Fire Situation
In situations where the battery is on fire, if it is safe to do so, disconnect the battery pack by turning of the
circuit breaker to shut off the power to the system. Use FM-200 or Co2 fire extinguisher for the battery
and an ABC fire extinguisher for the other parts of the system.
Under any fire situation, please evacuate the people from the building immediately before trying to
extinguish it.
Water Situation
The battery modules are not water resistant. Hence care should be taken not to get it wet. If you find the
battery completely or partially submerged in water do not try to open. Contact an authorized personnel or
Fox for further instructions.
5. Product Information
1. Mira-HV25 is a battery module, it needs to be used with Mira-BMS controller;
2. Mira-BMS is the controller of the whole system, so each system must have one Mira-BMS;
3. Our system consists of at least 2 Mira-HV25 + 1 Mira-BMS and up to 8 Mira-HV25 + 1 Mira-BMS.
5.1 Battery Module Specifications
 Specifications for Mira-HV25
 Battery module                                     Mira-HV25
 Nominal capacity (kWh)                                2.45
 Maximum charge voltage (V)                            58.8
 Discharge cut voltage (V)                             46.4
 Max. charge/discharge current (A)                   48A/48A
 Operating temperature (°C)                          -10 ~ 55
 Storage temperature (°C)                            -10 ~35
 Charge/Discharge efficiency (%)                        >95
 Ingress protection                                    IP21
 Protective class                                        I
 Cycle life                                  >4000 @25°C @80% SOH
 Available SOC range                                3%~100%
 Weight (kg)                                        30.2±1 kg
 Dimensions (L*W*H) (mm)                           440*420*122
5.2 Mira-BMS Specifications
 Specifications for Mira-BMS
 Model NO.                                            Mira-BMS
 Operating voltage range(V)                         86.4-500VDC
 Max. charge/discharge current (A)                     48A/48A
 Total voltage measurement accuracy                   ±1.0%FSR
 Total voltage measurement channel                         4
 Current measurement range                          -100A~+100A
 Communication interfaces                                 CAN
 Available SOC range                                  3%~100%
 Charge/Discharge efficiency (%)                          >95
 Operating temperature (°C)                            -10 ~ 55
 Storage temperature (°C)                               -10 ~35
 Humidity                                              5%~95%
 Weight (kg)                                           6.5±1 kg
 Dimensions (L*W*H) (mm)                             440*420*122
                                                       3
         5.3 Battery System Specifications
Specifications for Battery System
The number of        2*Mira-      3*Mira-         4*Mira-         5* Mira-      6*Mira-      7* Mira-      8* Mira-
batteries             HV25         HV25            HV25            HV25          HV25         HV25          HV25
Normal
                      102.4        153.6          204.8             256            307.2      358.4         409.6
voltage(V)
Normal capacity
                        48          48              48              48              48          48            48
(Ah)
Voltage range(V)     92.8-117.6   139.2-176.6   185.6-235.5     232.0-294.4   278.4-353.2   324.8-412.1   371.2-471.0
Recommended
charging                                                            24
current(A)
Max.
charge/discharge                                                    48
current (A)
CC-CV charging
                                                                     3
cut-off current(A)
Peak charge
                                                                    60
current(A)(30s)
Peak discharge
                                                                    60
current(A)
Operating                                                   Charge: 0°C ~55°C
temperature (°C)                                          Discharge: -10°C ~55°C
Storage
                                                                -10°C ~35°C
temperature (°C)
Cycle life                                            ≥4000 @25°C @ 80%SOH
Ingress
                                                                   IP21
protection
Protective class                                                     I
Communication
                                                                   CAN
interfaces
Altitude [m]                                                       <2000
Pollution degree                                                    PD2
                     66.7±1kg      94.8±1kg     123.0±1kg        151.1±1kg    179.2±1kg     207.3±1kg     235.5±1kg
                       (Net)         (Net)        (Net)             (Net)       (Net)         (Net)         (Net)
Weight (kg)
                     73.5±1kg     104.1±1 kg    134.6±1 kg       165.1±1kg    195.7±1 kg    226.2±1 kg    256.7±1 kg
                      (Gross)       (Gross)      (Gross)          (Gross)      (Gross)       (Gross)       (Gross)