LS-5 Series: 2breaker
LS-5 Series: 2breaker
37665
LS-5 Series V2
LS-512/522
2breaker
Multi-Breaker
Control for Designed as a compact
solution for complex power
complex power management applications management applications
Control up to 32 breakers on
DESCRIPTION up to 32 bus segments in an
application
Woodward’s LS-5 Series are synchronizer controllers with integrated mains decoupling and protec-
tion features. The applications range from independent synch check relay to complex power man- Purpose built application
agement relay with multiple utility feeds, bus tie breakers and group breakers in combination with modes
Woodward’s easYgen-3400XT/3500XT equipped genset controllers. Wiring efforts are reduced to
a minimum, since only one CAN bus connection is required between all LS-5 and easYgen control- Synch check and mains
lers to transmit AC measurement signals, I/O states, flags etc. decoupling in one compact
controller
The LS-5x2 relays simplify the applications where load bus is served by a mains circuit breaker
(MCB) and a generator group breaker (GGB). It senses voltage and current, quantifies the syn- Utility import/export control
chronization parameters and transmits the signals via CAN bus to the easYgen-3400XT/3500XT
genset controllers. The two breakers control capability along with mains decoupling and protection Accepts utility approved
features make it a perfect choice for transfer switch control under guidance of an external supervi- power measurement for
sory control. The LS-5x2 is software selectable to be applied as an LS-5x1 thereby facilitating hard-
loading/unloading
ware standardization to OEM switchgear builders, generator packagers, and system integrators.
The LS-5x2 Series is available in two different mounting styles. An LS-522 with a plastic housing
Automatic and Manual mode
and graphic LCD display is designed to be mounted on the cabinet’s front door. An LS-512 with an LS-5 “Stand alone” mode for
aluminum powder coated housing without display is designed to be back panel mounted.
use without easYgen-
FEATURES 3400XT/3500XT System
LogicsManager functionality
Up to 16 LS-5x2 relays can be operated in one network with up to 32 easYgen-3400XT/3500XT for application customization
Remotely selectable breaker transition modes: Open, Closed (short parallel <100ms), Inter-
change, Indefinite parallel Adjustable vector groups for
Software selectable to function as one breaker control synchronization
Internal power calculation with option to feed active power from external transducer
Phase match or slip frequency synchronization with voltage matching CAN and RS-485 interfaces for
Full protection package (including df/dt (ROCOF), phase shift, and mains voltage increasing remote control and
protection according to new German grid code) visualization
Segment control for the load sharing
Event Log with up to 300 entries True RMS sensing
Automatic date and time synchronization between the LS-5 units and the connected easYgen-
3400XT/3500XT controls Available as cabinet front door
LS-5 “Stand alone” mode without the easYgen-3400XT/3500XT is possible mounted or DIN-Rail back
Preconfigured application modes that simplify the configuration process for complex multi- panel mounted
breaker applications rugged metal housing
AUTOmatic and MANual mode
Full remote control via CAN or RS-485 interface Freely configurable relay
Breaker open/close failure detection outputs
Mains decoupling “Test” mode
Lock keypad feature Freely configurable discrete
4 freely configurable alarms inputs
8 Freely configurable LED`s on the LS-512 back panel mountable device
Multilingual capability: English, German, Spanish, French, Italian, Portuguese, Japanese, RoHS2, BDEW and VDE AR-N
Chinese, Russian, Turkish, Polish 4105 compliant
SPECIFICATIONS
Power supply.......................................................... 12/24 Vdc (8 to 40 Vdc) Analog input (isolated) ...........................................................freely scalable
Intrinsic consumption .................................................. max.~ 5 W (LS-511) Type ............................................................................................. 4 to 20 mA
................................................................................... max..~ 6 W (LS-521) Resolution .............................................................................................. 11 Bit
Ambient temperature (operation) ....................... -20 to 70 °C / -4 to 158 °F Maximum permissible voltage between genset Ground & PE .............. 100 V
Ambient temperature (storage) ........................ -30 to 80 °C / -22 to 176 °F Internal load ........................................................................................... 50 Ω
Ambient humidity...................................................... 95 %, non-condensing Accuracy ............................................................................................. Class 1
Voltage ...............................................................................................( /) Relay outputs ............................................................................ potential free
120 Vac [1] Rated (Vrated) ............................................69/120 Vac Contact material ................................................................................... AgCdO
Max. value (Vmax) ............................................86/150 Vac Load (GP) ............................................................... AC: 2.00 Aac@250 Vac
Rated voltage phase – ground ............................150 Vac DC: 2.00 Adc@24 Vdc / 0.36 Adc@125 Vdc / 0.18 Adc@250 Vdc
Surge volt.(Vsurge) ....................................................2.5 kV Pilot duty (PD) ................................................................................. AC: B300
and 480 Vac [4] Rated (Vrated) ..........................................277/480 Vac DC: 1.00 Adc@24 Vdc / 0.22 Adc@125 Vdc / 0.10 Adc@250 Vdc
Max. value (Vmax) ..........................................346/600 Vac Housing (LS-522) Front door mounting ............................. Plastic housing
Rated voltage phase – ground ............................300 Vac Dimensions WxHxD .......................................... 219 × 171 × 61 mm
Surge volt.(Vsurge) ....................................................4.0 kV Front cutout WxH ............................... 186 [+1.1] × 138 [+1.0] mm
Accuracy .......................................................................................... Class 1 Connection ....................................................... screw/plug terminals 2.5 mm²
Linear measuring range .............................................................. 1.25×Vrated Front.................................................................................... insulating surface
Measuring frequency............................................... 50/60 Hz (30 to 85 Hz) Sealing Front .................................. IP66 (with screw fastening)
High Impedance Input; Resistance per path ....... [1] 0.498 M, [4] 2.0 M Front .................................. IP54 (with clamp fastening)
Current (Isolated) .......................... System A/B: 3/1phase Back ...................................................................... IP20
Rated (Irated) ............................................................... [1] ../1 A or [5] ../5 A Weight ........................................................................................approx. 850 g
Linear measuring range ........................................................ Igen = 1.5×Irated Housing (LS-512) Back panel mounting....................Sheet metal housing
Burden .......................................................................................... < 0.15 VA Dimensions WxHxD .......................................... 190 × 167 × 47 mm
Rated short-time current (1 s) .................................[1] 50×Irated, [5] 10×Irated Connection ....................................................... screw/plug terminals 2.5 mm²
Discrete inputs .............................................................................. isolated Protection system ................................................................................... IP 20
Input range ............................................................. 12/24 Vdc (8 to 40 Vdc) Weight (plastic/sheet metal) .............................................. approx. 850/840 g
Input resistance .............................................................. approx. 20 kOhms Disturbance test (CE) ............ tested according to applicable EN guidelines
Listings ..................................... CE, UL/cUL, BDEW, VDE AR-N 4105, EAC
Marine ............................................................................. Pending: LR, ABS
DIMENSIONS
Plastic housing for front panel mounting Metal housing for cabinet mounting
TERMINAL DIAGRAM
EXAMPLE APPLICATION
FEATURES OVERVIEW
CONTACT LS-512 LS-522
I/Os
North & Central America Display No Yes
Tel.: +1 970 962 7331 Configurable LEDs on Faceplate Yes No
[email protected] System A/B voltage measurement 3-Phases + Neutral 3-Phases + Neutral
System A/B current measurement 3-Phase / 1-Phase 3-Phase / 1-Phase
South America Discrete inputs 8 8
Tel.: +55 19 3708 4800 Relay outputs 6 6
[email protected] 0/4-20mA Input (Optional power system A/B) 1 1
CAN Interface 1 1
Europe RS-485 Interface 1 1
Tel. Stuttgart: +49 711 78954 510 Control
Tel. Kempen: +49 2152 145 331 Automatic and Manual operating modes
[email protected] Breaker synchronization ( +/- slip frequency / phase
matching)
Middle East & Africa Vector group adjustment for synchronization
Tel.: +971 4 430 8744 Configurable dead bus closure direction
HMI
[email protected]
Configuration via HMI and PC
Event recorder with real time clock (battery backup)
Russia
Date and Time Synchronization between LS-5 units
Tel.: +49 711 78954 515 and easYgen-3400XT/3500XT
[email protected]
Protection
Over-/undervoltage (59/27)
China Over-/underfrequency (81O/U)
Tel.: +86 512 8818 5515 Voltage asymmetry (47)
[email protected] Phase shift (78)
df/dt (ROCOF) (81)
India QV monitoring
Tel.: +91 124 4399 500 Time-dependent voltage
[email protected] Mains voltage increase (accord. to VDE-AR-N-4105)
Monitoring
ASEAN & Oceania Breaker open/close monitoring
Tel.: +49 711 78954 510 Synchronization time out monitoring
[email protected] Voltage Plausibility
Freely configurable alarms 4 4
www.woodward.com Counter
Circuit breaker closure counter
Subject to alterations, errors excepted.
Energy Counters
Subject to technical modifications. Listings/Approvals
UL / cUL / EAC / CE Marked
This document is distributed for informa-
tional purposes only. It is not to be con- Pending: LR & ABS Marine
strued as creating or becoming part of Part Numbers Metal housing Plastic housing with display
any Woodward Company contractual or LS-512 (1A / 5A) 8440-2181 / 8440-2153 ---
warranty obligation unless expressly LS-522 (1A / 5A) --- 8440-2179 / 8440-2151
stated in a written sales contract.
DIN-Rail mounting Kit for LS-511 8923-1746 ---
We appreciate your comments about the DPC-RS-232 direct configuration cable 5417-557
content of our publications. Please send DPC-USB direct configuration cable 5417-1251
comments including the document num- Spare parts: Plug set containing all terminal plugs 8928-7544 8928-7545
ber below to
[email protected]
37665 - 2017/06/Stuttgart