SITEMANAGER 11xx/33xx
INITIAL SETUP
GENERAL SAFETY NOTICE, PLEASE READ THIS CAREFULLY BEFORE INSTALLING THE SITEMANAGER. D Applying UPLINK settings for accessing the Internet
The SiteManager is completely safe to use, if you comply with the below general instructions: The SiteManager requires being able to access the Internet via an Uplink port in order to target a
GateManager server. By default it will receive its IP address by DHCP, and you only need to manually
a. Read this Initial Setup guide carefully before setting up the SiteManager. configure the Uplink if you will use a fixed IP on UPLINK1, or if you want to use a USB broadband
b. In order for this product to conform with the safety certifications, the SiteManager must modem as UPLINK2.
be installed in a Restricted Access Location.
c. When mounting the SiteManager make sure the surface is dry and well ventilated and Select one of the following 4 methods:
not exposed to direct sunshine.
1. Using the Secomea Appliance Launcher.
If the SiteManager becomes wet or damp, the SiteManager should at once be discon-
nected and handled with care as moist/water on or in the SiteManager may cause the a. Download and install the Appliance Launcher tool from here:
SiteManager to malfunction or compromise safety. https://kb.secomea.com/docs/appliance-launcher
d. Do not use the SiteManager in locations with extreme temperatures or near heat- or b. Connect the DEV1 or UPLINK1 port of the SiteManager to the local network and power it
cooling sources. on. The SiteManager must be on the same Subnet as your PC. Alternatively connect the
SiteManager with an Ethernet cable directly to your PC.
e. At all times keep the SiteManager free from dust and dirt.
c. Power on the SiteManager and wait approx. 1 minute for it to become ready.
f. Do not disassemble or in any other way tamper with the SiteManager unless authorised
to do so. d. Start the Appliance Launcher and the SiteManager should be listed in the first screen. If
it does not appear immediately, try pressing the Search button a couple of times. (Note
g. Do not use any unauthorised power supply when powering the SiteManager.
that the Appliance Launcher will only show the SiteManager if your PC has a genuine
h. Do not use an old or badly maintained power supply with the SiteManager. private IP address (10.x.x.x, 172.16-31.x.x, 192.168.x.x or 169.254.x.x))
i. At all times comply with the correct power specifictations as under powering the Site- e. Follow the Wizard and set the UPLINK1 address if you want to use a fixed IP address, or
Manager may result in malfunctioning of the SiteManager or connected USB devices. continue the wizard to menu UPLINK2 to set the SSID/WiFi Key for an integrated or
j. Make sure that only competent and skilled personal undertakes the installation and optional USB WiFi module, or PIN Code for an integrated or optional broadband modem.
setup of the SiteManager.
k. Do not connect or try to connect the SiteManager to unauthorized equipment. 2. Using the default IP address (10.0.0.1)
l. Make sure your SiteManager always has the latest version of our firmware installed for a. Connect the DEV1 port of the SiteManager to the Ethernet port of your PC using a
best functionality and cyber security protection. standard Ethernet cable.
m. Only use new or well-maintained cables when connecting to the SiteManager. b. Configure your PC’s Ethernet adapter to 10.0.0.2 subnet mask 255.255.255.0.
n. Regularly inspect and check the SiteManager to make sure its surface is unbroken c. Power on the SiteManager and wait approx. 1 minute for it to become ready.
and that there are no signs of damages to the SiteManager. If the surface is broken or d. Type the following in your web browser: https://10.0.0.1
there are signs of damages to the SiteManager immediately disconnect the SiteMan-
e. Login with user admin and the SiteManagers’ MAC address as password (printed on the
ager.
product label).
A DIN Rail Mounting f. Enter menu System --> UPLINK1 to set the UPLINK1 address if you want to use a fixed IP
address, or enter menu UPLINK2 to set the SSID/WiFi Key for an integrated or optional
USB WiFi module, or PIN Code for an integrated or optional broadband modem.
Push the SiteManager from down and Release and ensure that the g. Continue with section E to configure GateManager settings.
upwards to apply tension on the SiteManager it is firmly mounted
spring-lock, and in the same movement 3. Using a DHCP server
push the SiteManager in, and over the a. Connect the UPLINK port of the SiteManager to your local network and power it on.
top of the DIN rail.
b. After approx. 1 minute the SiteManager should have received an IP address from your
DHCP server.
c. Check the lease list of the DHCP server to see what the IP address is.
d. Type the IP address in your web browser preceded with https:// (e.g.
https://192.168.41.13).
e. Login with user admin and the SiteManagers’ MAC address as password (printed on the
product label).
f. Enter menu System --> Uplink1 to set the UPLINK1 address if you want to set a fixed IP
address, or enter menu UPLINK2 to set the SSID/WiFi Key for an integrated or optional
USB WiFi module, or PIN Code for an integrated or optional broadband modem.
g. Continue with section E to configure GateManager settings.
4. Using a USB memory stick
B POWER
a. Login to the GateManager Portal and locate the domain in which the SiteManager
SiteManager must be fed 12 - 24V DC. Power consumption is max. 6W for the unit including an should connect.
integrated broadband modem (xx39 models) or optional USB mounted broadband modem (xx29 and
b. Click the “USB Configuration” symbol , and set the UPLINK1 or UPLINK2 port settings.
xx49 models) If the SiteManager is connected to a local Intranet with a DHCP server, you do not have
to configure anything.
Power should be applied to the c. Click create to save the configuration file locally to your PC.
GND and +V terminals only!
d. Copy the configuration file to a fat32 formatted USB memory stick.
It is recommended to connect the earth ground e. Power ON the SiteManager and wait until the SiteManager is ready (Status has stopped
blinking)
in orderto reduce interference of noise.
f. Insert the memory stick, and wait until the SiteManager has automatically rebooted. If
C Ethernet ports the SiteManager has GateManager access, STATUS should turn green.
g. Remove the memory stick. No further configuraiton is needed.
Use a standard Ethernet patch cable (straight or cross over) to connect the UPLINK1 port to a switch
in a network that has access to the Internet.
E Applying settings for connecting to a GateManager server
The DEV port can be connected to an existing network separate from the UPLINK1 network, or you can
create a separate device network isolated from the UPLINK1 network. But you can also just connect 1. In the SiteManager Web GUI enter the menu GateManager --> General (if using the Appliance
the UPLINK1 port, and only access equipment on the Uplink side. Launcher, follow the wizard to the GateManager Parameters page).
192.168.2.100/24 192.168.2.2/24 2. Enter the IP address of the GateManager server that the SiteManager should connect to, and a
Domain Token for the domain where the SiteManager should appear. You should have received
this information from your administrator or from where you received the SiteManager.
3. When the settings are entered, you should reboot the SiteManager. Observe that the Status LED
goes steady Green, which indicates that the SiteManager is connected to the GateManager.
IP 10.0.0.2
4. Once attached to the GateManager, you can use the GateManager Console or a LinkManager
Client to get remote access to the SiteManager Web GUI to perform additional configuration
192.168.2.2/24 (DEV ports, Agents etc.)
DO NOT CONNECT THE DO NOT ASSIGN DEV
DEV AND UPLINK1 ADDRESS IN THE SAME 5. Detailed guides, new firmware etc. can be downloaded from: http://support.secomea.com
PORTS TO THE SAME LOGICAL NETWORK AS
PHYSICAL NETWORK UPLINK1
192.168.2.5/24
Secomea A/S - Smedeholm 12-14 - DK2730 Herlev - Denmark Applicable to SiteManager models: 1129, 1139, 1149, 3329, 3339, 3349
Tel: +45 8870 8650 - www.secomea.com - [email protected] DOC: SM11xx-33xx_initial_contact_v07
F LED signaling I Serial ports (Serial cables are not included with the product)
Refer to the following table. The Power LED is Green when power is supplied. SiteManager is equipped with a RS232 Serial port with full flow control support. The pinout of the
DB9 connector corresponds to the standard Serial COM port of a PC. You should be able to use an
State (All models) STATUS CONNECT ordinary NUL-modem cable for most equipment.
- For Omron PLCs use the cable XM2S-09.
Booting Steady Red Blink -
- For Siemens MPI- or PPI connection use either a RS232-to-MPI adapter,
GateManager Connecting 2 Red Blink - a USB-to-MPI adapter or an Ethernet-to-MPI/PPI adapter (Secomea p/n 26940)
or Disconnected - For other PLCs refer to the documentaiton for the PLC for information about special Serial
pinout.
- Remote Management is disabled via - long pause + 2
INPUT1 or SiteManager GUI Green Blink J Internet access via broadband modem (UPLINK2)
- SiteManager in SMS Wakeup mode
Note: On xx39 models a broadband modem is integrated. On xx29 models you must install an exter-
GateManager Connected On Green - nal 4G/3G/GPRS USB modem. The SiteManager includes a large number of USB modem drivers, but
not all may work. Refer to the Secomea web site for a USB modem compatibility list.
- UPLINK is physically disconnected, or On Red -
- GateManager configuration is missing in The broadband modem connection is referred to as UPLINK2. The SiteManager will as default always
the SiteManager, or attempt to use the Ethernet connection (UPLINK1), and only use UPLINK2 if the Internet connection
- No route to GateManager host due to its is lost on UPLINK1. Once a connection is established on UPLINK2, switching to UPLINK1 will only be at-
address being configured as DNS name, tempted at next reboot, or if the Internet connection on UPLINK2 is lost.
and a DNS server is not configured or is
not reachable/working. I the modem is using a SIM PIN code you should enter the PIN code in the System > UPLINK2 menu
LinkManager Connected - On Green of the SiteManager. The SiteManager will automatically detect the APN (Access Point Name) from an
internal table, but can also be manually entered via the SiteManager GUI.
State (model xx49 only) UPLINK2 If your modem or SIM card does not have a PIN Code, you do not have to make any further configura-
tion of UPLINK2 in the SiteManager (The PIN Code can be removed from a SIM card by inserting it into
- No WiFi SSID configured Off a standard mobile phone, and use the remove SIM card function of the phone).
- SSID configured but no WiFi Key con-
figured In order to reduce data traffic, you can configure UPLINK2 to let the broadband connection enter
- SSID and WiFi Key configured, but no ac- sleep-mode if idle. The connection will be reestablished when sending an SMS to the phone number
cess point found matching the SSID. on the SIM card.
WiFi SSID Found but not connected yet. 2 Green Blink
Note that when using a USB WiFi adapter as explained in the following, broadband uplink is disabled.
Possible WiFi Key error.
WiFi connected successfully. On Green SIM insertion (xx39 models)
State (xx39 models only) UPLINK2 Slide the SIM card into the slot.
No SIM card detected Off
Wrong or missing SIM Pin code 3 Green Blink
SIM PIN code OK, but no connection. 2 Green Blink
(Trouble shoot in SiteManager GUI)
GPRS connected (slow connection) On Green + 1 Green Blink Use a sharp object, such as a
screwdriver, to push the SIM card
3G connected (fast connection) On Green further into the slot (approx 2 mm),
until you hear the click of the
SiteManager is in SMS Wakeup mode long pause + 2 Green Blink spring lock.
Note that it may take some time for the Status LED to reflect a new state. For instance a GM Discon-
nect may take up to 4 minutes to be reflected, depending on the Keep-alive Interval setting on the
GateManager.
G USB ports (USB cable is not included with the product)
The USB port can be used for attaching selected USB equipped PLCs and for connecting a noptional
USB broadband adapter to use as Internet connection (see details below) The SIM card is properly inserted when it is
level with the SiteManager cabinet.
Note: The USB port limits the power drain for peripheral devices to 500mA per USB connector in
compliance with the USB 2.0 standard.
K Internet access via WiFi (UPLINK2)
H IO Ports On xx49 models a WiFi client module is integrated. On other models WiFi client mode can be
Digtial Input port 1 and 2: In “OFF” (inactive) state at 2.34 V or above, and in the “ON” (active) state at achieved by inserting a Secomea USB WiFi adapter (e.g. p/n 27250).
0.16 V or below. The behavior for input voltages between 0.16 V and 2.34 V is undefined.
There is an internal 10 kohms pull-up resistor to 3.3 V, so an unconnected input port is in the “OFF” The connection is referred to as UPLINK2. When enabling the WiFi client, the SiteManager will be by
state. Input port 1 is by default assigned to toggle GateManager Access. By connecting a simple on/off default attempt to connect with the SSID “sitemanager” and the MAC address of the SiteManager as
switch you can control when remote service should be allowed. WiFi Key. A specific SSID and WiFi Key can be configured in the System > UPLINK2 menu.
Relay Output 1: Output1 is a “dual pin” port where both pins are isolated when OFF and short-circuited Note that connecting the USB WiFi adapter will disable any integrated wireless module used for
when ON. Output port 1 is by default configured to go active when a LinkManager is connected, and can UPLINK2.
be used to turn on a lamp that notifies the users that the device is being serviced.
Maximum sink current is 0.5 A. Maximum Voltage is 24V L WiFi Access Point (AP) support via external USB WiFi adapter
xx49 models can operate as a WiFi Access Point using a Secomea USB WiFi adapter (e.g. p/n 27250).
Digital Output 2: Output2 is a “single pin” port, which is pulled towards GND when ON, and is high-
impedance when OFF. The port is an “open drain” kind, which means that (just like a switch) no voltage
The SSID to be broadcasted in AP mode and the WiFi Key can be configured in the System > DEV1
is output by the port itself, but must be supplied either from an external source (max 24 V) or from
menu.
the Vout (5V) pin. In the “OFF” (inactive) state, the impedance is min 24 Mohms; in the “ON” (active) state,
the impedance is max 0.5 ohms. Maximum sink current is 0.2 A.
Note that connecting the USB WiFi adapter will disable the integrated WiFi module used for UPLINK2.
Refer to the guide “Working with IO ports” for application scenarios.
M Regulation Notices
Product compliancy: • CE (EN 61000-6-2, EN 61000-6-4, EN 301 489-1, EN 301 489-3) • FCC 47 cfr part 15 * • UL Listed (file #E358541, ITE 4ZP8) • IEC CB certified (DK-30193-A2-UL) • RCM Compliant • Japan Tele MIC (007-D160018007) (xx49 models)
* NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a
commercial environment. This equipment generates, uses, and can radiate radio frequency energy, and if it is not installed and used in accordance with the instruction manual, it may cause harmful interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his own expense.. Operation is subject to the following conditions:
1. This device may not cause harmful interference.
2. his device must accept any interference received, including interference that may cause undesired operation.
Specific to the integrated WiFi module (models 1149 and 3349 only)
1. The module supports IEEE 802.11 b/g/n radio in the 2.412 – 2.462 GHz band, with a maximum output power of +15dBm for IEEE 802.11g/n and +17dBm for IEEE 802.11b
2. The module is listed under FCC Certification ID: QOQWF111. To fully comply to FCC/IC the maximum gain of a connected antenna must not exceed 2.0 dBi
3. The module is in conformity with the essential requirements and other relevant requirements of the R&TTE Directive (1999/5/EC).
4. The module is in conformity with the following standards and/or normative documents: Safety: EN 60950-1:2006+A11:2009+A1:2010+A12:2011, EMC: EN301 489-1/-17, Spectrum: EN 300 328 V1.8.1 (2006-10)
Specific to the integrated broadband module (models 1139 and 3349 only)
1. The module is PTCRB and FCC approved. To fully comply to FCC/IC the following conditions must be met: a) At least 20 cm separation distance between the antenna and the user’s body must be maintained at all times. b) The maximum gain of a connected
antenna including cable loss in a mobile-only exposure condition must not exceed 3.5 dBi in the cellular band.
2. The module is in conformity with the essential requirements and other relevant requirements of the R&TTE Directive (1999/5/EC).
3. The module is in conformity with the following standards and/or normative documents: Safety: EN 60950-1:2006+A11:2009, EMC: EN 301 489-1/-7/-24, Radio: EN 301 511, EN 301 908-1/-2
第十二條 經型式認證合格之低功率射頻電機,非經許可,公司、商號或使用者均不得擅自變更頻率、加大功率或變更原設計之特性及功能。 第十四條 低功率射頻電機之使用不得影響飛航安全及干擾合法通信;經發現有干擾現象時,應立即停用,並改善至無干
擾時方得繼續使用。 前項合法通信,指依電信法規定作業之無線電通信。 低功率射頻電機須忍受合法通信或工業、科學及醫療用電波輻射性電機設備之干擾。