MEGAcel I Filters

Submittal Options Configuration Nomenclature


E24A24A A 1 P 13 F 2 T 0 AA
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10)
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10)
SIZE DEPTH SEALANT MEDIA ACCEPTANCE GASKET GASKET SEPARATOR FACEGUARD FRAME &
LEVEL MATERIAL LOCATION CONFIGURATION

(1) Size: E 24 A 24 A (6) Gasket/Gel Material:


B – Polyurethane Gel P – None
Designates Imperial Measurement Filter Width in Additional E – EPDM T – Neoprene
Fractions of an Inch F – Silicone Gel U – Poron
Filter Height in Whole Inches
(see chart below)
*Gaskets are ¼" thick x ¾" wide
Filter Height in Additional
Filter Width in Whole
Fractions of an Inch
Numbers
(see chart below)
Fractional Notation for Imperial Sizes: (7) Gasket/Gel Location:
A=0 B = 1/8 C=¼ D = 3/8 0 – None
E=½ F = 5/8 G=¾ H = 7/8 1 – Air Entering SIde
2 – Air Leaving Side
3 – Both Sides
E23D11G 5 – Extractor Clips
Example:
23 3/8" High x 11 ¾" Wide

(2) Depth: (8) Separator:


A – 11 ½" T = Aluminum
W = Vinyl Coated Aluminum

(3) Bond: (9) Faceguard:


1 – Polyurethane 0 – None
1 – Air Entering SIde
(4) Media: 2 – Air Leaving Side
P – eFRM (99.99% on 0.3 micron or H13) 3 – Both Sides
T – eFRM (99.999% on 0.3 micron or H14)

(5) Acceptance Level: (10) Frame and Configuration:


13 – 99.99% on 0.3 micron, scanned 21 – 99.95% on MPPS (H13) AA – Galvanized Steel - Gel Seal BA – Galvanized Steel - Gasket Seal
14 – 99.999% on 0.3 micron, scanned 22 – 99.995% on MPPS (H14) AB – 304 Stainless Steel - Gel Seal BB – 304 Stainless Steel - Gasket Seal
AC – 409 Stainless Steel - Gel Seal BC – 409 Stainless Steel - Gasket Seal
AD – Aluminum - Gel Seal BD – Aluminum - Gasket Seal

MEGAcel® I eFRM Specifications


1.0 General 2.6.3 Fluid seal material shall be characterized for chemical resistance to known
1.1 Air filters shall be HEPA grade air filters with eFRM (expanded FluoroResin Media), industry accepted decontamination agents, cleaning agents, and filter testing
aluminum separator, of metal frame, urethane sealant, and either polydimethylsiloxane reagents.
fluid seal or dry gasket seal.
2.6.4 Fluid seal material shall be tested for chemical compatibility to all
1.2 Sizes shall be noted on drawings and/or other supporting materials. materials in contact during manufacturing including gloves, tools, mixing
equipment, dispensing equipment, and packaging materials, as well as
2.0 Construction
potential airborne contaminants and poisons.
2.1 Filter media shall be of continuously pleated eFRM (expanded FluoroResin Media),
no glass allowed, and pleated using aluminum foil separators. 2.6.5 Fluid seal material shall demonstrate resistance to accelerated life cycle
testing.
2.2 eFRM media shall be compatible with industry standard validation and testing
methodologies using an acceptable oil aerosol agent (i.e. PAO). 2.6.6 Fluid seal shall withstand knife-edge insertion to partial depth without
complete depth cutting or full length splitting.
2.2.1 The aluminum separator shall be tapered at a 3:1 ratio to aid in aerodynamic
and compression properties and shall be minimum 13 mils thick. 3.0 Performance
3.1 The filter shall have a tested efficiency of (99.99% or 99.999% @ 0.3um OR
2.3 The media pack shall be affixed permanently to the filter frame assembly by
99.95% or 99.995% @ MPPS) when tested under the guidance of either
means of a polyurethane sealant.
IEST RP-CC-001 or EN1822.
2.4 The filter frame shall be of minimum of 18ga. galvanized steel, galvaneal, 304 SST
3.2 Each Filter shall be tested for initial (clean) pressure drop at rated flow. Maximum
or 0.063 in. mill finished aluminum. The filter frame shall be designed for use in either
initial pressure drop per overall efficiency rating for 24" x 24" x 11½" filter shall be as
gasket seal or fluid seal systems.
follows:
2.5 Gasket system filters shall be factory installed 1/4" thick by 3/4" wide dovetailed,
close-celled neoprene affixed to the sealing surface. Filter frame sealing surface to Overall Efficiency Airflow (CFM) Nom. Initial ∆P
have a flatness tolerance of +/- 1/32".
99.99% @ 0.3µm/99.95% @ MPPS 2000 0.73" w.g.
2.6 Fluid Seal system filters shall have:
2.6.1 A continuous trough around the perimeter of the filter with continuous, 99.999% @ 0.3µm/99.995% @ MPPS 2000 1.01" w.g.
integral indication of acceptable fluid seal fill level. The fluid seal trough shall be
3.3 Each filter shall be factory scanned in accordance with IEST-RP-CC034 or
filled at the factory.
EN1822.
2.6.2 Fluid seal material shall be characterized for all salient mechanical, physical,
3.4 Filter shall be listed by Underwriters Laboratories as UL 900.
and chemical properties such as Hardness/Penetration, Tack, and Migration of
free silicone.

AAF has a policy of continuous product research and


improvement. We reserve the right to change design
and specifications without notice.

©2023 AAF International and its affiliated companies.

AFP-CS-104E 01/24