1 EEE4115F 2020 Cables Notes
1 EEE4115F 2020 Cables Notes
EEE4115F 2021
CABLES
A power system comprises sources, loads and connections between them. The connection is
usually by metallic conductor. Various names are used: wire, cable, feeder, branch, transmission
line, distributor, etc.
Overhead lines usually comprise bare conductor, insulated by the air, supported above the ground
on structures, from which the conductors are insulated.
Cables are insulated from their surroundings by a non-conducting sheath. Cables are usually
installed underground, on cable trays, or fixed to supports. Sometimes cables are supported as
overhead lines (aerial bundle conductor cables).
The performance and cost are affected by the materials, construction and installation, so consider
the alternatives.
Cable insulation
The insulation for cables extends over the whole length of the conductor. It has to be flexible,
resistant to the effects of heating, mechanically strong to resist damage, as well as being a good
insulator. Early cables were insulated with double layers of cotton or with rubber. Modern cable
insulations include:
• PVC (polyvinyl chloride)
• oil impregnated paper, encased in a layer of lead (PILC) or corrugated aluminium
• XLPE (cross linked polyethylene)
A single conductor in a layer of insulation is an insulated wire or a single-core cable. Several cores,
insulated from each other, can be manufactured in one cable. The cores of multi-core cables may
be round or shaped.
The cable may be armoured to resist physical damage by layers of steel wire, steel tape or medium
density polyethylene (MDPE). The outside of the cable may be covered with a layer of PVC or
tarred jute to reduce water penetration to the armouring.
Special cables are made using fire-retardant insulation for safety-critical installations.
Environmental regulations also require cables with special reduced smoke/chemical emissions in
cases of fire.
Conductor heating
Conductor resistance depends on the resistivity of the conductor material, the cross-sectional area
and the length.
The current flowing through the resistance of the conductor results in:
• voltage drop dV = I.R
• power loss P = dV.I = I2.R
• energy loss P.t = I2.R.t during period t
These equations apply for dc, and the equations for ac are very similar (dV = I.Z, and power loss =
|I|2.R), provided the ac current is defined as Irms.
The heat generated as losses in the conductor will heat the conductor, but is dissipated radially into
the surroundings, as illustrated in Figure 3 for an overhead line or an underground cable.
• For overhead conductors: higher wind speed and lower energy absorption from solar
radiation.
• For underground cables: lower ground thermal resistivity.
The continuous rating, when time t is long, (called the thermal rating or the continuous current
carrying capacity) describes the condition when:
Rate of heat generated in the conductor resistance = Rate of heat lost by cooling.
The ‘rate” is measured by the power I2.R and R is virtually constant,
Therefore, P I2 and the thermal rating can be expressed in [A]
Note the thermal rating is independent of the operating voltage of the conductor. Small differences
arise for cables operating at different voltages because of the temperature limits of the insulation
and the effects of cable insulation on the heat transfer. Some typical nominal thermal ratings for
cables are shown in Table 2
Table 2: Some typical nominal thermal ratings for cables
Area of each 3-core Al PILC 2-coreCu PVC 1-core Cu XLPE
conductor [mm2] in ground [A] in ground [A] in ground [A]
1,5 23
2,5 30
4 38
6 48
10 64
16 82
25 80 126 169
35 100 147 205
50 125 176 245
70 155 215 302
95 185 257 366
120 210 292 422
The thermal rating must be adjusted if the conditions of the installation differ from the standard
conditions defining the nominal rating, as shown in Table 3.
The effective current rating limits the maximum load which can be delivered by an overhead line or
cable.
Example 2: Calculate the maximum power that can be delivered by the cable operating at 230 Vac
if the load power factor is 0,85.
Example 3: Calculate the power delivered if the cable operates at 550 V and the load power factor is
0,95.
Imax = 74 A
P = 550 x 74 x 0,95 / 1000 = 38,67 kW
This power could be delivered at 230 V, but a larger size cable would be needed.
Exercise: Draw a graph of power delivered (at upf and at pf=0,9) against cable size, using 2-core
copper PVC cable operating at 230 or 550 V, where the overall current capacity derating factor is
0,95.
Fault rating
The maximum operating temperature allows for extra heating caused by a fault. Fault current flows
for only a short time, after which the circuit breaker trips or the fuse blows to protect the system. It
is assumed that no heat can be dissipated during the short period of the fault. All the energy is
converted into raising the temperature of the conductor. Factors affecting the temperature rise
include:
• specific heat of conductor
• size of conductor
• duration of fault current
Example 4: Calculate the maximum allowable fault duration for 35 mm2 Cu XLPE cable if the
fault current is 7 kA.
T = (k.A/Isc)2 sec = (143 x 35 / 7000)2 = 0,51 sec
Cable selection exercise: Select a 12,7 kV 1-core copper conductor XLPE cable to supply a load
of 2,7 MW at power factor of 0,90. Two cables (phase and neutral) are laid together in the ground,
touching, and no other derating factor applies. A fault current of 12 kA could flow for up to 1,2 sec.
The cable size must be adequate for the continuous current rating and the fault current.