G0022PKLSCA5T4000S
GENSET 22 kVA PERKINS / LEROY SOMER
1. MAIN FEATURES
Three-phase Diesel SOUNDPROOF
Length (L) 1620 mm
Perkins / 404A-22G1 Leroy Somer / TAL040F
Height (H) 1120 mm
Grupel / G545 50 Hz Width (W) 725 mm
1500 r.p.m. 400 V Weight 635 kg
Fuel tank daily capacity 45 L
0.8 32 A
Acoustic pressure level @ 1m 79 ± 2 dB(A)
Standby Power(ESP) 22 kVA 18 kW 71 ± 2 dB(A)
Acoustic pressure level @ 7m
Prime Power (PRP) 20 kVA 16 kW
Continuous Power(COP) - -
2. ROOM INSTALLATION
EXHAUST SYSTEM 50 Hz VENTILATION SYSTEMS 50 Hz
COP PRP ESP COP PRP ESP
Exhaust gas temperature (°C) - 445 505 Combustion air flow (m³/min) - 1.45 1.45
Exhaust gas flow (m³/min) - 3.64 3.94 Cooling airflow (m³/min) 40.2
Evacuated heat (kW) - 14 16.6 Maximum load losses (Pa) 125
Maximum back pressure (kPa) 10.2 Alternator cooling air flow (m³/min) 3.6
Exhaust silencer attenuation (dB) 18-25
RADIATION 50 Hz
Output diameter (mm) 65
COP PRP ESP
Engine (kW) - 3.3 4.4
Alternator (kW) 2.06 2.06 2.34
Parque Empresarial de Soza, Parcela A, Lote 5 - 3840-342 - Vagos - Portugal
T: +351 234 790 070 F: (+351) 234 920 670 -
[email protected] - www.grupel.eu 1/4
Grupel reserves the right to change any data contained in this document without prior notice. 2023-03-15 09:20
PC.1.6-0
G0022PKLSCA5T4000S
3. ENGINE SPECIFICATIONS
GENERAL SPECIFICATIONS 50Hz
Model 404A-22G1
Emissions (UE/USEPA) Not applicable / Not applicable
Performance grade G2 CONSUMPTION 50 Hz
Operating method 4 stroke Fuel consumption l/h g/kWh
Fuel type Diesel ESP 6.1 244
Refrigeration system Closed water circuit / antifreeze PRP 5.3 237
Aspiration system Natural COP - -
Injection system Indirect 75% 4 238
No. and Cylinder arrangement 4 In-line 50% 2.9 258
Displacement (L) 2.216 Oil consumption < 0.1% of fuel consumption
Cylinder bore (mm) 84
REFERENCE CONDITIONS
Cylinder stroke (mm) 100
Temperature (°C) 25
Compression ratio 23,3:1
Atmospheric pressure (kPa) 100
Regulation Mechanical / Electronic (optional)
Rotation speed (r.p.m.) 1500 CAPACITY (°C)
Piston speed (m/s) 5 Coolant (L) 7
Gross power COP (kWm) - Oil (L) 10.6
Gross power PRP (kWm) 18.7
STARTING SYSTEM
Gross power ESP (kWm) 20.6
Voltage (V) 12
Fan Power (kWm) -/0/0
Power (kW) 2
Net Power COP (kWm) -
Battery (Ah) 62
Net Power PRP (kWm) 18.4
Net Power ESP (kWm) 20.3
BMEP COP (kPa) -
BMEP PRP (kPa) 669
BMEP ESP (kPa) 650
4. ALTERNATOR SPECIFICATIONS
GENERAL SPECIFICATIONS
Model TAL040F
Phases No. Three-phase
Protection IP23
Wave form distortion with no load < 3,5%
Insulation H
Wave form distortion with balanced linear load < 5%
Temperature rise H
Winding Leads 6
R.F.I. telephone interference THF < 2%
Excitation (standard/optional) SHUNT / AREP+
IEC 61000-6-2/3/4, VDE 0875G/N, EN
R.F.I. Suppression AVR Model (standard/optional) R120 / R180
55011
Coupling Flexible disks Voltage Regulation (standard/optional) ± 1 % / ± 0,5 %
Support Single bearing Icc (standard/optional) - / 2,7In:5s
Power Efficiency
PF (cos Ø) Phase Voltage (V) PRP/ESP (kVA) PRP/ESP (%) Xd X'd X"d
0.8 Three-phase 400 20 / 22 87.12 / 86.7 1.94 0.155 0.077
Parque Empresarial de Soza, Parcela A, Lote 5 - 3840-342 - Vagos - Portugal
T: +351 234 790 070 F: (+351) 234 920 670 -
[email protected] - www.grupel.eu 2/4
Grupel reserves the right to change any data contained in this document without prior notice. 2023-03-15 09:20
PC.1.6-0
G0022PKLSCA5T4000S
5. CONTROL PANEL
ELECTRICAL GRID Grupel G545
Voltage (F-F / F-N) ●/●
Current [a] ○
Frequency ●
kVA,kW, cos Ø [a] ○
Inversion control between main-group ●
GENSET Grupel G545
Voltage (F-F / F-N) ●/● PROTECTIONS AND ALARMS Grupel G545
High / low battery voltage A
Current intensity ●
Failure in battery charge alternator A
Frequency ●
Failure to stop A/S
RMS Values ●
Failure to start A/S
Generator phase sequence ●
Low fuel level A/S
Generator earth current [a] ○
Overload A/S
No. of registered events 400
Earth leakage A/S
Real time clock ●
Asymmetry between phases A/S
PIN Protection ●
Maintenance A/S
kWh, kVAr, kVAh, kVArh, cos Ø ●
High / Low generator frequency A/S
Synchroscope [i] ○
Engine overspeed A/S
No. of available outputs [b] 4
Engine underspeed A/S
Indication of alarms on LCD ●
Generator overvoltage A/S
Hours of engine operation ●
Generator undervoltage A/S
Total no. of LED indicators 15
ECU Alert (if applicable) A/S
No. of LED alarms 4
Low oil pressure A/S
Sound signalling alarms -
Low level of radiator water [f] A/S
Schedule ●
Engine high temperature A/S
Fuel level ●
Fuel leakage/ theft A
Parque Empresarial de Soza, Parcela A, Lote 5 - 3840-342 - Vagos - Portugal
T: +351 234 790 070 F: (+351) 234 920 670 -
[email protected] - www.grupel.eu 3/4
Grupel reserves the right to change any data contained in this document without prior notice. 2023-03-15 09:20
PC.1.6-0
G0022PKLSCA5T4000S
6. CONTROL PANEL
ENGINE Grupel G545 APPLICATIONS Grupel G545
Engine speed ● Automatic or manual start-up ●
Low oil pressure protection ● Remote start by dry contact ●
Oil pressure reading [c] ○ Automatic by mains failure ●
High temperature engine protection ● Alternating with timesharing ●
Engine temperature reading [c] ○ Multi-generators synchronization and load sharing (max. 48
○
Engine battery voltage ● generators) [i]
Intensity of the engine battery [d] ○ Generator-Mains in synchronism and load sharing (1
○
generator and 1 mains) [i]
Fuel Consumption [e] ●
Low level of radiator water [f] ○ OPTIONAL EXPANSIONS Grupel G545
Scheduled engine maintenance ● G-08 (8 dig. inputs) ○
G-06 (8 relay outputs) ○
COMMUNICATION Grupel G545 G-GSM (GSM and/or GPS by MLAT) ○
USB female type B (max. 6m) ●
G-ETH (ethernet module) ○
USB female type A [g] ○
G-ETH (ethernet module according to SNMP protocol) ○
RS232 port (max. 15m) -
G545 (mirror controller, maximum distance 1km) ○
RS485 port (max. 1,2Km) ●
G175 (convert QTC into QTA) ○
Ethernet port RJ45 [g] ○
G545 (convert QTC into QTA) ○
GSM + location via MLAT [h] ○
ModBus RTU protocol ● STANDARDS
ModBus TCP protocol [g] ○ Working temperature -30 ≤°C ≤ 70
SNMP protocol [g] ○ Protection degree (front panel) IP65
CAN port (max. 40m) ● Degree of humidity (during 48hr) 93%, 40°C
MSC port (max. 240m) [i] ○
PLC functionality ●
Legenda Dimensions and weights guidelines. Environmental reference conditions: 100kPa, 25
● Available °C, 30% relative humidity and fuel temperature below 40 °C. Power ratings according
○ Optional to ISO 8528-1:2018.
- Not available Emergency power (ESP): Maximum power available to supply variable loads for a
maximum period of 200h/year. The average load factor in 24h of operation must not
A Warning Alarm
exceed 70% of the ESP regime. It does not allow overload.
S Stop alarm
Prime power (PRP): Maximum power available to supply variable loads for an
[a] Need additional CT
unlimited number of hours. The average load factor in 24 hours of operation must not
No. of outputs available for standard configuration. The outputs do not exceed 70% of the PRP rating. Allows an overload of 10% for a maximum period of 1
[b]
include relays and additional terminal connections.
hour every 12 hours of operation. Overloading may not exceed 25 hours/year.
If the information is not provided by the engine-ECU, you need an additional Continuous power (COP): Maximum power available to supply constant loads for an
[c]
sensor
unlimited number of hours per year, between the maintenance intervals and
[d] Needs additional ammeter
environmental conditions advertised by the manufacturer.
[e] If information provided by the engine ECU These specifications are subject to change without notice.
[f] Required additional sensor
[g] Requires G-ETH
[h] Requires G-GSM
[i] Requires G-Sync
DISTRIBUTOR
Parque Empresarial de Soza, Parcela A, Lote 5 - 3840-342 - Vagos - Portugal
T: +351 234 790 070 F: (+351) 234 920 670 -
[email protected] - www.grupel.eu 4/4
Grupel reserves the right to change any data contained in this document without prior notice. 2023-03-15 09:20
PC.1.6-0