VVS/S-type

Fan Coil Unit

www.vtsgroup.com
01 VTS Group
1.1. VTS Group ...................................................................................................................................................................................................................................................................................................06
1.2. 3 pillars of success ..................................................................................................................................................................................................................................................................08

02 Support for designers


2.1. ClimaCad Online 4.0 ............................................................................................................................................................................................................................................................... 12
2.2. VTS BIM ..............................................................................................................................................................................................................................................................................................................14

03 VENTUS VVS Air Handling Units


3.1. General specification ...........................................................................................................................................................................................................................................................18
3.2. Technical specification...................................................................................................................................................................................................................................................... 26
3.2.1. VVS 021-120 - Recuperator - cross-flow plate exchanger.......................................................................................... 26
3.2.2. VVS 150-650 - Recuperator - cross-flow plate exchanger..................................................................................... 28
3.2.3. VVS 021-120 - Regenerator (rotary heat wheel)............................................................................................................................... 30
3.2.4. VVS 150-650- Regenerator (rotary heat wheel).............................................................................................................................. 32
3.2.5. VVS 21-120 - Supply & Exhaust.............................................................................................................................................................................................. 34
3.2.6. VVS 150-650 - Supply & Exhaust...................................................................................................................................................................................... 36
3.2.6. Additional configuration functions - VVS 021-650
- recuperator (hex & premium plus), regenerator (rotary heat wheel),
supply & exhaust........................................................................................................................................................................................................................................................................... 38
3.3. Components ..........................................................................................................................................................................................................................................................................................40
3.4. Controls..............................................................................................................................................................................................................................................................................................................48
3.4.1. Description.............................................................................................................................................................................................................................................................................48
3.4.2. Control elements ................................................................................................................................................................................................................................................. 52

04 VENTUS S-type Air Handling Units


4.1. Technical specification......................................................................................................................................................................................................................................................60

05 Fan Coil Unit


5.1. Technical specification...................................................................................................................................................................................................................................................... 66

06 WING units
6.1. WING ........................................................................................................................................................................................................................................................................................................................ 72

07 Psychrometric chart (Mollier)


7.1. Psychrometric chart (Mollier)..............................................................................................................................................................................................................................79
01
VTS Group

04
VTS Group VTS Group

OUR MISSION
VTS GROUP – is a manufacturer
of technically advanced HVAC equipment,
combining innovative technologies in the field
of research&development, production
AHU#1
and logistics.

WARSAW LC*
LUXEMBOURG HQ

ATLANTA LC*

DUBAI LC*

BANGALORE LC*

SHORTEST *
ON THE MARKET

L E A D
TIME
VVS021 - VVS650

*
Logistics center

06 07
VTS Group

3 PILLARS OF SUCCESS
Constantly highest quality of products. Best prices on the market.
Shortest lead time. These 3 pillars of marketing policy allows VTS
to be always one step head, wherever in the world.

Following the best practices of the branch, SHORTEST

ON THE MARKET
VTS has created a network of 4 efficiently L E A D
TIME
running production and logistic centers
(Atlanta, Dubai, Warsaw, Bangalore),
enable to ensure the shortest lead time on

4
the market, wherever in the world. CENTERS

L O G I S T I C

$ PRICE
COMPETITIVE

Large-scale production of repetative


units allow VTS to offer them at the most
competitive price, simultaneously keeping
their highest possible quality 150 000
U N I T S
SOLD ANNUALLY

Multistage quality control system allows BEST


VTS to offer up to 2-years warranty
of trouble free equipment operation. QUALITY

2
WARRANTY
YEARS

UP TO FOR EACH
U N I T

09
08
02
Support
for designers
Support for designers Support for designers

CLIMACAD ONLINE 4.0 (CCOL 4) CCOL 4.0 utilises latest technologies and software platforms. The tool has been developed
in SaaS model (Software as a Service). It’s best advantage is, that service is accessible wherever
in the world. Any device equipped with web-browser and internet access is all you need to experience
the power of our CCOL 4.0.
Infinite number Simple
of configurations and easy selection

Friendly Integration with CRM, DESIGN VERSATAILTY


user interface ERP & WMA systems
» Infinite units configurations.
Certified by » Detecting of configurations errors.

VVS021 - VVS650

CCOL4 OPTIMIZED FOR

» any
web-browser DYNAMIC AHU LENGTH DEFINITION

» CCOL4 applys dynamic optimizing of AHU length

Hd
H2
based on automatic air treatment functions.
placements with regard to minimum gaps between
them in order to secure their propper performance.

Hf
» any operating system L_1

» any device
MANAGING OF YOUR DATA BASE

» Self-creating and devellpment by designer of own


projects and AHU selections data base.
» Sharing of self-made AHU selections with VTS
enginners for pricing.
DATA EXPORT TO

SUBMITTAL QUOTATION TECHNICAL


SPECIFICATION

www.ccol4.com
12 13
Support for designers Support for designers

VTS BIM - new approach to digital models


of Air Handling Units
VTS has enabled dynamic generating The Autodesk REVIT® families
of VENTUS VVS, VENTUS Compact shared by VTS significantly facilitate
and American VENTUS AVS units entire building modelling process done
digital models as on-line service. by designing bureaus. At the moment,
This became possible thanks to the generator is an unique tool in entire
implementation of new AHU selection BIM environment. It enables to generate
tool – the ClimaCAD OnLine 4.0 brand new VENTUS units model
[CCOL 4.0], equipped with .rfa on the spot, in any configuration
[Revit®] files generator. or any parameters.

3 steps to generate the model: As a result the client is given:

Login to CCOL 4.0 AHU configuration and Selection export to .fra file Digital model of the air handling unit with fully parametrized VTS enables also a library of static families for WING air curtains
In order to generate .fra model, all connectors: and VOLCANO air heaters.
You can login using our web-site: parameters specyfing
Intuitive unit configurator enables you need to do is to enter personal Air, The models includes:
to select a unit, perfectly fitting information (including e-mail address) Hydraulic, parametrized electric and hydraulic connectors,
to your design assumptions. of a person to whom the model is to be Sanitary, both vertical and horizontal mounting options,
sent. The system will automatically sent
Electric, presentation of units effective air range,
the link to the site from where model
and also a set of complete technical and dimensioning parametrized angle of heater’s to the horizontal plane.
can be downloaded. Entire process take
information, including clearly marked maintenance and
no longer than 15 minutes.
service zone of the unit.
14 Models can be downloaded from: https://vtsgroup.com/vtsbim.html 15
Support for designers Support for designers

VTS BIM -air handling units perfectly


fitted for designer’s needs.
VTS supports generating of air handling The VENTUS BIM families include
units models in LOD 400 maintenance and service zones Service clearance
LOD
(Level Of Development) standard. of the units as standard.
repair & maintenance
400 as standard.
These zones reserve minimum space
to secure proper maintenance and repair
conditions of the unit, and allow to avoid

as standard
any collisions with remaining building
elements or installations.

16 17
03
Units
- VENTUS VVS
VVS

Airflow
from 1 100 m3/h
from 100 000 m /h
3

Up to 87%
of energy recovery
efficiency

14
sizes

DURABLE RELIABLE SMART USER


AND TIGHT COMPONENTS CONTROLS SAFETY
STRUCTURE
Technical Specification Technical Specification

STRUCTURE

ALUMINIUM COLUMNS
AS STANDARD
FOR ALL TYPES
OF UNITS

V PROFILE C PROFILE
VS 21-180 VS 230-650

GALVANIZED STEEL SUPPORT


AS STANDARD FOR ALL TYPES
OF UNITS

FRAME FAN SECTION CAGE STRUCTURAL COLUMNS

» easier transport » increased longitudinal stiffness » thermal breaks on the mullion as standard
» greater profile resistance to deflection of the structure » high resistance to weather conditions
» easier sections assembly and UV rays

22 23
Technical Specification Technical Specification

TIGHTNESS

THERMAL LABIRYNTH
BREAK TIGHTNENING

ADDITIONAL ADDITIONAL
POST SEALING SEALING BLADE

CANOPY ERGONOMIC INSPECTION PANEL LOCK ALUMINUM STRUCTURAL POSTS WITH ADDITIONAL SEALING BLADE
AND THERMAL BREAK
» The canopy is made of 0,5 mm steel sheet, double » Highly aesthetic and ergonomic handles
side coated with 185 um of zinc (DX51D AZ185). securing perfect tightness of inspection panels. » Broken thermal bridge as standard – eliminates humidity condensation on units structural elements.
» Canopy is assembled of modules equipped » Blade along the inspection window ensures labyrinth tightening between panel and AHU body
with self-latching grooves securing perfect tightness – currently the most effective solution on the market, mainly applied to laboratory equipment.
of the joints. Modular structure of the canopy
» Symmetrical groove in the vertical post’s mounting feet secures its 100% tightness with the AHU casing
ensures its easy and safe assembly.
structure.

24 25
Technical Specification Technical Specification

VVS 021-120 – RECUPERATOR DIMENSIONS - VVS021-VVS120 – RECUPERATOR


- CROSS-FLOW PLATE EXCHANGERS - CROSS-FLOW PLATE EXCHANGERS
Nominal parameters Recommended airflow range Opening BIG - inlet-outlet Opening SMALL - inlet-outlet
Unit size VVS021 VVS030 VVS040 VVS055 VVS075 VVS100 VVS120 END (FF) END (FS)
Size WA HA WA1 HA1 Size WA HA WA1 HA1
18 000 VVS021 150 112 405 168
VVS021 500 210 230 119
VVS030 700 210 130 185 VVS030 200 112 380 234
12 000
VVS040 600 310 284 135 VVS040 250 112 459 234

6 000 VVS055 850 310 244 202 VVS055 350 112 494 301
[m3/h]

VVS075 900 400 290 217 VVS075 500 112 490 361
0 VVS100 1200 400 230 267 VVS100 350 210 655 362
VVS120 1400 400 245 286 VVS120 400 210 745 381

Min airflow 806 806 806 1 180 1 180 1 180 1 958 1 958 1 958 2 878 2 878 2 878 3 805 3 805 3 805 4 863 4 863 4 863 5 815 5 815 5 815
Opening BIG - inlet-outlet Opening SMALL - inlet-outlet
Max airflow 2 730 2 184 2 163 3 900 3 120 3 090 5 200 4 160 4 120 7 150 5 720 5 665 9 750 7 800 7 725 13 000 10 400 10 300 15 600 12 480 12 360

Hfd END (US) END (US)


90 90 90 90 90 90 90
Hfu - - - - - - - Size WA HA WA1 HA1 Size WA HA WA1 HA1
H 538 670 670 805 925 1 025 1 062 VVS021 500 210 230 120 VVS021 150 112 405 120
W 961 961 1 168 1 339 1 480 1 660 1 891 VVS030 700 210 130 120 VVS030 200 112 380 120
[mm]

Hi 368 500 500 635 755 855 892 VVS040 600 310 284 120 VVS040 250 112 459 120
Wi 881 881 1 088 1 259 1 400 1 580 1 811 VVS055 350 112 494 120
VVS055 850 310 244 120
H2 986 1 250 1 250 1 520 1 760 1 960 2 034
VVS075 900 400 290 120 VVS075 500 112 490 120
I 40 40 40 40 40 40 40
VVS100 1200 400 230 120 VVS100 350 210 655 120

Selected configurations Dimension VVS120 1400 400 245 120 VVS120 400 210 745 120
Length of selected configurations

Opening BIG - inlet-outlet Opening SMALL - inlet-outlet


END (BS) END (FF)
L2 2221 2221 2221 2953 2953 3318 3318 Size WA HA WA1 HA1 Size WA HA WA1 HA1
L1 2221 2221 2221 2953 2953 3318 3318 VVS021 112 150 120 149 VVS021 821 313 70 70
K - - - - - - - VVS030 112 200 120 190 VVS030 821 440 70 70
FPDV/FVPD_cd
Lt 2221 2221 2221 2953 2953 3318 3318 VVS040 1028 440 70 70
VVS040 112 250 120 165
L2 2221 2221 2221 2953 2953 3318 3318
VVS055 112 350 120 182 VVS055 1199 575 70 70
L1 2221 2221 2221 2953 2953 3318 3318
VVS075 112 500 120 167 VVS075 1340 695 70 70
K - - - - - - -
FPDV/FPDV_pd
Lt 2221 2221 2221 2953 2953 3318 3318 VVS100 210 350 120 292 VVS100 1520 795 70 70
L2 2221 2221 2221 2953 2953 3318 3318 VVS120 210 400 120 286 VVS120 1751 832 70 70
L1 2587 2587 2587 3318 3318 3684 3684
[mm]

K - - - - - - -

FAN OUTLET OPENINGS


FPDCV/FVPD_cd
Lt 2587 2587 2587 3318 3318 3684 3684
L2 3318 3318 3318 4050 4050 4415 4415
L1 3318 3318 3318 4050 4050 4415 4415 Plug Fan DIDW
K - - - - - - -
FPDMCV/FVMPD_cd
END (FS) END (FS)
Lt 3318 3318 3318 4050 4050 4415 4415
Size WA HA WA1 HA1 Size WA HA WA1 HA1
L2 3684 3684 3684 4415 4415 4781 4781
VVS021 500 210 230 119 VVS021 206 206 377 84
L1 3318 3318 3318 4050 4050 4415 4415
K 366 366 366 365 365 366 366 VVS030 700 210 130 185 VVS030 256 256 352 142
FPDMCVH/FVMPD_cd VVS040 600 310 284 135 VVS040 288 288 441 92
Lt 3684 3684 3684 4415 4415 4781 4781
VVS055 850 310 244 202 VVS055 408 408 340 84
Entire range of configuration in ClimaCAD OnLine 4 selection tool - www.ccol4.com
VVS075 900 400 290 217 VVS075 452 452 420 94
VVS100 1200 400 230 267 VVS100 510 510 480 112
L2 VVS120 1400 400 245 286 VVS120 572 572 480 88

WB 1
WB
Plug Fan DIDW
HC HC 1

LB END (US) END (US)


LB 1
Hi

Size WA HA WA1 HA1 Size WA HA WA1 HA1


HA HA 1

VVS021 500 210 230 119 VVS021 206 206 377 307
H2

VVS030 700 210 130 185 VVS030 256 256 352 322
VVS040 600 310 284 135 VVS040 288 288 441 336
VVS055 850 310 244 202 VVS055 408 408 340 390
H
Hi

VVS075 900 400 290 217 VVS075 452 452 420 390
K= L
11 LC VVS100 1200 400 230 267 VVS100 510 510 480 420
LC 1 WA WA1
Hfd
L1 VVS120 1400 400 245 286 VVS120 572 572 480 480
Wi
W
26 27
Technical Specification Technical Specification

VVS 150-650 – RECUPERATOR DIMENSIONS - VVS150-VVS650 – RECUPERATOR


- CROSS-FLOW PLATE EXCHANGERS - CROSS-FLOW PLATE EXCHANGERS
Nominal parameters Recommended airflow range Opening BIG - inlet-outlet Opening SMALL - inlet-outlet
Unit size VVS150 VVS180 VVS230 VVS300 VVS400 VVS500 VVS650 END (FF) END (FS)
Size WA HA WA1 HA1 Size WA HA WA1 HA1
90 000 VVS150 500 210 792 431
VVS150 1400 500 342 286
VVS180 1700 500 192 388 VVS180 600 210 742 533
60 000
VVS230 1800 600 346 338 VVS230 550 310 971 483

30 000 VVS300 2060 700 262 438 VVS300 700 310 942 633
[m3/h]

VVS400 2760 700 162 554 VVS400 900 310 1092 749
0 VVS500 3060 800 262 504 VVS500 900 400 1342 704
VVS650 3360 900 168 693 VVS650 1150 400 1273 943

Min airflow 7 167 7 167 7 167 8 640 8 640 8 640 10 398 10 398 10 398 13 491 13 491 13 491 18 704 18 704 18 704 21 817 21 817 21 817 28 725 28 725 28 725

Max airflow 19 500 15 600 15 450 23 400 18 720 18 540 29 900 23 920 23 690 39 000 31 200 30 900 52 000 41 600 41 200 71 500 57 200 56 650 84 500 67 600 66 950 Opening BIG - inlet-outlet Opening SMALL - inlet-outlet
Hfd 90 120 120 120 120 120 120 END (US) END (US)
Hfu 0 80 80 80 80 80 80 Size WA HA WA1 HA1 Size WA HA WA1 HA1
H 1 163 1 397 1 397 1 696 1 929 1 929 2 406 VVS150 1400 500 342 120 VVS150 500 210 792 120
W 2 085 2 085 2 493 2 585 3 085 3 585 3 697
[mm]

VVS180 1700 500 192 120 VVS180 600 210 742 120
Hi 993 1 197 1 197 1 496 1 729 1 729 2 206
VVS230 1800 600 346 120 VVS230 550 310 971 120
Wi 2 005 2 005 2 413 2 505 3 005 3 505 3 617
VVS300 2060 700 262 120 VVS300 700 310 942 120
H2 2 236 2 754 2 754 3 352 3 818 3 818 4 772
VVS400 2760 700 162 120 VVS400 900 310 1092 120
I 40 40 40 40 40 40 40
VVS500 3060 800 262 120 VVS500 900 400 1342 120

Selected configurations Dimension VVS650 3360 900 168 120 VVS650 1150 400 1273 120
Length of selected configurations

Opening BIG - inlet-outlet Opening SMALL - inlet-outlet


END (BS) END (FF)
L2 3684 3684 3684 4781 4781 4781 5513 Size WA HA WA1 HA1 Size WA HA WA1 HA1
L1 3684 3684 3684 4781 4781 4781 5513 VVS150 210 500 120 286 VVS150 1945 933 70 70
K - - - - - - - VVS180 210 600 120 338 VVS180 1945 1137 70 70
FPDV/FVPD_cd
Lt 3684 3684 3684 4781 4781 4781 5513 VVS230 2353 1137 70 70
VVS230 310 550 120 363
L2 3684 3684 3684 4781 4781 4781 5513
VVS300 310 700 120 438 VVS300 2445 1436 70 70
L1 3684 3684 3684 4781 4781 4781 5513
VVS400 310 900 120 454 VVS400 2945 1669 70 70
K - - - - - - -
FPDV/FPDV_pd
Lt 3684 3684 3684 4781 4781 4781 5513 VVS500 400 900 120 454 VVS500 3445 1669 70 70
L2 3684 3684 3684 4781 4781 4781 5513 VVS650 400 1150 120 568 VVS650 3557 2146 70 70
L1 4050 4050 4050 5147 5147 5147 5878
[mm]

K - - - - - - -

FAN OUTLET OPENINGS


FPDCV/FVPD_cd
Lt 4050 4050 4050 5147 5147 5147 5878
L2 5147 5147 5147 6244 6244 6244 6975
L1 5147 5147 5147 6244 6244 6244 6975 Plug Fan DIDW
K - - - - - - -
FPDMCV/FVMPD_cd
END (FS) END (FS)
Lt 5147 5147 5147 6244 6244 6244 6975
Size WA HA WA1 HA1 Size WA HA WA1 HA1
L2 5513 5513 5513 6610 6610 6610 7341
VVS150 500 210 230 119 VVS150 642 642 610 98
L1 5147 5147 5147 6244 6244 6244 6975
K 366 366 366 366 366 366 366 VVS180 700 210 130 185 VVS180 718 718 480 162
FPDMCVH/FVMPD_cd VVS230 600 310 284 135 VVS230 804 804 770 112
Lt 5513 5513 5513 6610 6610 6610 7341
VVS300 850 310 244 202 VVS300 902 902 740 172
Entire range of configuration in ClimaCAD OnLine 4 selection tool - www.ccol4.com
VVS400 900 400 290 217 VVS400 1010 1010 1040 470
VVS500 1200 400 230 267 VVS500 1134 1134 1230 102
VVS650 1400 400 245 286 VVS650 1270 1270 1215 180

Plug Fan DIDW


END (US) END (US)
Size WA HA WA1 HA1 Size WA HA WA1 HA1
VVS150 1400 500 342 286 VVS150 642 642 610 510
VVS180 1700 500 192 388 VVS180 718 718 480 520
VVS230 1800 600 346 338 VVS230 804 804 770 600
VVS300 2060 700 262 438 VVS300 902 902 740 600
VVS400 2760 700 162 554 VVS400 1010 1010 1040 640
VVS500 3060 800 262 504 VVS500 1134 1134 1230 700
Hfd VVS650 3360 900 168 693 VVS650 1270 1270 1215 720

28 29
Technical Specification Technical Specification

VVS 021-120 - ROTARY HEAT WHEEL DIMENSIONS - VVS021-VVS120


Nominal parameters Recommended airflow range
- ROTARY HEAT WHEEL
Unit size VVS021 VVS030 VVS040 VVS055 VVS075 VVS100 VVS120
Opening BIG - inlet-outlet Opening SMALL - inlet-outlet
18 000 END (FF) END (FS)
Size WA HA WA1 HA1 Size WA HA WA1 HA1
12 000
VVS021 500 210 230 119 VVS021 150 112 405 168
VVS030 700 210 130 185 VVS030 200 112 380 234
6 000
[m3/h]

VVS040 600 310 284 135 VVS040 250 112 459 234
0 VVS055 850 310 244 202 VVS055 350 112 494 301
VVS075 900 400 290 217 VVS075 500 112 490 361
VVS100 1200 400 230 267 VVS100 350 210 655 362
Min airflow 806 806 806 1 180 1 180 1 180 1 958 1 958 1 958 2 878 2 878 2 878 3 805 3 805 3 805 4 863 4 863 4 863 5 815 5 815 5 815
VVS120 1400 400 245 286 VVS120 400 210 745 381
Max airflow 2 730 2 415 2 163 3 900 3 450 3 090 5 200 4 600 4 120 7 150 6 325 5 665 9 750 8 625 7 725 13 000 11 500 10 300 15 600 13 800 12 360

Hfd 90 90 90 90 90 90 90
Hfu 0 0 0 0 0 0 0 Opening BIG - inlet-outlet Opening SMALL - inlet-outlet
H 538 670 670 805 925 1 025 1 062 END (US) END (US)
W 961 961 1 168 1 339 1 480 1 660 1 891
[mm]

Size WA HA WA1 HA1 Size WA HA WA1 HA1


Hi 368 500 500 635 755 855 892 VVS021 500 210 230 120 VVS021 150 112 405 120
Wi 881 881 1 088 1 259 1 400 1 580 1 811
VVS030 700 210 130 120 VVS030 200 112 380 120
H2 986 1 250 1 250 1 520 1 760 1 960 2 034
VVS040 600 310 284 120 VVS040 250 112 459 120
I 40 40 40 40 40 40 40
VVS055 850 310 244 120 VVS055 350 112 494 120
Selected configurations Dimension Length of selected configurations VVS075 900 400 290 120 VVS075 500 112 490 120
L2 1 830 1 830 1 830 2 196 2 196 2 562 2 562 VVS100 1200 400 230 120 VVS100 350 210 655 120
L1 1 830 1 830 1 830 2 196 2 196 2 562 2 562 VVS120 400 210 745 120
VVS120 1400 400 245 120
K 366 366 366 732 732 1 098 1 098
FRV/FRV_cd
Lt 1 830 1 830 1 830 2 196 2 196 2 562 2 562
L2 2 562 2 562 2 562 2 928 2 928 3 294 3 294 Opening BIG - inlet-outlet Opening SMALL - inlet-outlet
L1 2 562 2 562 2 562 2 928 2 928 3 294 3 294 END (BS) END (FF)
K 366 366 366 366 366 366 366 Size WA HA WA1 HA1 Size WA HA WA1 HA1
FRMV/FVMR_cd
Lt 2 562 2 562 2 562 2 928 2 928 3 294 3 294 VVS021 821 313 70 70
VVS021 112 150 120 149
L2 1 830 1 830 1 830 2 196 2 196 2 562 2 562
VVS030 112 200 120 190 VVS030 821 440 70 70
L1 2 196 2 196 2 196 2 562 2 562 2 928 2 928
VVS040 112 250 120 165 VVS040 1028 440 70 70
K 366 366 366 732 732 1 098 1 098
FRHV/FRV_cd
Lt 2 196 2 196 2 196 2 562 2 562 2 928 2 928 VVS055 112 350 120 182 VVS055 1199 575 70 70
L2 2 562 2 562 2 562 2 928 2 928 3 294 3 294 VVS075 112 500 120 167 VVS075 1340 695 70 70
L1 2 928 2 928 2 928 3 294 3 294 3 660 3 660 VVS100 210 350 120 292 VVS100 1520 795 70 70
[mm]

K 0 0 0 0 0 0 0 VVS120 210 400 120 286 VVS120 1751 832 70 70


FRMHV/FVMR_cd
Lt 2 928 2 928 2 928 3 294 3 294 3 660 3 660
L2 1 830 1 830 1 830 2 196 2 196 2 562 2 562
L1 2 196 2 196 2 196 2 562 2 562 2 928 2 928
K 366 366 366 732 732 1 098 1 098
FAN OUTLET OPENINGS
FRCV/FRV_cd
Lt 2 196 2 196 2 196 2 562 2 562 2 928 2 928
Plug Fan DIDW
L2 2 562 2 562 2 562 2 928 2 928 3 294 3 294
L1 2 928 2 928 2 928 3 294 3 294 3 660 3 660
END (FS) END (FS)
K 0 0 0 0 0 0 0 Size WA HA WA1 HA1 Size WA HA WA1 HA1
FRMCV/FVMR_cd VVS021 500 210 230 119 VVS021 206 206 377 84
Lt 2 928 2 928 2 928 3 294 3 294 3 660 3 660
L2 3378 3378 3378 3744 3744 4110 4110 VVS030 700 210 130 185 VVS030 256 256 352 142
L1 4138 4138 4138 4504 4504 4870 4870 VVS040 600 310 284 135 VVS040 288 288 441 92
K 366 366 366 366 366
VVS055 850 310 244 202 VVS055 408 408 340 84
FRMCV/FVMR_cd
Lt 4138 4138 4138 4504 4504 5236 5236
VVS075 900 400 290 217 VVS075 452 452 420 94
VVS100 1200 400 230 267 VVS100 510 510 480 112
VVS120 1400 400 245 286 VVS120 572 572 480 88
Entire range of configuration in ClimaCAD OnLine 4 selection tool - www.ccol4.com

Plug Fan DIDW


END (US) END (US)
Size WA HA WA1 HA1 Size WA HA WA1 HA1
VVS021 500 210 230 119 VVS021 206 206 377 307
VVS030 700 210 130 185 VVS030 256 256 352 322
VVS040 600 310 284 135 VVS040 288 288 441 336
VVS055 850 310 244 202 VVS055 408 408 340 390
VVS075 900 400 290 217 VVS075 452 452 420 390
VVS100 1200 400 230 267 VVS100 510 510 480 420
VVS120 1400 400 245 286 VVS120 572 572 480 480
Hfd

30 31
Technical Specification Technical Specification

VVS 150-650- ROTARY HEAT WHEEL DIMENSIONS - VVS150-VVS650


Nominal parameters Recommended airflow range
- ROTARY HEAT WHEEL
Unit size VVS150 VVS180 VVS230 VVS300 VVS400 VVS500 VVS650
Opening BIG - inlet-outlet Opening SMALL - inlet-outlet
90 000 END (FF) END (FS)
Size WA HA WA1 HA1 Size WA HA WA1 HA1
60 000
VVS150 1400 500 342 286 VVS150 500 210 792 431
VVS180 1700 500 192 388 VVS180 600 210 742 533
30 000
[m3/h]

VVS230 1800 600 346 338 VVS230 550 310 971 483
0 VVS300 2060 700 262 438 VVS300 700 310 942 633
VVS400 2760 700 162 554 VVS400 900 310 1092 749
VVS500 3060 800 262 504 VVS500 900 400 1342 704
Min airflow 7 167 7 167 7 167 8 640 8 640 8 640 10 398 10 398 10 398 13 491 13 491 13 491 18 704 18 704 18 704 21 817 21 817 21 817 28 725 28 725 28 725
VVS650 3360 900 168 693 VVS650 1150 400 1273 943
Max airflow 19 500 16 350 15 450 23 400 19 620 18 540 29 900 25 070 23 690 39 000 32 700 30 900 52 000 43 600 41 200 71 500 59 950 56 650 84 500 70 850 66 950

Hfd 90 120 120 120 120 120 120


Hfu 0 80 80 80 80 80 80 Opening BIG - inlet-outlet Opening SMALL - inlet-outlet
H 1 163 1 397 1 397 1 696 1 929 1 929 2 406 END (US) END (US)
W 2 085 2 085 2 493 2 585 3 085 3 585 3 697 Size WA HA WA1 HA1 Size WA HA WA1 HA1
[mm]

Hi 993 1 197 1 197 1 496 1 729 1 729 2 206 VVS150 1400 500 342 120 VVS150 500 210 792 120
Wi 2 005 2 005 2 413 2 505 3 005 3 505 3 617 VVS180 1700 500 192 120 VVS180 600 210 742 120
H2 2 236 2 754 2 754 3 352 3 818 3 818 4 772
VVS230 1800 600 346 120 VVS230 550 310 971 120
I 40 40 40 40 40 40 40
VVS300 2060 700 262 120 VVS300 700 310 942 120
Selected configurations Dimension Length of selected configurations VVS400 2760 700 162 120 VVS400 900 310 1092 120
L2 2 562 2 562 2 562 2 928 2 928 2 928 2 928 VVS500 3060 800 262 120 VVS500 900 400 1342 120
L1 2 562 2 562 2 562 2 928 2 928 2 928 2 928 VVS650 1150 400 1273 120
VVS650 3360 900 168 120
K 1 098 1 098 1 098 1 464 1 464 1 464 1 464
FRV/FRV_cd
Lt 2 562 2 562 2 562 2 928 2 928 2 928 2 928
L2 3 660 3 660 3 660 4 026 4 026 4 026 4 026 Opening BIG - inlet-outlet Opening SMALL - inlet-outlet
L1 3 660 3 660 3 660 4 026 4 026 4 026 4 026 END (BS) END (FF)
K 0 0 0 0 0 0 0 Size WA HA WA1 HA1 Size WA HA WA1 HA1
FRMV/FVMR_cd
Lt 3 660 3 660 3 660 4 026 4 026 4 026 4 026 VVS150 1945 933 70 70
VVS150 210 500 120 286
L2 2 562 2 562 2 562 2 928 2 928 2 928 2 928
VVS180 210 600 120 338 VVS180 1945 1137 70 70
L1 2 928 2 928 2 928 3 294 3 294 3 294 3 294
VVS230 310 550 120 363 VVS230 2353 1137 70 70
K 1 098 1 098 1 098 1 464 1 464 1 464 1 464
FRHV/FRV_cd
Lt 2 928 2 928 2 928 3 294 3 294 3 294 3 294 VVS300 310 700 120 438 VVS300 2445 1436 70 70
L2 3 660 3 660 3 660 4 026 4 026 4 026 4 026 VVS400 310 900 120 454 VVS400 2945 1669 70 70
L1 4 026 4 026 4 026 4 392 4 392 4 392 4 392 VVS500 400 900 120 454 VVS500 3445 1669 70 70
[mm]

K 0 0 0 0 0 0 0 VVS650 400 1150 120 568 VVS650 3557 2146 70 70


FRMHV/FVMR_cd
Lt 4 026 4 026 4 026 4 392 4 392 4 392 4 392
L2 2 562 2 562 2 562 2 928 2 928 2 928 2 928
L1 2 928 2 928 2 928 3 294 3 294 3 294 3 294
K 1 098 1 098 1 098 1 464 1 464 1 464 1 464
FAN OUTLET OPENINGS
FRMHV/FVMR_cd
Lt 2 928 2 928 2 928 3 294 3 294 3 294 3 294
Plug Fan DIDW
L2 3 660 3 660 3 660 4 026 4 026 4 026 4 026
L1 4 026 4 026 4 026 4 392 4 392 4 392 4 392
END (FS) END (FS)
K 0 0 0 0 0 0 0 Size WA HA WA1 HA1 Size WA HA WA1 HA1
FRMCV/FVMR_cd VVS150 500 210 230 119 VVS150 642 642 610 98
Lt 4 026 4 026 4 026 4 392 4 392 4 392 4 392
L2 4110 4138 4138 4504 4504 4504 4504 VVS180 700 210 130 185 VVS180 718 718 480 162
L1 4870 4898 4898 5264 5264 5264 5264 VVS230 600 310 284 135 VVS230 804 804 770 112
K 366 366 366 366 366 366 366
VVS300 850 310 244 202 VVS300 902 902 740 172
FPDV/FVPD_cd
Lt 5236 5264 5264 5630 5630 5630 5630
VVS400 900 400 290 217 VVS400 1010 1010 1040 470
Entire range of configuration in ClimaCAD OnLine 4 selection tool - www.ccol4.com VVS500 1200 400 230 267 VVS500 1134 1134 1230 102
VVS650 1400 400 245 286 VVS650 1270 1270 1215 180

Plug Fan DIDW


END (US) END (US)
Size WA HA WA1 HA1 Size WA HA WA1 HA1
VVS150 1400 500 342 286 VVS150 642 642 610 510
VVS180 1700 500 192 388 VVS180 718 718 480 520
VVS230 1800 600 346 338 VVS230 804 804 770 600
VVS300 2060 700 262 438 VVS300 902 902 740 600
VVS400 2760 700 162 554 VVS400 1010 1010 1040 640
VVS500 3060 800 262 504 VVS500 1134 1134 1230 700
Hfd VVS650 3360 900 168 693 VVS650 1270 1270 1215 720

32 33
Technical Specification Technical Specification

VVS021-VVS150 - SUPPLY & EXHAUST DIMENSIONS - VVS021-VVS120 - SUPPLY & EXHAUST

Nominal parameters Recommended airflow range Opening BIG - inlet-outlet Opening SMALL - inlet-outlet
Unit size VVS021 VVS030 VVS040 VVS055 VVS075 VVS100 VVS120 END (FF) END (FS)
Size WA HA WA1 HA1 Size WA HA WA1 HA1
20 000
VVS021 500 210 230 119 VVS021 150 112 405 168
15 000 VVS030 700 210 130 185 VVS030 200 112 380 234
10 000 VVS040 600 310 284 135 VVS040 250 112 459 234
VVS055 850 310 244 202 VVS055 350 112 494 301
[m3/h]

5 000
VVS075 900 400 290 217 VVS075 500 112 490 361
0 SSV100 1200 400 230 267 SSV100 350 210 655 362
VVS120 1400 400 245 286 VVS120 400 210 745 381

Min airflow 806 806 806 806 1 180 1 180 1 167 1 167 1 958 1 958 1 958 1 958 2 878 2 878 2 878 2 878 3 805 3 805 3 805 3 805 4 863 4 863 4 863 4 863 5 815 5 815 5 815 5 815

Max airflow 2 163 2 730 3 570 3 780 3 090 3 900 5 100 5 400 4 120 5 200 6 800 7 200 5 665 7 150 9 350 9 900 7 725 9 750 12 750 13 500 10 300 13 000 17 000 18 000 12 360 15 600 20 400 21 600 Opening BIG - inlet-outlet Opening SMALL - inlet-outlet
Hfd 90 90 90 90 90 90 90 END (US) END (US)
H 538 670 670 805 925 1 025 1 062 Size WA HA WA1 HA1 Size WA HA WA1 HA1
VVS021 500 210 230 120 VVS021 150 112 405 120
[mm]

W 961 961 1 168 1 339 1 480 1 660 1 891


VVS030 700 210 130 120 VVS030 200 112 380 120
Hi 368 500 500 635 755 855 892
VVS040 600 310 284 120 VVS040 250 112 459 120
Wi 881 881 1 088 1 259 1 400 1 580 1 811
VVS055 850 310 244 120 VVS055 350 112 494 120
I 40 40 40 40 40 40 40
VVS075 900 400 290 120 VVS075 500 112 490 120
SSV100 1200 400 230 120 SSV100 350 210 655 120
Selected configurations Dimension Length of selected configurations VVS120 1400 400 245 120 VVS120 400 210 745 120

Lt 1181* 1181* 1181* 1547 1547 1913 1913


Opening BIG - inlet-outlet Opening SMALL - inlet-outlet
F-CV
END (BS) END (FF)
Size WA HA WA1 HA1 Size WA HA WA1 HA1
Lt 1490* 1490* 1490* 1856 2221 2587 2587
VVS021 112 150 120 149 VVS021 821 313 70 70
MFCV
VVS030 112 200 120 190 VVS030 821 440 70 70
Lt 1572* 1572* 1572* 1938 1938 2303 2303 VVS040 112 250 120 165 VVS040 1028 440 70 70
VVS055 112 350 120 182 VVS055 1199 575 70 70
[mm]

FCV

VVS075 112 500 120 167 VVS075 1340 695 70 70


Lt 2221* 2221* 2221* 2587 2587 2953 2953 SSV100 210 350 120 292 SSV100 1520 795 70 70
MFFCV VVS120 210 400 120 286 VVS120 1751 832 70 70

Lt 1098 1098 1098 1464 1464 1830 1830


FV
FAN OUTLET OPENINGS
Lt 732 732 732 1098 1098 1464 1464 Plug Fan DIDW
V
END (FS) END (FS)
Entire range of configuration in ClimaCAD OnLine 4 selection tool - www.ccol4.com Size WA HA WA1 HA1 Size WA HA WA1 HA1
VVS021 500 210 230 119 VVS021 206 206 377 84
VVS030 700 210 130 185 VVS030 256 256 352 142
VVS040 600 310 284 135 VVS040 288 288 441 92
VVS055 850 310 244 202 VVS055 408 408 340 84
VVS075 900 400 290 217 VVS075 452 452 420 94
SSV100 1200 400 230 267 SSV100 510 510 480 112
VVS120 1400 400 245 286 VVS120 572 572 480 88

Plug Fan DIDW


END (US) END (US)
Size WA HA WA1 HA1 Size WA HA WA1 HA1
VVS021 500 210 230 119 VVS021 206 206 377 307
VVS030 700 210 130 185 VVS030 256 256 352 322
VVS040 600 310 284 135 VVS040 288 288 441 336
VVS055 850 310 244 202 VVS055 408 408 340 390
VVS075 900 400 290 217 VVS075 452 452 420 390

General: SSV100 1200 400 230 267 SSV100 510 510 480 420
* If 8RD with eliminator, length will increase by 366mm VVS120 1400 400 245 286 VVS120 572 572 480 480
** If RA is required on top, length will increase by 366mm

34 35
Technical Specification Technical Specification

VVS 150-650 - SUPPLY & EXHAUST DIMENSIONS - VVS021-VVS120 - SUPPLY & EXHAUST

Nominal parameters Recommended airflow range Opening BIG - inlet-outlet Opening SMALL - inlet-outlet
Unit size VVS150 VVS180 VVS230 VVS300 VVS400 VVS500 VVS650 END (FF) END (FS)
Size WA HA WA1 HA1 Size WA HA WA1 HA1
120 000
VVS150 1400 500 342 286 VVS150 500 210 792 431
90 000 VVS180 1700 500 192 388 VVS180 600 210 742 533
VVS230 1800 600 346 338 VVS230 550 310 971 483
60 000
VVS300 2060 700 262 438 VVS300 700 310 942 633
[m3/h]

30 000 VVS400 900 310 1092 749


VVS400 2760 700 162 554
0 VVS500 3060 800 262 504 VVS500 900 400 1342 704
VVS650 3360 900 168 693 VVS650 1150 400 1273 943

Min airflow 7 167 7 167 7 167 7 167 8 640 8 640 8 640 8 640 10 398 10 398 10 398 10 398 13 491 13 491 13 491 13 491 18 704 18 704 18 704 18 704 21 817 21 817 21 817 21 817 28 725 28 725 28 725 28 725

Max airflow 15 450 19 500 25 500 27 000 18 540 23 400 30 600 32 400 23 690 29 900 39 100 41 400 30 900 39 000 51 000 54 000 41 200 52 000 58 000 62 000 56 650 71 500 77 000 79 000 66 950 84 500 87 000 100 000 Opening BIG - inlet-outlet Opening SMALL - inlet-outlet
Hfd 90 120 120 120 120 120 120 END (US) END (US)
Hfu 0 80 80 80 80 80 80 Size WA HA WA1 HA1 Size WA HA WA1 HA1
VVS150 1400 500 342 120 VVS150 500 210 792 120
H 1 163 1 397 1 397 1 696 1 929 1 929 2 406
VVS180 1700 500 192 120 VVS180 600 210 742 120
W 2 085 2 085 2 493 2 585 3 085 3 585 3 697
[mm]

VVS230 1800 600 346 120 VVS230 550 310 971 120
Hi 993 1 197 1 197 1 496 1 729 1 729 2 206
VVS300 2060 700 262 120 VVS300 700 310 942 120
Wi 2 005 2 005 2 413 2 505 3 005 3 505 3 617
VVS400 2760 700 162 120 VVS400 900 310 1092 120
H2 2 236 2 754 2 754 3 352 3 818 3 818 4 772
VVS500 3060 800 262 120 VVS500 900 400 1342 120
I 40 40 40 40 40 40 40
VVS650 3360 900 168 120 VVS650 1150 400 1273 120

Selected configurations Dimension Length of selected configurations Opening BIG - inlet-outlet Opening SMALL - inlet-outlet
END (BS) END (FF)
Lt 1913 1913 1913 2278 2278 2278 2278
Size WA HA WA1 HA1 Size WA HA WA1 HA1
F-CV
VVS150 210 500 120 286 VVS150 1945 933 70 70
VVS180 210 600 120 338 VVS180 1945 1137 70 70
Lt 2587 2587 2587 2953 2953 2953** 2953**
VVS230 310 550 120 363 VVS230 2353 1137 70 70
MFCV
VVS300 310 700 120 438 VVS300 2445 1436 70 70
Lt 2303 2303 2303 2669 2669 2669 2669 VVS400 310 900 120 454 VVS400 2945 1669 70 70
VVS500 400 900 120 454 VVS500 3445 1669 70 70
[mm]

FCV

VVS650 400 1150 120 568 VVS650 3557 2146 70 70


Lt 2953 2953 2953 3318 3318 3318** 3318**
MFFCV

FAN OUTLET OPENINGS


Lt 1830 1830 1830 2196 2196 2196 2196
FV Plug Fan DIDW
END (FS) END (FS)
Lt 1464 1464 1464 1830 1830 1830 1830
Size WA HA WA1 HA1 Size WA HA WA1 HA1
V
VVS150 500 210 230 119 VVS150 642 642 610 98
Entire range of configuration in ClimaCAD OnLine 4 selection tool - www.ccol4.com VVS180 700 210 130 185 VVS180 718 718 480 162
VVS230 600 310 284 135 VVS230 804 804 770 112
VVS300 850 310 244 202 VVS300 902 902 740 172
VVS400 900 400 290 217 VVS400 1010 1010 1040 470
VVS500 1200 400 230 267 VVS500 1134 1134 1230 102
VVS650 1400 400 245 286 VVS650 1270 1270 1215 180

Plug Fan DIDW


END (US) END (US)
Size WA HA WA1 HA1 Size WA HA WA1 HA1
VVS150 1400 500 342 286 VVS150 642 642 610 510
VVS180 1700 500 192 388 VVS180 718 718 480 520
VVS230 1800 600 346 338 VVS230 804 804 770 600
VVS300 2060 700 262 438 VVS300 902 902 740 600
VVS400 2760 700 162 554 VVS400 1010 1010 1040 640
General: VVS500 3060 800 262 504 VVS500 1134 1134 1230 700
* If 8RD with eliminator, length will increase by 366mm VVS650 3360 900 168 693 VVS650 1270 1270 1215 720
** If RA is required on top, length will increase by 366mm

36 37
Technical Specification

ADDITIONAL CONFIGURATION CUNCTIONS - VVS


021-650 - RECUPERATOR (HEX & PREMIUM PLUS),
REGENERATOR (HEAT WHEEL), SUPPLY & EXHAUST

Dimension Function version Remaining configuration functions – typical lengths of function arrangement
VVS021 VVS030 VVS040 VVS055 VVS075 VVS100 VVS120

F7/F9 762 762 762 762 762 762 762


L
EU4/F5 366 366 366 366 366 366 366
F

L H 366 366 366 366 366 366 366

C
L 366 366 366 366 366 366 366

C
[mm]

L S 1098 1098 1098 1098 1098 1098 1098

E(e1) 366 366 366 366 366 366 366


L E(e2) 762 762 762 762 762 762 762

E E(e3) 1098 1098 1098 1098 1098 1098 1098

L M 762 762 762 762 762 762 762

L W 1098 1098 1098 1098 1098 1098 1098


Dimension Function version Remaining configuration functions – typical lengths of function arrangement
VVS150 VVS180 VVS230 VVS300 VVS400 VVS500 VVS650

F7/F9 762 762 762 762 762 762 762


L
EU4/F5 366 366 366 366 366 366 366
F

L H 366 366 366 366 366 366 366

C
L 366 366 366 366 366 366 366

C
[mm]

L S 1098 1098 1098 1098 1098 1098 1098

E(e1) 366 366 366 366 366 366 366


L E(e2) 762 762 762 762 762 762 762

E E(e3) 1098 1098 1098 1098 1098 1098 1098

L M 1098 1098 1098 1098 1098 1098 1098

L W 1098 1098 1098 1098 1098 1098 1098

38
Components Components

PANEL FILTERS
COMPONENTS Design and application Specification
FAN SET » Box Type » Working temperature:
» Pleated filtration fabric shielded by max (+70)°C, 100% RH.
steel net, installed in 50 mm thick
Design and application Specification frame. Filtration classes available
> DIRECT DRIVE » Single inlet, radial, backward curved, » Low and medium pressure
» Filtration fabric made of polyester » ISO Coarse 75% (ISO 16890)
free running fan. ventilation systems with fan static
PLUG FAN SET » Impeller made of SAN (styrene/ pressure not exceeding
fibres. - G4 (EN779).
acrylonitryle) construction material 2000 Pascals. » Applied as initial air filtration stage.
with 20% glass fiber. » Maximum fan set working
» Direct drive – fan impeller installed temperature: 60°C.
directly on motor shaft.
» Fan section consisting of single
or multiple fans (fan array) in BAG FILTERS
order to ensure optimum working
parameters.
Design and application Specification
» Flange Type & Bag Type » Working temperature:
> BELT DRIVE DIDW » The DIDW centrifugal fans (Double Wheel » Filtration fabric made of polyester max (+70)°C, 100% RH.
Inlet Double Width Fans) are suitable » The wheels are available in options:
FAN SET for supply or extract applications in - Forward curved blades,
fibres.
» Bags fixed to to 25 mm thick frame. Filtration classes available
commercial, process and industrial - Backward curved bladed
HVAC systems. (air foil or straight shape) » Length: 300/600 mm. » ISO ePM10 50% (ISO 16890)
» The impeller with forward curved - M5 (EN779).
» Sizes are in accordance with AMCA » Applied as initial, secondary of final
standard 99-0098-76 R20. blades is manufactured in galvanized air filtration stag » ISO ePM2,5 65% (ISO 16890)
sheet steel. - F7 (EN779).
» The operating limit is design to meet
the requirement of class I, II and III » The impeller with backward inclined » ISO ePM1 70% (ISO 16890)
limit as defined in AMCA standard blades is made of cold rolled sheet - F9 (EN779).
99-2408-69. steel backward curved blades with
polyester powder coating finish.
Housing HEPA FILTERS
» For all sizes the housing is
manufactured in galvanized sheet Design and application Specification
steel with the housing fixed to the side
plates in “pittsburg lock” form system. » Flange Type & Box Type » Working temperature: max (+70)°C,
Frame » Filter Media: Glass Fiber / Spun 100% RH.
» The frame is manufactured with Bonded Polyester
galvanized angular bars or steel » Length 300/600 mm. Filtration classes available
finished with polyester powder coating. » Applied as final air filtration stage » H13 (EN 1822).
Shaft » Frame Material: Aluminum (SS 304 / » Filtration Rating: 0. 3 Micron & More
» Shafts are manufactured from C45 GI (Galvanized Steel)) » Filtration Efficiency: 90- 99. 9 %
carbon steel coated with an anti-
corrosion varnish after assembly.
Bearings
» Bearings used are either deep groove
Shape Classification Length [mm] Position BracketType
ball bearing type with an eccentric
locking collar or an adapter sleeve, or Box EU4 ISO Coarse 75% (ISO 16890)- G4 (EN779) 50 Ext / Int Slide / Flange

spherical roller bearings type sealed EU4 ISO Coarse 75% (ISO 16890)- G4 (EN779) 300 Int Slide
at both sides for different duty. EU5 ISO ePM10 50% (ISO 16890) - M5 (EN779) 300 Int Slide / Flange
300 Int Slide / Flange
Bag EU7 ISO ePM2,5 65% (ISO 16890) - F7 (EN779)
600 Int Slide

> AC MOTORS » Fan and motor mounted on common » Available Energy classes: IE2, IE3 300 Int Slide / Flange
housing, separated from AHU casing » Rated voltage: 3x230V AC, 3x400V AC.
ISO ePM1 70% (ISO 16890) - F9 (EN779)
600 Int Slide
by set of rubber vibration absorbing
» Number of poles: 2 or 4. ISO Coarse 75% (ISO 16890)- G4 (EN779) Ext&Int Slide
mounts. EU4&EU5
ISO ePM10 50% (ISO 16890) - M5 (EN779
350
» Motor winding insulation class: F Int&Int Slide
» Motors of TEFC type
(fitted for VFD operations). ISO Coarse 75% (ISO 16890)- G4 (EN779), Ext&Int
(Totally Enclosed, Fan-Cooled). Box&Bag EU4&EU7
ISO ePM2,5 65% (ISO 16890) - F7 (EN779)
350 Slide
» Bearings lifetime: L10= 20000h Int&Int
» Motors fitted for IEC standard.
/ L50 = 100000h. ISO Coarse 75% (ISO 16890)- G4 (EN779) Ext&Int
» Variable Frequency Drive (VFD) – 350 Slide
» Protection degree: IP55. ISO ePM1 70% (ISO 16890) - F9 (EN779) Int&Int
standard equipment of the fan-set.
» Maximum working ambient Box/Bag H13 300 Int Flange

temperature: 60°C.
40 41
Components Components

CASING CROSSFLOW PLATE HEAT RECUPERATOR

Design and application Specification Design and application Specification


» Casing structure made of ‘sandwich’ » Working temperature: » Recuperator made of crosswise » Energy recovery at very high supply
type panels formed in ‘C’ shape and (-40)°C ÷ (+90)°C. stamped aluminum plates, between and exhaust air stream separation
reinforced by system of internal » Panel thickness: 40mm. which supply and exhaust air (reaching 99,9%)
frames. passes alternately in counterflow » Heat recovery reaching up to 80%
» Thermal conductivity PPU
» "Sandwich"" double skin panels made arrangement. depending on flow rate face velocity
λ= 0,022 W/mK.
of rigid polyurethane foam. » As standard, the recuperator is of the air passing the recuperator.
» Casing fire resistance:
» Indoor and outdoor application. equipped with by-pass damper,
non-flamable, non fire spreading
enabling its securing against
» Inspection panels mounted (NRO).
frosting and heat recovery capacity
on AHU side. » Moisture absorption: 0,04%. regulation.
» Casing supported on steel base rails. » PPU density: ρ= 42kg/m³. » Optionally, the recuperator can be
» Eurovent certification equipped with integrated mixing box.
• Mechanical strength of casing: » The recuperator provides sensible
-1000 Pa ÷ 1000 Pa < 2mm (D1 - PN heat recovery for warmer air to the
EN 1886: 2008), colder one. For winter season –
• Casing tightness: (MB): (-400) Pa recovery of heat from return air to
VVS021 - VVS650
- 0,05 l/sm², (+700) Pa - 0,13 l/sm² supply. For summer – recovery of
(L1 -PN EN 1886: 2008); (RU): (+400) chill from return air to supply.
Pa - 0,93 l/sm²,
• Casing heat transfer coefficient: K=
0,6 W/m²K (T2 - PN EN 1886: 2008),
• Thermal bridges coefficient: Kb =0,52 RUN-AROUND COIL
(TB3 - PN EN 1886: 2008).
Design and application Specification
ROTARY HEAT WHEEL » Set of two water coils – one in » Indirect Energy recovery
supply, the other one in exhaust (sensible heat) at 100% supply
airstream. and exhaust airstreams separation.
Design and application Specification
» The coil in return airstream recovers » Max heat-transfer fluid operation
» Rotor made of aluminum with shaft » Up to 86% of energy recovery,
the heat (cooler) and passes it pressure: 1,6MPa=16bar
suspended on bearings, installed in depending on airflow rate and its
to the coil in the supply air (heater) (tested 21 bar).
steel housing. velocity in the heat wheel window.
by means of heat-transfer fluid » Max glycol concentration: 50%.
» Rotor filling – two layers of (water-glycol mixture). In case of chill
alternately winded aluminium foil recovery, entire process is reversed.
– one flat, the other – corrugated –
» System applied for supply and
making small ducts for the air.
exhaust air handling units installed
» Rotor drive system with smooth remotely to each other."
revolutions control enabling to
maintain highest recovery efficiency
and to adjust degree of recovery
performance.
» Purge zone reducing the
cross-contamination effect of
contaminated exhaust air to supply
to absolute minimum.
» Set of gaskets installed both on the
wheel outer edge and bar separating MIXING SECTION
supply from exhaust air being an
additional protection against cross-
contamination. Design and application Specification
» Rotary heat wheel recovers sensible » Section equipped with two air inlets/ » Direct Energy recovery (sensible
heat from return air to supply, which outlets aided with dampers, enabling and latent heat) resulting from partial
passes the unit in opposite direction. regulation of fresh and recirculation mixing of fresh air with return one.
The process enables heat recovery air share (recirculation). » Control of fresh air share in entire
in winter time, same as cool recovery airflow supplied to handled spaces.
in summer. » Working temperature range:
» Humidity recovery from return -40 ÷ +70°C.
to supply in case the rotor pad
temperature is lower than dew point
of return air – typically during winter
season.
42 43
Components Components

WATER HEATER DIRECT EXPANSION COIL AS CONDENSER IN HEAT PUMP CIRCUIT


Design and application Specification Design and application Specification
» Block of copper pipes integrated » Max glycol concentration: 50%. » Block of copper pipes integrated with » Max medium temperature: 60°C.
with another block of aluminum fins, » Max medium temperature: 150°C. another block of aluminum fins, creating » Max medium working pressure:
creating expanded heat exchange expanded heat exchange surface. Pipes
» Max medium working pressure: 3,84MPa = 38,4bar (test: 50bar).
surface. Pipes are bonded to the are bonded to the collectors, equipped
1,6MPa = 16bar (test: 21bar). » Heating capacity: parameter resulting
collectors, equipped with headers with headers (for connecting entire coil
(for connecting entire coil to the » Heating capacity: parameter resulting from individual performance
to the cooling system circuit).
medium supply system). from individual performance calculaation of selected unit (CCOL).
calculaation of selected unit (CCOL). » Heating of the air supplied to the
» Heating of the air supplied to the handled spaces.
handled spaces. » Medium side pressure drop –
parameter resulting from individual » Re-heating of the air as a part of air
» Re-heating of the air as a part of air dehumidifying process.
performance calculation of selected
dehumidifying process.
unit (CCOL).
» The coil can be applied if heating
medium is available (local boiler or
district heating system). WATER COOLER
» Coil headers are equipped with
medium damping valve and air vent.
Design and application Specification
» Connecting the coil in parallel
» Block of copper pipes integrated » Max glyccol concentration: 50%.
medium flow vs air, will result in its
with another block of aluminum fins, » Min supplying medium temperature:
capacity reduction by over a dozen
creating expanded heat exchange +2°C.
percent.
surface. Pipes are bonded to the
» max medium working pressure:
collectors, equipped with headers
1,6MPa = 16bar (test: 21bar).
(for connecting entire coil to the
medium supply system). » Cooling capacity: parameter resulting
from individual parameters of
» Cooling of the air supplied to handled
selected unit (CCOL).
spaces.
ELECTRIC HEATER » Cooling and dehumidifying of
» Medium pressure drop / flow rate:
parameter resulting from individual
the air as a part of air complex
Design and application Specification performance calculation of selected
dehumidifying process in summer
unit (CCOL).
» Set of resistive heating elements » Max permissible ambient season.
made of CR-Ni-Fe alloy, 6 kW/400V temperature around heating » For reversed operationg mode
» Coil can be applied in complex air
each. elements: 65°C. (heating) max medium working
conditioning systems consisting of
temperature: 140°C.
» Coils mounted on hot-dip galvanized few or over a dozen of units supplied
steel frame. from common chilling source (chiller)
» Heater is equipped with power or in case of single unit of relatively
terminals and thermostat protecting high cooling capacity.
against overheating.
» In case of AHU with complete DX COOLING COIL
controls, heater is equipped with
integrated capacity control module. Design and application Specification
» Heating capacity can be modified by » Block of copper pipes integrated » Min. Refrigerant evaporation
means of smooth regulation module with another block of aluminum fins, temperature: +3°C.
(HE module, set of Solid State Relays creating expanded heat exchange » Max refrigerant working pressure:
as optional parts of AHU controls) or surface. Pipes are bonded to the 2,2MPa=22bar (test: 29 bar).
by means of automatic engaging of collectors, equipped with headers
» Cooling capacity - parameter
next heating sections. (for connecting entire coil to the
resulting from individual performance
cooling system circuit).
calculation of selected unit (CCOL).
» DX cooler is also available as heater
execusion (so calleed Condenser).
» Cooling and dehumidifying of
the air as a part of air complex
dehumidifying process in summer
season.
» Coil usually applied for smallerd
cooling capacity systems vs
water coolers or for individual air
conditioning systems.

44 45
Components Components

EVAPORATIVE HUMIDIFIER AIR DAMPER

Design and application Specification Design and application Specification


» Humidifying process based on water » Max air face velocity across the » Blades made of aluminium with rubber » Air leakage at closted damper:
adiabatic evaporation from the humidifier pad: 3,00 m/s gasket on the edges. 50 m3/h*m2 - at 100 Pascals of
humidifier pad. (VS 21-VS 55); » Aluminum frame. pressure difference.
» Humidifying pad made of CELDEK II 4,00 m/s (VS 75-VS 650). » Workint temperature range:
» Blades drive realized by means of gears
material. » Water pressure range: made of composite material, installed -40 ÷ +70°C.
» Humidifier housing made of stainless 0,15 ÷ 0,75 MPa. on frame internal side.
steel. » Requirements regarding water » Damper is equipped with square pivot,
» System of direct water dropping quality – standard tap water. fitted for actuator (dampers of cross
(VVS021-VVS055). section greater than 4 m2 have 2 linked
» System of water recirculation aided pivots).
by pump (VVS075-VVS650).
» Droplet eliminator integrated with
humidifier filling (VVS075-VVS650).
» System is equipped with water
drainage system preventing against
high water level in the pan and
floating valve controlling its refilling
(VVS075-VVS 650).

FLEXIBLE CONNECTION

Design and application Specification


SOUND ATTENUATING SECTION » Flexible connection made of 1 » Max air face velocity: 5m/s.
mm thick and 30 mm wide hot-dip » Working conditions: -40 ÷ +70°C.
galvanized steel profiles and polyester
Design and application Specification fabric coated with PVC.
» Sound attenuator consists of noise » Max air face velocity: v=5m/s. » Flame resistance: UL94 - HB [ISO 1210].
attenuating bars installed » Working conditions: -40 ÷ +70°C.".
in the AHU casing. » Flexible connection resistant to UV
radiation.
» Attenuating bars of 140 mm
width filled with sound-absorbing, » Working temperature range:
inflammable mineral wool (density: -30°C do +70°C.
60 and 80 kg/m3). » Max connection length
» Attenuating bar housing: frame made (fully spread position): 110 mm.
of hot-dip galvanized steel. » Flexible connection installed on each
» Bar outer surface: thin veil preventing AHU/Duct joint eliminates transfer
against bar filling migration to the air. of possible AHU vibrations to the
ventilation ductwork.
» Number of attenuating bars: 2÷13,
depending on block size.

AIR INTAKE AND DISCHARGE LOUVERS


INTERNAL LIGHT
Design and application Specification
» Air intake louver made of aluminum » Max air face velocity: 5m/s.
Design and application Specification profile, blades made of ABS material. » Working conditions: -40 ÷ +70°C.
» Energy saving lamp with securing » Working conditions: -40 ÷ +70°C. » Air outlet louver made of aluminum
shade. profile, blades made of ABS material.
» Facilitation of AHU inspection » Protection of air handling unit installed
actions: filter, fan and humidifier outdoor against meteorological
compartment. conditions (precipitation, sand).

46 47
Controls Controls

PAREMETERS REGULATION FUNCTIONS


CONTROLS
Regulation of temperature and humidity
» Regulation of supply, return air temperature and humidity in handled spaces.
All controls for VENTUS air handling units is available as optional equipment. » Control of water coils valves (heater, cooler) and condensing unit.
» Control of rotary heat wheel revolutions, by-pass damper and mixing box, depending on AHU type
Range of controls is always fitted to configuration of the AHU selected in the CCOL4 tool. Controls is capable and configuration.
to regulate all user parameters: air temperature, its humidity, maximum permissible CO2 concentration and the
flow rate. Also, controls support preventive and securing functions like protection of the water heater against Airflow rate regulation
freezing or energy recovery system against icing, protection of motors against overloading, monitoring of air » Constant Air Volume (CAV) available as standard.
filters actual status of contamination and many other. Applied algorithms can optimize performance of all air » Constant static pressure maintenance in trunk duct (Variable Air Volume – VAV) available as option.
treatment components in order to minimize consumption of all energy media supplied to the unit. » Setting of constant revolutions for each fan individually – VFD setting for AC motors or constant revolutions
The system includes control and power supply circuit. percentage in case of EC motors.

CO2 regulation
» By means of mixing box – for units with air recirculation.
HMI Basic » By means of airflow rate change – for all types of supply and exhaust units (function can be engages together
» Engaging and disengaging the AHU, with mixing box control).
change of operational modes.
» Change of temperature, airflow,
humidity, max CO2 level settings, etc. [Pa]
» Errors reporting. 3050
2000
» Time schedule setting. obr/min

1800
2815
Change of ductwork resistance
– by adjusting damper
HMI Advanced 1600

» All users and service functions except 1400


visualization
2425
• AHU engaging and disengaging, 1200 Change of fan revolutions
• Change of operational modes.
» Change of temperature, airflow, 1000
humidity, max CO2 level settings, etc. 2035
» Parameters setting and reporting. 800

» Errors reporting.
600
» Time schedule setting.
400

200
USER
BMS 1000 2000 3000 4000 5000 6000 7000 8000 9000 [m3/h]
» User function like in HMI Advanced. QN
» User’s customized visualization (BMS).
PROTECTION FUNCTIONS
» Protection against rotary heat wheel icing, by means of wheel revolutions reduction.
» Protection against hexagonal counterflow and cross-flow recuperator icing by means of by-pass damper
Remote visualization opening. Functions realized as optional:
» All user function like in HMI Advanced: • Optimizing of icing protection function by change of minimum return air temperature threshold downstream
• VTS visualization. the energy recovery unit vs return air parameters.
» Clear interface of schedule • Minimizing of recovery efficiency drop during defrosting
programming, presenting unit’s » Anti-freezing protection of water heater
operating time individually for each day • Antifreeze thermostat installed downstream the heater
of the week.
• Strap-on return water temperature sensor
» Energy consumption analysing module. » Fans overload protection (functions realized by EC motors drives)
» Individual parameters monitoring of » Fire alarm input – AHU immediate disengaging in case of lack of external start permission from overall fire
each functional block. protection system.
» Filing of all AHU’s parameters recorded
in few minutes intervals.

48 49
Controls

PREVENTIVE FUNCTIONS
» Constant filter contamination status control:
• Constant monitoring of filter pressure drop by means of static pressure transducers,
• Evaluation of filter contamination status for vs actual airflow rate.
» Fans shutting-down delay – fan’s run out for systems with electric heater
» Water heater pre-heating before fun’s start up.
» Periodical heater pump engaging in summer – to prevent against limescale accumulation
» Opening of water heater regulation valve before engaging the fans.

TIME SCHEDULE FUNCTIONS


» Weekly schedule operational modes programming (HMI Advanced i Basic).
» Clear visualization of schedule settings by means of web-browser (computers and mobile devices).

POWER SUPPLY AND CONTROL CIRCUITS


» The mains component of the controls is the control box – with microprocessor controller installed inside.
The control box is usually mounted on side wall of the AHU or in units direct vicinity.
» Control box is equipped with controller, power protection circuits, terminal block enabling connecting
of all control elements.
» Electric protection of fans, rotary heat wheel drive, control elements and heater pump are installed inside
the control box.
» Control of fan-sets (variable frequency drives in case of AC motors of specialized drives for EC ones)
is realized by means of digital communication based on ModBUS protocol. Fan control elements are set
with individual address enabling them to be properly identified in the control system.
» Communication with static pressure and CO2 transducers also realized by ModBUS protocol.
» For other control elements, digital or analogue signals are used.

50
Controls Controls

CONTROL ELEMENTS
OVERHEAT PROTECTION THERMOSTATE FOR ELECTRIC HEATER
CONTROL ELEMENTS
Functions and application Operational parameters
Functions and application Operational parameters » Protection of electric heater » Power cut-off temperature setpoint:
» Regulation of supply and exhaust air » Measurement range: against overheating. 65°C.
temperature. -50°C to +90°C. » Power re-switch on temperature
» Protection of the energy recovery » Measurement accuracy: ±0,5K. setpoint : 45°C.
unit against freezing. » Sensor type: NTC 10k. » Nominal voltage: 20V DC
» Outdoor air temperature » Air humidity range: 5 ÷ 100%. or 230V AC.
measurement in order to identify » Output signal: potential-free contact.
» Protection degree: IP67.
need of heat/chill recovery and
engagement protecting function for » Shielded cable length: max. 100 m.
water heater.
DIFFERENTIAL PRESSURE SWITCH

ROOM AIR TEMPERATURE SENSOR Functions and application Operational parameters


» Monitoring of filter’s contamination. » Measurement range: 30 do 500 Pa.
Functions and application Operational parameters » Control of the operation of a » Nominal operating voltage: 250V AC
» Regulation o temperature » Measurement range: direct driven fan unit in case of (Imax=3A).
in handled space. -20°C do +70°C. cooperation with electric heater. » Output signal: potential free contact.
» Measurement accuracy: ±0,5K. » Working temperature range:
» Sensor type: NTC 10k. -20°C do 60°C.
» Air humidity range: » Protection degree: IP 54.
5 ÷ 95% no condensation.
» Protection degree: IP20.
» Shielded cable length: max. 100 m. FILTER CONTAMINATION INDICATOR

STRAP-ON MEDIUM TEMPERATURE SENSOR Functions and application Operational parameters


» Measurement of air pressure » Max. Pressure difference: 800 Pa.
drop on filters, activated manually » Accuracy: 2,5% of the range.
Functions and application Operational parameters
(button).
» Protection of water heater against » Measurement range: » Protection degree (interface side):
» Signal light (LED) informing about IP 65.
freezing by means of return medium -20°C do +70°C.
exceeding pressure drop thresholds.
temperature monitoring. » Measurement accuracy: ±0,5K.
» Low battery warning light signal.
» Sensor type: NTC 10k.
(Function supported by controller. » Air humidity range: 5 ÷ 100%.
Sensor out of VTS offer.)
» Protection degree: IP67.
» Shielded cable length: max. 100 m.

DIFFERENTIAL PRESSURE TRANSDUCER


ANTI-FREEZE THERMOSTATE
Functions and application Operational parameters
Functions and application Operational parameters » Regulation of supply and exhaust air » Measurement range: 6000 Pa.
» Protection of water heater » Measurement range: -18 ÷ +15°C. (CAV function). » Measurement accuracy:
against freezing by means of air » Hysteresis: 1,7 ÷ 12K. » Regulation of static pressure 0,25% of the range.
off-coil temperature monitoring in ventilation system trunk duct » Communication: ModBus RTU.
» Nominal voltage: (VAV function).
(recommended temperature
30V DC or 230V AC. » Supply voltage: 21,5V to 30V DC or
threshold setting: +5°C). » Constant monitoring of filter
» Output signal: potential-free contact. 21,5V do 26,5V AC.
pressure drop (control of filter
» Protection degree: IP 44. » Working temperature range:
contamination level).
-20°C do 50°C.
» Protection degree: IP 65.
52 53
Controls Controls

AIR HUMIDITY TRANSDUCER THREE-WAY VALVE FOR WATER HEATER OR COOLER

Functions and application Operational parameters Functions and application Operational parameters
» Regulation of supply and return » Measurement range: 0-100%. » Smooth regulation of water heater » Regulation mode: 0 do 100% (smooth).
air humidity in handled spaces » Tolerance: +/- 3%. or cooler capacity. » Control signal: 0-10V.
(support for air humidyfing and
» Communication: ModBus RTU. » Full open/close time: 90 s.
dehumidyfing).
» Supply voltage: 24V DC. » Valve supply voltage: 24V AC/DC.
» Measurement of return air humidity
– automatic change of anti-freeze » Working temperature: -40°C to 80°C. » Working temperature: +5°C do 50°C.
threshold temperature setting of » Protection degree: IP 65. » Medium temperature range:
cross-flow recuperator depending -10°C do 120°C.
on return air parameters*. » Max glycol concentration: 50%.
» Protection degree: IP 54.
* Also available as integrated with air temperature sensor

ELECTRIC HEATER CONTROL MODULE – MHE TYPE


CO2 TRANSDUCER
Functions and application Operational parameters
Functions and application Operational parameters » Power supply, protection and » Regulation mode: 0 to 100%
» Regulation of CO2 concentration in » Measurement range: 0 do 2000 ppm. smooth regulation of electric (smooth).
handled spaces (control of mixing (heating) capacity of multi-stage » Nominal voltage: 3*400V/50Hz.
» Tolerance: electric heaters by means of PWM
box or airflow rate). • between 400 and 1250 ppm: +/-3%, » Control circuits supply voltage:
(Pulse Width Modulation).
• between 1250 and 2000 ppm: +/-5%. 24V AC.
» Communication: ModBus RTU. » Binary input signal: 3 x 24V DC.
» Supply voltage: 24V DC. » Binary output signal 6 x 24V DC.
» Working temperature: 0 do 50°C. » PWM 1 x 24V DC.
» Protection degree: IP 54. » Working temperature: 0°C do 50°C.

ON/OFF DAMPER ACTUATOR


VARIABLE FREQUENCY DRIVE
Functions and application Operational parameters
» Airflow opening or closing in the » Regulation mode: ON/OFF
AHU (connectors of air intake and (two-point). Functions and application Operational parameters
discharge) – for units with water » Angle of rotation: 90°. » Smooth regulation of fan-set » Frequency regulation range:
heater actuators with return spring capacity. 10 ÷ 100 Hz.
» Torque: 16 Nm (max damper
are applied. » “Soft-start” of the fan without » Communication: ModBus RTU
cross-section: 4 m2).
mechanical and electric shock. RS485.
» Full open/close time: 120 s
(with spring: 10 s). » Motor protection against » Supply voltage:
overloading and stucking. • single-phase 200 ÷ 240V AC,
» Supply voltage: 24V AC/DC. • three-phase 380 ÷ 480V AC.
» Working temperature: -20°C do 50°C. » Working temperature: 0°C to 40°C.
» Protection degree: IP 54. » Protection degree: IP 20.

SMOOTH CONTROL DAMPER ACTUATOR

Functions and application Operational parameters


» Smooth regulation of return and » Regulation mode: 0 do 100% (smooth).
fresh air mixing (recirculation) – for » Control signal: 0-10V.
units with water heater actuators
» Angle de rotation: 90°.
with return spring are applied.
» Torque: 16 Nm (max damper
» Protection of cross-plate or
cross-section: 4 m2).
hexagonal recuperator against
frosting – smooth regulation of by- » Full open/close time: 90s
pass damper opening. (with spring: 10 s).
» Supply voltage: 24V AC/DC.
» Working temperature: -20°C do 50°C.
» Protection degree: IP 54.
54 55
Controls

HMI BASIC USER INTERFACE

Functions and application Operational parameters


» Maintenance of Air handling » Power supply directly from the
unit – temperatures setting and controller.
reading, change of operating » Communication with controller –
modes, independent time schedule RS485 serial port.
management, alarm codes
» Max length of communication
displaying.
cable: max. 500 m.
» Configuration of controller’s
» Working temperature: -20°C to 60°C.
universal inputs and outputs.
» Humidity: <85% (no condensation).
» Protection degree: IP 31.

HMI ADVANCED USER INTERFACE

Functions and application Operational parameters


» Maintenance of Air handling Unit » Power supply directly from
– parameters setting and reading the controller
(temperature, airflow, CO2, humidity » Communication with controller
etc), change of operational modes. – RS485 serial port
» Weekly schedule programming. » Max length of communication
» Service maintenance – cable: max. 1200 m,
configuration of all advanced AHU » Working temperature: -20°C to 60°C.
operating parameters, configuration
» Humidity: <85% (no condensation).
controllers universal inputs and
outputs. » Protection degree: IP 20.
» Remote configuring of variable
frequency drives.
» AHU alarms and errors monitoring
(full text description) and cancelling.
.

SUPPLY AND CONTROL BOX

Functions and application Operational parameters


» Control of all components and » Supply voltage: 3x400 VAC or 1x230
processes of Air Handling Unit, V AC.
especially realization of regulation » Supply frequency: 50 Hz, +/- 1 Hz.
(temperature, airflow, CO2, humidity)
» Control circuits supply voltage:
and protection functions (anti-
24 V AC.
freezing of energy recovery heat
exchanger or water heater, fan-sets » Water heater pump supply voltage:
overloading etc). 230 V AC (max.10A).
» Alarms handling, self-diagnostics. » Communication with internal
controls circuits, VFD’s or EC motors
» Filling of all operating parameters
controller: ModBus RTU.
history.
» ModBus communication: TCP/IP.
» Communication with user interfaces
(HMI). » Working temperature: 0 to 50°C.
» Humidity: <85% (no condensation).
» Protection degree: IP 54.

56
04
Units
- VENTUS S-type
S-type S-type

UNIT CASING: DIRECT DRIVE PLUG FAN SET


Monocoque technology - a self supporting shell structure Blower
used in Formula 1 car and aviation. This is exactly how » Single inlet, radial, backward curved, free running fan.
we design our products, therefore our units feature low » Impeller made of SAN (styrene/ acrylonitryle)
weight and optimal height, are easy for transportation construction material with 20% glass fiber.
TECHNICAL SPECIFICATIONS and further installation. Moreover double skin “sandwich” » Direct drive – fan impeller installed directly on motor
panels with 40 mm rigid polyurethane foam ensure best shaft.
thermal insulation. » Fan section consisting of single or twin fans .
» Thermal conductivity: PPU λ= 0,022 W/mK
CASING AIR FILTERS COOLING COIL » PPU density: ρ= 42kg/m³. AC Motors
• 40 mm “Sandwich” double skin panels • Pleated filtration fabric shielded by steel • Hydronic coils - 4, 6 rows available » Casing heat transfer coefficient: K=0.6 W/m2K » Fan and motor mounted on common housing,
made of rigid polyurethane foam net, installed in 50 mm thick frame • DX - 6 rows, 2 sections available » Casing mechanical strength: separated from AHU casing by set of rubber vibration
• Inspection panels mounted on AHU side • Filtration fabric made of polyester fibres • Max operating pressure - 1,6 MPa
• Working max parameters: max • Testing pressure - 2,1 MPa
+2500 Pa ÷ 2500 Pa < 2 mm absorbing mounts.
• High anticorrosive protection:
- Galvanized zinc (Zn) coating: 180g/m² temperature (+70)°C, max. RH100% • Drain tray: stainless steel, water outlet 1” » Casing tightness: -400 Pa - 0.05 l/sm2 » Motors of TEFS (Totally Enclosed, Fan-Cooled).
- External protection coating material • ISO Coarse 75% (ISO 16890) - G4 (EN779) +700 Pa - 0.13 l/sm3 » Motors fitted for IEC standard.
thickness: polyester / 25μm » Anticorrosive protection: » Variable Frequency Drive (VFD) – standard part of the
• Inspection panels on both sides
- Galvanized zinc (Zn) coating: 180g/m² fan-set.
» External protection coating material thickness: » Available Energy classes: IE2
polyester 25μm » Available voltage: 1x230V/50Hz, 3x380V/50Hz,
» Inspection panels mounted on AHU side. 3x400V/50Hz, 3x400V/60Hz.
» Number of poles: 2.
» Motor winding insulation class: F (fitted for VFD
NO THERMAL BRIDGES operations).
Our Monocoque casing is a framework free construction. » Bearings lifetime: L10= 20000h / L50 = 100000h.
This eliminates the problem of water condensation on the » Protection degree: IP55.
external AHU side - and therefore - no more of harmful » Working conditions: 60°C.
water dripping from the ceiling.
EC Motors
» Set of fan and motor mounted on common rail,
DRAIN TRAY fixed to the AHU fan diaphragm.
They are fabricated from heavy stainless steel and are to » EC motors are Permanent Magnet motor,
prevent condensation. characterised by much higher efficiency vs traditional
inductive AC motors.
» EC motors (Electronically Commutated) – where
COOLING COILS mechanical commutator switching the windings has
Fabricated from copper tubes mechanically bonded with been replaced with electronic one.
aluminum fins and are leak tested at 305 psig pressure. » Change of revolutions is done by means of changing
Hydronic the frequency rate of windings switching (rate or
» Copper pipe: dimensions: ½” magnetic field rotating).
» Fin Type: corrugated fin » Highly inductive permanent magnets have applied in
» Row: 4 or 6 rows EC motors used by VTS, which enabled to achieve high
» Max operating pressure: 1,6 MPa torque at relatively small dimensions.
» Testing pressure: 2,1 MPa » Rated voltage: EC motors of nominal capacity equal or
DIRECT DRIVE PLUG FAN SET DIRECT DRIVE PLUG FAN SET DIRECT DRIVE PLUG FAN SET
> BLOWER > AC MOTORS > EC MOTORS » Equipped with air discharge valve less 0,75kW - 1x230V AC.
• Single inlet, radial, backward curved, • Fan and motor mounted on common • Set of fan and motor mounted
and water outlet valve » Motor widing insulation class: F.
free running fan housing, separated from AHU casing by on common rail, fixed to the AHU fan » Protection degree: IP54. » Maximum working ambient
• Direct drive – fan impeller installed set of rubber vibration absorbing mounts diaphragm. > DX temperature: 55°C.
directly on motor shaft • Motors of TEFS (Totally Enclosed, • EC motors are Permanent Magnet
• Fan section consisting of single Fan-Cooled) motor, characterised by much higher
» Copper pipe: dimensions: ½” » Lifespan: - 70 000 hours at load not exceeding 70%
or twin fans • Variable Frequency Drive (VFD) efficiency vs traditional inductive AC » Fin Type: corrugated fin of nominal capacity at ambient temperature not
• Smooth regulation – standard part of the fan-set motors. » Row: 6 rows , 2 - sections exceeding 35°C, - 30 000 hours at 100% capacity load
• Available Energy classes: IE2 • Required regulation with 0-10V
• Junction box on casing regulator or ModBus signal
» Max operating pressure: 1,6 MPa at ambient temperature not exceeding 55°C.
• Junction box on casing » Testing p ressure: 2,1 MPa
AIR FILTERS
» All Units are provided with air filers.
TYPICAL APPLICATION » Pleated filtration fabric shielded by steel net,
installed in 50 mm thick frame.
» Filtration fabric made of polyester fibres.
residential industrial small » Working max parameters: max. temperature (+70)°C,
buildings buildings businesses max RH100%.
» ISO Coarse 75% (ISO 16890) - G4 (EN779).

sports retail and garages


facilities warehouses and workshops

60 61
S-type S-type
ELECTRICAL WIRING DIAGRAMS
ELECTRICAL WIRING DIAGRAMS
ELECTRICAL WIRING DIAGRAMS
3 PHASE WITH VFD
3 phase with VFD 1 phase1 PHASE
- 1 EC MOTOR
- 1 EC MOTOR 1 PHASE - 2 EC MOTORS
1~230V 50Hz 1~230V 50Hz
3~400V 50Hz 3~400V 50Hz 3~400V 50Hz

PE

PE
N

N
L

L
L1 L2 L3 L1 L2 L3 L1 L2 L3

SV .. iG5A SV .. iG5A SV .. iG5A


factory tested

control
control
(OPTIONAL)

(OPTIONAL)
(DEFAULT)

(DEFAULT)
connection box

connection box
U V W U V W U V W

MODBUS

MODBUS
ANALOG

ANALOG
POWER

POWER

POWER
230VAC

230VAC

230VAC
SIGNAL

SIGNAL
GND

GND

GND

GND
0-10V

0-10V
PE

PE

PE
A+

A+
B-

B-
N

N
L

L
0-10V 0-10V
10V 10V
GND GND
GND GND
Pot Pot
+5V +5V
Speed Speed
M1 speed/gnd M1 speed/gnd
1~ I/O
5V 1~ I/O
5V
+5V +5V
ST ST
start/stop start/stop
A+ A+
A A
B- B-
EC MOTOR B EC MOTOR B
GND GND
GND GND
PE PE
ELECTRICAL WIRING DIAGRAMS
ELECTRICAL WIRING DIAGRAMS
PE PE
L L
L L
N N
N N
PE

PE

PE
L1

L1

L1
L2

L2

L2
L3

L3

L3
0-10V
10V
GND
M1 M1 M2 GND

1 phase - 2 EC MOTOR
Pot

3~ 3~ 1 PHASE 3- ~1 EC MOTOR 1 PHASE - 2 EC MOTORS M2


+5V
Speed
speed/gnd
1~ I/O
5V
1~230V 50Hz 1~230V 50Hz +5V
ST
start/stop
A+

3 PHASE WITH VFD


A
B-
PE

PE
EC MOTOR B
N

N
L

L
GND
GND

(-)

HH
PE

hh
PE
(-) (-)

H
L
L

h
N
N
3~400V 50Hz 3~400V 50Hz 3~400V 50Hz

L1 L2 L3 L1 L2 L3 L1 L2 L3 w
w w

control
control

SV .. iG5A SV .. iG5A SV .. iG5A W


W LLW L
(OPTIONAL)

(OPTIONAL)
(DEFAULT)

(DEFAULT)
connection box

connection box
MODBUS

MODBUS
ANALOG

ANALOG
POWER

POWER

POWER
230VAC

230VAC

230VAC
SIGNAL

SIGNAL
Dimensions Duct Connection FAN Motor
U V W U V W U V W Weight
Unit size H W L hxw Model Rated Output
GND

GND

GND

GND
0-10V

0-10V
PE

PE

PE
A+

A+
B-

B-
N

N
L

L
10V
GND
0-10V
GND
10V
GND
0-10V
GND
[mm] [-] [kW] [kg]
Pot Pot

SVS-35 530 1130 1120 210 x 700 VS 315 1,5 106


+5V +5V
Speed Speed
M1 speed/gnd M1 speed/gnd
1~ I/O
5V 1~ I/O
5V
+5V +5V

SVS-50 595 1300 1120 310x550 VS 355 1,5 124


ST ST
start/stop start/stop
A+ A+
A A
B- B-
EC MOTOR B EC MOTOR B
GND GND
GND GND

PE
L
N
PE
L
N
PE
L
N
PE
L
N
SVS-70 530 2000 1120 310x1200 VS 315 x 2 1,5 x 2 181
10V
0-10V
GND
SVS-85 655 2000 1120 410x1400 VS 400 x 2 1,5 x 2 205
GND
Pot

M2
+5V
Speed SVS-100 655 2200 1120 410x1400 VS 400 x 2 1,5 x 2 220
PE

PE

speed/gnd
L1

L1

L1
L2

L2

L2
L3

L3

L3

1~ I/O
5V
+5V
ST
start/stop
A+
M1 M1 M2
A
B-
EC MOTOR B
GND
GND
3~ 3~ 3~ PE
PE

Min Air Flow Max Air Flow Air Flow


L
L
N
N

Unit size
CFM
Fan set with AC Motor CMH CFM CMH CFM
0 1000 2000 3000 4000 5000 6000
Unit Rated Efficiency Protection Rated Current at
Model Poles SVS-35 1500 883 3500 2060
size Output Class Grade 415V/3ph/50Hz 230V/1ph/50Hz 380V/3ph/50Hz 400V/3ph/50Hz 400V/3ph/60Hz
[-] [kW] [-] [-] [-] [A] [A] [A] [A] [A] SVS-50 2100 1236 4500 2660
SVS-35 VS 315 1,5 2 IE2 IP55 / F 3,1 5,54 3,36 3,1 3,19
SVS-70 3000 1766 7000 4120
SVS-50 VS 355 1,5 2 IE2 IP55 / F 3,1 5,54 3,36 3,1 3,19
SVS-70 VS 315 x 2 1,5 x 2 2 IE2 IP55 / F 6,2 11,08 6,72 6,2 6,38 SVS-85 3400 2001 8500 5003
SVS-85 VS 400 x 2 1,5 x 2 2 IE2 IP55 / F 6,2 11,08 6,72 6,2 6,38 SVS-100 4200 2472 9500 5621
SVS-100 VS 400 x 2 1,5 x 2 2 IE2 IP55 / F 6,2 11,08 6,72 6,2 6,38

Fan set with EC Motor Coil Volume Coil Connections


Unit Rated Protection Rated Current at Unit size WCL4R WCL6R DX6R WCL4R, WCL6R DX6R
Model
size Output Grade 230V/1ph/50Hz
[Liters] fDin fDout fDin fDout
[-] [kW] [-] [A]
SVS-35 6,33 9,5 9,5 DN32 DN32 2x5/8'' 2xØ28
SVS-35 VS 315 0,75 IP54 / F 3,7
SVS-50 8,24 12,36 12,36 DN50 DN50 2xØ22 2xØ35
SVS-50 VS 315 0,75 IP54 / F 3,7
SVS-70 VS 315 x 2 0,75 x 2 IP54 / F 7,2
SVS-70 12,08 18,13 18,13 DN50 DN50 2xØ22 2xØ35
SVS-85 VS 315 x 2 0,75 x 2 IP54 / F 7,2 SVS-85 15,44 23,16 23,16 DN50 DN50 2xØ22 2xØ35
SVS-100 VS 315 x 2 0,75 x 2 IP54 / F 7,2 SVS-100 17,23 25,84 25,84 DN50 DN50 2xØ22 2xØ42

62 63
05
Fan Coil Unit
Fan Coil Unit Fan Coil Unit

Technical Specifications

CASING COOLING COIL


Top cover material: Back cover: Copper pipe:
• Galvanized steel • Galvanized steel • Dimensions: 3/8” (9.52 mm)
• Thickness: 0.8 mm • Thickness: 0.8 mm Fin:
Base material: Top cover for plenum: • Thickness: 0.105 mm
• Galvanized steel • Galvanized steel • Fin pitch: 10 FPI Unit Casing:
• Thickness: 0.8 mm • Thickness: 0.8 mm • Louvered type Al-fin Galvanized steel casing of minimum 0.8 mm thickness. Casing is internally lined with 6mm closed
Side panel material: Side panel for plenum: cell elastomeric foam insulation.
• Galvanized steel • Galvanized steel
• Thickness: 0.8 mm • Thickness: 0.8 mm
Plenum box insulation:
• 6 mm closed cell foam

Drain Tray:
They are fabricated from heavy gauge galvanized steel and are insulated to prevent condensation.
Powder coated on both sides to RAL 9002.

Cooling Coils:
Fabricated from copper tubes mechanically bonded with aluminum fins and are leak tested at 350 Psig nitrogen
pressure.

Blower:
Fans are forward curved centrifugal type of double inlet, statically and dynamically balanced to ensure quiet
operation.

BLOWER: FILTER: DRAIN TRAY:


Blower material: • Filter frame: Aluminum alloy • Material: galvanised steel
• Type: DIDW Forward Curved Centrifugal Fan • Material: Double layer aluminum • Thickness: 0.8 mm
• Thickness: 12.5 mm • Insulation material: PE, 3 mm
Air Filters:
• Material: Galvanized steel
• EU-2 filter grade as per EN779 • Water outlet: 7/8’’ All Units are provided with 12.5 mm Aluminum Mesh filter as a standard option. Filters accessible from rear end of
Motor:
• Powder coated to RAL 9002 the unit and is easily removable by pulling out from unit frame.
• Type: Single phase capacitor type
• Insulation: B
• Protection grade: IP20

Fan Motors:
Motors are single phase, 3 speed, 220-240V/1 Phase/50 Hz with internal thermal protection.

Typical applications:

Hotels

66 67
Fan Coil Unit Fan Coil Unit

Dimension - Chilled water (WS) Chilled Water (WS) - Product family and general technical specification

LENGTH FILTER SIZE CONNECTION


Model F-VS-SD-300-WS F-VS-SD-400-WS F-VS-SD-600-WS F-VS-SD-800-WS F-VS-SD-1000-WS F-VS-SD-1200-WS
A B C D E F G mm Inches mm Rated parameters Units Speed

Low Static , Chilled Water Unit


F-VS-SD-300-WS 890 628 600 668 640 534 234 575 x 200 x 12.5 NPS 1/2" DN15
1 Cooling Capacity Total [BTU/hr] High Speed 13487 16348 24590 32227 36926 43821
F-VS-SD-400-WS 990 728 700 768 740 534 234 675 x 200 x 12.5 NPS 1/2" DN15 at DBT 80 °F / WBT
67 °F water at (7.2°C
/ 12.2°C) (45°F/54°F) Sensible [BTU/hr] High Speed 9850 11601 17489 22967 26704 31514
F-VS-SD-600-WS 1240 958 930 998 970 534 234 905 x 200 x 12.5 NPS 1/2" DN15 Air Flow at 0,2” wg
- [CFM] High Speed 462 520 792 1056 1260 1478
(Low Static Unit)
F-VS-SD-800-WS 1490 1228 1200 1268 1240 534 234 1175 x 200 x 12.5 NPS 3/4" DN20 Air Flow at 0,0 wg
- [CFM] High Speed 621 507 1064 1287 1536 1802
(Low Static Unit)

G
F-VS-SD-1000-WS 1690 1428 1400 1468 1440 534 234 1375 x 200 x 12.5 NPS 3/4" DN20 [dB(A)] High Speed 46 46 46 46 47 48
Sound Pressure Level
according
F-VS-SD-1200-WS 1890 1628 1600 1668 1640 534 234 1575 x 200 x 12.5 NPS 3/4" DN20 - [dB(A)] Medium Speed 41 41 40 40 42 44
to ISO 11203 at 1
C F meter from the unit
[dB(A)] Low Speed 35 35 34 33 34 35
A
Type [-] - 3/8”, 0.28mm Thick Copper tubes

Dimensional drawings Face Area [ft2] - 1.31 1.53 1.97 2.62 3.06 3.5

Coil Row / FPI [-] - 3/10.58 3/10.58 3/10.58 3/10.58 3/10.58 3/10.58
D
Size [mm x mm] - 203.2x600 203.2x700 203.2x930 203.2x1200 203.2x1400 203.2x1600
E
Nominal water
US GPM Med Speed 1.8 2.4 3.6 4.8 6 7.2
flow rate

Type [-] - Centrifugal , Forward Curve DIDW

1
Fan Material [-] - GI

Quantity [pcs.] - 2 2 2 3 4 4

Power Supply
[W] - 80 80 80 130 160 160
(Output)

Max Power
[W] - 183 183 183 262 360 360
G

Input

Fan motor FLA [A] - 0.90 0.9 0.9 1.5 1.8 1.8

Type/Class/IP [-] - Class B/IP20 Class B/IP20 Class B/IP20 Class B/IP20 Class B/IP20 Class B/IP20
C C F
Revolutions [rpm] H/M/L 1000/900/750 1000/900/750 1000/900/750 1000/900/750 1000/900/750 1000/900/750
B A
A Quantity [-] - 1 1 1 2 2 2

Drive method - [-] - Direct Drive

Unit [kg] - 21 22 26 34 39 44
Weight
D Shipping [kg] - 23 24 29 37 43 48

E L [mm] - 890 990 1190 1490 1690 1890

Electrical wiring diagrams (for all models) Unit Dimensions W [mm] - 526

H [mm] - 230
TERMINAL STRIP
L [mm] - 915 1015 1215 1515 1715 1915
YELLOW GRAY
NEUTRAL 1
M A C Shipping Dimensions W [mm] - 535
RED
HIGH 2 WHITE H [mm] - 244
BLUE
MEDIUM 3 LEGENDS SYMBOL: Inlet (MPT) [inch] - 1/2" NPS 1/2" NPS 1/2" NPS 3/4" NPS 3/4" NPS 3/4" NPS
BLACK
LOW 4 C - CAPACITOR
Outlet (MPT) [inch] - 1/2" NPS 1/2" NPS 1/2" NPS 3/4" NPS 3/4" NPS 3/4" NPS
A - AMPERE Connections
5
Drain Pan Inch
[inch] - 7/8 7/8 7/8 7/8 7/8 7/8
OD

FIELD WIRING
INSTALLED BY USER C
B
A
68 69
06
WING air curtain
Wing Wing
MAX. AIR RANGE:
4m
MAX. AIR RANGE: ELECTRICITY
EXHAUST FLOW RATE:
4MAX.
m AIR RANGE: SAVINGS
1950-4600 m3/h
Ambient Air Curtains 4m
EXHAUST FLOW RATE: Modern design of the EC motor
1950-4600 m3/h RATE:
EXHAUST FLOW and fansaves energy compared

1950-4600 m3/h
to old generation solutions. SIDE MOUNTED
MOTOR

Insure superior curtain performance


due to uniformity in velocity
and minimalising dead zone effect.

DIMENSIONS
C200

210
2098* 465

C150

210
210
210

2098* 465

1582* 2098* 465

C100
210
210

210

1582*

1066*
1582* * - width does not include side covers
210

HMI WING EC CONTROLLER


210

STREAM RANGE 1066* * - width does not include side covers

DOOR OPTIMUM
1066* FUNCTION * - width does not include side covers

Vertical air function


Door Optimum stream range
allows Horizontal
to maintain full protection of the door opening airtime
and at the same stream
optimizerange
costs assosiated with its operation.
It keeps theinstallation
(maximum air curtain operating
height) on minimum speed, and when the doors are going
(for to beinstallation)
vertical open protect the door opening from the first moment,
STREAM RANGE
against access of the outside air. Opening the door increases also the speed of air by +1 or +2 levels, depending on user’s preferences.
STREAM RANGE 1 SPEED 2 SPEED 3 SPEED

Vertical5air stream range Horizontal air stream range


installation
height [m]

- 7 m/s * 7 - 9 m/s * 9,6 - 11 m/s *


5 - 7 m/s *

2,2 m/s *
1 SPEED

Verticalinstallation
(maximum air stream range
height) Horizontal
(for air stream range
vertical installation)
(maximum installation height)
1 SPEED 2 SPEED 3 SPEED
(for vertical installation) SIMPLE GALVANIZED SMART
CLEANING STEEL CASING DOOR PROTECTION
2 SPEED

2,3 m/s*
7 - 9m/s*
installation
height [m]

52,2 m/s *
-17m/s*
SPEED m/s *
7 - 29 SPEED m/s *
9,6 -311SPEED
* - air stream speed [m/s]
5 - 7* m/s *

2,2 m/s *
1 SPEED

2,3
installation
height [m]

5 - 7 m/s * - 9 m/s *
2,37 m/s* 9,6 - 11 m/s *
2,2 m/s *

Thanks to the optimized construction Double coating (galvanization + powder


1 SPEED

5 - 7 m/s

2,9 Air curtain with advanced WING EC


9,6 - 11 m/s *

of the covers, cleaning the curtain paint) provides long-term protection CONTROLER may perform according to
2,3 m/s*
3 SPEED

2,3 m/s* is comfortable and does not require against corrosion and consistent the door opening sensor. Smart Door
2 SPEED

2,3 m/s*
7 - 9m/s*

4,0
the disassembly of any part, always aesthetic qualities. Casing colour
* - air stream speed [m/s]

2,2rate
* - air flow m/s*[m/s] protection gives you not only permanent
2 SPEED

2,3 m/s*
7 - 9m/s*

2,3 ensuring hygienic operation. RAL 9016. temperature comfort but also secure
ir stream speed [m/s]

2,2 m/s* 2,3 m/s*


2,9 air stream range [m] 2,3 2,9 4,0
2,3 inside environment from dust, pollution,
9,6 - 11 m/s *

2,3 m/s* insects and unpleasant scents.


2,3 m/s*
3 SPEED

2,9
2,3 m/s*
6 - 11 m/s *

72 4,0 73
2,3 m/s*
3 SPEED

* - air flow rate [m/s] 2,3 m/s*


4,0
1066* * - width does not include side covers

Wing Wing

STREAM RANGE
STREAM RANGE TECHNICAL PARAMETERS
Vertical air stream range Horizontal air stream range AMBIENT CURTAIN
(maximum installation height) (for vertical installation) Parameters Unit
WING C100 WING C150 WING C200
AC EC AC EC AC EC
1 SPEED 2 SPEED 3 SPEED
maximum door width m 1 1,5 2
(1 device)
installation
height [m]

5 - 7 m/s * 7 - 9 m/s * 9,6 - 11 m/s *

5 - 7 m/s *

2,2 m/s *
maximum door height

1 SPEED
(vertical stream range)* m 4
maximum exhaust CFM 1147 1883 2707
flow rate
supply voltage V/ph/Hz ~230/1/50

2 SPEED

2,3 m/s*
7 - 9m/s*

* - air stream speed [m/s]


2,2 m/s*
2,3 motor power kW 0,235 0,2 0,375 0,3 0,58 0,45
2,3 m/s*
2,9 rated current A 1,2 1,1 1,7 1,3 2,6 1,9

9,6 - 11 m/s *

2,3 m/s*
3 SPEED
weight kg 20,5 19 27,5 25,5 34,5 32,5
2,3 m/s*
4,0
* - air flow rate [m/s] protection rating IP 20

air stream range [m] 2,3 2,9 4,0 max. velocity* m/s 11

INSTALLATION
INSTALLATION
INSTALLATION casing colour RAL RAL 9016 or RAL 7016

WING C100, C150, C200 (AMBIENT CURTAIN)


Dedicatedbrackets
Dedicated bracketsand
andfixing
fixingpoints
points Themaximum
The maximummounting
mountingheight
heightisis4m.
4m.
enableimmediate
enable immediateinstallation
installation Theminimum
The minimumdistance
distancebetween
betweenthe theair
airoutlet
outlet WING C100 WING C150 WING C200
Fan speed
ofthe
of thecurtain.
curtain. ofthe
of thecurtain
curtainand
andthe
theceiling
ceilingisisonly
only30
30cm.
cm. I II III I II III I II III
Qp [m³/h] 1050 1500 1950 1500 2250 3200 2340 3400 4600
db (A) ** 53 59 62 54 62 63 57 61 63
* air stream range depends on curtain operation speed
CCEEI ILLI INNGG ** measurement conditions: semi-open space, horizontal installation on the wall, measurement performed 5m away from the device

min.30
min. 30cm
cm

DEDICATEDBRACKETS
DEDICATED BRACKETS
4m
max. 4
max. m

EN-C
FASTENINGPINS
FASTENING PINS
1,5 m 1,5 m 2m 1m 1m
CONTROL
1,5 m 1,5 m 2m 1m 1m
3700 (4000*)

3700 (4000*)

3700 (4000*)

CC
EEI LI L
I NI N
GG

min.30
min. 30cm
cm 1,5mm
1,5 1,5mm
1,5 2 2mm 1m
1m
3700 (4000*)

3700 (4000*)

1,5 m(4000*)

HORIZONTAL
INSTALLATION
1,5 m
3700
max. 4 m
max. 4 m

4000

4000

3000
4000

4000

3000

3000 3000 1000


* WING C
HMI WING EC controller HMI WING EC WIFI controller Wall controller WING/VOLCANO Potentiometer EC (0-10 V) Door sensor (reed switch)*
1,5 m
1,5 m

3000 3000 1000


Motor support EC Motor support EC Power ~230/1/50 Contact configu-
Motor support AC supply voltage V/ph/Hz NO
ration
horizontalinstallation
horizontal installation 3000
3000 3000
3000 4000
4000 Power ~230/1/50 Power ~230/1/50 Power supply ~230/1/50 0,02 A for
supply voltage V/ph/Hz supply voltage V/ph/Hz voltage V/ph/Hz Permissible load Switching current 500 mA
0-10V
1m

1,5 m
1,5 m

1A for 230VAC 1A for 230VAC


Permissible load Permissible load Permissible load 6(3) A Work mode Manual Switching voltage max 200 V
0,02A for 0-10V 0,02A for 0-10V
3000

VERTICAL
3000

3000
1m

1,5 m
1,5 m

Setting range 5...40 °C Setting range 5...40 °C Settings range 10...30 °C Protection rating IP 30 Connection screw
1m
1m

INSTALLATION
1,5 m
1,5 m
2m

3000

WING C
3000

3000

1,5 m

Protection rating IP 20 Protection rating IP 20 Protection rating IP 30


1,5 m

* cooperation with controller WING EC


3000

3000
3000

3000

ALL EC AIR CURTAINS ARE CHARACTERIZED BY EASE AND SIMPLICITY OF CONNECTION


2m

*
1,5 m
1,5 m
2m
2m

1,5 m
1,5 m

3700 (4000*) 7400 (8000*) 3700 (4000*)


74 75
3700 (4000*) 4000
4000 7400 (8000*) 8000
8000 3700 (4000*)
verticalinstallation
vertical installation
NOTES NOTES

76
NOTES

PSYCHROMETRIC CHART
Water vapour
pressure

air temperature

barometric pressure 100 kPa Humidity


ratio
(g/kg)

78
VTS CLIMA INDIA PRIVATE LIMITED
#520, B- Block, Carlton Towers
Old Airport Road, Bangalore – 560008
[email protected]

India Sales Offices:


Bangalore - Mumbai - Delhi - Chennai - Hyderabad
Kochi - Ahmedabad - Pune - Nagpur - Kolkata - Chandigarh