Parameter settings of the AC motor drive (VFD-S)

Description of Digital Keypad


This digital keypad includes two parts: Display panel and keypad. Display panel provides the parameter
display and shows operation status of the AC drive. Keypad provides programming interface between
users and AC drives.
KEY Description
RUN Key Start inverter drive operation
STOP/RESET Key Stop inverter drive operation and reset the inverter after faults
occurred
PROG/DATA Key Set the different parameters and enter information. Mode
UP and DOWN Key Sets the parameter or changes the numerical data such as the
freq. reference
MODE key Key Change between different display number modes.

@: The parameter can be set during operation,*: Twice the value for 460V class.

Parameters Explanation Settings Factory Copower

Setting Setting

Group 0: User Parameters

0-00 Identity Code of AC Drive Read-only d#

0-01 Rated Current Display Read-only d##.#

0-02 Parameter Reset d10: Reset Parameter to Factory


d0
Setting

0-03 Start-up Display Selection @ d0: F (setting frequency)

d1: H (actual frequency)


d0 d1
d2: (user-defined unit)

d3: A (output current)

0-04 User-Defined Unit @ d0: Display User-Defined Unit (u)

d1: Display Counter Value (C)

d2: Display Process Operation (1= tt)

d3: Display DC-BUS Voltage (U)

d4: Display output voltage (E) d0

d5: Display frequency commands of

PID (P)

d6: Display PID feedback (after

multiplying by Gain) (b)

0-05 User-Defined Coefficient K @ d0.1 to d160 d1.0


0-06 Software Version Read-only d#.#

0-07 Password Input d0 to d999 d0

0-08 Password Decode d0 to d999 d0

Group 1 Basic Parameters

1-00 Maximum Output Freq. d50.0 to d400 Hz d60.0

1-01 Maximum Voltage Frequency d10.0 to d400 Hz


d60.0
(Base Freq)

1-02 Maximum Output Voltage d2.0V to d255V* d230*

1-03 Mid-Point Frequency d1.0 to d400 Hz d1.0

1-04 Mid-Point Voltage d2.0V to d255V* d12*

1-05 Minimum Output Frequency d1.0 to d60.0 Hz d1.0

1-06 Minimum Output Voltage d2.0V to d255V* d12*

1-07 Upper Bound of freq. d1 to d110% d100

1-08 Lower Bound of freq. d0 to d100% d0

1-09 Acceleration Time 1 (Tacc1) @ d0.1 to d600 Sec d10.0 d0.5

1-10 Deceleration Time 1 (Tdec1) @ d0.1 to d600 Sec d10.0 d0.4

1-11 Acceleration Time 2 @ d0.1 to d600 Sec d10.0 d0.5

1-12 Deceleration Time 2 @ d0.1 to d600 Sec d10.0 d0.5

1-13 Jog Acceleration / Deceleration d0.1 to d600 Sec


d10.0
Time @

1-14 Jog Frequency @ d1.0 Hz to d400 Hz d6.0

1-15 Auto Acceleration / Deceleration d0: Linear Acceleration/Deceleration

d1: Auto Acceleration, Linear

Deceleration

d2: Linear Acceleration, Auto

Deceleration

d3: Auto Acceleration/Deceleration


d0
d4: Linear Acceleration; Auto

Deceleration, Stall Prevention during

Deceleration

d5: Auto Deceleration; Auto

Acceleration, Stall Prevention during

Deceleration

1-16 S-Curve in Acceleration d0 to d7 d0

1-17 S-Curve in Deceleration d0 to d7 d0

1-18 Jog Decelerating Time d 0.0 Jog Decelerating Time


d0.0
Determined by Pr.1-13 d 0.1 to d600

Group 2 Operation Method Parameters


2-00 Source of Frequency Command d0: Master Frequency input determined

by digital keypad. (record the frequency

of power loss and it can do analog

overlap plus)

d1: Master Frequency determined by

analog signal DC 0V-10V (external

terminal AVI). (won’t record the

frequency of power loss and it can’t do

analog overlap plus)

d2: Master Frequency determined by

analog signal DC 4mA - 20mA (external

terminal AVI). (won’t record the

frequency of power loss and it can’t do

analog overlap plus)


d3: Master Frequency determined by d0

Potentiometer on the digital keypad.

(won’t record the frequency of power

loss and it can do analog overlap plus)

d4: Master Frequency operated by

RS-485 serial communication interface

and record frequency of power loss.

(record the frequency of power loss and

it can do analog overlap plus)

d5: Master Frequency operated by

RS-485 serial communication interface

and won’t record frequency before

power loss. (won’t record the frequency

of power loss and it can do analog

overlap plus)

2-01 Source of Operation Command d0: by Digital Keypad

d1: by external terminals, keypad

STOP enabled

d2: by external terminals, keypad

STOP disabled d0 d2

d3: by RS-485 communication

interface, keypad STOP enabled

d4: by RS-485 communication


interface, keypad STOP disabled
2-02 Stop Method d0: Ramp Stop d1: Coast Stop d0

d3: 3KHz d7: 7KHz

d4: 4KHz d8: 8KHz


2-03 PWM Carrier Frequency d10
d5: 5KHz d9: 9KHz

d6: 6KHz d10: 10KHz

2-04 Reverse Operation d0: Enable REV d1: Disable REV d0

2-05 Loss of ACI Signal d0: 0 Hz, continue running

d1: Stop the frequency output d0

d2: Last ACI input command

d0: Disable
Analog Auxiliary Frequency
2-06 d1: Enable + AVI d0
Operation
d2: Enable + ACI

Group 3 Output Function Parameters

d0: analog frequency


3-00 Analog Output Signal d0
d1: analog current

3-01 Analog Output Gain @ d1 to d200% d100

3-02 Desired Freq. Attained d1.0 to d400 Hz d1.0

3-03 Terminal Count Value d0 to d999 d0

3-04 Preliminary Count Value d0 to d999 d0

Multi-Function Output1 d0: Not Used


3-05 d1
(Photo-coupler Output) d1: AC Drive Operational

d2: Max. Output Freq. Attained

d3: Zero Speed

d4: Over Torque

d5: Base-Block (B.B.)

d6: Low Voltage Detection

d7: AC Drive Operation Mode

d8: Fault Indication

d9: Desired Freq. Attained


Multi-Function Output2 (Relay
3-06 d10: PLC Program Running d8
Output)
d11: PLC Program Step Complete

d12: PLC Program Complete

d13: PLC Program Operation Pause

d14: Terminal Count Value Attained

d15: Preliminary Count Value Attained

d16: Ready State Indicator

d17: FWD command indication


d18: REV command indication
Group 4 Input Function Parameters

4-00 Potentiometer Bias Frequency @ d 0.0 to d 100.0% d0.0

Potentiometer Bias Polarity @ d0: Positive Bias


4-01 d0
d1: Negative Bias

Potentiometer Frequency Gain


4-02 d1 to d200 % d100
@

Potentiometer Reverse Motion d0: Forward Motion Only


4-03 d0
Enable d1: Reverse Motion enabled

Multi-Function Input Terminal 1 d0: Parameter Disable


4-04 d1 d2
(M0, M1) d1: FWD/STOP, REV/STOP

Multi-Function Input Terminal 2 d2: FWD/REV, RUN/STOP


4-05 d6
(M2) d3: 3-wire Operation Control Mode

Multi-Function Input Terminal 3 d4: E.F. External Fault Input (N.O.)


4-06 d7
(M3) d5: E.F. External Fault Input (N.C.)

Multi-Function Input Terminal 4 d6: Reset


4-07 d8 d0
(M4) d7: Multi-Step Speed Command 1

Multi-Function Input Terminal 5 d8: Multi-Step Speed Command 2

(M5) d9: Multi-Step Speed Command 3

d10: Jog Operation

d11: Acceleration/deceleration Speed

Inhibit

d12: First or Second

Acceleration/deceleration Time

Selection

d13: Base-Block (B.B.) (N.O.)

d14: Base-Block (B.B.) (N.C.)

d15: Increase Master Frequency


4-08 d9 d13
d16: Decrease Master Frequency

d17: Run PLC Program

d18: Pause PLC

d19: Counter Trigger Signal

d20: Counter Reset

d21: Select ACI / Deselect AVI

d22: Disable PID function

d23: JOG FWD

d24: JOG REV

d25: The source of master frequency is


AVI.
d26: The source of master frequency is

ACI.

d0: Disable
4-09 Line Start Lockout d0
d1: Enable

d0: Up/down frequency by

acceleration/deceleration time

d1: Up frequency according to constant

speed, down frequency according to

Up/down frequency command deceleration time


4-10 d3
mode d2: Up frequency according to

acceleration time, down frequency

according to constant speed

d3: Up/down frequency by constant

speed

Acceleration /Deceleration speed


4-11 d0 to d1000 Hz/sec d1
of constant up/down frequency

Group 5 Multi-Step Speed and PLC Parameters

5-00 1st Step Speed Freq. d0.0 to d400 Hz d0.0 d15

5-01 2nd Step Speed Freq. d0.0 to d400 Hz d0.0

5-02 3rd Step Speed Freq. d0.0 to d400 Hz d0.0

5-03 4th Step Speed Freq. d0.0 to d400 Hz d0.0

5-04 5th Step Speed Freq. d0.0 to d400 Hz d0.0

5-05 6th Step Speed Freq. d0.0 to d400 Hz d0.0

5-06 7th Step Speed Freq. d0.0 to d400 Hz d0.0

d0: Disable PLC Operation d1: Execute

one program cycle d2: Continuously

execute program cycles d3: Execute

one program cycle step by step d4:


5-07 PLC Mode d0
Continuously execute one program

cycle step by step d5: Disable PLC

operation, but can set direction of 1st

speed to 7th speed

5-08 PLC Forward/ Reverse Motion d0 to d255 (0: FWD 1: REV) d0

5-09 Time Duration Step 0 d0 to d65500 Sec d0

5-10 Time Duration Step 1 d0 to d65500 Sec d0

5-11 Time Duration Step 2 d0 to d65500 Sec d0

5-12 Time Duration Step 3 d0 to d65500 Sec d0

5-13 Time Duration Step 4 d0 to d65500 Sec d0


5-14 Time Duration Step 5 d0 to d65500 Sec d0

5-15 Time Duration Step 6 d0 to d65500 Sec d0

5-16 Time Duration Step 7 d0 to d65500 Sec d0

Group 6 Protection Parameters

6-00 Over-Voltage Stall Prevention d0: Disable


d1
d1: Enable

6-01 Over-Voltage Prevention Level 230V series: d350 to d410V d390

460V series: d700 to d820V d780

6-02 Over-Current Stall Prevention d20 to d150%


d130
Level

6-03 Over-Torque Detection Mode d0: Disabled

d1: Enabled during constant speed

operation and continue to run to OL1 or

OL.

d2: Enabled during Constant Speed

Operation and halted after detection d0

d3: Enabled during running and

continues before Continuous Output

Time Limit (Pr.6-05) is reached

d4: Enabled during running and halted

after Over-Torque detection

6-04 Over-Torque Detection Level d30 to d200% d150

6-05 Time setting for Over-torque d0.1 to d10.0 Sec


d.01
Detection

6-06 Electronic Thermal Overload d0 to d2


d2
Relay Selection

6-07 Electronic Thermal Characteristic d30 to d600 Sec d60

6-08 Present Fault Record d0: No Fault occurred

6-09 Third Most Recent Fault Record d1: Over Current (oc)

6-10 d2: Over Voltage (ov)

d3: Over Heat (oH)

d4: Over Load (oL)

d5: Over Load (oL1) d0

d6: External Fault (EF)

d7: Not Used

d8: Not Used

d9: Current exceed during Acceleration


(ocA)
d10: Current exceed during

Deceleration (ocd)

d11: Current exceed during Steady

State (ocn)

d12: Ground Fault (GF)

Group 7 Motor Parameters

7-00 Motor Rated Current @ d30 to d120% d85

7-01 Motor No-Load Current @ d0 to d90% d50

7-02 Torque Compensation @ d0 to d10 d01

7-03 Slip Compensation @ d0.0 to d10.0 d0.0

Group 8 Special Parameters

8-00 DC Braking Voltage Level d0 to d30% d0

8-01 DC Braking Time during Start-Up d0.0 to d60.0 Sec d0.0

8-02 DC Braking time during Stopping d0.0 to d60.0 Sec d0.0

8-03 Start-Point for DC Braking d0.0 to d400 Hz d0.0

8-03 Start-Point for DC Braking d0.0 to d400 Hz d0.0

d0: Stop Operation after Momentary

Power Loss

d1: Continues after Momentary Power

Momentary Power Loss Loss, speed search starts with Master


8-04 d0
Operation Selection Frequency

d2: Continues after Momentary Power

Loss, speed search starts with

Minimum Output Frequency

Maximum Allowable Power Loss


8-05 d0.3 to d5.0 Sec d2.0
Time

8-06 B.B. Time for Speed Search d0.3 to d5.0 Sec d0.5

Maximum Speed Search Current


8-07 d30 to d200% d150
Level

8-08 Skip Frequency 1 Upper Bound d0.0 to d400 Hz d0.0

8-09 Skip Frequency 1 Lower Bound d0.0 to d400 Hz d0.0

8-10 Skip Frequency 2 Upper Bound d0.0 to d400 Hz d0.0

8-11 Skip Frequency 2 Lower bound d0.0 to d400 Hz d0.0

8-12 Skip Frequency 3 Upper bound d0.0 to d400 Hz d0.0

8-13 Skip Frequency 3 Lower Bound d0.0 to d400 Hz d0.0

8-14 Auto Restart After Fault d0 to d10 d0

d0: AVR Function Enable


8-15 AVR Function d2
d1: AVR Function Disable
d2: AVR Function Disable when

Deceleration

8-16 Dynamic Braking Voltage d350 to d450V* d380*

8-17 DC Braking Lower Bound Limit d0.0 to d400 Hz d0.0

Group 9: Communication Parameters

9-00 Communication Address @ d1 to d254 d1

d0: Baud Rate 4800 bps

d1: Baud Rate 9600 bps


9-01 Transmission Speed @ d1
d2: Baud Rate 19200 bps

d3: Baud Rate 38400 bps

d0: Warn and Keep Operating

d1: Warn and Ramp to Stop


9-02 Transmission Fault Treatment @ d0
d2: Warn and Coast to Stop

d3: Keep Operating without Warning

d0: Disable
Modbus Communication
9-03 d1 to d20: time setting (1 sec d0
Watchdog Timer @
increment)

d0: 7,N,2 (Modbus, ASCII)

d1: 7,E,1 (Modbus, ASCII)

d2: 7,O,1 (Modbus, ASCII)

d3: 8,N,2 (Modbus, ASCII)

9-04 Communication Protocol @ d4: 8,E,1 (Modbus, ASCII) d0

d5: 8,O,1 (Modbus, ASCII)

d6: 8,N,2 (Modbus, RTU)


d7: 8,E,1 (Modbus, RTU)

d8: 8,O,1 (Modbus, RTU)


Wiring diagram of the AC motor drive (VFD-S)