0% found this document useful (0 votes)
123 views10 pages

Elins Mechatron - Examination - Electrical Automation

Elins Mechatron_ Examination _ Electrical Automation

Uploaded by

victor victor
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
123 views10 pages

Elins Mechatron - Examination - Electrical Automation

Elins Mechatron_ Examination _ Electrical Automation

Uploaded by

victor victor
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

a

h
c
e
m
sn
ile
ELINS MECHATRON Pengetahuan sebagai Pintu Gerbang Teknologi
Beranda Video Tutorial Electrical Electronica Kontak Daftar Alamat dan Website Perusahaan Pelayaran dan Pengeboran

Arsip Blog

▼ 2017 (13)
▼ Februari (8)
► Feb 18 (5)
▼ Feb 19 (3)
Music MP3
EXAMINATION : ELECTRO
Ayo bro dengerin music ini !!!
EXAMINATION : ELECTRICAL AUTOMATION
EXAMINATION : INSTRUMENTATION
0:22 / 30:02
► Juni (5)
Widget by seocips.com

Minggu, 19 Februari 2017 Translate

EXAMINATION : ELECTRICAL AUTOMATION Выбрать язык ​▼

1. PT-100 sensors are some times used with 3 or even 4 wires. What is the reason for this? name 
Higher measuring accuracy.
 message 
 Upgrade  

aaa 1 week ago


High Voltage (HV) cables are
smaller than low voltage cables for a
given power rating. Why is this so?

juj 3 months ago


12. The correct time to
synchronise is usually taken to be when
the synchroscope reaches the “5 to 12”
position and is rotating slowly clockwise.
This to allow for

Ajot 16 months ago


2. In the diagram below we want to verify the resistance of the PT100 sensor. What is the correct
calculation? After successful synchronising an
R(Pt100) = R1 - R2 incoming machine the kW and kVar
loading are respectively transferred by
the following controls:

nnn 19 months ago

A motor using a rheostat in the

3. In some cases we can see that a resistor is connected over an alarm contact (see diagram). Why
is this connection used?
To monitor the cable/wires for break.

SAIFUL ARIE

ELINS MECHATRON
Lihat profil lengkapku
Total Tayangan Halaman

1 3 1 8 0 7

Tema PT Keren Sekali. Gambar tema oleh fpm.


Diberdayakan oleh Blogger.

4. Please indicate the correct sequence of action to take place in an alarm/monitoring and safety
system.
Alarm, st.by start, slowdown. Shutdown

5. What is an A/D and a D/A converter?


A converter that converts an analogue signal to a digital signal and vice versa.

6. Which of the 3 alternatives below is giving an OR-function?


Figure 2.

7. What is an I/P Transducer?


A transducer that converts a known electric current to a pressure proportional to the current.
8. Which of the 3 alternatives given is correct for a NOT-gate?
Figure 1.

9. Which of the 3 alternatives given is correct for an AND-gate?


Figure 3.

10. When calibrating an pressure transducer we have to adjust both SPAN and ZERO. Please
indicate in which order these adjustments should be done.
First Zero adjustment and the Span adjustment. Then Zero should be rechecked.

11. In a PID controller we have possibility to change the setting of the Proportional band (P), the
Reset time (1) and the Rate time (D). Please indicate which curve shows the typical response to
change in demand if the setting of the proportional band is too wide.
Figure 1.

12. In a PID controller we have possibility to change the setting of the Proportional band (P), the
Reset time (I) and the Rate time (D). Please indicate which curve shows the typical response to
change in demand if the setting of the reset time is too fast.
Figure 3.
13. n a PID controller we have possibility to change the setting of the Proportional band (P), the Reset
time (I) and the Rate time (D). Please indicate which curve shows the typical response to change in
demand if the setting of the rate time is too short.
Figure 2.

14. Earthing of signal cables. Which of the 4 alternatives is correct for a cable for analogue signals?
Figure 1.

15. In a fresh water tank with a height of 5 meters we shall use a pressure transmitter for level
measurement. The tank has a vent-pipe leading to deck 8 meters above the top of the tank. What
pressure shall we use as a guidance when ordering the pressure transducer?
1,3 Bar.

16. In a fresh water tank we are using a pressure transmitter with a range of 0-0.5 bar / 4-20mA for
level measurement. The transmitter is for different reasons installed 30 centimeters from the bottom of
the tank, and the tank is 5 meters high. What will the output from the transmitter be when the tank is
full? (Pending no calibration is made)
18,8 mA.
17. In a fresh water tank we are using a pressure transmitter with a range of 0-0.5 bar/4-20mA for
level measurement.The transmitter is for different reasons installed 30 centimeters from the bottom of
the tank,and the tank is 5 meters high. What will the output from the transmitter be when the tank is
empty?
4 mA.

18. What is the signal we measure out from a NiCr/Ni thermocouple?


mV.

19. In connection with exhausts gas measurement with a thermocouple we are normally using an
amplifier which gives a mA-signal out. Why is this done?
The signal out from a thermocouple is mV,and can not be transferred over any longer distance without
loss of voltage, giving a very bad accuracy.

20. Which of the 4 alternatives shows a PNP transistor?


Figure 2.
21. Which of the 4 alternatives shows a NPN transistor?
Figure 3.

22. Due to the relative low resistance of a Pt 100 sensor we might have to compensate for the cable-
resistance to ensure a correct reading. Which of the 4 alternatives given is correct for the connection
of this compensation resistance.
Figure 3.

23. When the cable length from the temperature sensor to the place where we want to read the
temperature exceeds approx. 10 meters we normally have to, in case of a Pt 100, in some way
compensate for the cable resistance. Do we also have to do this if we choose to use a T802
temperature sensor?
No

24. Some equipment may be marked with the following symbol: What does that mean?
Intrinsically safe.
25. In installations of INTRINSICALLY SAFE equipment it is required that all equipment should be
separated from non-intrinsically safe equipment, and to be of a special colour. What colour is that?
Blue

26. What is this?


A zener barrier. (Positive)

27. What is a ZENER BARRIER?


A zener barrier is a unit made to obtain intrinsically safety in installations for instrumentation in
hazardous areas.

28. Can a ZENER BARRIER be installed in an hazardous area?


No, as only the output from the barrier is intrinsically safe this is not allowed.

29. What is the difference between a THERMOSTAT and a TEMPERATURE TRANSMITTER, if any?
The thermostat has one or more contacts (open or closed) depending on the temperature/setting. The
temperature transmitter converts a temperature signal to an electric signal.

30. What is the difference between a PRESSURE SWITCH and a PRESSURE TRANSMITTER, if
any?
The pressure switch has contact(s) that will change between open and closed position.The pressure
transmitter converts a pressure signal into an electric signal.

31. What is the symbol for a THYRISTOR?


Figure 2.

32. What is the definition of DEAD BAND?


The change needed in the input signal to produce a change in the output signal.
33. What is an analogous signal?
A variable electric signal.

34. What is digital signal?


A signal representing 0 = "low" and 1 = "High"

35. What is Hz the abbreviation for?


Frequency in an Alternating Current (AC)

36. P = U x I x Root of 3) x cos (fi) What is the formula for I ?


Formula 1

37. Which alternative is correct for measuring current over the load L?
Figure 3.

38. Temperature sensors may be marked Pt 100. What does it mean?


100 ohm at 0° C

39. Temperature sensors may be marked T 802. What does it mean?


802 ohm at 20° C

40. What is the most common signal from an I/P converter?


4-20mA/3-15 PSI
41. Which method is best for determining earth failure on a 24 VDC power supply?
A lamp, (0-50 mA) and a mA-meter in series.

42. Which statement is correct with regards to power supply for equipment supplied through Zener-
barriers?
The 0-voltage must always be grounded.

Diposting oleh ELINS MECHATRON di 09.54

4 komentar:

DIAC 15 Februari 2018 pukul 22.27


DIAC offers placement oriented training programs for the PROFESSIONAL & FRESHERS
Degree / Diploma Mechanical engineers, Production engineers, who are looking for the
placement in core manufacturing sector. Call @9310096831.

Balas

Unknown 23 Januari 2020 pukul 23.33

Instruments
Balas

David Sokim 22 November 2021 pukul 22.27

Thanks admin for sharing such wonderful content on this topic. Now I have got everything I
need to know. Here’s another informative content for those who want to buy Voltage Output
Pressure Transducers, Noshok gauges distributors. I personally used there services and I
really had a great experience with the kind of work they provided.
Balas

David Sokim 22 Februari 2022 pukul 23.04

This blog seems sharing interesting tips, as I was looking to buy Voltage Output Pressure
Transducers and other equipments.
Electronic Indicating Pressure Switch
Balas
Agar dapat memberikan komentar, klik tombol di bawah untuk login dengan
Blogger.

LOGIN DENGAN BLOGGER

Posting Lebih Baru Beranda Posting Lama

Langganan: Posting Komentar (Atom)

You might also like