Technical Data for OPEN - CLOSE Duty
Technical Data SA 3 - SA 100
OPEN-CLOSE Duty
Torque Range1) Running Handwheel Weight (without epac unit)4)
Output Valve Attachment Stem Dia. Permissible Hand-
S2-15min Ratio approx.
Speed Torque2) O/P drive Thrust for wheel
Model
at 50Hz S2-15min Type A Type A Dia. Std.
rpm Nm Standard Option Max. mm Max. kN mm With
Min.Nm Max.Nm
DIN:3210 ISO:5210
Std. Std. kg With TBG* kg
TBG*
11
16
22
32
SA 3 45 20 30 11 G0 F 10 26 25 250 1:1 2:1 33 39
63
90
1253)
1803)
SA 3.5 16 20 35 11.5 G0 F 10 26 25 250 1:1 2:1 33 39
4
5.6
8
11
16
22
SA 6 20 60 21 G0 F 10 26 40 250 1:1 2:1 33 39
32
45
63
90
1253)
20 55
1803)
4
5.6
8
11
16
22
SA 12 40 120 42 G0 F 10 38 60 250 1:1 2:1 33 39
32
45
63
90
1253)
40 110
1803)
4
5.6
8
11
SA 15 16 50 150 53 G0 F 10 38 60 250 1:1 2:1 33 39
22
32
45
63
4
5.6
8
11
16
22
SA 25 100 250 88 G ½ F 14 52 120 360 1:1 3:1 71 87
32
45
63
90
1253)
100 220
1803)
1) Tripping torque adjustable for both direction.
2) Permissible average torque for the whole travel.
3) Non Self locking.
4) The approximate weight of an epac unit is 16 Kg.
We reserve the right to alter data according to improvements made. Previous data sheets become invalid with the issue of this data sheet.
30
Technical Data for OPEN - CLOSE Duty
Technical Data SA 3 - SA 100
OPEN-CLOSE Duty
. 1)
Handwheel
Output Torque Range Running Valve Attachment Stem Dia. Permissible Hand- Weight (without epac unit)4)
S2-15Min. Ratio approx.
Speed Torque2) O/P drive Thrust for wheel
Model
at 50Hz S2-15min Type A Type A Dia. Std.
rpm Min.Nm Max.Nm Standard Option With
Nm Max. mm Max. kN mm Std. Std. kg With TBG* kg
DIN:3210 ISO:5210 TBG*
4
5.6
8
11
16
22
SA 30 100 300 105 G ½ F 14 52 120 360 1:1 3:1 71 87
32
45
63
90
1253)
100 264
1803)
4
5.6
8
11
16
22
SA 50 200 500 175 G ½ F 14 52 160 640 1:1 3:1 99 116
32
45
63
90
1253)
200 450
1803)
4
5.6
8
11
16
22
SA 60 200 600 210 G ½ F 14 52 160 640 1:1 3:1 99 116
32
45
63
90
1253)
200 540
1803)
4
5.6
8
11
16
22 1000
SA 100 400 350 G3 F 16 65 190 800 1:1 4:1 131 152
32
45
63
90
1253)
400 900
1803)
Enclosure: IP68 - IS:13947 (Part I) :1993, Appendix C / IEC 60947 - I : 2004.
Actuators are rated for short time duty S2-15 min, based on 40°C ambient temperature. The nominal current is based on running torque
approximately 35% of max. torque. The max. torque can be utilised for a short time (e.g. to seat or unseat a valve) and the current can rise
to max. value, refer corresponding column for current at max. torque in Electrical Data.
Note : Revolution for Full Stroke (Min./Max.) - 1 - 480 or 1 - 4800
* - Top Bevel Gear Set.
We reserve the right to alter data according to improvements made. Previous data sheets become invalid with the issue of this data sheet.
31
Technical Data for Regulating Duty
Technical Data SAR 3 - SAR 100
Regulating duty
Torque Hand- Handwheel Weight (without epac
Output Modulating Number Stem Dia. Permissible
Range1) S4- Valve Attachment wheel unit)4)
Speed Torque2) of starts O/P drive Thrust for Ratio
Model 25% Dia. approx.
at 50Hz S4-25% max. Type A Type A
Standard Std. With Std.
rpm Min.Nm Max.Nm Nm Option ISO:5210 c/h Max.mm Max. kN Std. With TBG* kg
DIN:3210 mm TBG* kg
11
16
SAR 3 22 20 30 20 G0 F 10 1200 26 25 250 1:1 2:1 33 39
32
45
4
5.6
8
SAR 6 11 30 60 30 G0 F 10 1200 26 40 250 1:1 2:1 33 39
16
22
32
45
4
5.6
8
11 1200
SAR 12 60 120 60 G0 F 10 38 60 250 1:1 2:1 33 39
16
22
32
45 900
4
5.6
8
SAR 15 11 60 150 75 G0 F 10 1200 38 60 250 1:1 2:1 33 39
16
22
32
4
5.6
8
SAR 25 11 120 250 125 G ½ F 14 1200 52 120 360 1:1 3:1 71 87
16
22 900
32 600
45
4
5.6
8
SAR 30 11 150 300 150 G ½ F 14 1200 52 120 360 1:1 3:1 71 87
16
22
32 600
45
4
5.6 1200
8
SAR 50 11 250 500 250 G ½ F 14 900 52 160 640 1:1 3:1 99 116
16
22 600
32
45
4
5.6 1200
8
SAR 60 300 600 300 G ½ F 14 52 160 640 1:1 3:1 99 116
16
22 600
32
4 1200
5.6 900
8
SAR 100 11 500 1000 500 G3 F 16 600 65 190 800 1:1 4:1 131 152
16
22
32
45
1) Tripping torque adjustable for both direction.
2) Permissible average torque for the whole travel.
3) The approximate weight of an epac unit is 16 kg.
Encloser: IP68 - IS:13947 (Part I) : 1993, Appendix C / IEC 60947 - I : 2004
Actuators are rated for intermittent duty S4-25% ED, based on 40° C ambient temperature. The nominal current is based on modulating
torque of approximately 35% of max. torque. The max. torque can be utilised for a short time (e.g. to seat or unseat a valve ) and the current
can raise to max. value, refer corresponding column for current at max. torque in Electrical Data.
We reserve the right to alter data according to improvements made. Previous data sheets become invalid with the issue of this data sheet.
34