InteliCharger

65/12 AF

Order code: ICHG-65-12-AF

Automatic Battery Charger

Datasheet
Product description Certifications and standards
EN 62368-1
Automatic battery chargers provide a cost effective
EN 61000-6-2
solution to most industrial battery charging
EN 61000-6-4
requirements. The two stage constant current –
UL1236 Edition 8
constant voltage characteristic ensures accurate and
CSA C22.2 No. 107.2-01
efficient battery charging and is designed for permanent
RoHS 3 Directive (EU 2015/863)
connection to the batteries maintaining them in a fully
charged condition without overcharging. Device can be
also set as power supply.

Key features
Cost effective
Micro-processor control
Compact size – DIN rail mounting
Sealed electronic construction
Robust & high reliability
Fully automatic operation
Power supply mode
Universal AC input ranges
Low ripple output
Passive cooling
Fail alarm contact set

| InteliCharger 65_12 AF Datasheet | Date of issue: 1/6/2020


Technical data

Operating conditions Alarms and Levels


Working Temperature -10 ºC to +50 ºC Float = Factory set to
Working Humidity 20 to 90 % RH 13.8 V
DC Output Voltages
Storage Temperature -20 ºC to +85 ºC Boost = Float
Voltage +4 V
Storage Humidity 10 to 95 % RH
Loss of AC input or DC
Unpacked Weight 400 g AC / Charger Fail
output voltage ctrl
Withstand Voltage Input – Output 1.5 kV AC
Float Voltage
Input – Output 500 V DC
Isolation Resistance Low DC Voltage Alarm -12 % Alarm,
/ 100M Ω
-8 % Reset
Protections Float Voltage
Constant Current High DC Voltage Alarm +7 % Alarm,
Overload Protection
Limit/Fold back +5 % Reset
105 % - 125 % Float Voltage
Over Voltage Protection
Over Voltage Protection Shutdown. Recycle I/P to +10 %, instant SD
restart
Open circuit on DC
Output shutdown with Battery Disconnected
Over Temp. Protection output
automatic recovery
Automatic
protection.
Reversed Battery Protection
Disabled when in
PSU mode.

Input Specification
Voltage Range, V IN 90 to 264 V AC
Frequency 47 to 63 Hz
Input Current 1.5 A rms max.
Leakage Current None

Output Specification
12.0 V Nominal 6.0
Voltage/Current
Apk
Ripple & Noise ±0.5 %
Line Regulation ±1.0 %
Load Regulation ±1.5 %0
Efficiency Up to 90 %

Fault Relay is active, if


DC short circuit
Battery voltage lower than 95 % of nominal voltage
Charger is switched OFF (* in case of DC connected, it
takes longer time to switch to NC status)

InteliCharger 65_12 AF Datasheet 2


Dimensions, terminals and mounting
Power supply mode

To activate Power supply mode connect pin


7 and 8.
No connection = Default = Charger mode

Note: Dimensions are in mm.

Calibration
1. Disconnect the battery. Connect a DC voltmeter to the ± output terminals.
2. Turn the "CAL" potentiometer fully anti-clockwise. When the status LED flashes green/red @5 Hz, adjust
the "CAL" potentiometer and set the desired float voltage level.
3. When the LED red/green @5 Hz flash sequence ends, the unit is calibrated.

Manufacturer:
ComAp a.s.
Czech Republic E-mail: info@[Link]
Phone: +420 246 012 111 Web: [Link]

© ComAp. Features and specification are subject to change without prior notice.