Product datasheet
Specifications
motor circuit breaker GV3-ME -
40..63 A - screw clamp terminal -
thermomagnetic
GV3ME63
notification_critical_stroke Discontinued on: 27 Feb 2012
notification_critical_stroke Discontinued
Main
Range TeSys
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Name TeSys GV3
Product Or Component Type Circuit breaker
Device Short Name thermal magnetic circuit breaker
Device Application Motor
Poles Description 3P
Network Type AC
Control Type Push-button
Motor Power Kw 22 kW at 400...415 V AC 50/60 Hz
30 kW at 400...415 V AC 50/60 Hz
30 kW at 500 V AC 50/60 Hz
37 kW at 500 V AC 50/60 Hz
37 kW at 660...690 V AC 50/60 Hz
45 kW at 660...690 V AC 50/60 Hz
Trip Unit Technology Thermal-magnetic
Utilisation Category Category A conforming to IEC 60947-2
AC-3 conforming to IEC 60947-4-1
Connections - Terminals Power circuit: screw clamp terminal 1 cable(s) 2.5…35 mm²solid
Power circuit: screw clamp terminal 1 cable(s) 2.5 mm²flexible without cable end
Power circuit: screw clamp terminal 2 cable(s) 16 mm²flexible with cable end
Complementary
Network Frequency 50/60 Hz
Mounting Mode Fixed
Mounting Support Plate
Rail
Mounting Position Vertical
Horizontal
Thermal Protection Adjustment 40…63 A conforming to IEC 60947-4-1
Range
Phase Failure Sensitivity Yes conforming to IEC 60947-4-1 § 7-2-1-5-2
[Ue] Rated Operational Voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
600 V AC 50/60 Hz conforming to UL 508
600 V AC 50/60 Hz conforming to CSA C22.2 No 14
[Ui] Rated Insulation Voltage 690 V conforming to IEC 60947-2
[Ith] Conventional Free Air 63 A conforming to IEC 60947-4-1
Thermal Current
22 May 2024 1
Network Frequency 50/60 Hz conforming to IEC 60947-4-1
50/60 Hz conforming to UL
50/60 Hz conforming to CSA
[Uimp] Rated Impulse Withstand 6 kV conforming to IEC 60947-2
Voltage
Power Dissipation Per Pole 8W
Mechanical Durability 30000 cycles
Electrical Durability 30000 cycles for AC-3 at 440 V In/2
Maximum Number Of Switchings 25 cyc/h
Rated Duty Continuous conforming to IEC 60947-4-1
Tightening Torque 5 N.m - on EverLink BTR screw connectors - cable 2.5…16 mm²
5 N.m - on EverLink BTR screw connectors - cable 2.5…3.5 mm²
Breaking Capacity 100 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
4 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
2 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] Rated Service Short-Circuit 100 % at 230...240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking Capacity 50 % at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
60 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
Height 120 mm
Width 61 mm
Depth 113 mm
Net Weight 0.7 kg
Environment
Standards IEC 60947-2
IEC 60947-4-1
BS EN
DIN EN 60947-2
DIN EN 60947-4-1
EN 60947-2
EN 60947-4-1
NF EN
Product Certifications UL
CSA
LROS (Lloyds register of shipping)
Protective Treatment TC
Ip Degree Of Protection IP20 conforming to IEC 60529 (open mounted)
IP55 conforming to IEC 60529 (in enclosure)
Shock Resistance 22 gn 20 ms conforming to IEC 60068-2-27
Vibration Resistance 2.5 gn (f= 0…25 Hz) conforming to IEC 60068-2-6
Ambient Air Temperature For -20…40 °C in enclosure
Operation -20…60 °C open mounted
Ambient Air Temperature For -40…80 °C
Storage
Fire Resistance 960 °C conforming to IEC 60695-2-1
Operating Altitude <= 3000 m
Resistance To Mechanical Impact 0.5 J
Packing Units
Unit Type Of Package 1 PCE
2 22 May 2024
Number Of Units In Package 1 1
Contractual warranty
Warranty 18 months