Functions

L-VIS Touch Panel  BACnet  Modbus


CEA‑709 M-Bus
LVIS-ME200/ME212/ME215/3ME15‑Gx/3ME7-Gx  OPC
Datasheet #89017304

L-VIS Touch Panels for BACnet networks are ideally suited for visualization and
operation of various applications in building automation. L-VIS Touch Panels visu-
L-WEB

alize building systems, can be used as room operator panels, in hospital operation
or isolation rooms, conference and reception areas. The fully customizable user
screens can show dynamic pages that are easy to navigate. L-VIS Touch Panels
make use of an extremely low power embedded controller platform utilizing an
embedded operating system. This makes L‑VIS resistant against problems when
re-booting after power outage and also against any viruses.
L-ROC

L-VIS impresses with its timeless design, harmonic integration into modern and
historical architecture, and with its extremely user friendly concept. The shallow
installation depth and low thermal power loss allow mounting in almost any
location.

Different Sizes
L-INX

L-VIS Touch Panels are available in the following variations:

LVIS-ME200 5.7” Touch Display 320 x 240 256 colors


Aluminium frame with anodized finish
LVIS-3ME7-Gx 7™ Touch Display 800 480 256 k colors
Frameless glass front and capacitive touch
L-IOB

LVIS-ME212 12.1” Touch Display 800 x 600 65 536 colors


Aluminium frame with anodized finish
LVIS-ME215 15” Touch Display 1024 x 768 65 536 colors
Aluminium frame with anodized finish
Gateways

LVIS-3ME15‑Gx 15” Touch Display 1024 x 768 256 k colors


Frameless glass front and capacitive touch

OPC Dynamic Graphical Pages


BACnet Modbus XML-DA
The graphical pages may consist of multiple dynamic graphical controls that show
the current plant status in real time. It is also possible to access decentralized
L-VIS

schedules, alarm servers, or trends. The graphical projects are designed with the
L-VIS/L-WEB configuration tool free of charge. Without any know-how in HTML or
Java, user specific graphical pages can be created. Dynamic information is shown
through value or text controls, changing symbols, bar charts, trend views, alarm
and event lists, or schedule controls. The L-VIS/‌L-WEB configuration tool allows for
y=f(x) using most of the pixel graphic formats (GIF, JPG, BMP, TIF, PNG) or vector graphics
L-DALI

VNC BACnet
(SVG).

Playback of Audio Files and Streams


The L-VIS Touch Panel supports the playback of stereo MP3, WAV, and MP3 streams
(for example webradio). The playback will be started or stopped by the respec-
Routers, NIC

tive action object. The action object is linked to one of the available audio files
or to the URL of an MP3 stream. When accessing a playback via L-WEB, it will be
executed locally on the client.

Automatic Page Generation


Pages including data point names and values, alarm views, schedules, or trends
Interfaces

can be created automatically by the L-VIS/‌L-WEB configuration tool. This signifi-


cantly reduces engineering time and cost.

Connectivity and Data Points


The L-VIS Touch Panels support connectivity to BACnet/‌IP and BACnet MS/‌TP and
implement the BACnet Building Controller (B-BC) profile. They include a fully fea-
Accessories

tured built-in BACnet/‌IP to MS/‌TP router with BBMD and slave proxy functional-
ity. In addition, the L‑VIS Touch Panels provide connectivity to Modbus TCP via
Ethernet/‌IP and to Modbus RTU via RS-485.

92 www.loytec.com
Functions
L-VIS Touch Panel

LVIS-ME200/ME212/ME215/3ME15‑Gx/3ME7-Gx
Math objects can calculate any kind of formula using data points available on the
device. The resulting data point value can then be either shown on the page or

L-WEB
provided via a BACnet object. All BACnet server objects are automatically mapped
to OPC XML-DA data points that can be accessed via Web services.
The L-VIS devices provide fully featured AST™ functionality (Alarming, Scheduling,
and Trending) and can be integrated perfectly into the L-WEB System.
The LVIS-ME212/ME215/3ME15‑Gx/3ME7-Gx devices are equipped with two

L-ROC
Ethernet ports including a built-in Ethernet switch. This allows for building a daisy
chained line topology of up to 20 devices, which reduces costs for network instal-
lation. Dual Ethernet port devices also allow the setup of a redundant Ethernet
installation (ring topology), which increases reliability. The redundant Ethernet
topology is enabled by the Rapid Spanning Tree Protocol (RSTP), which is sup-
ported by most managed switches.

L-INX
Features

• High resolution TFT touch display with dimmable backlight • Alarming, Scheduling, and Trending (AST™)
• Anodized aluminium front frame or frameless glass front • Event-driven e-mail notification

L-IOB
and capacitive touch (LVIS-3ME15‑Gx/LVIS-3ME7-Gx) • Math objects to execute mathematical
• Flush-mounting in combination with the mounting frame operations on data points
• Stores customized graphical pages • Compliant with ANSI/ASHRAE–135‑2008
• Visualization of customized graphical pages and ISO 16484‑5 standard

Gateways
through built-in Touch Panel, LWEB‑900 (building • Supports BACnet MS/‌TP and BACnet/‌IP
management) and LWEB‑802/‌803 • BACnet Client Function (Write Property,
• Device configuration and graphical page creation with Read Property, COV Subscription)
the L-VIS/L-WEB configuration tool free of charge • BACnet Client Configuration with configuration
• Supports all popular graphic file formats such tool (scan and EDE import)
as BMP, ICO, JPEG, TIFF, PNG, MNG, GIF • B-BC (BACnet Building Controller)
• Support of SVG vector graphics • Integrated BACnet/‌IP to BACnet MS/‌TP Router

L-VIS
• Supports alpha blending • Modbus TCP and Modbus RTU (Master or Slave)
• Supports popular font types such as • Integrated web server for device configuration
TrueType, Type-1, BDF, PCF, and OTF and monitoring data points
• Supports Unicode text • Access to network statistics
• Built-in OPC XML-DA server

L-DALI
• Configurable via Ethernet/‌IP
• Built-in OPC XML-DA client • Playback of audio files and streams (LVIS-ME21x only)

LVIS-ME200 LVIS-ME212 2 x Ethernet / IP


Routers, NIC

Ethernet / IP
Web Graphics LVIS-ME215 SWITCH
Web Graphics
Interface Interface

Alarming Alarming
Modbus OPC XML-DA OPC XML-DA Modbus OPC XML-DA OPC XML-DA
BACnet/IP Scheduling E-Mail BACnet/IP Scheduling E-Mail
TCP Client Server TCP Audio Client Server
Trending Trending
Interfaces

Data Point Abstraction Layer Data Point Abstraction Layer


ROUTER

ROUTER

y=f(x) y=f(x)

BACnet Modbus 5.7’’ Touch Digital Digital L-TEMP1 BACnet Modbus 12.1/15’’ Touch Digital Digital L-TEMP1
Backlight Backlight
MS/TP RTU Input 0 Input 1 Sensors MS/TP RTU Input 0 Input 1 Sensors
VISUALIZATION VISUALIZATION
Accessories

DIGIN0 DIGIN1 DIGIN0 DIGIN1


V1.2.8 V1.2.8

buildings under control 93


Functions
L-VIS Touch Panel

LVIS-ME200/ME212/ME215/3ME15‑Gx/3ME7-Gx
LVIS-3ME7-Gx 2 x Ethernet / IP

LVIS-3ME15-Gx
L-WEB

Web Graphics
SWITCH
Audio Interface

Alarming
Modbus OPC XML-DA OPC XML-DA
IP-852 BACnet/IP Scheduling E-Mail
TCP Client Server
Trending
L-ROC

Data Point Abstraction Layer

ROUTER
RNI
Backlight y=f(x)

BACnet Modbus Touch Digital Digital L-TEMP1


TP/FT-10
MS/TP RTU Input 0 Input 1 Sensors
VISUALIZATION
7” / 15”
DIGIN0 DIGIN1
L-INX

V1.2.9

Specifications 5.7”, 7”
Type LVIS-ME200 LVIS-3ME7-Gx
Screen size 5.7” (145 mm) 7” (179 mm)
L-IOB

Dimensions (mm) 210 x 164 x 63 (L x W x H), DIM001 223.5 x 162 x 65 (L x W x H), DIM035
Dimensions cut-out (mm) 180 x 150 x 57 (L x W x H) 195 x 143 x 61 (L x W x H)
Display resolution 320 x 240, 256 colors 800 x 480, 256 k colors
Interfaces 1 x Ethernet (100Base-T) 2 x Ethernet (100Base-T), Switch
Gateways

OPC XML-DA (server, client), OPC XML-DA (server, client)


BACnet/‌IP, HTTP, FTP, BACnet/IP, LonMark IP-852, HTTP, FTP,
SMTP, NTP, VNC, HTTPS, SMTP, NTP, VNC
Modbus TCP (Master or Slave) Modbus TCP (Master or Slave)
1 x RS‑485 (ANSI TIA/EIA-485) BACnet MS/‌TP 1 x TP/‌FT‑10
or 1 x RS‑485 (ANSI TIA/EIA-485) BACnet MS/‌TP or
Modbus RTU (Master or Slave) Modbus RTU (Master or Slave)
2 x Digital Input 2 x Digital Input
L-VIS

1 x Digital interface for up to 1 x Digital interface for up to 4 L‑TEMP1 sensors


4 L‑TEMP1 sensors 2 x USB-A, 1 x USB-B (PC)
speaker, audio output
Power supply 20-35 V DC / 24 V AC ±10 % 24 VDC ±10 %
typ. 3 W, backlight on: 8 W backlight on: 7 W
Operating conditions +10 °C to 40 °C, 10-90 % RH @ 50 °C, non condensing
L-DALI

Degree of protection Front: IP54 / back: IP10


Tools L‑VIS/L‑WEB Configurator
Resource limits 5.7”, 7”
OPC data points 2 000 10 000
Routers, NIC

VNC clients 16 16
BACnet server objects 512 512
BACnet calendar objects 25 25
BACnet scheduler objects 100 (64 data points per object) 100 (64 data points per object)
BACnet notification classes 32 32
Interfaces

E‑mail templates 100 100


Math objects 500 2 000
Alarm logs 10 10
Trend logs 100 (390 000 entries, ≈ 6 MB) 512 (4 000 000 entries, ≈ 60 MB)
Accessories

Total trended data points 256 512


Connections (Local/Global) 1 000/250 2 000/250
Number of L-WEB clients 15 (simultaneously) 32 (simultaneously)

94 www.loytec.com
Functions
L-VIS Touch Panel

LVIS-ME200/ME212/ME215/3ME15‑Gx/3ME7-Gx
Specifications 12.1”, 15”
LVIS-ME212 LVIS-ME215/3ME15‑Gx

L-WEB
Type
Screen size 12.1” (307 mm) 15” (381 mm)
Dimensions (mm) 329 x 268.3 x 65 (L x W x H), DIM002 394 x 318 x 65 (L x W x H), DIM003
Dimensions cut-out (mm) 300 x 250 x 61 (L x W x H) 355 x 295 x 61 (L x W x H)
Display resolution 800 x 600, 65 536 colors 1024 x 768, 65 536 colors

L-ROC
Interfaces 2 x Ethernet (100Base-T), Switch, 2 x Ethernet (100Base-T), Switch,
OPC XML-DA (server, client), OPC XML-DA (server, client),
BACnet/‌IP, HTTP, FTP, BACnet/‌IP, HTTP, FTP,
HTTPS, SMTP, NTP, VNC, HTTPS, SMTP, NTP, VNC,
Modbus TCP (Master or Slave) Modbus TCP (Master or Slave)
1 x RS‑485 (ANSI TIA/EIA-485) BACnet MS/‌TP or 1 x RS‑485 (ANSI TIA/EIA-485) BACnet MS/‌TP or
Modbus RTU (Master or Slave) Modbus RTU (Master or Slave)

L-INX
2 x Digital Input 2 x Digital Input
1 x Digital interface for up to 4 L‑TEMP1 sensors 1 x Digital interface for up to 4 L‑TEMP1 sensors
2 x USB-A, 1 x USB-B (PC) 1 x USB-A, 1 x USB-B (PC)
speaker, audio output speaker, audio output
Power supply 24 V DC ±10 % or 85-240 V AC 24 V DC ±10 % or 85-240 V AC
2.5 W, backlight on: 13 W backlight on: 11 W
Operating conditions +10 °C to 40 °C, 10-90 % RH @ 50 °C, non condensing

L-IOB
Degree of protection Front: IP54 / back: IP10
Tools L‑VIS/L‑WEB Configurator
Resource limits 12.1”, 15”
OPC data points 10 000 10 000

Gateways
VNC clients 16 16
BACnet server objects 512 512
BACnet calendar objects 25 25
BACnet scheduler objects 100 (64 data points per object) 100 (64 data points per object)
BACnet notification classes 32 32

L-VIS
E‑mail templates 100 100
Math objects 2 000 2 000
Alarm logs 10 10
Trend logs 512 (4 000 000 entries, ≈ 60 MB) 512 (4 000 000 entries, ≈ 60 MB)
Total trended data points 512 512

L-DALI
Connections (Local/Global) 2 000/250 2 000/250
Number of L-WEB clients 32 (simultaneously) 32 (simultaneously) Routers, NIC
Interfaces
Accessories

buildings under control 95


Functions
L-VIS Touch Panel

LVIS-ME200/ME212/ME215/3ME15‑Gx/3ME7-Gx
Order number Product description
LVIS-ME200 BACnet Touch Panel with 5.7” display, B-BC
L-WEB

LVIS-3ME7-G1 CEA-709, BACnet, and Modbus Touch Panel 7” (frameless glass front and capacitive touch), silver
LVIS-3ME7-G2 CEA-709, BACnet, and Modbus Touch Panel 7” (frameless glass front and capacitive touch), black
LVIS-ME212 BACnet Touch Panel with 12.1” display, B-BC
LVIS-ME215 BACnet Touch Panel with 15” display, B-BC
LVIS-3ME15-G1 CEA-709, BACnet, and Modbus Touch Panel 15” (frameless glass front and capacitive touch), silver
L-ROC

LVIS-3ME15-G2 CEA-709, BACnet, and Modbus Touch Panel 15” (frameless glass front and capacitive touch), black
LVIS-3ME15-G3 CEA-709, BACnet, and Modbus Touch Panel 15” (frameless glass front and capacitive touch), white
LVIS-FRAME1 Mounting frame for 5.7” Touch Panels
LVIS-FRAME7 Mounting frame for 7” Touch Panels
LVIS-FRAME12 Mounting frame for 12.1” Touch Panels
L-INX

LVIS-FRAME15 Mounting frame for 15” Touch Panels


L‑TEMP1 External temperature sensor
L-IOB
Gateways
L-VIS
L-DALI
Routers, NIC
Interfaces
Accessories