AD485-3 Interface Expansion Module User Manual
AD485-3 Interface Expansion Module
Software Version
No. Version Date Note
1 V1.0 2022-02-20 Original release.
Chongqing Mebay Technology Co.,Ltd
Add: No6-2,Building 4, Gangan Rd, Jiangbei District, Chongqing.
Tel:+86-23-6869 3061
Fax:+86-23-6765 8207
Web:http://www.mebay.cn
http://www.cqmb.cn
E_mail:
[email protected] 2
AD485-3 Interface Expansion Module
Symbol Description
Symbol Description
Remind operators to operate correctly, otherwise it may cause
the equipment not to work correctly.
Note
It is indicated that potential hazards can damage equipment
without proper precautions.
Be care
It is indicated if appropriate preventive measures are not taken,
potentially dangerous situations may result in death, serious
Warning personal injury or significant property losses.
3
AD485-3 Interface Expansion Module
Warning
1.The installation of this equipment must be carried out by professionals.
2.When installing and operating the controller, please read the entire instruction
manual first.
3.Any maintenance and commissioning of the equipment must be familiar with all the
equipment.
4.Safety standards and precautions in advance, otherwise it may cause personal
injury or damage to related equipment.
5.After the installation of the controller is completed, please verify that all protection
functions are valid.
Be Care
1.Please keep the good connection of the power supply of the controller. Do not
share the connection lines of the positive and negative electrodes of the battery
with the floating charger.
2.During the operation of the engine, do not disconnect the battery, otherwise it may
cause damage to the controller.
4
AD485-3 Interface Expansion Module
Catalogue
Summary ......................................................................................................................6
Main Features .............................................................................................................. 6
Parameters .................................................................................................................. 6
Overall Dimension and Wiring Diagram ....................................................................... 7
Installation instruction ................................................................................................ 10
Notes:
1. All rights reserved. No part of this duplication may be reproduced in any material
form (including photocopying or storing in any medium by electronic means or others)
without the written permission of the copyright holder.
2. MEBAY Technology reserves the rights to change the contents of this document
without prior notice.
5
AD485-3 Interface Expansion Module
Summary
AD485-3 is the expansion module of RS485 interface, which has 3 interfaces,
namely RS485 hostinterface, RS485 slave 1 interface, RS485 slave 2 interface. It
can convert 1# RS485 interface to 2# RS485 interface, providing convenience for
customers to monitor and collect data via Modbus-RTU protocol.
Main Features
Dual core 32bit high performance single chip microcomputer.
With three RS485 interfaces;
35mm guide rail installation method;
DC(8~36)V continuous power supply;
Module design: All the connections are adapted with European connectors so that
installation, connection, repair and replacement can be more easily.
Parameters
Options Parameters
Working voltage DC 8V----36V Continuous
Power consumption Working:MAX 1W (Standby:MAX 0.5W)
Use shielded 120Ω twisted pair
Stop bit: 1-bit Parity bit: None
RS485 interface
RS485 slave interface supports host computer settings
(baud rate, communication address)
Working condition -40-70℃
Storage condition -40-80℃
Protection Level IP20
Overall dimension 88mm*37mm*63mm
Weight 0.15Kg
6
AD485-3 Interface Expansion Module
Overall Dimension and Wiring Diagram
Overall Dimension:
7
AD485-3 Interface Expansion Module
Descriptions of terminal connection
No. Indicator Description
1 Power Power indicator, always on when powered on.
RS485 RS485 (HOST) communication indicator; Red to send, green
2
(HOST) to receive; it flashes 500ms whensending or receiving data.
RS485 (SLAVE-1) communication indicator; Red to send,
RS485
3 green to receive; it flashes 500ms whensending or receiving
(SLAVE-1)
data.
RS485 (SLAVE-2) communication indicator; Red to send,
RS485
4 green to receive; it flashes 500ms whensending or receiving
(SLAVE-2)
data.
Cable cross
No. Function Description
sectional area
1 Battery Negative Input B- Controller power supply input B-. 1.0mm2
2 Battery Negative Input B+ Controller power supply input B+. 1.0mm2
3
4 RS485 A RS485 communication interface : A 120 Ω 1.0mm2
RS485
5 RS485 B shielded wire and good grounding are 1.0mm2
HOST
6 RS485 SCR recommended. 1.0mm2
7 RS485 RS485 A RS485 slave interface communicates with PC 1.0mm2
8
AD485-3 Interface Expansion Module
8 SLAVE-1 RS485 B monitoring interface, SCR can be short 1.0mm2
connected with A(+), which is equivalent to
9 RS485 SCR connecting 120Ωmatching resistor between 1.0mm
2
10 RS485 A A(+) and B(-). 1.0mm2
RS485
11 RS485 B 1.0mm2
SLAVE-12
12 RS485 SCR 1.0mm2
AD485-3 Typical Wiring Diagram
Monitoring Monitoring
Interface Interface
SCR
SCR
A+
A+
B-
B-
7 8 9 10 11 12
RS485 SLAVE 1 RS485 SLAVE 2
MODE: AD485-3
8-36V RS485 HOST
1 2 3 4 5 6
B- B+
SCR
A+
B-
BATTERY
Controller
BATTERY NEGATIVE MUST BE GROUNDED
9
AD485-3 Interface Expansion Module
Installation instruction
10