CCG A2F FITTING INSTRUCTIONS FOR CCG A2F EExde CABLE GLAND
EExde IIC compression gland 1. Make sure gasket ➀ is in place.
NOTE:
Check correct gland size. Use orange thread
cap-safety gauge. If cable bedding passes
➀
for FLEXIBLE CABLE through hole in end cap, use a gland one
size smaller.
2. Screw gland unit into apparatus and tighten gland inner ➁.
3. Pass cable end through gland assembly.
4. Tighten outer nut ➂ to produce a seal and grip on the cable.
➂
Safe and Simple
For more detailed fitting instructions please refer to product packaging
G 220606 Tel: South Africa +27 11 394-2020, Australia (Perth) +61 8 9 3012100, (Brisbane) +61 7 33499880, HongKong +852 34272090
Singapore +65 6 842 1002, UK +44 1 14 243 4500
®
A2F EExde compression gland
Technical Data
Type A2F
Gland Material Brass (Nickel Plated)
Seal Material Thermoplastic Elastomer (Silicone on request)
Cable Type Unarmoured
N Sealing Area Outer sheath
A
Optional Accessories Locknut, Shroud, Earth Tag, Adaptor / Reducer
Standards and Certifications
Hazardous Area Classification
CENELEC / ATEX Category 2, Category 3, EExde IIC 2 GD
L C Compliance Code Certification No.
CENELEC / ATEX
EN60079-0 2004 EPSILON 06 ATEX 2066X
Gland Entry Thread Cable Details Maximum Hexagonal EN60079-1 2004 EPSILON 06 ATEX 2066X
Product Length
Size Length Details (Max)
Code Diameter Min-Max
Reference ‘N’ ’L‘ ’A‘ ’C‘ ’Flats‘ ’Crns‘
054116 00-16ss M16 15 13.0-8.0 25 24 27
054100 *00-20ss M20-1/2/3/4 15 3.0-8.0 25 24 27
0541-0 *0-20s M20-1/2/3/4 15 7.0-11.0 35 24 27
054101 *1-20 M20-1/2/3/4 15 11.0-15.5 25 27 31
054102 *2-25 M25-3/4 /1 15 15.0-20.5 30 35 40
054103 *3-32 M32-1/11/4 15 20.0-26.5 25 42 48
054104 4-40 M40-11/4 /11/2 15 26.0-34.5 30 52 60
054105 5-50 M50-11/2/2 15 34.0-44.5 38 65 75
054106 6-63 M63-2/21/2 15 44.0-57.0 43 82 94
054107 7-75 M75-21/2/3 15 56.0-68.0 50 96 110
054108 8-80 M80-3 20 65.0-74.0 54 96 110
054109 9-90 M90-3/31/2 20 73.0-82.0 70 110 125
054110 10-100 M100-31/2/4 20 81.0-92.0 70 125 142
054111 11-110 M110-4 20 91.0-102.0 70 135 153
*All dimensions are in mm.
*For use with Posi-Fit boxes. † Dimensions may differ from published table.
Features and Benefits Ingress Protection IP 66/67/68
• For indoor/outdoor use and hazardous areas. Operating Temperature -30˚C to +130˚C
• Fitted with specially formulated elastomeric displacement seal, giving superior cable retention,
explosion protection and IP rating. Special Conditions for Safe Use - X
• Manufactured from high quality brass and nickel plated. Glands must be used as part of a certified assembly in surface installations only
• Supplied with a polypropylene or neoprene sealing gasket. Not for use on Exd enclosures that are larger than 2000cm3 volume in group IIC gases in zone 1 areas