Product datasheet

Specifications

motor circuit breaker GV3-ME -


40..63 A - screw clamp terminal -
thermomagnetic
GV3ME63

notification_critical_stroke Discontinued on: 27 Feb 2012

notification_critical_stroke Discontinued

Main
Range TeSys

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Name TeSys GV3

Product Or Component Type Circuit breaker

Device Short Name thermal magnetic circuit breaker

Device Application Motor

Poles Description 3P

Network Type AC

Control Type Push-button

Motor Power Kw 22 kW at 400...415 V AC 50/60 Hz


30 kW at 400...415 V AC 50/60 Hz
30 kW at 500 V AC 50/60 Hz
37 kW at 500 V AC 50/60 Hz
37 kW at 660...690 V AC 50/60 Hz
45 kW at 660...690 V AC 50/60 Hz

Trip Unit Technology Thermal-magnetic

Utilisation Category Category A conforming to IEC 60947-2


AC-3 conforming to IEC 60947-4-1

Connections - Terminals Power circuit: screw clamp terminal 1 cable(s) 2.5…35 mm²solid
Power circuit: screw clamp terminal 1 cable(s) 2.5 mm²flexible without cable end
Power circuit: screw clamp terminal 2 cable(s) 16 mm²flexible with cable end

Complementary
Network Frequency 50/60 Hz

Mounting Mode Fixed

Mounting Support Plate


Rail

Mounting Position Vertical


Horizontal

Thermal Protection Adjustment 40…63 A conforming to IEC 60947-4-1


Range
Phase Failure Sensitivity Yes conforming to IEC 60947-4-1 § 7-2-1-5-2

[Ue] Rated Operational Voltage 690 V AC 50/60 Hz conforming to IEC 60947-2


600 V AC 50/60 Hz conforming to UL 508
600 V AC 50/60 Hz conforming to CSA C22.2 No 14

[Ui] Rated Insulation Voltage 690 V conforming to IEC 60947-2

[Ith] Conventional Free Air 63 A conforming to IEC 60947-4-1


Thermal Current

22 May 2024 1
Network Frequency 50/60 Hz conforming to IEC 60947-4-1
50/60 Hz conforming to UL
50/60 Hz conforming to CSA

[Uimp] Rated Impulse Withstand 6 kV conforming to IEC 60947-2


Voltage
Power Dissipation Per Pole 8W

Mechanical Durability 30000 cycles

Electrical Durability 30000 cycles for AC-3 at 440 V In/2

Maximum Number Of Switchings 25 cyc/h

Rated Duty Continuous conforming to IEC 60947-4-1

Tightening Torque 5 N.m - on EverLink BTR screw connectors - cable 2.5…16 mm²
5 N.m - on EverLink BTR screw connectors - cable 2.5…3.5 mm²

Breaking Capacity 100 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2


15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
4 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
2 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2

[Ics] Rated Service Short-Circuit 100 % at 230...240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking Capacity 50 % at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
60 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2

Height 120 mm

Width 61 mm

Depth 113 mm

Net Weight 0.7 kg

Environment
Standards IEC 60947-2
IEC 60947-4-1
BS EN
DIN EN 60947-2
DIN EN 60947-4-1
EN 60947-2
EN 60947-4-1
NF EN

Product Certifications UL
CSA
LROS (Lloyds register of shipping)

Protective Treatment TC

Ip Degree Of Protection IP20 conforming to IEC 60529 (open mounted)


IP55 conforming to IEC 60529 (in enclosure)

Shock Resistance 22 gn 20 ms conforming to IEC 60068-2-27

Vibration Resistance 2.5 gn (f= 0…25 Hz) conforming to IEC 60068-2-6

Ambient Air Temperature For -20…40 °C in enclosure


Operation -20…60 °C open mounted

Ambient Air Temperature For -40…80 °C


Storage
Fire Resistance 960 °C conforming to IEC 60695-2-1

Operating Altitude <= 3000 m

Resistance To Mechanical Impact 0.5 J

Packing Units
Unit Type Of Package 1 PCE

2 22 May 2024
Number Of Units In Package 1 1

Contractual warranty
Warranty 18 months

22 May 2024 3