressor wires are secured, the N
dissipation is good; UVW is correctly connected and Rectify on site by after-sales
◆ Check if the compressor the variable frequency board and personnel.
resistance is normal, module board are wired correctly.
◆ Check if the compressor
wiring UVW is wrongly
connected and if the inverter
board and module board are Y
wired securely.
N Replace on site by after-sales
Check if the power module is normal personnel.
3. Abnormity confirmation
conditions
225
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Fan motor module hardware over current
digital 20 times
display tube:
110-4, 5 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
6E
Diagnosis Troubleshooting
MRV 5 series
N
2. Abnormity detection method Check if the supply voltage is normal Rectify on site by after-sales
personnel.
226
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Compressor out of control
digital 20 times
display tube:
111-0 ,1 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
6F
Diagnosis Troubleshooting
MRV 5 series
N
Check if the supply voltage is normal Replace on site by after-sales
personnel.
2. Abnormity detection method
Y
◆ Check if the module is in
normal conditions and if P and
N is short-circuited to U, V and
W; Measure with diode to see if Check if the electrical cabinet and
there is a voltage drop between compressor wires are secured, the N
UVW is correctly connected and Replace on site by after-sales
P/N and U/V/W.
the variable frequency board and personnel.
◆ Check if the module is
module board are wired correctly.
securely fixed and the heat
dissipation is good;
◆ Check if the compressor
winding is normal.
◆ Check if the compressor Y
wiring UVW is connected
correctly and the inverter board Check if the PWM signals
from 6 channels on variable N Replace the variable frequency
and module board is securely
frequency control board and control board.
wired.
IPM driver board are normal.
3. Abnormity confirmation
conditions
Y
Over current of module N
hardware Replace the power module.
Check if the power module is normal
4. Possible causes
Y
◆ The module alarms failure
as it broke down;
◆ Liquid shock is found in Check if the compressor, resistance N
compressor which results in and insulation are normal Replace the compressor.
over current upon starting or
operating;
◆ The compressor winding is Y
burned out;
◆ UVW wiring is wrongly The compressor is overloading
and check for the causes.
connected or the inverter board
and module board are wired
insecurely.
227
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Compressor module radiator temp. too high
digital 20 times
display tube:
112-0 ,1 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
70
Diagnosis Troubleshooting
MRV 5 series
3. Abnormity confirmation Check if the module is N Secure the module and paint
conditions secured and the cooling with radiating silica gel evenly.
silica gel is even up
Raise failure alarm when
temperature ≥94°C.
INV control board recovers Y
automatically when
temperature ≤94°C.
N
4. Possible causes Check if has 117 failure Replace the power module.
228
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Fan motor module radiator temp. too high
digital 20 times
display tube:
112- 4, 5 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
70
Diagnosis Troubleshooting
MRV 5 series
229
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Compressor module DC BUS under voltage
digital 20 times
display tube:
114-0 ,1 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
72
Diagnosis Troubleshooting
MRV 5 series
3. Abnormity confirmation
conditions
Y
Raise failure alarm when
power voltage<DC420V.
INV control board recovers Test if the voltage of DC bus is Y The detection circuit of variable
automatically when voltage below 420V. frequency board is damaged,
>DC420V replace the board.
4. Possible causes
N
◆ Incorrect wiring may result
Replace and compare the
in under voltage alarm;
neighboring electrical cabinet
◆ PTC or relay damage may
by troubleshooting.
result in under voltage;
◆ Low power voltage may
result in under voltage.
230
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Fan motor module DC BUS under voltage
digital 20 times
display tube:
114-4, 5 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
72
Diagnosis Troubleshooting
MRV 5 series
3. Abnormity confirmation
conditions
Y
When the power voltage
<DC283V, fault and alarm.
Voltage> DC283V, the When the fan running, testing the Y
DC voltage between DC + (red Replace the fan motor
motor built-in control panel
automatically restored line), DC- (white line) if it less
than 283?
4. Possible causes
N
◆ Incorrect wiring may result
in under voltage alarm; Check the rectifier bridge,
◆ PTC or SCR damage may reactor, electrolytic capacitor
result in under voltage; of inverter main circuit
◆ Low power voltage may
result in under voltage.
231
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Compressor module DC BUS over voltage
digital 20 times
display tube:
115-0, 1 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
73
Diagnosis Troubleshooting
MRV 5 series
Raise failure alarm when Test if the voltage of DC bus is above 642V. Y The detection circuit of variable
power voltage>DC642V. frequency board is damaged.
INV control board recovers Replace the board.
automatically when voltage
N
<DC642V.
Replace and compare the
4. Possible causes neighboring electrical cabinet
by troubleshooting.
◆ Incorrect connection may
result in over voltage alarm;
◆ High power voltage may
result in over voltage.
232
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Compressor module software over current
digital 20 times
display tube:
117-0, 1 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
75
Diagnosis Troubleshooting
MRV 5 series
N
Check if the supply voltage is normal. Adjust the supply voltage.
2. Abnormity detection method
Y
◆ Check if the compressor is
insecurely connected;
◆ Check the system for liquid
shock.
Check if the electrical
◆ Check if the module is in
cabinet is wired correctly, N
normal conditions and subject Readjust wiring and fixing method in
to short circuit. the compressor matches
accordance with the circuit diagram.
◆ Check if the compressor is U, V and W correctly
well. and the variable frequency
◆ Check if the compressor board and module board
wiring UVW is connected is connected securely.
correctly and the inverter board
and module board is securely
wired.
Y
3. Abnormity confirmation N
conditions Replace the power module.
Check if the power module is normal.
Over current of module software
Y
4. Possible causes
N
Check if the detection circuit of Replace the variable frequency
variable frequency board is normal. board.
233
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Fan motor module software over current
digital 20 times
display tube:
117- 4, 5 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
75
Diagnosis Troubleshooting
MRV 5 series
N
Check if the supply voltage is normal. Adjust the supply voltage.
2. Abnormity detection method
Y
3. Abnormity confirmation N
conditions Replace the fan motor
Motor rotation is smooth, the sound
Double fan: fan running current is normal
value over 5.5A, single fan: fan
Y
running current value over 6A
N
4. Possible causes
Running current value is normal Replace the fan motor
234
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Current detecting circuit abnormal of com-
digital 20 times pressor module
display tube:
119-0, 1 LED1 LED2
Indoor wired Outdoor unit LED status
controller77 Normal Normal
Diagnosis Troubleshooting
MRV 5 series
4. Possible causes Y
To be continued
235
Continued
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Current detecting circuit abnormal of com-
digital 20 times pressor module
display tube:
119-0, 1 LED1 LED2
Indoor wired Outdoor unit LED status
controller77 Normal Normal
Diagnosis Troubleshooting
MRV 5 series
Y
◆ The inverter board and
current sensor is anti-
connected or the current
Confirm if the wiring harness
sensor is in incorrect between inverter control board N
direction. CN9 and module driver board Correct the wrong connection.
◆ The inverter board or CNDR1 is reliably connected?
current sensor is damaged.
To be continued
236
Continued
Diagnosis Troubleshooting
MRV 5 series
3. Abnormity confirmation N
conditions
237
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Compressor module power supply abnor-
digital display 20 times mal
tube:
120-0, 1 LED1 LED2
121-0, 1
Indoor wired Outdoor unit LED status
controller: 78, Normal Normal
79
Diagnosis Troubleshooting
MRV 5 series
N
2. Abnormity detection method Check if the supply voltage is normal Adjust the power supply.
Y
The power supply of inverter
control board is interrupted
instantly. Check if the voltage between P N The DC bus voltage of variable
and N is less than 375V. frequency board is abnormal,
4. Possible causes replace the board.
Y
◆ The supply voltage is found
with abnormal fluctuations. Check the rectifier bridge,
◆ The PTC or relay does not electrolytic capacitor, electric
contact. reactor in variable frequency
◆ The inverter control board is loop.
in poor performance.
238
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Radiator temp. sensor of compressor mo-
digital 20 times dule is abnormal.
display tube:
122-0, 1 LED1 LED2
Indoor wired Outdoor unit LED status
controller: 7A Normal Normal
Diagnosis Troubleshooting
MRV 5 series
◆ Check if the temperature Check if the sensor and N Adjust the connection
acquisition circuit of inverter variable frequency board is between temperature sensor
board is normal. connected correctly. and variable frequency
◆ Check if the resistance of board.
temperature sensor is normal.
◆ Check if they are connected
correctly Y
3. Abnormity confirmation
Check if the sensor N
conditions Replace the sensor.
resistance is normal.
The temperature sensor is
disconnected or the resistance
Y
is incorrect.
239
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Hardware instantaneous over current of the
digital display 20 times compressor module rectifier side
tube:
123-0, 1 LED1 LED2
Indoor wired
Outdoor unit LED status
controller: 78,
Normal Normal
7B
Diagnosis Troubleshooting
MRV 5 series
N
2. Abnormity detection method Check if the supply voltage is normal Adjust the power supply.
240
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Compressor module three-phase power
digital display 20 times failure
tube:
124-0, 1 LED1 LED2
Indoor wired
Outdoor unit LED status
controller: 78,
Normal Normal
7C
Diagnosis Troubleshooting
MRV 5 series
N
Check if the power supply voltage
2. Abnormity detection method Adjust the power supply.
too low or lack of phase
Y
◆ Check if the modules' R, S,
T are correct, if missing phase Check if the electrical box connect N Reconnect or re-fix it in
correctly accordance with wiring
◆ Check if the power supply of
diagram.
the electrical box lack of phase,
if the voltage is too low
Y
N Reconnect or re-fix it in
Check if the inverter module connect
accordance with wiring
3. Abnormity confirmation well diagram.
conditions
Y
Module three-phase power
failure N
Check if the inverter module is
Replace the inverter module
normal
4. Possible causes
241
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Compressor frequency un-match
digital 20 times
display tube:
125-0, 1 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
7D
Diagnosis Troubleshooting
MRV 5 series
N
2. Abnormity detection method Whether the power supply voltage is Adjust the power supply.
too low or fluctuating significantly
◆ Check if the communication
circuits of power module and Y
inverter board are securely
inserted and connected.
◆ Check if the power module Check if the electrical box connect N Reconnect or re-fix it in
is well. correctly accordance with wiring
diagram.
◆ Check if the inverter board
is well. Y
3. Abnormity confirmation
conditions N
Check if the inverter module is Replace the inverter module
(current frequency ≥ INV normal
target frequency +3Hz) or
(target frequency ≥0 && actual
Y
frequency =0) for continuous 5
minutes
Compressor winding resistance, N
4. Possible causes Replace the compressor
insulation is normal
◆ The power module and
inverter board are connected
loosely, which results in
detection failure of compressor
rotation speed.
◆ The power module is
damaged.
242
Failure code LED5 Failure description:
Outdoor Indoor unit LED status Fan motor speed un-match
digital 20 times
display tube:
125-4, 5 LED1 LED2
Indoor wired
Outdoor unit LED status
controller:
Normal Normal
7D
Diagnosis Troubleshooting
MRV 5 series
N
2. Abnormity detection method Whether the power supply voltage is Adjust the power supply.
too low or fluctuating significantly
Y
3. Abnormity confirmation
conditions
N
Check if the inverter module is Replace the inverter module
Hall signal logic built-in the fan normal
motor is wrong too many times
Y
4. Possible causes
243
23.2 Lack of refrigerant judgment method
(1) Refer to the R410A system static balance pressure reference value form
(2) Check if the temp. difference between coil pipe and ambient temp. less than 4oC, if yes, it means the system
lack of refrigerant.
244
23.3 The checking method for the valve
1. After the valve is energized, listen to the sound of valve action, if no action enter the next checking.
For the solenoid valve: check if the PCB terminal has 220V output, if yes, change the solenoid valve coil, if not OK,
change the solenoid valve body.
For the electronic expansion valve: measure the resistance value.
245
23.5 Fan motor detection standard
246
Fan motor code: 0150401919
247
23.6 Power module detection standard
P N
CN21
CN24
CN22
R S T U V W
248
23.7 Compressor detection standard
W U
249
23.8 Sensor resistance table
250
R80=50kΩ±3% B25/80=4450K±3%
Temp Resistance (kΩ) % (Resist. Tol)
(°C) Rmax R (t) Normal Rmin MAX (+) MIN (-)
0 1749.014 1921.993 2094.972 9 9
1 1651.431 1813.265 1975.099 8.93 8.93
2 1560.165 1711.646 1863.127 8.85 8.85
3 1474.737 1616.593 1758.449 8.78 8.78
4 1394.709 1527.611 1660.513 8.7 8.7
5 1319.683 1444.25 1568.817 8.63 8.63
6 1249.295 1366.096 1482.897 8.55 8.55
7 1183.21 1292.773 1402.336 8.48 8.48
8 1121.124 1223.935 1326.746 8.4 8.4
9 1062.756 1159.265 1255.774 8.33 8.33
10 1007.85 1098.474 1189.098 8.25 8.25
11 956.167 1041.293 1126.419 8.18 8.18
12 907.491 987.477 1067.463 8.1 8.1
13 861.621 936.799 1011.977 8.03 8.03
14 818.372 889.052 959.732 7.95 7.95
15 777.574 844.042 910.51 7.88 7.88
16 739.066 801.59 864.114 7.8 7.8
17 702.705 761.533 820.361 7.73 7.73
18 668.353 723.717 779.081 7.65 7.65
19 635.885 688.001 740.117 7.58 7.58
20 605.185 654.254 703.323 7.5 7.5
21 576.145 622.355 668.565 7.43 7.43
22 548.663 592.189 635.715 7.35 7.35
23 522.645 563.651 604.657 7.28 7.28
24 498.006 536.644 575.282 7.2 7.2
25 474.662 511.076 547.49 7.13 7.13
26 452.538 486.862 521.186 7.05 7.05
27 431.563 463.922 496.281 6.98 6.98
28 411.671 442.182 472.693 6.9 6.9
29 392.8 421.572 450.344 6.83 6.83
30 374.891 402.028 429.165 6.75 6.75
31 357.891 383.489 409.087 6.68 6.68
32 341.749 365.898 390.047 6.6 6.6
33 326.416 349.201 371.986 6.53 6.53
34 311.848 333.349 354.85 6.45 6.45
35 298.004 318.295 338.586 6.38 6.38
36 284.843 303.995 323.147 6.3 6.3
251
R80=50kΩ±3% B25/80=4450K±3%
Temp Resistance (kΩ) % (Resist. Tol)
(°C) Rmax R (t) Normal Rmin MAX (+) MIN (-)
37 272.329 290.407 308.485 6.23 6.23
38 260.427 277.493 294.559 6.15 6.15
39 249.104 265.216 281.328 6.08 6.08
40 238.329 253.541 268.753 6 6
41 228.073 242.437 256.801 5.93 5.93
42 218.308 231.873 245.438 5.85 5.85
43 209.01 221.82 234.63 5.78 5.78
44 200.154 212.252 224.35 5.7 5.7
45 191.715 203.142 214.569 5.63 5.63
46 183.674 194.467 205.26 5.55 5.55
47 176.009 186.204 196.399 5.48 5.48
48 168.703 178.333 187.963 5.4 5.4
49 161.735 170.832 179.929 5.33 5.33
50 155.089 163.682 172.275 5.25 5.25
51 148.748 156.866 164.984 5.18 5.18
52 142.698 150.367 158.036 5.1 5.1
53 136.924 144.168 151.412 5.03 5.03
54 131.411 138.255 145.099 4.95 4.95
55 126.148 132.613 139.078 4.88 4.88
56 121.122 127.229 133.336 4.8 4.8
57 116.32 122.089 127.858 4.73 4.73
58 111.732 117.181 122.63 4.65 4.65
59 107.347 112.494 117.641 4.58 4.58
60 103.157 108.018 112.879 4.5 4.5
61 99.15 103.741 108.332 4.43 4.43
62 95.319 99.654 103.989 4.35 4.35
63 91.655 95.748 99.841 4.28 4.28
64 88.149 92.014 95.879 4.2 4.2
65 84.795 88.443 92.091 4.13 4.13
66 81.584 85.028 88.472 4.05 4.05
67 78.511 81.761 85.011 3.98 3.98
68 75.569 78.636 81.703 3.9 3.9
69 72.752 75.645 78.538 3.83 3.83
70 70.052 72.781 75.51 3.75 3.75
71 67.466 70.04 72.614 3.68 3.68
252
R80=50kΩ±3% B25/80=4450K±3%
Temp Resistance (kΩ) % (Resist. Tol)
(°C) Rmax R (t) Normal Rmin MAX (+) MIN (-)
72 64.988 67.415 69.842 3.6 3.6
73 62.613 64.901 67.189 3.53 3.53
74 60.337 62.493 64.649 3.45 3.45
75 58.154 60.185 62.216 3.38 3.38
76 56.06 57.973 59.886 3.3 3.3
77 54.051 55.852 57.653 3.23 3.23
78 52.125 53.82 55.515 3.15 3.15
79 50.275 51.87 53.465 3.08 3.08
80 48.5 50 51.5 3 3
81 46.728 48.206 49.684 3.07 3.07
82 45.028 46.484 47.94 3.13 3.13
83 43.397 44.832 46.267 3.2 3.2
84 41.833 43.246 44.659 3.27 3.27
85 40.332 41.723 43.114 3.33 3.33
86 38.891 40.26 41.629 3.4 3.4
87 37.509 38.856 40.203 3.47 3.47
88 36.181 37.506 38.831 3.53 3.53
89 34.905 36.209 37.513 3.6 3.6
90 33.68 34.962 36.244 3.67 3.67
91 32.503 33.764 35.025 3.73 3.73
92 31.373 32.612 33.851 3.8 3.8
93 30.286 31.504 32.722 3.87 3.87
94 29.242 30.439 31.636 3.93 3.93
95 28.236 29.413 30.59 4 4
96 27.271 28.427 29.583 4.07 4.07
97 26.342 27.478 28.614 4.13 4.13
98 25.448 26.564 27.68 4.2 4.2
99 24.589 25.685 26.781 4.27 4.27
100 23.762 24.838 25.914 4.33 4.33
101 22.966 24.023 25.08 4.4 4.4
102 22.199 23.237 24.275 4.47 4.47
103 21.462 22.481 23.5 4.53 4.53
104 20.751 21.752 22.753 4.6 4.6
253
R80=50kΩ±3% B25/80=4450K±3%
Temp Resistance (kΩ) % (Resist. Tol)
(°C) Rmax R (t) Normal Rmin MAX (+) MIN (-)
105 20.067 21.049 22.031 4.67 4.67
106 19.408 20.372 21.336 4.73 4.73
107 18.773 19.72 20.667 4.8 4.8
108 18.162 19.091 20.02 4.87 4.87
109 17.573 18.485 19.397 4.93 4.93
110 17.005 17.9 18.795 5 5
111 16.459 17.337 18.215 5.07 5.07
112 15.931 16.793 17.655 5.13 5.13
113 15.422 16.268 17.114 5.2 5.2
114 14.933 15.763 16.593 5.27 5.27
115 14.46 15.275 16.09 5.33 5.33
116 14.005 14.804 15.603 5.4 5.4
117 13.565 14.349 15.133 5.47 5.47
118 13.141 13.911 14.681 5.53 5.53
119 12.733 13.488 14.243 5.6 5.6
120 12.339 13.08 13.821 5.67 5.67
121 11.958 12.685 13.412 5.73 5.73
122 11.591 12.305 13.019 5.8 5.8
123 11.238 11.938 12.638 5.87 5.87
124 10.897 11.584 12.271 5.93 5.93
125 10.567 11.242 11.917 6 6
126 10.249 10.911 11.573 6.07 6.07
127 9.943 10.593 11.243 6.13 6.13
128 9.647 10.285 10.923 6.2 6.2
129 9.362 9.988 10.614 6.27 6.27
130 9.087 9.701 10.315 6.33 6.33
131 8.822 9.425 10.028 6.4 6.4
132 8.566 9.158 9.75 6.47 6.47
133 8.319 8.9 9.481 6.53 6.53
134 8.08 8.651 9.222 6.6 6.6
135 7.85 8.411 8.972 6.67 6.67
136 7.629 8.18 8.731 6.73 6.73
137 7.416 7.957 8.498 6.8 6.8
138 7.209 7.741 8.273 6.87 6.87
139 7.011 7.533 8.055 6.93 6.93
140 6.82 7.333 7.846 7 7
254
R25=10kΩ±3% B25/50=3700K±3%
Temp Resistance (kΩ) % (Resist. Tol)
(°C) Rmax R (t) Normal Rmin MAX (+) MIN (-)
-30 145.819 135.018 124.217 7 7
-29 138.071 129.126 120.181 6.93 6.93
-28 131.793 123.339 114.885 6.85 6.85
-27 125.665 117.684 109.703 6.78 6.78
-26 119.706 112.18 104.654 6.71 6.71
-25 113.933 106.843 99.753 6.64 6.64
-24 108.361 101.687 95.013 6.56 6.56
-23 102.997 96.719 90.441 6.49 6.49
-22 97.847 91.946 86.045 6.42 6.42
-21 92.915 87.371 81.827 6.35 6.35
-20 88.2 82.994 77.788 6.27 6.27
-19 83.702 78.815 73.928 6.2 6.2
-18 79.417 74.832 70.247 6.13 6.13
-17 75.342 71.041 66.74 6.05 6.05
-16 71.471 67.437 63.403 5.98 5.98
-15 67.798 64.015 60.232 5.91 5.91
-14 64.316 60.769 57.222 5.84 5.84
-13 61.017 57.692 54.367 5.76 5.76
-12 57.895 54.778 51.661 5.69 5.69
-11 54.942 52.019 49.096 5.62 5.62
-10 52.149 49.409 46.669 5.55 5.55
-9 49.51 46.941 44.372 5.47 5.47
-8 47.016 44.607 42.198 5.4 5.4
-7 44.659 42.4 40.141 5.33 5.33
-6 42.433 40.315 38.197 5.25 5.25
-5 40.332 38.345 36.358 5.18 5.18
-4 38.346 36.482 34.618 5.11 5.11
-3 36.472 34.723 32.974 5.04 5.04
-2 34.7 33.059 31.418 4.96 4.96
-1 33.027 31.487 29.947 4.89 4.89
0 31.445 30 28.555 4.82 4.82
1 29.951 28.594 27.237 4.75 4.75
2 28.538 27.264 25.99 4.67 4.67
3 27.202 26.006 24.81 4.6 4.6
4 25.938 24.815 23.692 4.53 4.53
255
R25=10kΩ±3% B25/50=3700K±3%
Temp Resistance (kΩ) % (Resist. Tol)
(°C) Rmax R (t) Normal Rmin MAX (+) MIN (-)
5 24.742 23.687 22.632 4.45 4.45
6 23.61 22.619 21.628 4.38 4.38
7 22.538 21.607 20.676 4.31 4.31
8 21.522 20.647 19.772 4.24 4.24
9 20.559 19.737 18.915 4.16 4.16
10 19.646 18.874 18.102 4.09 4.09
11 18.779 18.054 17.329 4.02 4.02
12 17.958 17.276 16.594 3.95 3.95
13 17.177 16.537 15.897 3.87 3.87
14 16.436 15.834 15.232 3.8 3.8
15 15.731 15.166 14.601 3.73 3.73
16 15.061 14.53 13.999 3.65 3.65
17 14.424 13.925 13.426 3.58 3.58
18 13.817 13.349 12.881 3.51 3.51
19 13.24 12.8 12.36 3.44 3.44
20 12.69 12.277 11.864 3.36 3.36
21 12.166 11.778 11.39 3.29 3.29
22 11.666 11.302 10.938 3.22 3.22
23 11.189 10.848 10.507 3.15 3.15
24 10.734 10.414 10.094 3.07 3.07
25 10.3 10 9.7 3 3
26 9.898 9.604 9.31 3.06 3.06
27 9.514 9.226 8.938 3.13 3.13
28 9.147 8.864 8.581 3.19 3.19
29 8.796 8.519 8.242 3.25 3.25
30 8.459 8.188 7.917 3.31 3.31
31 8.137 7.871 7.605 3.38 3.38
32 7.828 7.568 7.308 3.44 3.44
33 7.532 7.277 7.022 3.5 3.5
34 7.248 6.999 6.75 3.56 3.56
35 6.977 6.733 6.489 3.63 3.63
36 6.716 6.477 6.238 3.69 3.69
37 6.466 6.232 5.998 3.75 3.75
38 6.227 5.998 5.769 3.81 3.81
39 5.997 5.773 5.549 3.88 3.88
40 5.776 5.557 5.338 3.94 3.94
41 5.564 5.35 5.136 4 4
256
R25=10kΩ±3% B25/50=3700K±3%
Temp Resistance (kΩ) % (Resist. Tol)
(°C) Rmax R (t) Normal Rmin MAX (+) MIN (-)
42 5.36 5.151 4.942 4.06 4.06
43 5.166 4.961 4.756 4.13 4.13
44 4.978 4.778 4.578 4.19 4.19
45 4.799 4.603 4.407 4.25 4.25
46 4.625 4.434 4.243 4.31 4.31
47 4.46 4.273 4.086 4.38 4.38
48 4.301 4.118 3.935 4.44 4.44
49 4.148 3.969 3.79 4.5 4.5
50 4.001 3.826 3.651 4.56 4.56
51 3.86 3.689 3.518 4.63 4.63
52 3.724 3.557 3.39 4.69 4.69
53 3.594 3.431 3.268 4.75 4.75
54 3.468 3.309 3.15 4.81 4.81
55 3.349 3.193 3.037 4.88 4.88
56 3.233 3.081 2.929 4.94 4.94
57 3.123 2.974 2.825 5 5
58 3.015 2.87 2.725 5.06 5.06
59 2.913 2.771 2.629 5.13 5.13
60 2.815 2.676 2.537 5.19 5.19
61 2.721 2.585 2.449 5.25 5.25
62 2.63 2.497 2.364 5.31 5.31
63 2.543 2.413 2.283 5.38 5.38
64 2.459 2.332 2.205 5.44 5.44
65 2.379 2.255 2.131 5.5 5.5
66 2.301 2.18 2.059 5.56 5.56
67 2.228 2.109 1.99 5.63 5.63
68 2.156 2.04 1.924 5.69 5.69
69 2.088 1.974 1.86 5.75 5.75
70 2.021 1.91 1.799 5.81 5.81
71 1.958 1.849 1.74 5.88 5.88
72 1.897 1.791 1.685 5.94 5.94
73 1.839 1.735 1.631 6 6
74 1.782 1.68 1.578 6.06 6.06
75 1.728 1.628 1.528 6.13 6.13
257
R25=10kΩ±3% B25/50=3700K±3%
Temp Resistance (kΩ) % (Resist. Tol)
(°C) Rmax R (t) Normal Rmin MAX (+) MIN (-)
76 1.676 1.578 1.48 6.19 6.19
77 1.626 1.53 1.434 6.25 6.25
78 1.578 1.484 1.39 6.31 6.31
79 1.531 1.439 1.347 6.38 6.38
80 1.486 1.396 1.306 6.44 6.44
81 1.443 1.355 1.267 6.5 6.5
82 1.401 1.315 1.229 6.56 6.56
83 1.362 1.277 1.192 6.63 6.63
84 1.323 1.24 1.157 6.69 6.69
85 1.285 1.204 1.123 6.75 6.75
86 1.249 1.169 1.089 6.81 6.81
87 1.214 1.136 1.058 6.88 6.88
88 1.181 1.104 1.027 6.94 6.94
89 1.148 1.073 0.998 7 7
90 1.116 1.042 0.968 7.06 7.06
91 1.085 1.013 0.941 7.13 7.13
92 1.056 0.985 0.914 7.19 7.19
93 1.026 0.957 0.888 7.25 7.25
94 0.998 0.93 0.862 7.31 7.31
95 0.971 0.904 0.837 7.38 7.38
96 0.944 0.879 0.814 7.44 7.44
97 0.918 0.854 0.79 7.5 7.5
98 0.893 0.83 0.767 7.56 7.56
99 0.867 0.806 0.745 7.63 7.63
100 0.843 0.783 0.723 7.69 7.69
101 0.819 0.76 0.701 7.75 7.75
102 0.796 0.738 0.68 7.81 7.81
103 0.772 0.716 0.66 7.88 7.88
104 0.749 0.694 0.639 7.94 7.94
105 0.727 0.673 0.619 8 8
258
24. Parts Replacement Instructions
24.1 Compressor replacement
Take the following procedures to ensure sufficient maintenance space and good visibility.
259
Step 3: Remove terminal box cover of
compressor
260
Step 7: Unsoldering the discharge pipe / suction pipe
/ oil return pipe with a welding torch at the marked
position as shown in the picture
261
25. Smartlink
25.1 Smartlink Introduction
Smartlink is one kind of wireless communication technology, which contains Master wireless module, Slave wireless
module and Repeater.
1. Master wireless module, Slave wireless module and Repeater share the same hardware but with different
software program inside.
2.Repeater is powered by extra 5V power adapter
262
Connectable indoor series Model PCB code PCB version Remarks
AB*MCERA
4-way cassette 0151800113 V12.4
AB*MCERA(C)
Round flow 4-way cassette AB*MRERA 0151800227 V6.6
MINI 4-way cassette AB*MCERA(M) 0151800244BA V4.1
2-way cassette AB*MBERA 0151800161B V12.4
One way cassette AB*MAERA 0151800244BA V4.1
AC*MCERA
Convertible 0151800113 V6.6
AC*MFERA
DC Slim low ESP duct AD*MSERA(D) 0151800244 V6.6 The PCB spare parts
required for the wireless
Slim low ESP duct AD*MSERA 0151800161C V11.9
system and the MRV 5-RC
Low ESP duct AD*MLERA 0151800113 V6.6
system must also be the
AD*MNERA 0151800113 V6.6
changed version (the version
AD*MMERA 0151800113 V6.6 number is in the table or
Medium ESP duct 0151800161C later than this version or
AD*MJERA V11.9
0151800161G the production time is after
AD*MJERAB 0151800161D V11.9 January 1, 2019)
AD*MHERA 0151800113 V6.6
High ESP duct 0151800244
AD*MQERA V6.6
0151800227A
AS*MFERA
AS*MNERA
N plate high wall 0151800244B V4.1
AS*MFERAB
AS*MNERAB
Console AF*MBERA 0151800452 V0.8
PCB production time
263
25.2 Smartlink benefits
• Easy Installation
Traditional wired connection has complex operation procedures, such as wiring, wire threading, wire binding and
wire cutting etc. which cost a lot of labor and resources.
Smartlink as a wireless communication technology, make installation easier by removing the complex wire
connection procedure.
• Smart networking
Traditional AC wire connection method is hand-in-hand, which is not flexible.
Smartlink realizes smart networking by dip switch operation. Besides, when the communication signal of the units
changes, it can seek other strong signal path nearby and keep the stable communication of the system.
• Convenient Maintenance
Under wired connection system, communication error of one unit will cause all the units communication error which
make the system stop running. It is so hard for the maintainer to find the error unit only by checking all the units in
turn.
But for the system with smartlink, if one unit has communication error which will not affect other units. Because
other units will change their communication path by choosing the stronger communication path to keep the system
running. Therefore, it is convenient for the maintainer to maintain by focusing on the error unit.
• Stable performance.
For the system adopting wired communication, there are a lot of wire related problems such as wire aging and wire
broken caused by users or animals affecting the normal use of units.
Smartlink can reduce the possibility of above problems and make performance more stable by adopting wireless
communication.
264
25.3 Smartlink specification
Item Model BOM No. Spare part code Indoor PCB connection terminal
IGU11
5V
Indoor 1
Indoor 2 Indoor 3 Indoor 4 Indoor n
P Q CN34 CN34 CN34 CN34 CN34
PQ PQ PQ PQ
Note:
If the system unit adopts Zigbee wireless communication, it must adopt wireless and wired hybrid mode.
The PQ cable must be connected to the IDU which one with the smallest address number
265
25.5 Dimension
266
25.6 The installation requirement of Smartlink
(1). The Connection requirement of wireless communication system
For the MRV system adopting wireless communication, it is recommended to adopt the mix-connection solution
of wired and wireless communication, namely the master ODU connecting with one nearest IDU by wire and all
IDUs adopting wireless communication with each other within the system. The ODU does not need to be equipped
with a wireless module. The first indoor unit connected to the outdoor unit is used as the main IDU . The main
IDU wireless module(IGU09) needs to be installed, and the slave IDU wireless module (IGU10) are installed the
other IDU. (Note: for the MRV 5-RC system, the outdoor and all the valve boxes must be connected by the wires,
the indoor unit which is not connected with valve box must be connected by wires, the valve box as the main IDU,
indoor units connected with valve box as the slave IDU)
(2) The installation requirement IDU wireless module
a. If IDU wireless module as standard module means its installation has been finished before delivering. If as
optional module, it needs to be installed in the specific location, with communication wire connecting to CN 34 port
of IDU PC board.
b. The antenna of the IDU wireless module is rotatable. Keep the antenna more than 10cm away from metals
c. Keep the IDUs with wireless module more than 10m away from the Wifi devices in the room.
(3) The installation requirement of Repeater
a. Add one repeater when the distance between any two wireless modules (both ODU wireless module and IDU
wireless module) exceeds per 100m.
b. Add one repeater when there is one wall or other similar buildings between any two wireless modules, both
ODU wireless module and IDU wireless module.
Remark: Do not need to add the repeater when there is only one wall between ODUs and ODUs
c. Repeater should be installed in the open space as far as possible, especially keeping the antenna more than
10cm away from metals
d. Repeater must be supplied power separately by its own power adapter. The installation of the repeater should
consider the convenience of connection to external single-phase 220V AC power supply and the required
waterproof position.
Remark: According to the above requirement, the number of repeaters to be installed should be calculated in
advance . Adding the repeaters based on above requirements can ensure the reliability and stability of wireless
communication system.
(4) The installation requirement of IDUs
a. For the system adopting wireless communication , the installation of IDUs should use network structure instead
of line-type structure;
b. Do not install the IDUs in the space surrounded by metal, such as metro computer room and hospital X-ray
room, otherwise the system should adopt the wired connection.
c. Keep the IDUs more than 10m away from the Wifi devices in the room.
CN34
267
25.7 The debugging guidance of Smartlink
Set BM2-4 on
Waiting
Yes
Yes
Normal communication
and ending networking
268
Each system can finish automatic networking debugging separately, as shown in the left debugging chart.
Note:
1. For the first time of debugging Smartlink wireless communication units, the air conditioner units must be
powered on separately, other IDUs without networking are forbidden to be powered on. The units finishing the
networking must be powered off and then other units can start networking in sequence. All the units can be
powered on till all of them finishing networking.
2.After finding all the IDUs, it needs to check the error rate of wireless communication system by ODU LED
display area. The checking method of the error rate is shown in table below. 0% indicates the best communication
quality and 20% or less can ensure the normal running of the units.
3.When error rate is very high, it is necessary to confirm whether the repeater is added in accordance with the
standard requirement (one repeater needs to added through per wall).
269
Power Wireless module Communication
Indicator quantity indicator indicator
270
26. Central control & BMS system for MRV5
26.1 Central control system
Central controller information used by MRV5-H system
No. Model Max. outdoor system Qty. Max. indoor Qty.
1 YCZ-A004 32 256
2 HC-SA164DBT 32 64
3 YCZ-G001 8 32
System schematic
Homebus
RS-485 Max. 1000m
Central
controller
271
MRV 5 - Wiring Diagram
ODU-MRV 5
IDU IDU
Communication wire connection example
P Q P Q P Q BUS-B BUS-A
272
IDU IDU
32
P Q P Q BUS-B BUS-A
Outdoor
P Q
System
HC-SA164DBT
26.2 BMS system
BMS information used by MRV5 system
No. Model Max. outdoor system Qty. Max. indoor Qty.
1 HCM-01A 32 400
2 HCM-03A 80 1500
3 HCM-05A 32 500
4 HCM-05 32 250
System schematic
Homebus
RS-485 Max. 1000m
TCP/IP
BMS
PC
273
MRV 5 - Wiring Diagram
ODU-MRV 5
IDU IDU
P Q P Q P Q BUS-B BUS-A
Communication wire connection example
ODU-MRV 5
IDU IDU
P Q P Q P Q BUS-B BUS-A
274
System schematic (Billing system)
Homebus
IGU02
RS-485 Max. 1000m
IGU02
IGU02
IGU02
BMS TCP/IP
HCM
PC
ODU-MRV5 Gateway:IGU02
IDU IDU AC NC GND GND GND GND GND HB1 485- 485-
P Q P Q
P Q AC NC 5V M1 SUB1 SUB2 SUB3 HB2 485+ 485+
ODU-MRV5 Gateway:IGU02
IDU IDU AC NC GND GND GND GND GND HB1 485- 485-
P Q P Q
P Q AC NC 5V M1 SUB1 SUB2 SUB3 HB2 485+ 485+
●
HCM-03A
275
26.3 Dip switch setting for address
1 2 3 4 5 6 7 8 Address
OFF OFF OFF OFF OFF OFF OFF OFF 0
OFF OFF OFF OFF OFF OFF OFF ON 1
OFF OFF OFF OFF OFF OFF ON OFF 2
OFF OFF OFF OFF OFF OFF ON ON 3
OFF OFF OFF OFF OFF ON OFF OFF 4
OFF OFF OFF OFF OFF ON OFF ON 5
OFF OFF OFF OFF OFF ON ON OFF 6
OFF OFF OFF OFF OFF ON ON ON 7
OFF OFF OFF OFF ON OFF OFF OFF 8
OFF OFF OFF OFF ON OFF OFF ON 9
OFF OFF OFF OFF ON OFF ON OFF 10
OFF OFF OFF OFF ON OFF ON ON 11
OFF OFF OFF OFF ON ON OFF OFF 12
OFF OFF OFF OFF ON ON OFF ON 13
OFF OFF OFF OFF ON ON ON OFF 14
OFF OFF OFF OFF ON ON ON ON 15
OFF OFF OFF ON OFF OFF OFF OFF 16
OFF OFF OFF ON OFF OFF OFF ON 17
OFF OFF OFF ON OFF OFF ON OFF 18
OFF OFF OFF ON OFF OFF ON ON 19
OFF OFF OFF ON OFF ON OFF OFF 20
OFF OFF OFF ON OFF ON OFF ON 21
OFF OFF OFF ON OFF ON ON OFF 22
OFF OFF OFF ON ON ON ON ON 23
OFF OFF OFF ON ON OFF OFF OFF 24
OFF OFF OFF ON ON OFF OFF ON 25
OFF OFF OFF ON ON OFF ON OFF 26
OFF OFF OFF ON ON OFF ON ON 27
OFF OFF OFF ON ON ON OFF OFF 28
OFF OFF OFF ON ON ON OFF ON 29
OFF OFF OFF ON ON ON ON OFF 30
OFF OFF OFF ON ON ON ON ON 31
OFF OFF ON OFF OFF OFF OFF OFF 32
OFF OFF ON OFF OFF OFF OFF ON 33
OFF OFF ON OFF OFF OFF ON OFF 34
OFF OFF ON OFF OFF OFF ON ON 35
OFF OFF ON OFF OFF ON OFF OFF 36
OFF OFF ON OFF OFF ON OFF ON 37
OFF OFF ON OFF OFF ON ON OFF 38
OFF OFF ON OFF OFF ON ON ON 39
OFF OFF ON OFF ON OFF OFF OFF 40
OFF OFF ON OFF ON OFF OFF ON 41
OFF OFF ON OFF ON OFF ON OFF 42
OFF OFF ON OFF ON OFF ON ON 43
OFF OFF ON OFF ON ON OFF OFF 44
276
1 2 3 4 5 6 7 8 Address
OFF OFF ON OFF ON ON OFF ON 45
OFF OFF ON OFF ON ON ON OFF 46
OFF OFF ON OFF ON ON ON ON 47
OFF OFF ON ON OFF OFF OFF OFF 48
OFF OFF ON ON OFF OFF OFF ON 49
OFF OFF ON ON OFF OFF ON OFF 50
OFF OFF ON ON OFF OFF ON ON 51
OFF OFF ON ON OFF ON OFF OFF 52
OFF OFF ON ON OFF ON OFF ON 53
OFF OFF ON ON OFF ON ON OFF 54
OFF OFF ON ON OFF ON ON ON 55
OFF OFF ON ON ON OFF OFF OFF 56
OFF OFF ON ON ON OFF OFF ON 57
OFF OFF ON ON ON OFF ON OFF 58
OFF OFF ON ON ON OFF ON ON 59
OFF OFF ON ON ON ON OFF OFF 60
OFF OFF ON ON ON ON OFF ON 61
OFF OFF ON ON ON ON ON OFF 62
OFF OFF ON ON ON ON ON ON 63
OFF ON OFF OFF OFF OFF OFF OFF 64
OFF ON OFF OFF OFF OFF OFF ON 65
OFF ON OFF OFF OFF OFF ON OFF 66
OFF ON OFF OFF OFF OFF ON ON 67
OFF ON OFF OFF OFF ON OFF OFF 68
OFF ON OFF OFF OFF ON OFF ON 69
OFF ON OFF OFF OFF ON ON OFF 70
OFF ON OFF OFF OFF ON ON ON 71
OFF ON OFF OFF ON OFF OFF OFF 72
OFF ON OFF OFF ON OFF OFF ON 73
OFF ON OFF OFF ON OFF ON OFF 74
OFF ON OFF OFF ON OFF ON ON 75
OFF ON OFF OFF ON ON OFF OFF 76
OFF ON OFF OFF ON ON OFF ON 77
OFF ON OFF OFF ON ON ON OFF 78
OFF ON OFF OFF ON ON ON ON 79
OFF ON OFF ON OFF OFF OFF OFF 80
OFF ON OFF ON OFF OFF OFF ON 81
OFF ON OFF ON OFF OFF ON OFF 82
OFF ON OFF ON OFF OFF ON ON 83
OFF ON OFF ON OFF ON OFF OFF 84
OFF ON OFF ON OFF ON OFF ON 85
OFF ON OFF ON OFF ON ON OFF 86
OFF ON OFF ON OFF ON ON ON 87
OFF ON OFF ON ON OFF OFF OFF 88
OFF ON OFF ON ON OFF OFF ON 89
OFF ON OFF ON ON OFF ON OFF 90
277
1 2 3 4 5 6 7 8 Address
OFF ON OFF ON ON OFF ON ON 91
OFF ON OFF ON ON ON OFF OFF 92
OFF ON OFF ON ON ON OFF ON 93
OFF ON OFF ON ON ON ON OFF 94
OFF ON OFF ON ON ON ON ON 95
OFF ON ON OFF OFF OFF OFF OFF 96
OFF ON ON OFF OFF OFF OFF ON 97
OFF ON ON OFF OFF OFF ON OFF 98
OFF ON ON OFF OFF OFF ON ON 99
OFF ON ON OFF OFF ON OFF OFF 100
OFF ON ON OFF OFF ON OFF ON 101
OFF ON ON OFF OFF ON ON OFF 102
OFF ON ON OFF OFF ON ON ON 103
OFF ON ON OFF ON OFF OFF OFF 104
OFF ON ON OFF ON OFF OFF ON 105
OFF ON ON OFF ON OFF ON OFF 106
OFF ON ON OFF ON OFF ON ON 107
OFF ON ON OFF ON ON OFF OFF 108
OFF ON ON OFF ON ON OFF ON 109
OFF ON ON OFF ON ON ON OFF 110
OFF ON ON OFF ON ON ON ON 111
OFF ON ON ON OFF OFF OFF OFF 112
OFF ON ON ON OFF OFF OFF ON 113
OFF ON ON ON OFF OFF ON OFF 114
OFF ON ON ON OFF OFF ON ON 115
OFF ON ON ON OFF ON OFF OFF 116
OFF ON ON ON OFF ON OFF ON 117
OFF ON ON ON OFF ON ON OFF 118
OFF ON ON ON OFF ON ON ON 119
OFF ON ON ON ON OFF OFF OFF 120
OFF ON ON ON ON OFF OFF ON 121
OFF ON ON ON ON OFF ON OFF 122
OFF ON ON ON ON OFF ON ON 123
OFF ON ON ON ON ON OFF OFF 124
OFF ON ON ON ON ON OFF ON 125
OFF ON ON ON ON ON ON OFF 126
OFF ON ON ON ON ON ON ON 127
278
1 2 3 4 5 6 7 8 Address
ON OFF OFF OFF OFF OFF OFF OFF 128
ON OFF OFF OFF OFF OFF OFF ON 129
ON OFF OFF OFF OFF OFF ON OFF 130
ON OFF OFF OFF OFF OFF ON ON 131
ON OFF OFF OFF OFF ON OFF OFF 132
ON OFF OFF OFF OFF ON OFF ON 133
ON OFF OFF OFF OFF ON ON OFF 134
ON OFF OFF OFF OFF ON ON ON 135
ON OFF OFF OFF ON OFF OFF OFF 136
ON OFF OFF OFF ON OFF OFF ON 137
ON OFF OFF OFF ON OFF ON OFF 138
ON OFF OFF OFF ON OFF ON ON 139
ON OFF OFF OFF ON ON OFF OFF 140
ON OFF OFF OFF ON ON OFF ON 141
ON OFF OFF OFF ON ON ON OFF 142
ON OFF OFF OFF ON ON ON ON 143
ON OFF OFF ON OFF OFF OFF OFF 144
ON OFF OFF ON OFF OFF OFF ON 145
ON OFF OFF ON OFF OFF ON OFF 146
ON OFF OFF ON OFF OFF ON ON 147
ON OFF OFF ON OFF ON OFF OFF 148
ON OFF OFF ON OFF ON OFF ON 149
ON OFF OFF ON OFF ON ON OFF 150
ON OFF OFF ON ON ON ON ON 151
ON OFF OFF ON ON OFF OFF OFF 152
ON OFF OFF ON ON OFF OFF ON 153
ON OFF OFF ON ON OFF ON OFF 154
ON OFF OFF ON ON OFF ON ON 155
ON OFF OFF ON ON ON OFF OFF 156
ON OFF OFF ON ON ON OFF ON 157
ON OFF OFF ON ON ON ON OFF 158
ON OFF OFF ON ON ON ON ON 159
ON OFF ON OFF OFF OFF OFF OFF 160
ON OFF ON OFF OFF OFF OFF ON 161
ON OFF ON OFF OFF OFF ON OFF 162
ON OFF ON OFF OFF OFF ON ON 163
ON OFF ON OFF OFF ON OFF OFF 164
ON OFF ON OFF OFF ON OFF ON 165
ON OFF ON OFF OFF ON ON OFF 166
ON OFF ON OFF OFF ON ON ON 167
ON OFF ON OFF ON OFF OFF OFF 168
ON OFF ON OFF ON OFF OFF ON 169
ON OFF ON OFF ON OFF ON OFF 170
ON OFF ON OFF ON OFF ON ON 171
ON OFF ON OFF ON ON OFF OFF 172
279
1 2 3 4 5 6 7 8 Address
ON OFF ON OFF ON ON OFF ON 173
ON OFF ON OFF ON ON ON OFF 174
ON OFF ON OFF ON ON ON ON 175
ON OFF ON ON OFF OFF OFF OFF 176
ON OFF ON ON OFF OFF OFF ON 177
ON OFF ON ON OFF OFF ON OFF 178
ON OFF ON ON OFF OFF ON ON 179
ON OFF ON ON OFF ON OFF OFF 180
ON OFF ON ON OFF ON OFF ON 181
ON OFF ON ON OFF ON ON OFF 182
ON OFF ON ON OFF ON ON ON 183
ON OFF ON ON ON OFF OFF OFF 184
ON OFF ON ON ON OFF OFF ON 185
ON OFF ON ON ON OFF ON OFF 186
ON OFF ON ON ON OFF ON ON 187
ON OFF ON ON ON ON OFF OFF 188
ON OFF ON ON ON ON OFF ON 189
ON OFF ON ON ON ON ON OFF 190
ON OFF ON ON ON ON ON ON 191
ON ON OFF OFF OFF OFF OFF OFF 192
ON ON OFF OFF OFF OFF OFF ON 193
ON ON OFF OFF OFF OFF ON OFF 194
ON ON OFF OFF OFF OFF ON ON 195
ON ON OFF OFF OFF ON OFF OFF 196
ON ON OFF OFF OFF ON OFF ON 197
ON ON OFF OFF OFF ON ON OFF 198
ON ON OFF OFF OFF ON ON ON 199
ON ON OFF OFF ON OFF OFF OFF 200
ON ON OFF OFF ON OFF OFF ON 201
ON ON OFF OFF ON OFF ON OFF 202
ON ON OFF OFF ON OFF ON ON 203
ON ON OFF OFF ON ON OFF OFF 204
ON ON OFF OFF ON ON OFF ON 205
ON ON OFF OFF ON ON ON OFF 206
ON ON OFF OFF ON ON ON ON 207
ON ON OFF ON OFF OFF OFF OFF 208
ON ON OFF ON OFF OFF OFF ON 209
ON ON OFF ON OFF OFF ON OFF 210
ON ON OFF ON OFF OFF ON ON 211
ON ON OFF ON OFF ON OFF OFF 212
ON ON OFF ON OFF ON OFF ON 213
ON ON OFF ON OFF ON ON OFF 214
ON ON OFF ON OFF ON ON ON 215
ON ON OFF ON ON OFF OFF OFF 216
ON ON OFF ON ON OFF OFF ON 217
ON ON OFF ON ON OFF ON OFF 218
280
1 2 3 4 5 6 7 8 Address
ON ON OFF ON ON OFF ON ON 219
ON ON OFF ON ON ON OFF OFF 220
ON ON OFF ON ON ON OFF ON 221
ON ON OFF ON ON ON ON OFF 222
ON ON OFF ON ON ON ON ON 223
ON ON ON OFF OFF OFF OFF OFF 224
ON ON ON OFF OFF OFF OFF ON 225
ON ON ON OFF OFF OFF ON OFF 226
ON ON ON OFF OFF OFF ON ON 227
ON ON ON OFF OFF ON OFF OFF 228
ON ON ON OFF OFF ON OFF ON 229
ON ON ON OFF OFF ON ON OFF 230
ON ON ON OFF OFF ON ON ON 231
ON ON ON OFF ON OFF OFF OFF 232
ON ON ON OFF ON OFF OFF ON 233
ON ON ON OFF ON OFF ON OFF 234
ON ON ON OFF ON OFF ON ON 235
ON ON ON OFF ON ON OFF OFF 236
ON ON ON OFF ON ON OFF ON 237
ON ON ON OFF ON ON ON OFF 238
ON ON ON OFF ON ON ON ON 239
ON ON ON ON OFF OFF OFF OFF 240
ON ON ON ON OFF OFF OFF ON 241
ON ON ON ON OFF OFF ON OFF 242
ON ON ON ON OFF OFF ON ON 243
ON ON ON ON OFF ON OFF OFF 244
ON ON ON ON OFF ON OFF ON 245
ON ON ON ON OFF ON ON OFF 246
ON ON ON ON OFF ON ON ON 247
ON ON ON ON ON OFF OFF OFF 248
ON ON ON ON ON OFF OFF ON 249
ON ON ON ON ON OFF ON OFF 250
ON ON ON ON ON OFF ON ON 251
ON ON ON ON ON ON OFF OFF 252
ON ON ON ON ON ON OFF ON 253
ON ON ON ON ON ON ON OFF 254
ON ON ON ON ON ON ON ON 255
281
Appendixi table for manual updated information
282
Haier Commercial Air Condition
ADDRESS: No.1 Haier Road, Hi-tech Zone, Qingdao 266101 P.R. China
Web: Http://www.haier.com
283