August 19, 2004 DN-6971 • A0-110
NOTI•FIRE•NET™
Release 5.0
Section: Network Systems
GENERAL
NOTI•FIRE•NET™ is the interface which allows NOTIFIER Intelligent
Fire Alarm Control Panels to form a network. Each local control panel
(network node) maintains its own area of protection, while monitoring
and controlling other areas (other network nodes).
Local information is displayed at each network node. In areas such as
a security office, where the entire network must be monitored, network
annunciators are available.
NOTI•FIRE•NET™ (NFN) is a token-pass style network based on the
proven ARCNET® local area network technology, with four million nodes
installed worldwide. This computer LAN architecture makes NFN
extremely powerful, yet simple to configure and install.
FEATURES S635
• Fiber optic (multi-mode), wire, or combination wire/fiber communica-
tions path.
• NFPA Style 4 or Style 7 network operation.
• Based on proven ARCNET® technology.
• True peer-to-peer communications. Each node stores its own program
and communicates equally with all other nodes.
CS118
• Token-passing non-collision protocol.
• No “master” polling computer or other central weak link.
• Inherently regenerative system. Each node acts as a repeater to
reshape and regenerate data signals. Failure of any node does not
affect any other node/communications among surviving nodes.
• High-speed data communications (312,500 BPS) operates several
times as fast as competitive networks.
• Simple plug-in module, the SIB-NET, connects AM2020/AFP1010.
The NAM-232 connects AFP-200, AFP-300, and AFP-400 panels
anywhere on the network. The NCM connects the NFS-3030, NFS-
640, NCA, BACnet Gateway, and NWS.
• Multiple Network Control Stations (ONYX® NCS) may be placed
anywhere on the network. Additional ONYX® NCS’s may be used to
provide inherent “hot” backup.
• Multiple Network Control Annunciators (NCA) may be placed any-
where on the network. Version 5.0 does not support the INA.
• ONYX® Series NCS and NCA display all network activity. Unlike
competitive systems, the point display capacity is NOT held to less
than the maximum network capacity.
• Single small-gauge twisted-pair wire (no shield necessary) for data
communications path.
• Electrical isolation between nodes.
• Network clock synchronization (see page 3).
• History Buffers on NCA, ONYX® NCS, NFS-3030, NFS-640, AFP1010,
AM2020, AFP-200, AFP-300, and AFP-400 Intelligent Fire Control
Panels.
• Powerful Cooperative-Control-by-Event allows point(s) on one node
to activate point(s) on other nodes. Any input can turn on any output,
network-wide.
NOTI•FIRE•NET™ is a trademark and ONYX® is a registered trademark of NOTIFIER.
4644d1.wmf
ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows®
are registered trademarks of Microsoft Corporation. Pentium® & Intel® are registered
trademarks of Intel Corporation. ST® is a registered trademark of AT&T Corporation.
NOTIFIER® is a Honeywell company.
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications
or anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
Made in the U.S.A.
12 Clintonville Road, Northford, Connecticut 06472
DN-6971 • 08/19/04 — Page 1 of 4
6971conf.wmf
Page 2 of 4 — DN-6971 • 08/19/04
NCS NETWORK CONTROL STATION
The NCS is based on a UL 864-recognized computer. Special hardware and software are
added by NOTIFIER to make the NCS operate as a Command Center for NOTI•FIRE•NET™.
PENTIUM-BASED COMPUTER (ONYX® NCS) features:
• Intel® 2.0 GHz Pentium® IV microprocessor.
• 256 KB cache memory, 256 MB RAM.
• 40 GB hard drive, 1.44 MB floppy drive, 24/10/40X CD-RW drive.
• 17" flat-screen LCD monitor, Windows® 2000 keyboard, P/S 2 mouse,
300 Watt power supply, sound card, microphone, and internal speakers.
• Microsoft® Windows® 2000.
NCA NETWORK CONTROL ANNUNCIATOR
The NCA provides full annunciation of all network signals and may optionally allow system
control functions. 6869flat.jpg
• 640-character, backlit LCD display shows all network alarms and troubles.
• LEDs for POWER, FIRE ALARM, PRE-ALARM, SECURITY, SUPERVI-
SORY, SYSTEM TROUBLE, OTHER EVENT, SIGNAL SILENCED, POINT
DISABLE, and CPU FAILURE.
• Fixed Function Keys/Switches for FIRE ALARM SCROLL/DISPLAY, SECU-
RITY SCROLL/DISPLAY, SUPERVISORY SCROLL/DISPLAY, TROUBLE
SCROLL/DISPLAY, OTHER EVENT SCROLL/DISPLAY, SIGNAL SILENCE,
DRILL, AND SYSTEM RESET.
• Special Function Keys for DISABLE/ENABLE, PRINT SCREEN, LAMP TEST,
NEXT SELECTION/PREVIOUS SELECTION, and RECALL LAST ENTRY.
• Alphanumeric QWERTY keypad with tactile and audible feedback.
• Nonvolatile real-time clock can be synchronized with network by master node.
• Nonvolatile History Buffer (200 Alarm events, 1,000 System events).
6858ncs.wmf
• Two optically-isolated EIA-232 ports for printer and CRT terminal. NCA
• Mounts in ABS-4D surface/semi-flush cabinet with door and key lock.
• Mounts in CAB-3 or CAB-4 Series cabinets, using ADP-4(B) hinged dress panel.
• An NCM is required for every NCA.
4644sib.wmf
• 24 VDC power from remote or local supply (CAB-3/-4 Series cabinet required for local power).
SIB-NET
The SIB-NET is a plug-in board which allows an AM2020 or AFP1010 control panel to connect
to NOTI•FIRE•NET™. It plugs into the panel ICA-4L Interconnect Chassis Assembly.
• Plug-in module may be retrofitted into existing systems.
• Accepts one MIB series module.
• Two EIA-232 ports for CRT terminals, or EDP listed devices.
• Two EIA-232 ports for PRN printers, or EDP listed devices.
• EIA-485 port for ACS annunciators, LDM Series, LCD-80, AMG, etc.
SIB-NET
NAM-232
The NAM-232 (NAM-232F for Fiber, NAM-232W for Wire medium) provides the ability to con-
4644namw.wmf
nect the AFP-200, AFP-300 and AFP-400 intelligent control panels to NOTI•FIRE•NET™.
AFP-200 Network Interface Features: AFP-300/400 Network Interface Features:
• Acknowledge, Signal Silence, • Acknowledge, Signal Silence,
System Reset from NCA or NCS. System Reset from NCA or NCS.
• Limited CCBE operation. Cannot • Remote Annunciator Control from NCA. NAM-232W
participate in clock synchronization. • Read status, control On/Off, and point enable/
• Full network display. disable from NCA or NCS.
• Limited CCBE operation. Cannot serve
as a synchronization master clock.
4644mib.wmf
• Full network display.
MIB SERIES MEDIA INTERFACE BOARDS
The MIB mounts “piggyback” onto the SIB-NET module. It operates at 312K bits per second and
provides full signal regeneration and amplification before passing information on to the next MIB-WF
node. In combination with the panel software, it will support NFPA Style 4 or 7 configurations.
It is available in three versions: MIB-W (wire), MIB-F (fiber), and MIB-WF (hybrid wire/fiber).
RPT SERIES REPEATER MODULES
4644rpt.wmf
The RPT repeater is a single PC board that may be used to extend the distance of transmission.
It may also be used to change media type between wire and fiber. The RPT may mount in the RPT-WF
ABS-8R surface box, or in the CAB-3 or CAB-4 Series using one slot of the CHS-4 or CHS-4L.
Available as RPT-W (wire), RPT-F (fiber), and RPT-WF (wire/fiber converter). Requires 24 VDC.
DN-6971 • 08/19/04 — Page 3 of 4
SPECIFICATIONS NOTI•FIRE•NET™ VERSION 5.0
• ONYX® NCS Network Control Station ORDERING/COMPATIBILITY
See ONYX® NCS data sheet, DN-6869. REQUIREMENTS
• NCA Network Control Annunciator • The NCS must be version 4.0 or higher. To upgrade NCS
See NCA data sheet, DN-6858. version 1.0 to NCS version 4.0 or higher, order NCSKIT-NCW
(for wire) or NCSKIT-NCF (for fiber) and NCSCDUG-US-4.
• NAM-232 Network Interface Board • The NAM-232 (for AFP-200, AFP-300/400) firmware must
See NAM-232 data sheet, DN-5331. be version 5.0. To upgrade the NAM-232 for a version 5.0
• SIB-NET Serial Interface Board network, order NROM-NAM5.0M.
• The SIB-NET (for AM2020/AFP1010) firmware must be
NFN interface: standard MIB slot.
version 5.0. To upgrade the SIB-NET for a version 5.0
EIA-232 terminal ports (2): 2,400 baud, isolated. network, order AROM5.0M-SIB.
EIA-232 printer ports (2): 2,400 baud, isolated • NOTI•FIRE•NET™ version 5.0 will not support the INA.
EIA-485 ACS port: 20,833 baud, isolated. • See NOTI•FIRE•NET™ Ordering Bulletin on Magni-
Size: 8.0" x 8.0" (203.2 x 203.2 mm). Fire.com.
Compatible panels: AM2020, AFP1010. AGENCY LISTINGS AND APPROVALS
All NOTI•FIRE•NET™ equipment, including the NCS, NCA,
• MIB-W Media Interface Board MIBs, NAM-232, and RPTs are listed by Underwriters Labo-
Data rate (bits per second): 312,500. ratories in file S635. Listings are for UL category UOJZ (Con-
Maximum wire distance: 3,000 feet (914.4 meters), two trol Units System) and comply with UL standard 864 (control
channels. units for Fire-Protective Signaling Systems) and comply with
Wiring type: twisted pair. UL 1076 (Proprietary Burglar alarm units and systems) UL
1610.
Wire size: 14 AWG (2.0 mm²) to 18 AWG (0.75 mm²).
Certain software features described in this catalog sheet may
Board size: 3.5" (88.9 mm) x 5.0" (127.0 mm). not yet be included in this UL listing. Consult factory for lat-
est listing status.
• MIB-F Media Interface Board
Listings for many other agencies are in process. Consult
Data rate (bits per second): 312,500. factory for latest listing status.
Fiber distance: 10 dB loss, two channels.
Fiber type: dual, Plenum grade. ENGINEER/ARCHITECT
Fiber size: 62.5 µm/125 µm; wavelength: 850 nM. SPECIFICATIONS
Connector type: ST®. Complete specifications on NOTI•FIRE•NET™ and NOTI-
FIER’s complete line of fire alarm control and peripheral
Board size: 3.5" (88.9 mm) x 5.0" (127.0 mm) devices are available from NOTIFIER.
• MIB-WF Media Interface Board http://www.notifier.com
Specifications: same as MIB-W plus MIB-F; one channel
wire, one channel fiber.
• RPT-W, RPT-F, RPT-WF Repeaters
Wire/fiber specifications: same as MIB-W and MIB-F.
Board size: 4.4" (111.76 mm) x 6.5" (165.1 mm).
• NCM-W Network Communications Module
See NCM-W and NCM-F data sheet, DN-6861.
Compatible panels: NFS-640, NFS-3030.
• NCM-F Network Communications Module
See NCM-W and NCM-F data sheet, DN-6861.
Compatible panels: NFS-640, NFS-3030.
• BACnet Gateway
See BACnet Gateway data sheet, DN-6877.
• NWS NOTI•FIRE•NET™ Web Server
See NWS data sheet, DN-6928.
Page 4 of 4 — DN-6971 • 08/19/04