Installation Details Firedamper
Installation Details Firedamper
2" M
AX
The angles must be attached to all 4 sides of the sleeve with WALL OR FLOOR
butt joints at each corner. A minimum of two attachments are
required on each side, top and bottom. The angles need not be
1"
attached to each other at the corners. MIN LAP
V ER
O
ING
AIN
- Retaining angles must completely cover the clearance space RET GLE
AN
between the sleeve and the wall opening, plus overlap the EVE
SLE
wall a minimum of 1".
CT
This coverage includes all corners (fig. 2). DU
one leg inserted into the wall opening providing the required 6" M
AX
clearance is maintained between angle leg fasteners and the
2" M
wall / opening. AX
SSIF
LA IE INSTALLATION INSTRUCTIONS
D
C
UL R
IN CONFORMANCE TO
UNDERWRITERS LABORATORIES
REQUIREMENTS
BLADES FIRE
IN WALL DUCT
AIR STREAM
NOTES:
TOP 1. Sleeves shall be of the same gauge or heavier than the duct to which it attached. Gauge
BIDIRECTIONAL shall conform to SMACNA or ASHRAE standards.
Downstream
AIR FLOW 2. When the following sleeve connections are used, the minimum gauge of the sleeve shall
side of FIRE be 16 gauge on dampers not exceeding 36" W x 24" H and 14 gauge on larger dampers.
damper DAMPER a. Angle reinforced standing seam.
b. Angle reinforced pocket lock.
Optional
c. Companion angles.
Jack shaft
d. Metal fasteners approximately 16" on centers.
Locations
SSIF
LA IE INSTALLATION INSTRUCTIONS
MAXIMUM DAMPER SIZES RS -100
UL
D
C
IN CONFORMANCE TO
UNDERWRITERS LABORATORIES TYPE SINGLE UNITS IN INCHES 165° F is standard rating
R
REQUIREMENTS INSTALLATION Height Width
VERTICAL 36 36 *When used, Fusible link
VERTICAL 48 30
located in pin grooves.
HORIZONTAL 36 36
BLADES FIRE
IN WALL DUCT
AIR STREAM
TOP KBE rapid mounting angles (for use on one sided angle installations).
BIDIRECTIONAL These instructions apply to 1-1/2hrs rated dynamic multi-blades fire damper model:
AIR FLOW
Downstream KFD-555 mounted in masonary, block or metal stud, walls and floors.
side of FIRE Angles shall be minimumof 1-1/2" x 1-1/2" x 16 gauge for opening in metal stud
damper DAMPER
andconcrete / masonary walls and floors of 36"x36" and less.
Optional Mounting angles are only required on one side of wall or top of the floor. They must
Jack shaft be attached to both the sleeve and the wall.Mounting angles may be installed directly
Locations
to the metal stud under wall board on metalinstallations only.
Sizes larger will require the previous retaining angle design which consisted of 4
seperate angle per side.
DUCT
For one sided KBE rapid mounting angle installations, the sleeve fastners shall be
No#10 sheet metal screws spaced 3" from each end and no greater than 12" on
SLEEVE
FIRE center.With a minimum of two (2) fastners on each side, top and bottom wall/floor
WALL fasteners shall be No#10 sheet metal screw 2" long. Two screws on each side angle
spaced 3inches from each end, Three screws on each head and sill angles with one
VERTICAL INSTALLATION screw in the center and one at each end spaced 3 inches from the ends. Screw
fasteners used in metal stud must engage the metal stud a minimum of 1/2".
Screw fastner used in masonary walls or floors must engage the wall or floor a
EXPANSION AREA minimum of 2".
"S" TYPE
DUCT SLIP JOINTS Angles should verlap the partition a minimum of 1" around the entire opening.
**Refer to notes on page (2) for duct connection to fire damper and expansion
clearance
SLEEVE
FIRE FIRE
WALL DAMPER
MOUNTING
ANGLES
DUCT
HORIZONTAL INSTALLATION
KBE Rapid mounting angle MUST
be installed on top of floor
UL
D
C
IN CONFORMANCE TO
UNDERWRITERS LABORATORIES INSTALLATION Height Width
R
REQUIREMENTS VERTICAL 36 36
HORIZONTAL 36 36
UL
D
C
IN CONFORMANCE TO
INSTALLATION 165° F is standard rating
UNDERWRITERS LABORATORIES Width Height
R
REQUIREMENTS
VERTICAL 72 72
NOTES:
1. Sleeves shall be of 16Ga (1.5mm) or heavier than the duct to which it attached. Gauge shall
conform to SMACNA or ASHRAE standards.
RESET TABLE 2. Fire dampers assembly must be attached to sleeves on all four sides & must be attached to the
LINK
sleeve with one row of attachments on each side of the blade channel. Attachments must be
spaced a maximum of 5" (127mm) on centers and a maximum of 2" (50mm) from corners. The
14Ga x 5”
Mullion
Sleeve will attached by 5mm Steel Pop Rivet or self-piercing rivet or Welds 1/2” (13mm) min
ACTUATOR
FIRE plate Long.
DAMPER 3. Fire damper and sleeve assemblies must be installed in wall using retaining angles on each side
of the wall. Retaining angles must be attached to the sleeve using No.10 sheet metal screws or
1/4”(6mm) bolts and nuts.
4. When the following sleeve connections are used, the minimum gauge of the sleeve shall be 14
gauge.
DUCT a. Angle reinforced standing seam. c. Companion angles.
b. Angle reinforced pocket lock. d. Metal fasteners approximately 16" on centers.
SLEEVE
FIRE MOUNTING 5. The following breakaway sleeve connections may be used on all systems:
WALL ANGLES
a. Plain "S" slip b. Hemmed "S" slip c. Bar slip
d. Standing "S" slip e. Reinforced bar slip f. Angle slip
VERTICAL INSTALLATION g. Inside slip joint h. Double "S" slip
6. Clearance for expansion of 1/8" per foot (10mm per meter) of sleeve dimension is required.
MAXIMUM MULTIPLE SECTIONS Angles should lap Wall a minimum of 1”(25mm) around the entire opening.
7. The connecting ducts shall not be continuous, but shall terminate at the sleeve or frame.
TYPE 8. An ACCESS DOOR is a NFPA requirement for damper inspection and testing.
INSTALLATION Width Height 9. Maximum sleeve extension is 16" (401mm) on access door or actuator side of wall opening.
10. Maximum sleeve extension is 6" (152mm) on side of wall opening for dampers without
VERTICAL 120 72 access door or actuator.
11. Dampers are supplied with factory mounted actuators designed to close automatically upon
Single Section 30”x36” X 8 sections
detecting heat, or the loss of actuator power.
12.CAUTION : THE HEAVY DAMPER CLOSURE SPRING IS UNDER LOAD When damper
RS -100
is order with Fusible link.
165° F is standard rating (Standard) 13. A continuous bead of Nuflex 302, Dow Corning RTV-732, Dow Corning 999A, or GE-1200
silicone rubber sealant shall be applied between the damper and the sleeve for its entire profile on
one side of the installation as a minimum.
SSIF
LA IE
14. Installed damper units require operational checks upon completion to insure proper function-
INSTALLATION INSTRUCTIONS ing.
UL
D
C
IN CONFORMANCE TO
15. Factory mounted electrical actuator are supplied with the following voltage: 24VAC, 120VAC
UNDERWRITERS LABORATORIES
R
REQUIREMENTS & 220VAC. All wiring and connection shall conform to NEC or local electrical code.
120"
MAX WIDTH Actuator
ANGLES
30"W x 36"H
MAXIMUM Actuator
SINGLE
SECTION
REFER TO ANNEXURE - A
For actuator Details Wiring & Assembly DAMPER FRAME TO DAMPER FRAME ASSEMBLY
1/4" BOLTS AND NUTS ON 5.5 to 6" CENTERS MAXIMUM.
ANNEXURE --A
Actuator
Actuator
RS100
Actuator Actuator
RS100 or RS200
Actuator Actuator
Actuator Actuator
Neutral
Line
N
L
6. INSTALLING MULTIPLE FIRE SMOKE DAMPER SECTION ASSEMBLIES FOR VERTICAL Mount
A damper assembly is restricted to 8 maximum number of sections, but must not exceed the section sizes and overall sizes
120x72in. (reference Support Mullions for assemblies larger than the Maximum Overall Sizes shown).
Two section high dampers require reinforcement using a14 gauge, 5 in. wide mullion as shown in Figure 1 below. Dampers ordered
for individual installation may not be installed together. The full assembly size must be specified at the time the dampers are
ordered.