Energy Efficiency
y Variable speed scroll compressor technology is the best solution in terms of variable cooling capacity,
with a minimum compressor speed down to 25% of maximum value. It improves annual efficiency even
when requested cooling load is low, such as in the early stage of a data center life, or when the IT
equipment usage is subject to big fluctuations; this reduces the cooling equipment’s total cost of
ownership and payback time.
y New EC fan generation with extended speed modulation range (minimum speed down to 30% of
maximum value) in order to guarantee the requested supply air temperature at any moment.
y New generation of heat rejection condensers equipped with EC fans to reduce even further power
consumptions and reduce noise at the same time.
y Eurovent certified performance guarantees independent testing, thus delivering rating accuracy and
enhancing the unit’s reliability. The new IT Cooling program updates performance tolerance,
introducing stricter values than previous ones.*
Cooling Continuity
y Liebert® PDX can automatically manage a power failure for 60 seconds, keeping the Liebert iCOM™
control board and the BMS communication on and permitting system supervision during a power
outage event. When power is restored, the intelligent Liebert iCOM™ control adopts a fast restart,
recovering in less than 40 seconds at the requested operating condition.
y Electrically, units can be fed with two power sources combined with an ATS for full back-up or with
two separate lines, one for control and fans and the other for compressors and other equipments.
y The airflow continuity is guaranteed until the last unit fan is able to run, both in the indoor and
outdoor unit.
y In case of control sensor failure, the unit automatically adapts in order to grant the necessary cooling/
airflow continuity. A redundant sensor can be installed and activated only if the first one breaks or is
missing.
Flexibility
y Liebert® PDX is fit for extreme working conditions and environments; the extended working range
allows a maximum external temperature of 55°C and a minimum of -30°C, with an internal return air
temperature up to 40°C.
y Liebert® PDX extended compressor’s and evaporator fan’s speed modulation range improves system
scalability, particularly in case of variable data center load.
y Liebert® PDX units adapt perfectly to all kinds of installations; maximum equivalent piping length
between unit and condenser can reach 100 m. Two different coil treatments (epoxy coating and
electrofin) are available for the entire range of Liebert® condensers, making their installation possible
also in critical conditions.
y More than 4 airflow configurations allow the units to adapt to any data center layout and
configuration.
Our Presence
Global Presence
Manuf. and Assembly Locations 28
Service Centers 250+
Service Field Engineers 2,650+
Technical Support/Response 300+
Customer Experience Centers/Labs 16
US and Canada Latin America Europe, Middle East And Africa Asia Pacific
Manuf. and Assembly Locations 13 Manuf. and Assembly Locations 1 Manuf. and Assembly Locations 9 Manuf. and Assembly Locations 5
Service Centers 100+ Service Centers 20+ Service Centers 70+ Service Centers 60+
Service Field Engineers 850+ Service Field Engineers 240+ Service Field Engineers 590+ Service Field Engineers 970+
Technical Support/Response 120+ Technical Support/Response 20+ Technical Support/Response 90+ Technical Support/Response 80+
Customer Experience Centers/Labs 4 Customer Experience Centers/Labs 2 Customer Experience Centers/Labs 5 Customer Experience Centers/Labs 5
Vertiv™ Liebert® PDX with Variable Speed Compressors
Single circuit models PI015 PI021 PI025 PI031 PI033 PI041 PI045 PI047 PI051 PI057 PI075 PI059
Maximum net sensible cooling capacity (*) kW 19,2 23,9 29,1 32,7 37,0 50,9 56,4 52,5 60,9 62,4 77,5 70,4
Minimum net sensible cooling capacity (*) kW 5,9 7,0 8,5 9,6 11,8 15,4 18,1 15,8 18,2 17,5 23,3 13,0
Nom. ESP Pa 20 20 20 20 20 20 20 20 20 20 20 20
Net Total Cooling Capacity kW 15,8 19,8 24,5 27,8 31,9 43,2 49,3 43,7 51,1 52,0 65,4 60,6
Compressor Net Sensible Cooling Capacity kW 15,8 19,8 24,5 27,8 31,9 43,2 49,3 43,7 51,1 52,0 65,4 60,6
modulation 80% (*) nSHR 1 1 1 1 1 1 1 1 1 1 1 1
Unit Net Sensible EER 4,63 4,49 4,11 3,54 3,36 3,91 3,66 4,02 3,86 4,17 3,71 3,53
Airflow m3/h 4049 5040 6217 7126 8163 11080 12608 11199 13104 13273 16745 13191
Net Total Cooling Capacity kW 8,3 10,5 13,4 15,3 18,2 23,8 27,8 23,7 28,1 27,8 36,2 35,4
Net Sensible Cooling Capacity kW 8,3 10,5 13,4 15,3 18,2 23,8 27,8 23,7 28,1 27,8 36,2 35,4
Compressor
nSHR 1 1 1 1 1 1 1 1 1 1 1 1
modulation 40% (*)
Unit Net Sensible EER 5,46 5,20 5,17 4,77 4,76 5,25 5,05 4,95 4,92 5,25 4,99 4,64
Airflow m3/h 2112 2669 3372 3911 4665 6086 7099 6047 7166 7118 9222 9045
Dimensions (W x D) mm 840x890 1200x890 1750x890 1200x890
Height (H) mm 1970 2570
Weight kg 315 316 336 358 358 471 472 640 641 688 754 584
Aiflow Delivery
Down Flow UP - Fans Over the Raised Floor • • •
Down Flow UP - Frontal air delivery • • •
Down Flow UP - Back air Delivery •
Down Flow Down - Fans in the Raised Floor • •
Up Flow • • •
Cooling Version:
Air Cooled • • •
Water Cooled
Dual fluid (Chilled water + DX Air Cooled)
Dual fluid - Chilled water + DX Water Cooled
Freecooling
EconoPhase
* Performance at RAT 30°C / RH 35% - Condensing temperature 45°C - Downflow up air configuration. CE units - Power supply 400V/3ph/50Hz - High Power EC Fans - Refrigerant R410A
The Liebert EconoPhase pumped refrigerant economizer is compatible with the Liebert PDX indoor unit and the Liebert MC
condenser to improve overall system efficiency.
* Performance at RAT 30°C / RH 35% - Condensing temperature 45°C - Downflow up air configuration. CE units - Power supply 400V/3ph/50Hz - High Power EC Fans - Refrigerant R410A
Double circuit models PI044 PI054 PI062 PI074 PI068 PI082 PI094 PI104 PI120 PI092 PI150 PI165
Maximum net sensible cooling capacity (*) kW 56,0 62,0 73,1 82,9 78,5 97,4 105,1 112,8 136,2 94,3 169,3 176,2
Minimum net sensible cooling capacity (*) kW 8,6 9,4 11,3 13,1 12,5 13,5 15,1 16,8 22,2 13,5 22,2 24,9
Nom. ESP Pa 20 20 20 20 20 20 20 20 20 20 20 20
Net Total Cooling Capacity kW 45,2 51,1 60,4 70,5 64,8 79,2 87,1 95,4 119,8 80,7 146,4 153,7
Compressor Net Sensible Cooling Capacity kW 45,2 51,1 60,4 70,5 64,8 79,2 87,1 95,4 119,8 80,7 146,4 153,7
modulation 80% (*) nSHR 1 1 1 1 1 1 1 1 1 1 1 1
Unit Net Sensible EER 4,42 4,32 3,99 3,66 4,71 4,15 4,04 3,91 3,35 3,69 3,65 3,51
Airflow m3/h 11546 13093 15414 18134 16921 20667 22769 24854 31292 20603 38428 40076
Net Total Cooling Capacity kW 21,8 23,8 28,6 32,8 31,2 45,2 49,5 55,1 69,8 36,3 83,3 90,1
Net Sensible Cooling Capacity kW 21,8 23,8 28,6 32,8 31,2 45,2 49,5 55,1 69,8 36,3 83,3 90,1
Compressor
nSHR 1 1 1 1 1 1 1 1 1 1 1 1
modulation 40% (*)
Unit Net Sensible EER 4,14 4,20 4,03 3,94 4,53 5,10 5,10 5,04 4,66 4,21 4,99 4,83
Airflow m3/h 5590 6113 7311 8490 8129 11686 12881 13984 18157 9239 21719 23299
Dimensions (W x D) mm 1750x890 2550x890 1750x890 3350x890
Height (H) mm 1970 2570
Weight kg 671 682 723 708 935 957 967 987 1006 811 1496 1544
Aiflow Delivery
Down Flow UP - Fans Over the Raised Floor • • • •
Down Flow UP - Frontal air delivery • • •
Down Flow UP - Back air Delivery • •
Down Flow Down - Fans in the Raised Floor • • • •
Up Flow • • •
Cooling Version:
Air Cooled • • • • •
Water Cooled
Dual fluid (Chilled water + DX Air Cooled)
Dual fluid - Chilled water + DX Water Cooled
Freecooling
EconoPhase • •