0% found this document useful (0 votes)
96 views24 pages

Triton T80si Manual

Uploaded by

Richard Stern
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
96 views24 pages

Triton T80si Manual

Uploaded by

Richard Stern
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 24

T80si

electric
shower

Installation and
operating
instructions

Installers please note these instructions are to be left with the user

2180240T September 2009


T80si electric shower

CONTENTS Page

Important safety information........................................................... 1


Introduction.................................................................................... 2
Specifications................................................................................... 2
Advice to users................................................................................ 2
Main components........................................................................... 3
Electrical requirements..................................................................... 4
Water requirements......................................................................... 6
Siting of the shower........................................................................ 7
Fitting the shower to the wall.......................................................... 8
Plumbing connections.................................................................... 10
Electrical connections..................................................................... 11
Replacing the cover........................................................................ 12
Commissioning............................................................................... 13
Operating the shower.................................................................... 14
Operating functions........................................................................ 16
Instructions for installers and service engineers only....................... 17
Spare parts..................................................................................... 18
Fault finding................................................................................ 19 -20
Guarantee, service policy, etc....................................................rear cover

To check the product suitability for commercial and multiple installations, please contact Triton’s
specification advisory service before installation.
Telephone: 0844 980 0730
Facsimile: 0844 980 0744
E mail: [email protected]
T80si electric shower

PLEASE READ THIS IMPORTANT SAFETY INFORMATION


 Products manufactured by Triton are safe and without risk provided they are installed, used and
maintained in good working order in accordance with our instructions and recommendations.
 WARNING: DO NOT operate shower if frozen, or suspected of being frozen. It must thaw out
before using.
 DO NOT operate the unit if the showerhead or spray hose becomes damaged.
 DO NOT restrict flow out of shower by placing showerhead in direct contact with your body.
 DO NOT operate the shower if water ceases to flow during use or if water has entered inside
the unit because of an incorrectly fitted cover.
 WARNING: If restarting the shower immediately after stopping, be aware that a slug of
hot water will be expelled for the first few seconds.

1 GENERAL 300mm of the shower unit, as heat can


1.1 Isolate the electrical and water supplies before transfer along the pipework and damage
removing the cover. components.
1.2 Read all of these instructions and retain them 2.4 DO NOT fit any form of outlet flow control as
for later use. the outlet acts as a vent for the heater can.
1.3 DO NOT take risks with plumbing or electrical 2.5 DO NOT use excessive force when making
equipment. connections to the flexible hose or
showerhead, finger tight is sufficient.
1.4 Isolate electrical and water supplies before
proceeding with the installation. 2.6 All plumbing connections must be completed
before making the electrical connections.
1.5 The unit must be mounted onto the finished
wall surface (on top of the tiles). Do not tile up
to unit after fixing to wall. 3 ELECTRICAL
3.1 The installation must comply with BS 7671
1.6 Contact Customer Service (see back page), if
‘Requirements for electrical installations’ (IEE
any of the following occur:
wiring regulations), building regulations or any
a) If it is intended to operate the shower at particular regulations as specified by the local
pressures above the maximum or below the Electrical Supply Company.
minimum stated. A-001-A 3.2 This appliance MUST be earthed.
b) If the unit shows a distinct change in
3.3 In accordance with ‘The Plugs and Sockets etc.
performance.
(Safety) Regulations 1994’, this appliance is
c) If the shower is frozen. intended to be permanently connected to the
1.7 If it is intended to operate the shower in areas fixed wiring of the electrical mains system.
of hard water (above 200 ppm temporary 3.4 Make sure all electrical connections are tight
hardness), a scale inhibitor may have to be to prevent overheating.
fitted. For advice on the Triton Scale Inhibitor,
3.5 Fuses do not give personal protection against
contact Triton Customer Service.
electric shock.
1.8 The showerhead must be cleaned regularly 3.6 A 30mA residual current device (RCD) MUST
with descalent to remove scale and debris, be installed in all UK electric and pumped
otherwise restrictions to the flow on the outlet shower circuits. This may be part of the
of the unit will result in higher temperatures consumer unit or a separate unit.
and could also cause the Pressure Relief Device
3.7 Switch off immediately at isolating switch if
in the unit to operate.
water ceases to flow during use.
1.9 This product is not suitable for mounting into
3.8 Other electrical equipment i.e. extractor fans,
steam rooms or steam cubicles.
pumps must not be connected to the circuits
within the unit.
2 PLUMBING
2.1 The plumbing installation must comply with 3.9 Switch off at isolating switch when not in use.
Water Regulations, Building Regulations or any This is a safety procedure recommended with
particular regulations as specified by Local all electrical appliances.
Water Company or Water Undertakers and
3.10 As with all electrical appliances it is
should be in accordance with BS 6700.
recommended to have the shower and
2.2 The supply pipe must be flushed to clear installation checked at least every two years by
debris before connecting to the shower unit. a competent electrician to ensure there is no
2.3 DO NOT solder pipes or fittings within deterioration due to age and usage.


T80si electric shower

INTRODUCTION
Introduction ADVICE
Advice toTO USERS
users
This book contains all the necessary fitting and
IMPORTANT: When first installed the unit
operating instructions for your Triton T80si
will be empty. It is essential the unit should
electric shower. Please read them carefully.
contain water before the elements are
The shower installation must be carried out by a switched on. It is vital that the
suitably qualified person and in the sequence of I-001-A
commissioning procedure is followed.
this instruction book. Failure to carry out this operation will result
Care taken during the installation will provide a in damage to the unit and will invalidate the
long, trouble-free life from your shower. guarantee.

The following points will help you understand


SPECIFICATIONS
Specifications how the shower operates:
Electrical a. The electric heating elements operate at a
Nominal power Nominal power constant rate at your chosen power setting.
rating at 240V rating at 230V It is the rate of the water passing through
7.5kW – (32A MCB rating) 6.9kW – (32A MCB rating) the heater can which determines the water
8.0kW – (40A MCB rating) 7.4kW – (40A MCB rating) temperature. (The slower the flow, the hotter
the water becomes; the faster the flow, the
8.5kW – (40A MCB rating) 7.9kW – (40A MCB rating)
cooler the water).
9.5kW – (40A MCB rating) 8.7kW – (40A MCB rating)
b. During winter the mains water supply will
Water be cooler than in the summer, so the flow
Inlet connection – 15 mm diameter. rate will vary between seasons at any one
Outlet connection – ½” BSP male thread. temperature setting. At different times of the
year you may have to adjust the position of
Entry Points the temperature control to maintain your
Water – top, bottom, back, left or right. desired temperature setting.
Cable – top, bottom, back, left or right.
c. The stabiliser valve minimises variations in
Materials shower temperature during mains water
Backplate, cover, controls, showerhead – ABS. pressure changes. If changes in shower
Sprayplate – Acetal. temperature are experienced during normal
Elements – Minerally insulated corrosion resistant use, it will most likely be caused by the
metal sheathing. water pressure falling near to or below the
minimum level. The drop in pressure may
Dimensions (mm)
be due to water being drawn off at other
Height – 300, Width – 208, Depth – 110
points in the house whilst the shower is in
Standards and Approvals use. If pressure drops appreciably below
Splashproof rating IPX4. the minimum, the heating elements will
Complies with the requirements of current British automatically cut out.
and European safety standards for household If ever the water becomes too hot and you
and similar electrical appliances. cannot obtain cooler water, first check that
Complies with requirements of the British the sprayplate in the showerhead has not
Electrotechnical Approvals Board (BEAB). become blocked.
Meets with Compliance with European Do not place items such as soap or shampoo
Community Directives (CE). bottles on top of the unit. Liquid could seep
through the joint between the cover and
backplate, and possibly damage the sealing
Replacement parts can be ordered from Customer
Y-003-A
Service. See ‘spare parts’ for details and part numbers.
rubber.


T80si electric shower

MAIN COMPONENTS
Main components
Fig.1
Inside unit (fig.1)
1. Top cable/pipe entry 1
3 2 3
2. Wall screw fixings
3. Cover screw fixings
4
4. Thermal safety cut-out
5
5. Power selector assembly
6. Can and element assembly
7. Pressure switch/flag assembly 6 255
mm

7 300
8. Stabilising valve mm
9
9. Terminal block
8
10. Earth connection
11. Solenoid valve
12. Water inlet
10 11
13. Thermal cut-out (outlet)
14. Pressure relief device (PRD) 13 2
12
15. Shower outlet
58 mm

14 3
Inside cover (fig.2)
16. Start/Stop switch 15
208 mm

Note: Not all wiring is shown for reasons of clarity


Other items
Instructions, guarantee, etc.
Fig.2

16


T80si electric shower

ELECTRICAL REQUIREMENTS Shepperton Park,


Triton Road, Nuneaton,
WARNING! Warwickshire, CV11 4NR
W-006-A
THIS APPLIANCE MUST BE EARTHED

The installation, supply cable and circuit


protection must conform with BS 7671 (IEE
wiring regulations) and be sufficient for the Fig.3
amperage required.
The following notes are for guidance only:
1 The shower must only be connected to a
230-240V ac supply. If you are installing a
shower with a kilowatt rating above 9kW, it Fig.4 Schematic of installation circuit
is advisable to contact the local electricity
supply company. Pull cord
isolating switch
1.1 The electrical rating of the shower is shown
on the rating label (Fig.3) within the unit.
Shower
RCD unit
2 Before making any sort of electrical (can be part of
connection within the installation make sure consumer unit)
that no terminal is live. If in any doubt,
switch off the whole installation at the mains
supply and remove the correct fuse.
3 The shower must be connected to its own
independent electrical circuit. IT MUST NOT Fuse or Consumer
MCB unit Meter
be connected to a ring main, spur, socket Incoming
outlet, lighting circuit or cooker circuit. supply
80A or 100A fuse
3.1 The electrical supply must be adequate for main switch
the loading of the unit and existing circuits.
Meter
4 Check your consumer unit (main fuse box) tails
has a main switch rating of 80A or above
and that it has a spare fuse way which will
take the fuse or Miniature Circuit Breaker Table A
(MCB) necessary for the shower (Fig.4).
CIRCUIT PROTECTION
4.1 If your consumer unit has a rating below
80A or if there is no spare fuse way, then the unit cartridge
installation will not be straightforward and rating MCB fuse
may require a new consumer unit serving
7.0kW 30/32A 30A
the house or just the shower.
7.5kW 32A 35A
4.2 You will need to contact the local electricity
8.0kW 40A 35A
company. They will check the supply and
carry out what is necessary. 8.5kW 40A 45A
5 For close circuit protection DO NOT use a 9.0kW 40A 45A
rewireable fuse. Instead use a suitably rated 9.5kW 40/45A 45A
Miniature Circuit Breaker (MCB) or cartridge 10.5kW 45A 45A
fuse (see Table A).
5.1 A 30mA residual current device (RCD) must
be installed in all UK electric and pumped
shower circuits. This may be part of the
consumer unit or a separate unit.
6 A 45 amp double pole isolating switch with 
a minimum contact gap of 3 mm in both
cabling is bunched with others, surrounded
carry out what is necessary. by thermal loft or wall insulation or placed in
5 For close circuit protection DO NOT use a areas where the ambient temperature is
rewireable fuse. Instead use a suitably rated above 30°C. Under these conditions,
Miniature Circuit Breaker (MCB) T80si electric shower
or cartridge derating factors apply and it is necessary to
fuse (see Table A). select a larger cable size.
5.1 A 30mA residual current device (RCD) must 9.2 In the majority of installations, the cable
be installed in all UK electric and pumped will unavoidably be placed in one or more
shower circuits. This may be part of the of the above conditions. This being so, it
consumer unit or a separate unit. is strongly recommended to use a
6 A 45 amp double pole isolating switch with minimum of 10mm cabling throughout
a minimum contact gap of 3 mm in both the shower installation.
poles must be incorporated in the circuit. 9.3 In any event, it is essential that individual
6.1 It must have a mechanical indicator showing site conditions are assessed by a competent
when the switch is in the OFF position, and electrician in order to determine the correct
the wiring must be connected to the switch cable size and permissible circuit length.
without the use of a plug or socket outlet. Table B
6.2 The switch must be accessible and clearly
identifiable, but out of reach of a person Twin and earth PVC insulated cable
using a fixed bath or shower, except for the Current carrying capacity
cord of a cord operated switch, and should
be placed so that it is not possible to touch Clipped direct
the switch body while standing in a bath or or buried in a
E-002-A
shower cubicle. It should be readily Installed in an In conduit non-insulated
insulated wall trunking wall
accessible to switch off after using the
shower.
6 mm² 6 mm² 6 mm²
7 Where shower cubicles are located in any 35A 38A 47A
rooms other than bathrooms, all socket 10 mm² 10 mm² 10 mm²
outlets in those rooms must be protected by 47A 52A 64A
a 30mA RCD. 16 mm² 16 mm² 16 mm²
63A 69A 85A
8 The current carrying capacity of the cable
must be at least that of the shower circuit
Note: Cable selection is dependent on
protection (see Table B).
derating factors
8.1 To obtain full advantage of the power
provided by the shower, use the shortest
cable route possible from the consumer unit
to the shower.
8.2 It is also necessary to satisfy the
disconnection time and thermal constraints
which means that for any given combination
of current demand, voltage drop and cable
size, there is a maximum permissible circuit
length.
9 The shower circuit should be separated from
other circuits by at least twice the diameter
of the cable or conduit.
9.1 The current rating will be reduced if the
cabling is bunched with others, surrounded
by thermal loft or wall insulation or placed in
areas where the ambient temperature is
above 30°C. Under these conditions,
derating factors apply and it is necessary to
select a larger cable size.
9.2 In the majority of installations, the cable
will unavoidably be placed in one or more
of the above conditions. This being so, it 
is strongly recommended to use a
T80si electric shower

WATER REQUIREMENTS
Water requirements
Mains electric supply
(via double pole switch) The installation must be in accordance with
Water Regulations/Bylaws.
To ensure activation of the heating elements, the
shower must be connected to a mains water
Double
pole supply with a minimum running pressure of
isolating 100kPa (1.0 bar) at a minimum flow rate of eight
switch
litres per minute (nine litres per minute for the
9.5kW rated model).
Shower
unit For all units the maximum static pressure must
be no greater than 1000kPa (10 bar).
Isolating
stopvalve If in any doubt, the pressure should be checked.
Note: If the stated flow rate is not available, it
may not be possible to achieve optimum
Mains
performance from theB-004-A
unit throughout the year.
water The water supply can be taken from a cold water
supply
storage cistern provided there is a minimum
head of ten metres. Minimum head is the vertical
distance from the base of the cistern to the
showerhead. It must be an independent supply
Separate permanently to the shower only.
connected supply
from consumer unit If it is intended to operate the shower at
pressures above the maximum or below the
minimum stated, contact Triton Customer
Fig.5 Diagrammatic view (not to scale)
Service for advice.
Fig.5 shows a typical system layout.
Do not use jointing compounds on any pipe
fittings for the installation.


T80si electric shower

SITINGofOF
Siting THE
the SHOWER
shower
WARNING!
FOR EASE OF SERVICING, THE UNIT MUST The shower must not be positioned
ALWAYS BE MOUNTED ON THE SURFACE OF W-008-A
where it will be subjected to freezing
TILED WALLS. NEVER TILE UP TO THE UNIT.
conditions.
Refer to (Fig.6) for correct siting of shower.
Position the unit where it will not be in direct
contact with water from the showerhead. Shower unit can
be mounted either
Position the shower unit vertically. side of riser rail
Allow enough room between the ceiling and the
shower to access the cover top screws.
S-001-A
Note: Water Regulations (shower hose
connections) requires the showerhead be
‘constrained by a fixed or sliding attachment so Height of
showerhead
that it can only discharge water at a point not and shower
less than 25 mm above the spill-over level of the to suit user's
relevant bath, shower tray or other fixed requirement
Retaining
appliance’. The use of the supplied soap dish will ring Mains cold water
supply (either top,
in most cases meet this requirement, but if the side, bottom
showerhead can be placed within a bath, basin or rear entry)
or shower tray, then a double check valve, or
similar, must be fitted in the supply pipework to Shower unit
25 mm minimum must not
prevent back-flow. be within
an area
Pressure relief safety device 1 metre
Outline of bath from base
A pressure relief device (PRD) is designed into the or shower tray
shower unit which complies with European
standards. The PRD provides a level of appliance
protection should an excessive build up of Fig.6 Diagrammatic view (not to scale)
T00312
pressure occur within the shower.
Do not operate the shower with a damaged or IMPORTANT: The unit must be mounted on
kinked shower hose, or a blocked showerhead a flat surface which covers the full width
which can cause the PRD to operate. and length of the backplate. It is important
When commissioning, the showerhead must be that the wall I-002-A
surface is flat otherwise
removed from the flexible
P-001-A hose, while at the difficulty may be encountered when fitting
same time the temperature control must be at the cover and subsequent operation of the
the minimum flow position. Failure to follow this unit may be impaired.
procedure may also cause the PRD to operate.
Make sure the shower is positioned over a bath
or shower tray because if the PRD operates, then
water will eject from the bottom of the unit.
Should this happen, turn off the electricity and
water supplies to the shower at the isolating
switch and stopvalve. Contact Customer Service
for advice on replacing the PRD.


T80si electric shower

FITTING THE
Fitting the SHOWER
shower TO
to the THE WALL
wall
Fig.7
WARNING!
Check there are no hidden cables or
pipes before drilling holes for wall
W-005-A
plugs. Use great care when using power
tools near water. The use of a residual
current device (RCD) is recommended.

Note: The control knobs are an integral part of


the cover — do not attempt to remove them.
Unscrew the two top and one bottom retaining
screws (fig.7) and lift the cover from the
backplate.
Entry positions for the mains water and electric
cable are from the top, bottom, either side or
from the back.
Note: Deviations from the designated entry
points will invalidate product approvals.
If bottom entry has been chosen, fit the
appropriate cut-out in the top of the backplate
(fig.8).
If top entry has been chosen, fit the appropriate
cut-out in the bottom of the cover (fig.9).

Fig.8

Fig.9


T80si electric shower

If side entry is required, the cover will have to be


cut out. Carefully remove the appropriate area Fig.10
by using a knife or junior hacksaw (fig.10).
If installing a feed pipe from the back or bottom,
the centre of the inlet valve to the wall surface is
20 mm (fig.11).
Note: If entry is from the back, the nut of the
compression fitting will be partially behind the
surface of the wall (fig.11). This area must
be left clear when plastering over the pipework
in order to make the nut accessible for future
adjustments.
After choosing the site for the shower, use the Fig.11
backplate as a template and mark the two fixing
holes (fig.12).
Drill and plug the wall.
(An appropriate drill bit should be used. If the
wall is brick, plasterboard or a soft building block,
appropriate wall plugs and screws should be fitted).
Screw bottom fixing screw into position leaving
the base of the screw head protruding 6 mm out
20 mm
from the wall.
Hook the backplate over the bottom screw and
fit the top fixing screw into position.
Do not fully tighten the screws at this stage,
as the fixing holes are elongated to allow for Fig.12
out of square adjustment after the plumbing
connections have been completed.


T80si electric shower

WARNING!
PLUMBING CONNECTIONS
Plumbing connections
The outlet of the shower acts as a Plumbing to be carried out before wiring.
W-004-A
vent and MUST NOT be connected to Do not use jointing compounds on any pipe
anything other than the hose and fittings for the installation.
showerhead supplied. Do not use soldered fittings near the shower
unit as heat can transfer along the pipework and
can damage components.
Compression fittings must be used to connect
to the inlet of the shower.
Note: An additional stopvalve (complying with
Water Regulations) must be fitted in the mains
water supply to the shower as an independent
means of isolating the water in order to carry
out maintenance or servicing.
Important: Before completing the
connection of the water supply to the inlet of
the shower, flush out the pipework to remove
all swarf and system debris. To do this,
connect a hose to the pipework and turn on
the mains water supply long enough to clear
the debris to waste.
Procedure
Turn off water supply either at the mains
stopvalve or the isolating stopvalve. Connect the
mains water supply to the inlet of the shower
via 15 mm copper, stainless steel or plastic pipe
using a 15 mm x 15 mm compression fitting.
Note: The inlet fitting is designed to enter a
compression fitting only. Do not use push
fit connectors as full engagement cannot be
guaranteed. Do not use excessive force when
making these connections.
Make sure the backplate is square on the wall
and tighten the two retaining screws which hold
it to the wall.
Turn on the mains water supply and check for
leaks in the pipework connection to the shower.
IMPORTANT: Using a suitable sealant,
always seal around the incoming pipework to
prevent water entering the wall.
Note: At this stage no water can flow through
the unit.

10
T80si electric shower

ELECTRICAL CONNECTIONS
Electrical connections
Fig.13
Switch off the electricity supply at
the mains. E L N
Fig.13 shows a schematic wiring diagram. 1
The cable can be surface clipped, hidden or via
20 mm conduit.
9 2
Note: Conduit entry can only be from rear.
Route the cable into the shower unit and
connect to the terminal block (fig.14) as
follows:
5
7
Earth cable to terminal marked E
Neutral cable to terminal marked N 8 4
Live cable to terminal marked L

Important: Fully tighten the terminal block 6


screws and check that no cable insulation is 3
trapped under the screws. Loose connections
1. Terminal block 6. Solenoid valve
can result in cable overheating. 2. Thermal cut-out (main) 7. Element
Note: The supply cable earth conductor must 3. Thermal cut-out (outlet) 8. Element
be sleeved. The outer sheath of the supply cable 4. Microswitches 9. Neon
must be stripped back to the minimum. 5. Start/Stop button
The supply cable must be secured either by
routing through conduit or in trunking or by
Fig.14
embedding in the wall, in accordance with IEE
regulations.
The use of connections within the unit, or other Terminal
points in the shower circuit, to supply power to block
other equipment i.e. extractor fans, pumps etc.
will invalidate the guarantee.
DO NOT switch on the electricity supply until
the cover has been fitted.

Note: The elements on UK models are to 240V


specification andN-001-A
will give a lower kW rating if
the voltage supply is below 240V.

11
T80si electric shower

REPLACING
Replacing theTHE COVER
cover
Fig.15
The power selector spindle must be aligned as
shown (fig.15).
To check that the temperature control is
correctly positioned on the stabilising valve
temporarily place the cover in position so that
the splines engage and rotate the temperature
control fully anti-clockwise.
Remove the cover and position the temperature
control knob so that it points towards the ‘1’
Fig.16 Fig.17 position (fig.16).
Position the power selector to the Cold position
(fig.17).
Offer the cover to the backplate unit. Attached
to the Stop/Start switch inside the cover is a
two-wire lead. The socket on the end of this lead
must be connected to the plug that is situated
at the bottom of the right-hand side of the
backplate unit (fig.18).
Note: The plug and socket can only fit one way.
Replace the cover squarely to the backplate.
Fig.18 Make sure the cover side wall locates over the
guide rib on the back plate (fig.19). Guide
into position so that the knobs locate correctly
into the splined spindles while at the same time,
ensuring wires are not trapped.
Should any difficulty arise, recheck the points
above.
Secure the cover in position with the three
retaining screws.

Fig.19

Backplate

Cover

12
T80si electric shower

COMMISSIONING
Commissioning
Fig.20
WARNING!
Before normal operation of the
shower, it isW-001-A
essential the following
commissioning procedure is completed
correctly.

The first operation of the shower is intended to


flush out any remaining unit debris, and to make
sure the heater unit contains water before the
elements are switched on. This operation must be
carried out with the flexible hose screwed to the
outlet but without the showerhead attached. The Fig.21
Cold position must be used. Make sure the
outlet of the flexible hose is directed to waste.
Note: Make sure the start/Stop button is not
depressed in the cover which indicates ‘start’.
The button should be flush with the cover,
otherwise water will flow as soon as the electricity
is switched on.
Before turning on the electric and mains water
supplies to the shower, make sure that the power
selector is at the Cold position (fig.20) and the
temperature control is rotated fully clockwise to
‘10’, the minimum flow position (fig.21). Fig.22
Note: Failure to turn the control to ‘10’ may
cause the PRD to operate.
Turn on the mains water supply to the shower
at the isolating stop valve and then turn on the
electric supply to the shower at the isolating
switch. The power indicator will light.
Press the Start/Stop button (fig.22) and wait
until water starts to flow from the flexible hose.
Slowly rotate the temperature control fully anti-
clockwise to ‘1’, the maximum flow position Fig.23
(fig.23).
It will take about thirty seconds for a smooth flow
of water to be obtained whilst air and debris is
being flushed from the shower.
When a smooth flow of water is obtained, rotate
the temperature control from ‘1’ to ‘10’ several
times to release any trapped air within the unit.
Once flushing out has been completed, stop the
water flow by pressing the Start/Stop button.
Fit the showerhead to the flexible hose and place
in the showerhead holder. The shower is now
ready for normal operation.

13
T80si electric shower

OPERATING
Operating theTHE SHOWER
shower
Fig.24
WARNING!
Before normal operation of the
Power selector shower, it isW-001-A
essential the following
Cold
commissioning procedure is completed
correctly.

To start the shower


High
Press the Start/Stop button and water will
flow.
Economy
To stop the shower
Press the Start/Stop button and water will
cease to flow.

WARNING!
If restarting immediately after
Temperature stopping, beW-003-A
aware that a slug of hot
control water will be expelled for the first few
seconds.

To use the power selector


The power selector has three positions — cold,
economy and high — as shown in fig.24.
Blue symbol is for cold water only. Adjustment
of the temperature control at this setting will
only alter the force of the water from the
showerhead. It will not alter the water
Stop temperature.
button Single red symbol is the economy setting
for using less power when the ambient mains
water temperature is high during hot months.
At this setting adjust the temperature using the
Note: In normal use, it is in order to leave the temperature control.
water supply permanently on to the shower Note: If the stated flow rate required for the unit
unit, but as withN-002-A
most electrical appliances, cannot be met due to low water pressure, it will
the unit must be switched off at the be necessary to operate the unit on this setting
isolating switch when not in use. during the warmer months because of flow rate
limitations entering the unit.
Double red symbol is the high setting which
allows the highest flow achievable for your
preferred temperature. This setting should
normally be regarded as optimum shower
performance throughout the year. Temperature
adjustment at this setting is via the temperature
control.

14
T80si electric shower

To adjust the shower temperature


WARNING!
The water temperature is altered by increasing After any servicing of mains water
or decreasing the flow rate of the water through
supply, always flush out the pipework
the shower via the temperature control (fig.24).
W-002-A
to remove any debris.
After obtaining your preferred shower Always make sure the unit is started
temperature, the number can be remembered
on COLD in order to purge any air in
and left as the normal setting and should only
the pipework.
need to be altered to compensate for seasonal
changes in ambient water temperature.
Note: The preferred number on ‘economy’ Warning!
will give a different temperature to the same
number position on ‘high’. This appliance is not intended for use
by persons (including children) with
To decrease the shower temperature reduced physical, sensory or mental
Turn the temperature control anti-clockwise; capabilities, or lack of experience
this will increase the flow of water through the and knowledge, unless they have
shower and be indicated by the lower numbers. been given supervision or instruction
concerning use of the appliance by a
To increase the shower temperature
person responsible for their safety.
Turn the temperature control clockwise; this will
decrease the flow of water through the shower Children should be supervised to
and be indicated by the higher numbers. ensure that they do not play
with the appliance.
Note: It is advisable to be certain that the
showering temperature is satisfactory by testing
with your hand before stepping under the
showerhead. There will always be a time delay of
a few seconds between selecting a flow rate and
the water reaching the stable temperature for
that flow rate.
Caution: It is recommended that persons
who may have difficulty understanding or
operating the shower controls should not
be left unattended whilst showering. Special
consideration should be given to young
children and the less able bodied.

15
T80si electric shower

OPERATING FUNCTIONS
Operating functions
Fig.25
Power on indicator (fig.25)
Power ‘ON’ Indicator
When the electricity supply to the shower is
switched on at the isolating switch, the ‘power’
indicator will light.
Low pressure indicator (fig.25)
A red indication means the water pressure has
fallen below the minimum required for correct
operation of the shower. In this state the low
pressure cut-out has operated. This switches
off power to the heating elements preventing
undue temperature rises (water will continue to
flow). Power will automatically be restored when
adequate water pressure returns.
If the indication fluctuates between red and
green, this means that there is just enough
Low pressure indicator pressure and operating difficulties may be
encountered.
A green indication shows that water pressure
is high enough for satisfactory operation of the
shower.

Overheat cut-out
During normal operation if an overheat
temperature is sensed, power to the elements
will be reduced. Water will continue to flow.
When the temperature has cooled sufficiently,
power to the elements will be automatically
restored to the previous setting at the time of
interruption.

Safety cut-out
The unit is fitted with a non-resettable over-
temperature safety device. In the event of
abnormal operation which could cause unsafe
temperatures within the unit, the device will
disconnect the heating elements. It will require a
visit from a qualified engineer to determine the
nature of the fault and replace the safety device,
once the unit has been repaired.

16
T80si electric shower

INSTRUCTIONS
Instructions FORand
for installers INSTALLERS AND SERVICE
service engineers only ENGINEERS ONLY
Cleaning the inlet filter
Fig.26
The inlet filter is situated inside the solenoid inlet
(fig.26).
To gain access to the filter remove the cover,
then disconnect and remove the compression
fitting. Also, depending on the incoming
pipework arrangements, if there is not enough
slack in the pipework, it could mean the removal
of the unit from the wall.
When cleaning the filter, do not use a sharp Inlet
object, as it will cause damage. It is preferable to filter
use an old toothbrush or similar.

17
T80si electric shower

Spare parts SPARE PARTS


Ref. Description Part No.

1. Terminal block 22011410

4 2. Can assembly
3 7.5kW P84500440
5 8.0kW 84500450
8.5kW P07810700
9.5kW P07810701
2 3. Thermal cut-out (main) 22009860
4. Power neon 82300980
1 6 5. Switching module assembly
82500160
c/w actuator & m’switches
6. Stabiliser valve assembly 82600820
7
7. Solenoid valve assembly 83300450
8. Outlet pipe assembly
8 c/w wires & PRD 82201090

9 9. Pressure Relief Device 82800450


– Start/Stop switch assembly 83305380
– Terminal block live wire assy. 82301000
10. Cover assembly
84900010
c/w knobs & button
11. Insert trim – backplate 7052244
12. Insert trim – cover 7052245

10

11 12

18
T80si electric shower

FAULT FINDING
IMPORTANT: Switch off the electricity at the mains supply and remove the circuit fuse before
attempting any fault finding inside the unit.
Fault finding
Problem/Symptom Cause Action/Cure

1 Shower inoperable, 1.1 Interrupted 1.1.1 Blown fuse or circuit breaker. Check
no water flow. power supply. supply. Renew or reset fuse or circuit breaker. If it
fails again, consult a qualified electrician.
1.1.2 Power cut? Check other appliances and if
necessary, contact local Electricity Supply Co.
1.2 Unit malfunction. 1.2.1 Have unit checked. Ring Customer
Service.

2 Water too hot. 2.1 Not enough 2.1.1 Increase flow rate via temperature
water flowing through control.
the shower. 2.1.2 Blocked showerhead — clean or replace
blocked sprayplate in showerhead.
2.2 Blockage in 2.2.1 Check if stop valves are fully open. Check
supply. if blockage in inlet filter.
2.3 Increase in 2.3.1 Readjust flow rate to give increased flow.
ambient water 2.3.2 Select ‘economy’ power.
temperature.

3 Water temperature 3.1 Heater cycling on 3.1.1 See 'Water too hot' causes 2.1, 2.2 and
cycling hot/cool at outlet thermal cut-out. 2.3 and their appropriate action/cures. If it
intervals. continues, contact Triton Customer Service.

4 Water too cool or 4.1 Too much flow. 4.1.1 Reduce flow rate via temperature control.
cold. 4.2 Water pressure 4.2.1 Is water supply mains or tank fed?
below minimum 4.2.2 If tank fed, replumb to mains water
required (see rating supply or see 4.2.4.
label). 4.2.3 If mains fed, make sure that the mains
stopvalve is fully open and there are no other
restrictions in the supply while shower is in use,
or see 4.2.4.
4.2.4 Fit pump to give minimum pressure
(see rating label). Contact Customer Service for
advice.
4.3 Reduction 4.3.1 Readjust flow rate to give reduced flow.
in ambient water 4.3.2 Select ‘high’ power.
temperature.
4.4 Electrical 4.4.1 Have unit checked by suitably qualified
malfunction or safety electrician or contact Triton Customer Service.
cut-out operated.

19
T80si electric shower

FAULT FINDING

Problem/Symptom Cause Fault finding (continued)


Action/Cure

5 Shower varies from 5.1 Water pressure 5.1.1 Wait until the water pressure resumes to
normal temperature to has dropped below normal.
cold during use. minimum required.

6 Pressure relief 6.1 Blocked 6.1.1 Clean or replace blocked sprayplate in


device has operated showerhead. showerhead and then fit new PRD.
(water ejected from 6.2 Twisted/blocked 6.2.1 Check for free passage through hose.
PRD tube). flexible shower hose. Replace the hose if necessary and fit new PRD.
6.3 Showerhead 6.3.1 Fit new PRD. Commission unit with
not removed while showerhead removed.
commissioning.

7 Shower fails to shut 7.1 Faulty START/ 7.1.1 Replace switch.


off when STOP button STOP switch.
is pressed. 7.2 Debris in 7.2.1 Replace solenoid valve assembly.
solenoid.

Note: Identify cause of operation before fitting new PRD unit.


When fitting a new PRD, follow the commissioning procedure.
It is advised all electrical maintenance/repairs to the shower
should be carried out by a suitably qualified person.

20
T80si electric shower

21
UK SERVICE POLICY T80si electric shower
TRITOn STandaRd GUaRanTEE
In the event of a product fault or complaint occurring, the Triton guarantee this product against all
following procedure should be followed: mechanical and electrical defects arising from
1. Telephone Customer Service on 0844 980 0750 having available, faulty workmanship or materials for a period of
your details including post code, the model number and power two years for domestic use only, from the date of
rating of the product, together with the date of purchase. purchase, provided that it has been installed by
2. Based on information given over the telephone, a Triton Customer a competent person in full accordance with the
Service Advisor will attempt to diagnose the fault and confirm fitting instructions.
whether a site visit from a qualified service engineer is required. Any part found to be defective during this
3. All products attended to by a Triton service engineer must guarantee period we undertake to repair or replace
be installed in full accordance with the Triton installation at our option without charge so long as it has been
guide applicable to the product. (Every product pack contains properly maintained and operated in accordance
an installation guide, however, they can also be bought via our with the operating instructions, and has not been
Customer Service Spares Department). subject to misuse or damage.
4. Our engineer will require local parking and if a permit is required This product must not be taken apart, modified or
this must be available to the engineer on arrival at the call.
repaired except by a person authorised by Triton.
5. It is essential that you or an appointed representative (who must This guarantee applies only to products installed
be over 18 years of age) is present for the duration of the service within the United Kingdom and does not apply to
engineer's visit. If the product is in guarantee you must produce products used commercially. This guarantee does
proof of purchase.
not affect your statutory rights.
6. Where a call under the terms of guarantee has been booked and
the failure is not product related (i.e. scaling and furring, incorrect What is not covered:
water pressure, pressure relief device operation or electrical/ 1. Breakdown due to: a) use other than domestic
plumbing installation fault) a charge will be made. A charge will use by you or your resident family; b) wilful act
also be issued if nobody is at home when the service engineer
or neglect; c) any malfunction resulting from the
calls or adequate parking/permit is not available.
incorrect use or quality of electricity, gas or water
7. If the product is no longer covered by the guarantee an up front or incorrect setting of controls; d) failure to install
fixed fee will be charged before the site visit. in accordance with this installation guide.
8. Should proof of purchase not be available on an “in-guarantee” 2. Repair costs for damage caused by foreign
call, or should the service engineer find that the product is no objects or substances.
longer under guarantee, the engineer will charge the same
fixed price and the customer will be expected to pay the 3. Total loss of the product due to non-availability
engineer before he leaves. If payment is not made on the day an of parts.
administration charge will be added to the fixed charge. 4. Compensation for loss of use of the product or
9. If a debt is outstanding from a previous visit, or from any other consequential loss of any kind.
Triton purchase. Triton reserves the right to withhold service until 5. Call out charges where no fault has been found
the debt has been settled. with the appliance.
10. Triton takes the health, safety and wellbeing of its employees very 6. Call out charges where the water supply cannot
seriously and expects customers to treat all staff members with be isolated, this includes consequential losses
respect. Should any employee feel threatened or receive abuse, arising from unserviceable supply valves.
either verbally or physically, Triton reserves the right to withhold 7. The cost of repair or replacement of pressure
service and will support the employee with a legal prosecution. relief devices, showerheads, hoses, riser rails
Replacement Parts Policy and/or wall brackets, isolating switches,
Availability: It is the policy of the manufacturer to maintain parts electrical cable, fuses and/or circuit breakers or
availability for the duration of production and a period of five years any other accessories installed at the same time.
thereafter, in accordance with industry standards. 8. The cost of routine maintenance, adjustments,
Spare parts are available via our website, www.tritonshowers. overhaul modifications or loss or damage arising
co.uk, or by telephoning Triton Customer Service Spares Department. therefrom, including the cost of repairing
Payment should be made by credit/debit card (excluding American damage, breakdown, malfunction caused by
Express or Diners Card). corrosion, furring, pipe scaling, limescale,
Payment can also be made by pre-payment of a pro forma invoice by cheque or money order. system debris or frost.

Customer Service: % 0844 980 0750


Triton Showers
Triton Road Trade Installer Hotline: %
0844 980 0730
Nuneaton Fax: 0844 980 0744
Warwickshire CV11 4NR www.tritonshowers.co.uk
Triton is a division of Norcros Group (Holdings) Limited E-mail: [email protected]

Extended Warranty AVAILABLE NOW. Call 0844 980 0740 for more details.
29-5-2009 TRITON reserve the right to change product specification without prior notice. E&OA. © TRITON SHOWERS 2009
22

You might also like